Star-Delta Starters with Isolator

Type EXE2SI
Metal Enclosure to IP65 Installation Instructions
1. 2. 3. 4. 5. 6. 7. 8. 9.
Issue 10=

fb`VQTJQJN

==========
06.012230.10E 0808

Remove cover from starter by releasing catches with a screwdriver. Select overload: (see ratings / conversion charts below). Connect leads provided from Main Auxiliary 4 to Overload 95 and Main 5/L3 to Overload 96. Check operating coil voltage and frequency. Remove appropriate top/bottom knockouts. Mount base on a vertical surface using top keyhole slots for quick positioning and secure with screws in lower plain holes. To maintain environmental protection, ensure that rubber washers are fitted to fixing screws on outside of enclosure. Use large washer for keyhole fixing. Connect conduit bushes. Connect cables and ensure that all terminals are tight. Rubber washer Fixing screw Enclosure

10. When installed, set the hand/auto reset selector and adjust the current calibration to the desired value. 11. Replace cover and secure catches. =

Ratings
Starter Order references Coil Voltages (50Hz) 230V 400V
TA25DU8.5
1SAZ211201R1040

Approximate motor rating Requires Overload Overload rating Full load A min. 6.0 10 13 24 max. 8.5 14 19 32 400V/3PH AC3 KW 5.5 11 15 22 hp 7.5 15.0 20.0 30.0 230V/3PH AC3 KW 3.0 5.5 7.5 11.0 hp 4.0 7.5 10.0 15.0 20 35 80 80
Recommended max. fuse size for short circuit protection A

312EXE2SI-OL
1TVL405216E5099

314EXE2SI-OL
1TVL405416E5099

TA25DU14
1SAZ211201R1045

TA25DU19
1SAZ211201R1047

452EXE2SI-OL
1TVL405226E5099

454EXE2SI-OL
1TVL405426E5099

TA25DU32
1SAZ211201R1053

Note: This product is not suitable for d.c. applications. = = Terminal capacity
Isolator All ratings Main 0.7510mm
2

Overload < 7.5kW 11kW 15kW 22kW

Main 4mm 2 4mm 6mm2 2 6mm


2

Auxiliary 1x4mm / 2x2.5mm " " " " " "


2 2

Trip class requirements IEC 947-4-1


1.05 x FLC 1.2 x FLC 1.5 x FLC 7.2 x FLC No tripping Trip within 2 hours Trip within 4 minutes Trip between 4s and 10s

Summary
A range of star-delta motor starters with isolator Ingress protection to IP65. Painted steel enclosure. N.B. Space is available to fit standard ABB top and side mounted auxiliary contacts.

NOTE: FLC = Full load current =

ABB

Connection Data
Type 4 EXE2SI (400Vcoil)= =
L1 L2 L3

Conversion Chart
Motor full load current A Overload setting Delta loop current A

= ==========Type 2 EXE2SI (230V coil)=


L1 L2 L3 N

A1 L1 L2

A2 L3 13

01
02

A1 L1 L2

A2 L3 13

A1 L1 L2

A2 L3 13

A1

A2 L2 L3 13

01
02

A1 L1 L2

A2 L3 13

A1 L1 L2

A2 L3 13

L1

Star

01

Delta

Main

Star

01

Delta

Main

T1

T2

T3

14

VE5-1
02

T1

T2

T3

14

T1

T2

T3

14

T1

T2

T3

14

VE5-1
02

T1

T2

T3

14

T1

T2

T3

14

96

95

96

95

Overload
T1
2

Overload
T3
6

T2
4

T1
2

T2
4

T3
6

5 6 7 8 9 10 12 14 16 18 20 25 30 35 40 45 50 55

2.9 3.5 4.0 4.6 5.2 5.8 7.0 8.1 9.3 10.4 11.6 14.5 17.4 20.3 23.2 26.1 29.0 32.0

U2

V2 W2
E

U2

V2 W2

M 3
U1

~
U1

M 3

V1 W1

V1 W1

Note : Overload relay is fitted in the delta loop. It is therefore necessary to use the conversion chart to obtain correct overload setting for a particular motor full load current.

Circuit

Modification for remote 2-wire control


Supply L1 L2 L3 N

= p~JDelta = p~J = (main contactor in

Delta loop)
230v
Control

Overload should be in hand reset. Stop reset button will only stop motor whilst button is depressed, if pressure switch is closed.

L1

Supply L2 L3

230v
Control

400v
Control

400v
Control

Star

Delta

Main

Star

Delta

Main

Overload

Overload

Pressure switch

W2 V2 U2

W1

W2 V2 U2

W1

M 3~

V1 U1

M 3~

V1 U1

Overload Stop/Reset 96 95 8

Start 7 16 02 D 01 A2 A1

Overload Stop/Reset

Start 8 7 02 16 D 01 A2 A1

96

95

Link
15 18 02 S 01 A2

15

A1

18

02 S

01 A2

A1

A2

T
TES5 Electronic Timer

A1 14 S M 13 13 A2

A2

T
TES5 Electronic Timer

A1 14 S M 13 13 A2

14

A1

14

A1

Council of European Communities Directives: The products in this publication conform to relevant EEC Directives and EN Standards. Installation and use of such products must be carried out by competent, properly trained personnel, complying with any instructions supplied by ABB. Liability for improper incorporation, assembly, use, processing, storing or handling of goods remains the sole responsibility of the individual, or company carrying out such work. This publication is for information only. Whilst every care has been taken in the preparation of this leaflet, no liability is accepted for any consequence of its use. No licence to use any patent should be assumed. All dimensions are approximate only and subject to change without notice, as are other technical features resulting from continual development and improvement.

ABB Limited Tower Court, Foleshill Enterprise Park, Courtaulds Way, Coventry. CV6 5NX Tel: 02476 368500 Fax: 02476 364499

ABB

You might also like