Reading and Configuration tool Instruction manual

Version: Date: Document name:

2.07.00 8 June 2009 alphaset_user_manual_GBR.doc

alphaSET, user manual, Version 2.07.00 1 Overview

Page 2 of 137

COPYRIGHT
Copyright 2008 ELSTER Messtechnik GmbH. All rights reserved. All rights, also those the translation, the reproduction and the duplication of the document, or parts from it, reserved. No part of the document may be multiplicated without written permission of the ELSTER Messtechnik GmbH in any form (electronically, mechanically, photographically or another procedure) or be spread. Printed in Germany

Attention
ELSTER Messtechnik GmbH reserves itself the right to carry out changes in all products described in this manual to improve reliability, function or design. Specifications and information, which are described here, can change without notification. Not all occurrences, with all possible details and variations of the devices, which can appear during the installation, the use and maintenance, are covered by this manual ELSTER will not be responsible for errors in this document or for consequential damages in the reference to mechanism, achievement or use of this material. ELSTER does not take any responsibility and adhesion for the installation, use, achievement, care and support of products third.

For further information, see the following references:


ELSTER electricity meter customer support: ELSTER electricity meter customer support e-mail: ELSTER companies web side: ELSTER electricity meter web side: +0049 (0)6206 933 339 e-info@de.elster.com http://www.elstermesstechnik.com http://www.elstermetering.com

alphaSET, user manual, Version 2.07.00 1 Overview

Page 3 of 137

Table of contents
1 2 3 Overview ............................................................................................................................ 6 1.1 System overview ............................................................................................................ 6 1.2 Document history ........................................................................................................... 6 Referenced documents..................................................................................................... 7 Introduction / brief description ........................................................................................ 8 3.1 What is the alphaSET tool ? ........................................................................................... 8 3.2 System requirements...................................................................................................... 8 3.3 Installation / Update of alphaSET ................................................................................... 9 3.4 Start of the software and user-profile............................................................................ 14 3.4.1 First start after installation .................................................................................... 14 3.4.2 User-profile .......................................................................................................... 16 3.4.3 Use of the software ............................................................................................. 18 3.5 Indication of the software version ................................................................................. 21 User settings ................................................................................................................... 22 4.1 Communication ............................................................................................................ 22 4.2 Files ............................................................................................................................. 24 4.3 Read register / log files................................................................................................. 25 4.4 General Settings........................................................................................................... 26 4.5 User language .............................................................................................................. 27 4.6 IEC 1107-Address ........................................................................................................ 28 4.7 Change utility password ............................................................................................... 29 4.8 Password ..................................................................................................................... 30 Read meter data .............................................................................................................. 31 5.1 Read register list .......................................................................................................... 31 5.2 Read service list ........................................................................................................... 32 5.3 Read settings ............................................................................................................... 33 5.4 Read load profile .......................................................................................................... 35 5.4.1 Graphical display of load profile data ................................................................... 37 5.5 Read power quality monitoring ..................................................................................... 40 5.5.1 Graphical display of power quality data................................................................ 41 5.6 Read log file ................................................................................................................. 42 5.7 Read log file 2 .............................................................................................................. 44 5.8 Read meter error status................................................................................................ 45 5.8.1 Errors + Warnings................................................................................................ 45 5.8.2 Power Quality Supervision ................................................................................... 46 5.8.3 Error Messages ................................................................................................... 47 5.8.4 Status Messages ................................................................................................. 48 5.8.5 Print ..................................................................................................................... 49 5.8.6 Options ................................................................................................................ 50 5.9 Read communication protocol ...................................................................................... 51 Configuration of the meter ............................................................................................. 52 6.1 Open a parameter file................................................................................................... 52 6.2 Save a parameter set ................................................................................................... 53 6.3 Configuration of a meter by using a configuration file ................................................... 54 6.3.1 Switch point clock ................................................................................................ 54 6.3.2 Settings (without PW + ID) ................................................................................... 54 6.3.3 Settings and parameterisations (without PW + ID) ............................................... 55 6.4 Modify parameters........................................................................................................ 56

alphaSET, user manual, Version 2.07.00 1 Overview

Page 4 of 137

Change of meter configuration ...................................................................................... 57 7.1 Identifications ............................................................................................................... 58 7.2 Tariff source ................................................................................................................. 60 7.3 Switch point clock......................................................................................................... 61 7.3.1 Day type .............................................................................................................. 61 7.3.2 Season change.................................................................................................... 62 7.3.3 Tariff switch table................................................................................................. 63 7.3.4 Holiday-list ........................................................................................................... 64 7.3.5 Daylight saving time............................................................................................. 65 7.4 Switch point clock (Update) .......................................................................................... 66 7.4.1 Day type .............................................................................................................. 66 7.5 Times ........................................................................................................................... 67 7.5.1 Source of Times................................................................................................... 67 7.5.2 Display Timeouts ................................................................................................. 68 7.5.3 Communication Timeouts .................................................................................... 69 7.6 Demand reset............................................................................................................... 70 7.7 Demand overload ......................................................................................................... 71 7.7.1 Load limitation...................................................................................................... 71 7.7.2 Demand overload ................................................................................................ 72 7.7.3 Threshold value tan(phi) ...................................................................................... 72 7.8 Baud rate...................................................................................................................... 73 7.9 DLMS Parameters........................................................................................................ 74 7.10 Synchronization.......................................................................................................... 75 7.11 Backup time of the real time clock .............................................................................. 77 7.12 Inverting Inputs/Outputs ............................................................................................. 78 7.13 Power quality.............................................................................................................. 79 7.13.1 Release of power quality functionality .................................................................. 79 7.13.2 Load profile of power quality data ........................................................................ 80 7.13.3 Power Quality Monitoring ..................................................................................... 81 7.14 Copper-/Iron-losses .................................................................................................... 82 7.15 Meter Access Rights................................................................................................... 83 7.16 Display ....................................................................................................................... 85 7.16.1 Service list ........................................................................................................... 85 7.16.2 Display parameter................................................................................................ 87 7.17 Pulse constants .......................................................................................................... 90 7.18 Pulse inputs................................................................................................................ 91 7.18.1 Pulse inputs tabs. ................................................................................................ 91 7.18.2 Summation tab..................................................................................................... 92 7.19 Load profile / logfile - parameter ................................................................................. 93 7.19.1 Load profile parameter ...................................................................................... 93 7.19.2 Log file parameters ............................................................................................ 95 7.20 Energy / Demand measuring ...................................................................................... 96 7.21 Passwords.................................................................................................................. 97 7.22 Show settings ............................................................................................................. 98 8 Formatted Meter Commands.......................................................................................... 99 8.1 Set meter date/time using the W2 command .............................................................. 100 8.2 Read and Set time/date using the VDEW command .................................................. 101 8.3 Setting of pulse constants .......................................................................................... 102 8.4 Setting of outputs ....................................................................................................... 103 8.5 Control of Disconnect Relay ....................................................................................... 104 8.6 Activation of DCF 77 signal decoding ......................................................................... 105 8.7 Reset maximum demand (W1 or E2).......................................................................... 106

alphaSET, user manual, Version 2.07.00 1 Overview

Page 5 of 137

8.8 Reset meter error status............................................................................................. 107 8.9 Reset power quality monitoring .................................................................................. 108 8.10 Reset power quality supervision counter .................................................................. 109 8.11 Reset power-loss counter ......................................................................................... 110 8.12 Reset terminal cover open counter ........................................................................... 111 8.13 Reset register ........................................................................................................... 112 8.14 Set register values (pulse inputs).............................................................................. 113 8.15 Reset load profile + logbook ..................................................................................... 114 9 Integrated Ripple receiver (LCR).................................................................................. 115 10 Test .............................................................................................................................. 116 10.1 Read meter error ...................................................................................................... 117 10.2 Power-Quality........................................................................................................... 118 10.2.1 Main display....................................................................................................... 118 10.2.2 Options .............................................................................................................. 119 10.2.3 Print ................................................................................................................... 120 10.3 Test mode ................................................................................................................ 121 10.4 Communication Protocol .......................................................................................... 123 11 Modem ......................................................................................................................... 124 11.1 Phone Book.............................................................................................................. 125 11.1.1 Phone book part 1.............................................................................................. 125 11.1.2 Phone book part 2.............................................................................................. 126 11.1.3 Phone book part 3.............................................................................................. 128 11.2 Hang up.................................................................................................................... 129 11.3 Dial-up doesnt work! What to do? ............................................................................ 130 12 Extras ........................................................................................................................... 131 12.1 Construction of a restricted menu system................................................................. 131 13 Help .............................................................................................................................. 134 13.1 User manual alphaSet .............................................................................................. 134 13.2 How to use the new phone book............................................................................... 134 13.3 AlphaSet Release-notes........................................................................................... 135 13.4 About alphaSet......................................................................................................... 135 14 Image index ................................................................................................................. 136

alphaSET, user manual, Version 2.07.00 1 Overview

Page 6 of 137

1
1.1

Overview
System overview

This document describes the operation, the functional way and the installation as well as the technical data of the software tool alphaSET version 3. This tool was refined on the basis from alphaSET version 2 and is compatible to former versions. Therefore the following products can be served with this tool: AEM500 ARM500 AEM550 A220 AS220 / AS253 AS1253 A1350 A1440 A1500 A2500

1.2

Document history
Valid up to Valid up to alphaSET FW-Version version 3.03-xx 3.04-xx 3.06-xx 3.09-xx 3.12-xx 3.15-xx 3.15-xx 4.10 4.20 Changes Date Author

Version

2.01.00 2.02.00 2.03.00 2.04.00 2.05.00 2.06.00 2.07.00

- Initial Version - Adaptations to FW 4.20 4.20 and 5.00 - Adaptations to FW 5.00 4.30 and 5.10 - Adaptations to FW 4.30 and 5.10 4.40, 5.30, - Adaption to FW 4.40, 7.00 5.20, 5.30, 7.00 4.50, - Adaption to A1440, 7.00,9.00 AS253 and AS1253 4.50, 7.00, - Adaption to FW 9.20, 9.20, 8.10 8.10

30.10.2002 Thomasberger 20.08.2003 Dr. Eisenbei 24.02.2004 A. Aching 12.05.2005 Dr. Eisenbei 11.10.2006 H.Thomasberger 12.12.2008 H.Thomasberger 13.05.2009 C. Lopez H.Thomasberger L. Claus

alphaSET, user manual, Version 2.07.00 2 Referenced documents

Page 7 of 137

2
Title

Referenced documents
Version Date 1KGL 921500 V004D 11/05/2001 R 1.14 R 1.17 06/16/2006 07/16/2006 06/28/2006 01.03

AEM_PR_D_1.pdf A1500_PR_E.pdf A1350_PR_E.pdf

A220_PR_E.pdf R 1.06 Zhlerstandsbertragung, Tarif- und LastDIN EN 62056-21 steuerung; Datenbertragung fr festen und mobilen Anschlu Elektronische Elektrizittszhler VDEW-Lastenheft V2.0

12.97

alphaSET, user manual, Version 2.07.00 3 Introduction / brief description

Page 8 of 137

Introduction / brief description


What is the alphaSET tool ? What are the system requirements for the use of this software ? How do I install this software ? What must I do if I would like to update this software ? How do I start the software ? What will I see, if I start the software ? How do I find out, which user profile may execute which action? How do I find out, which software version I use ? How do I set a password for the communication with the meter?

The following section should help to clear basic questions to the alphaSET tool:

Additional information:
For additional information please refer to the product descriptions of the alpha meters (2 Referenced documents).

3.1

What is the alphaSET tool ?

The alphaSET tool is a Windows based software to read the data of the alpha meters AEM 500 / ARM 500 / AEM 550 / A220 / AS220 / AS253 / AS1253 / A1350 / A1440 / A1500 and A2500 (register, load profile, log book, etc.). Different parameters like setting and parametrization parameters can be changed according to user's profile. Setting parameter is those attitudes, which can be changed without breaking the certification seal. To get an access to the parameterisation parameters of the meter, a parameterisation-switch must be pressed which is via the calibration mark. The program is a 32 bit application, being based on a 32 bit environment that runs via Windows NT 4. X, as well as via Windows XP, Windows 2000 and Windows Vista

3.2

System requirements

Subsequet are the requirements for the use of the alphaSET software listed:
IBM PC or compatible PC with 800 MHz Pentium or higher with the following equipment:

16 MB RAM CD ROM disk drive at least one free, serial interface (COM1 to COM16) 50 MByte free hard disk memory Hardware components for communication IEC 61107-compatible optical probe for the optical interface CL0 Converter and RS232 cable for the electric interface (CL0-Interface) RS232 cable for the RS232 interface (optional) Windows 2000 / NT / XP / Vista Monitor with a resolution of at least 1024 x 768 pixel
-

alphaSET, user manual, Version 2.07.00 3 Introduction / brief description

Page 9 of 137

3.3

Installation / Update of alphaSET

You require administrator rights on your PC for the installation of this software-tool. Further it is urgently recommended that you close all windows programs, before starting the setup. Insert the CD-Rom with the product information and tools from ELSTER to your CDROM-drive. Automatically the following menu is displayed. Please select your language and then press the button alpha meter.

Image 3.3-1: Installation choose alpha meter

Select in the section AlphaSET the button Installation.

Image 3.3-2: Installation choose installation

alphaSET, user manual, Version 2.07.00 3 Introduction / brief description

Page 10 of 137

Within the next menu you have to choose the language of your setup.

Image 3.3-3: Installation choose language

AlphaSET is preparing the setup and you have to choose next here.

Image 3.3-4: Installation information1

alphaSET, user manual, Version 2.07.00 3 Introduction / brief description

Page 11 of 137

Choose the button next.

Image 3.3-5: Installation information2

Select your destination path of alphaSET and press the button Next.

Image 3.3-6: Installation select destination

If you update the program, no deinstallation of the old version is necessary. You can simply install the new version in the same directory.

alphaSET, user manual, Version 2.07.00 3 Introduction / brief description

Page 12 of 137

Image 3.3-7: Installation - phone book

You should only secure your phone book, if you have one, created from alphaSET-version below 3.13. Further information in chapter 13.2 SETUP checks now whether sufficient memory is available. Subsequently a communication window appears in which the installation progress is indicated.

Image 3.3-8: Installation - Progress

After completion a window appears with the information that SETUP generates program symbols. Then the program will ask you to restart your computer.

alphaSET, user manual, Version 2.07.00 3 Introduction / brief description

Page 13 of 137

Image 3.3-9: SETUP Complete

Normally it is NOT necessary, to restart the PC. After successful installation a message from SETUP appears.

Image 3.3-10: SETUP successful

Note: To secure all functions of the program alphaSET needs at least one installed Windows system printer, even if no printer is connected. According to your windows version, you have now a program group, or a start symbol of alphaSET

alphaSET, user manual, Version 2.07.00 3 Introduction / brief description

Page 14 of 137

3.4

Start of the software and user-profile

To start the alphaSET tool software: Chose in the Windows Start Menu > Programs > alphaSET > alphaSET Or click on the Icon on your desktop

To close the software choose File -> Quit

3.4.1

First start after installation

With the first start after installation of the alphaset sofware the following window will be displayed:

Image 3.4-11: Start - language

Here please select the language to operate the tool. With the following menu it is possible to take over all the settings from prior versions of your computer.

alphaSET, user manual, Version 2.07.00 3 Introduction / brief description

Page 15 of 137

Image 3.4-10: Start old settings

alphaSET, user manual, Version 2.07.00 3 Introduction / brief description

Page 16 of 137

3.4.2

User-profile

Normally, alphaSET starts with the menu of the profiles, e.g.:

Image 3.4-1: Input user-profile

Each of this profiles has different privileges, that means possibilities of access on the menu system of alphaSET. The user profiles are filed in the path " \ IniPfad ". If only one profile is in this path, this is started automatically, without showing the menu illustrated above. If no profile is in this path, the invisible profile "consumer" starts automatically, which has lowest privileges. The user profile serves the storage of all individual settings. If several persons work with a computer, each user can save his own settings, in order to fall back on them, if he uses again alphaSET. For information to the storage of an user's profile see chapter 4.1 "Communication".

alphaSET, user manual, Version 2.07.00 3 Introduction / brief description

Page 17 of 137

3.4.2.1

Overview of user profile functionality

Read Meter Read register Read load profile Read logfile Read meter configuration Read meter error Read service list Read power quality monitoring Change of parameters Change utility password File / read parameter File with parameter -> meter Identifications Tariff source Switch point clock Times Demand reset Overload threshold Baud rate Synchronization Power Quality Pulse inputs Backup time of real time clock Service List Display parameter Pulse constants Load-profile / logbook parameter Measuring energy / demand Read/ Set pulse constants Meter commands Set meter date/time Read/set date/time Read out DCF clock Reset demand maxima Reset meter error state Reset power-loss counter Reset register Reset load-profile and logbook General Switch to ripple receiver mode Test mode Communications protocols
Image 3.4-2: User profile

X X X X X X X

X X X X X X X

X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X

X X X X X X X X X X X X X X X X X X X X X X X

X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X

X X X X X X X

X X X X

X X X X X X X

X X X X X

X X X X X X X X X X X

Power Quality

alphaSET Software functions Meter reader Certification Installation MODEM

Utility

alphaSET, user manual, Version 2.07.00 3 Introduction / brief description

Page 18 of 137

3.4.3

Use of the software

After the selection of the user profile the alphaSET opening screen appears.

Menu bar

Title bar Icon bar

Image 3.4-3: Opening screen

The program alphaSET is a Windows - based application, which reflects the structure and the construction of Windows programs. The window of the main menu consists of The title bar The menu bar And the icon bar

In the submenus are further windows (document windows and dialogue windows) indicated, which show the name of the submenu in the title bar. The menu bar indicates the available menus, in which the individual actions and switching functions are specified as clear text. This bar contains several entries, which are described in the following chapters. The icon bar contains icons for the most used functions.

alphaSET, user manual, Version 2.07.00 3 Introduction / brief description

Page 19 of 137

3.4.3.1

Icon catalogue

The following list explains the available icons of the icon bar.

Read file

Save

Print

Read register

Read service list

Read load profile

Read power quality monitoring

Read logfile

Read meter configuration

Write Setting and parametrization parameter to the meter Set meter date/time

alphaSET, user manual, Version 2.07.00 3 Introduction / brief description

Page 20 of 137

Demand reset

Reset meter error state

Reset register

Reset load profile and logbook

Read meter error

Activate test mode

Open communication protocol

...about alphaSet

alphaSET, user manual, Version 2.07.00 3 Introduction / brief description

Page 21 of 137

3.5

Indication of the software version

To get information about the applied software version, select via Help the menu item "about alphaSET ... " or click on the following icon:

This command opens a window with the data about the program alphaSET and its version.

Image 3.5-1: Information screen

alphaSET, user manual, Version 2.07.00 4 User settings

Page 22 of 137

User settings

In this chapter the options for the user settings are described. You find these settings via the menu item Extras.

4.1

Communication

Select via Extras the menu item Options, there the register card Communication.

Image 4.1-1: Settings register card communication

COM-Port With the function "Com-Port" the interfaces Com 1 to Com 16 of the PC can be selected. By the start of alphaSET the program checks automatically the free COM-Ports of the computer. It is the decision of the PC user himself whether the selected COM-Port is still free for the use by alphaSET while the alphaSET-session. Initial Baud rate The initial baud rate of the communication between alphaSet and the connected meter can be adjusted by pull-down-menu. For more information to the baud rate shift see DIN EN 6205621. Utility password A password for the meter communication can be assigned to the user profile that means an interrogation of the utility password is not executed any more (useful if the same EVU password for different meters is used). Read with 300 Baud only This option enables the constant reading of the meter with 300 baud. The automatic baud rate shift is disabled.

alphaSET, user manual, Version 2.07.00 4 User settings

Page 23 of 137

Suppression of optical reflexion With this option a lack of the suppression of optical reflexion of the probe according to hardware can be compensated by software. Attention: The probes from P+E delivered by ELSTER do not need this option, because the suppression of optical reflexion is already realized in the hardware. Create communication log file By selection of this option a communication protocol is created automatically, which is also written directly in a text file. Waiting time between baud rate switch [ms] In this box the waiting time con be assigned in milliseconds between the baud rate switching. Data format With this choice the physical transmission of the data between the meter and alphaSET can be defined. Default is 7,E,1. The format 8, N, 1 is only required for special meters. Note: If the data of the counter are read by the AMR system modem, only the settings of this modem is relevant and not the settings of the meter. OK The actual settings are taken over by clicking on this button. They are automatically written in the user-profile and are available on the next start of alphaSET. Copy profile With the help of this button different settings can be saved in a new user-profile or releases can be transmitted out of other user profiles. Cancel Clicking on this button ignores all changes and you get back to the main program.

alphaSET, user manual, Version 2.07.00 4 User settings

Page 24 of 137

4.2

Files

Select via Extras the menu item Options, there the register card Files. In this menu the paths on the drives can be defined in which the different files should be stored. A click to the button enables the changing of the entries. In the pull down menu Proposal for file name(s) are several suggestions done for an automatic generation of the file name.

Image 4.2-1: Settings register card files

alphaSET, user manual, Version 2.07.00 4 User settings

Page 25 of 137

4.3

Read register / log files

Select via Extras the menu item Options, there the register card Register/Load Profile.

Image 4.3-1: Settings register/load profile tab

Read register In this window the user can select whether the register data should be shown with or without clear text (designations according to identification number system OBIS). The reading of the serial number can be deactivated here, too. Note: In addition to the deactivation of the reading of the serial number it must be guaranteed that not meter serial number is selected as Proposal for file name(s) (see 4.2 Files). Release readout of eHz If the new eHz (electronic residential 3-phase meter) should be readout this checkbox has to be selected. Load profile Dont read load profile / log book header: If the user reads load profile or log book, the header is always read first by default, to find out start, end and channel number of the profile. In the case of a reading without header, the selected period is questioned directly without reviewing previously, which one is available. In this process, all available load profiles in the meter are read. Read load-profile/event-log file without password: With this option it can be defined whether the load profile reading takes place with or without password interrogation.

alphaSET, user manual, Version 2.07.00 4 User settings

Page 26 of 137

4.4

General Settings

Select via Extras the menu item Options, there the register card General.

Image 4.4-1: Settings register card general

alphaSET

Edit passwords hidden: With activation the input of the password is not indicated any more in the clear text, only with ******** . Reset programming mode after parameterisation: After the change of parameters in a meter, the alphaSET puts the parameter mode of the counter automatically back. For more information about the parameter mode see chapter 7 Change of meter configuration. Check daylight saving set to EU standard: During the download of the tariff table to the meter an automatic check of the correct used EU daylight saving time will be executed and an error message is displayed if there's inconsistency.

alphaSET, user manual, Version 2.07.00 4 User settings

Page 27 of 137

4.5

User language

Select via Extras the menu item Options, there the register card Language.

Image 4.5-1: Settings register card language

Note: In order to activate all language changes, you should quit alphaSET and restart it after a language change.

alphaSET, user manual, Version 2.07.00 4 User settings

Page 28 of 137

4.6

IEC 1107-Address

Select via Extras the menu item IEC1107 address .

Image 4.6-1: IEC 1107-Address

An IEC1107-address can be registered here, which is send at every communication to the meter. The meter answers in this case only if the IEC1107-Address sent by alphaSET agrees with its configured address. The meter IEC address is used if more than one meter is connected to a modem by using the CL0 or RS485 interface.

alphaSET, user manual, Version 2.07.00 4 User settings

Page 29 of 137

4.7

Change utility password

Select via Extras the menu item Change utility password

Image 4.7-1: Utility password for communication

The communication-password (from alphaSET to the meter) can be preset in this menu. That has no effect to the utility password in the meter. 8 numeric chars are expected.

alphaSET, user manual, Version 2.07.00 4 User settings

Page 30 of 137

4.8

Password

Select via Extras the menu item Options, there the register card Password. The administrator of alphaSET can set different Passwords in order to protect the different versions of alphaSET. With this function all alphaSET users can have their own version on alphaSET with different permissions.

Image 4.8-1: Password settings .

alphaSET, user manual, Version 2.07.00 5 Read meter data

Page 31 of 137

Read meter data

You should first check the communication. The command read register is the simplest way to do it. If this doesnt work, please check the settings of alphaSET, see chapter 4 User settings.

5.1

Read register list

Select via Meter the menu item Read register or the following icon:

Image 5.1-1 Read register

By using this command the billing data list (register list or Std-dAtA on LCD) of a meter is read out. A window appears in which the reading data are visualized. If you have chosen the option read register with serial number (see chapter 4.3 Read register / log files), the serial number will be indicated in the title bar. The identification number is indicated in the first column, the measured value in the second column and in the third column is an interpretation of the identification number in clear text to be seen, if the identification number corresponds to the OBIS identification system.

alphaSET, user manual, Version 2.07.00 5 Read meter data

Page 32 of 137

5.2

Read service list

Select via Meter the menu item Read service list or the following icon:

Image 5.2-1: Read service list

By using this command the settable service list (AbL-dAtA on LCD) of a meter is read out. A window appears in which the reading data are visualized. The identification number is indicated in the first column, the measured value in the second column and in the third column is an interpretation of the identification number in clear text to be seen, if the identification number corresponds to the OBIS identification system. For further information see chapter 7.16.1

alphaSET, user manual, Version 2.07.00 5 Read meter data

Page 33 of 137

5.3

Read settings

Select via Meter the menu item Read settings or the following icon:

Image 5.3-1: Read meter configuration

This command enables the reading and displaying of the configuration of the meter. The input of a utility password is demanded for this operation. The following meter configurations are displayed: Type key Meter-Identification Pulse constants Demand measuring Load profile / log file Real time clock Tariff source Demand reset source Outputs Baud rate

alphaSET, user manual, Version 2.07.00 5 Read meter data

Page 34 of 137

Display control Display list Switch point clock

By clicking on close you get back to the main menu. The menu item modify appears in the menu bar after reading meter configuration. Note: You have the possibility to store the parameter set as text file, so that you can work with this parameter set in other programs (e.g. text progressing programs) The following check box serves for this:

In this case, the name (and path) for the text file is asked after inquiry of the file name for the parameter set. The default pathname is registered in Extras/Options/Files in the field read meter configuration. The content of the indicated window will be stored.

alphaSET, user manual, Version 2.07.00 5 Read meter data

Page 35 of 137

5.4

Read load profile

Select via Meter the menu item Read load profile, or the following icon:

Image 5.4-1: Read load profile

The load profile of the meter can be read with this command. The configuration of the load profile is read and displayed after confirming. Certain settings for the specific reading of the load profile can be taken here: Selection of the measuring channels (as far as they exist in the meter). Limitation of the reading period. This period can be defined in the from or to input fields. By deactivating the checkboxes at start and end, the appropriate time stamps are indicated. These stamps can be edited by double clicking on them. Should a certain window be selected repeatedly, this can be stored and again be activated by the button "stored values". Frequently used specifications like last month, last week, yesterday or today can be selected directly. Partial readout (possibly from FW 3.02), that means use of the R6-command. For more information see VDEW-Lastenheft. Depiction of primary values in accordance of the transformer ratio for Voltage and Current. The transformer ratio is 1:1 if no primary values are activated. Note: The indicated meter data are then secondary data.

alphaSET, user manual, Version 2.07.00 5 Read meter data

Page 36 of 137

After input of the reading period, the load profile of the meter is read by clicking on the button read load profile. If all data is read a new button Show load profile appears. With this command alphaSET shows all load profile data of the meter in a table. The following data are listed: Date Time Measured values of the channels (up to 8 channels) Status of the saved measuring periods.

Image 5.4-2: Data of load profile

The status-announcement is shortened, if several channels are parameterised, in accordance with:


FE: CS: MD: SC: RS: CC: PU: PF: Fatal fault Backup time of real time clock exhausted Measuring period disturbed (shorter measuring period) Season change Reset Device clock Power return Power failure

alphaSET, user manual, Version 2.07.00 5 Read meter data

Page 37 of 137

Reading of large amounts of LP-data: Only 1000 entries can be displayed in one chart. To view advanced data, click previous values or following values. Comment to the user profile Railway: A train number is additionally indicated in the depiction of the load profile values in the user profile "Railway: Comment to read load profile without header: You have the possibility to read load profile, without reading previously information of the meter. For this and for more information concerning settings see chapter 0.

5.4.1

Graphical display of load profile data

With the selection show load profile you get the data of the meter in a table and additionally a button to show this information graphically.

With this button you start the LP Analyzer tool and you get directly the following picture.

Image 5.4-3: Graphical data of load profile

alphaSET, user manual, Version 2.07.00 5 Read meter data

Page 38 of 137

The following icons are available for the user:

Back to the main window

Print

Change of scale of the y-axis

Maximum x-axis

Maximum y-axis

Maximum x-axis and y-axis

Additionally it is possible to zoom in. You just have to click in the graph and pull with the mouse, to mark of the area you want to see in more details. At the bottom the values of the load profile data is listed.

Image 5.4-4: Table settings 1

It is possible to show maximum of 8 channels. With the checkbox your are able to activate / deactivate the channels in the graph. If you double click on the field of the colour, you are able to choose different colours and types of designs.

alphaSET, user manual, Version 2.07.00 5 Read meter data

Page 39 of 137

To analyse in detail specific values of the load profile, you have to set the cursor to this line in the table of load profile date and then in the graph this position is displayed. Have a look at the next picture.

Image 5.4-5: Table settings 2

alphaSET, user manual, Version 2.07.00 5 Read meter data

Page 40 of 137

5.5

Read power quality monitoring

Select via Meter the menu item Read power quality monitoring or the following icon:

Image 5.5-1: Read power quality monitoring

The power quality profile of the meter can be read with this command. Structure and function mode are identically to chapter Fehler! Verweisquelle konnte nicht gefunden werden. Fehler! Verweisquelle konnte nicht gefunden werden. .

alphaSET, user manual, Version 2.07.00 5 Read meter data

Page 41 of 137

5.5.1

Graphical display of power quality data

With the selection Show power quality monitoring you get the data of the meter in a table and additionally a button to show this information graphically.

With this button you start the LP Analyzer tool and you get directly this following picture.

Image 5.5-2: Graphical data of power quality monitoring

Structure and function mode are identically to chapter 5.4.1 Graphical display of load profile data.

alphaSET, user manual, Version 2.07.00 5 Read meter data

Page 42 of 137

5.6

Read log file

Select via Meter the menu item Read log file or the following icon:

Image 5.6-1: Read logfile

Structure and function mode are identically to chapter Fehler! Verweisquelle konnte nicht gefunden werden. Fehler! Verweisquelle konnte nicht gefunden werden.. The representation of the logfile contains the date, the time and the event. According to the parametrization of the meter, one receives following entries: Power failure (3-phase or per phase) Power return (3-phase or per phase) Adjusting the time Functional error in the meter Demand reset Reset load profile and logbook Change energy/demand-tariff Backup time of real time clock exhausted Parameter change Season change terminal cover removal detection reverse run detection

alphaSET, user manual, Version 2.07.00 5 Read meter data

Page 43 of 137

Image 5.6-2: Data from logfile

alphaSET, user manual, Version 2.07.00 5 Read meter data

Page 44 of 137

5.7

Read log file 2

Select via Meter the menu item Read log file 2. With FW 5.20 of the A1350 and FW 7.00 of the A220 a second log file can be activated in the meter. In that case the following last 30 events can be read with alphaSET: Changes parameters (changes of meter configuration) Reset Register Reset load profile + logbook Reset power quality monitoring

Image 5.7-1: Data from logfile 2

alphaSET, user manual, Version 2.07.00 5 Read meter data

Page 45 of 137

5.8

Read meter error status

Select via Test the menu item Read meter error or the following icon:

5.8.1

Errors + Warnings

Image 5.8-1: Read meter error status

With the reading of the error status of the alpha meter, the possible error messages are listed. If a malfunction of the meter exists, this is indicated through a large red box in front of the error message. Little green boxes indicate on the other hand that no error exists. In this window the following two buttons can be used: Close The window closes and leads back to the main window Read meter error Reads the meter once again

alphaSET, user manual, Version 2.07.00 5 Read meter data

Page 46 of 137

5.8.2

Power Quality Supervision

To check the Power Quality Supervision upper and lower limits.

Image 5.8-2: Power Quality Supervision

alphaSET, user manual, Version 2.07.00 5 Read meter data

Page 47 of 137

5.8.3

Error Messages

To read the errors from the registers.

Image 5.8-3: Read meter error messages

alphaSET, user manual, Version 2.07.00 5 Read meter data

Page 48 of 137

5.8.4

Status Messages

This tab shows the status of the resources of the meter. The blue box indicates that the resource is not used, and the yellow box indicates that the resource is already in use.

Image 5.8-4: Read meter status messages

alphaSET, user manual, Version 2.07.00 5 Read meter data

Page 49 of 137

5.8.5

Print

In the Print card, are configured the settings for printing. The 4 cards described before can be printed: Errors + Warnings, Power Quality Supervision, Error Messages and the Status Messages.

Image 5.8-5: Set Print configuration

alphaSET, user manual, Version 2.07.00 5 Read meter data

Page 50 of 137

5.8.6

Options

The options for visualizing the errors and warnings can be set in this card. Read error+status out of meter classes and registers. Reads both options of error + warnings from the meter. To read with this option, the user password is required. Read error+status only out of meter classes. Reads only the error and status from the classes. It also requires user password Read error+status only out of the registers. To make this reading, the user password is not needed.

Image 5.8-6: Read meter error+status, Options

alphaSET, user manual, Version 2.07.00 5 Read meter data

Page 51 of 137

5.9

Read communication protocol

Select via test the menu item Communication protocol or the following icon:

If you choose this menu item, you can see the protocol of the last communication between alphaSET and the meter.

Image 5.9-1: Read communication protocol

It is also possible to view old communication protocols of alphaSET. You just have to click on the date and time row on the left hand side and you will get this protocol.

alphaSET, user manual, Version 2.07.00 6 Configuration of the meter

Page 52 of 137

6
6.1

Configuration of the meter


Open a parameter file

Select via File the menu item Read parameter or the following icon:

If you choose this menu item, you can open the following files directly:

Image 6.1-1: File - Read parameter

alphaSET, user manual, Version 2.07.00 6 Configuration of the meter

Page 53 of 137

6.2

Save a parameter set

Select via File the menu item Save or the following icon:

This command enables the saving of the reading data over a dialogue window. Parameter file: The file is saved by standard with the ending .par. Register content: The file is saved by standard with the ending .rg. Load profile content: The file is saved by standard with the ending .lp. Log file entries: The file is saved by standard with the ending .log. Switch programs: The file is saved by standard with the ending .uhr. Comment: You can only save, if you have previously read the corresponding data. (Screen display).

alphaSET, user manual, Version 2.07.00 6 Configuration of the meter

Page 54 of 137

6.3

Configuration of a meter by using a configuration file

Select via File the menu item File with parameter -> meter .

Image 6.3-1: File with parameter ->meter

6.3.1

Switch point clock

With this menu, the settings of the switch point clock can be loaded out of a switch programfile (ending: .uhr) and will be sent into the meter. The Utility password is required before the start of the communication. Note: The internal structure of the Switch point clock remained in the A1500 or A1350 same as in the AEM500 meter. If the file, that is to be loaded to the meter, contains only one switch point clock, the obligatory check of the firmware version is cancelled. Therewith can even old switch point clock programs be loaded without problem to the new meter. It is to be respected generally on that, which the day types, the energy tariffs and the maximum tariffs of the meter also agree with the switch point clock program.

6.3.2

Settings (without PW + ID)

With this menu all setting parameters (parameters which can be changed without breaking the certification seal), except password and identification, can be loaded of a parameter file (ending: .par) and be sent to the meter. After input of the file name, a window, in which date

alphaSET, user manual, Version 2.07.00 6 Configuration of the meter

Page 55 of 137

6.3.3

Settings and parameterisations (without PW + ID)

Icon in the icon bar:

With this menu, all setting and parameter-parameters (except password and identification) can be loaded of a parameter file (ending: .par) and be sent to the meter. After input of the file name, a window, in which date and time are indicated, appears. After confirming with OK, the utility password is queried before the data are loaded into the meter. Comment: The parametrization-button must be pressed previously before the programming of the meter starts. 6.3.3.1 Parameter-file WITHOUT calibration-data (without PW + ID) This menu item is a service function and to use only in consultation with ELSTER. Here are all parameters (class 0 to 6) of the meter (except password and identification) are written, only the calibration-data remain unchanged. This process is only possible with a special ELSTER password and requires no renewed calibration of the meter. 6.3.3.2 Parameter-file WITH calibration-data (without PW + ID) This menu item is a service function and to use only in consultation with ELSTER. Here are all parameters of the meter (except password and identification) written, also the calibration-data are changed. This process is only possible with a special ELSTER password and requires a new calibration of the meter.

alphaSET, user manual, Version 2.07.00 6 Configuration of the meter

Page 56 of 137

6.4

Modify parameters

With the menu item Modify parameters of a meter or a file can be changed, saved, and loaded again into the meter. This menu item is first visible, if the configuration of the meter was read before (see chapter Fehler! Verweisquelle konnte nicht gefunden werden. Fehler! Verweisquelle konnte nicht gefunden werden.), or a file was loaded directly (see chapter 6.1 Open a parameter file). The menu items in the upper section are setting parameters. The menu items in the lower section are parameterisation parameter and requiring an activation of the parameterisation button. After an alteration, you have to confirm the respective menu item with OK in order to send these new parameters to the meter. The following query appears:

Image 6.4-1: Data transfer

With a Yes the data are written directly into the meter. With a No this process is not executed, but that data are taken over into the database of alphaSET. This is the general flow in the change of parameters. The exact description to the single parameters themselves follows in the following chapters.

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 57 of 137

Change of meter configuration

Select the menu item Modify.

Image 7-0: Menu item Modify

This menu item is first visible if the configuration of the meter was read before (see chapter Fehler! Verweisquelle konnte nicht gefunden werden. Fehler! Verweisquelle konnte nicht gefunden werden.) or a parameter set was read by a file. The menu items in the upper section are setting parameters. The menu items in the lower section are parameterisation parameter and requiring an activation of the parameterisation button. Note: The menu entries of Modify are depending to the firmware version of the meter.

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 58 of 137

7.1

Identifications

Select via Modify the menu item Identifications.

Image 7.1-1: Identifications

The following parameters can be modified in this window:


Utility password 1 Utility-identification #1 Utility-identification #2 Utility-identification #3 Utility-identification #4 Utility-identification #5 Utility-identification #6 IEC 1107-identification (=Answer of the meter on the request telegram) e.g. : read register S: 13:36:29,09 -- /?!<CR><LF> E: 13:36:30,43 -- /ABB5\@V4.10 <CR><LF> S: 13:36:30,64 -- <ACK>050<CR><LF> E: 13:36:31,17 -- <STX>1-1:F.F(00000000)<CR><LF>

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 59 of 137

Note: \ and @ are firmly given indications, 14 further indications can be parametrized by the user. IEC 1107-address #1 (opt.) IEC 1107-address #2 (electr. 1) IEC 1107-address #3 (electr. 2) e.g. : read register S: 13:54:05,78 -- /?0000001234567890!<CR><LF> E: 13:54:07,67 -- /ABB5\@1234567 <CR><LF> S: 13:54:07,87 -- <ACK>050<CR><LF> E: 13:54:08,40 -- <STX>1-1:F.F(00000000)<CR><LF>

After clicking the button OK the following security query appears Do you want to transfer the modified data to the meter?. "Yes" writes the changes into the meter, "no" breaks off the menu, the data are however saved in alphaSET. Cancel" causes the leaving of the window. Note: With the IEC1107 address the leading zeros or blanks are suppressed. They are sent to the meter by alphaSET, but the meter ignores them.

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 60 of 137

7.2

Tariff source

Select via Modify the menu item Tariff source.

Image 7.2-1: Tariff source up to FW 4.01

Image 7.2-2: Tariff source from FW 4.10

Starting with the firmware version 4.10 it is possible to set the tariff source independently for energy and demand. Three options are available here: External control inputs Internal ripple receiver Internal switch point clock By clicking on the button OK appears the security query Do you want to transfer the modified data to the meter?. "Yes" writes the changes into the meter, "no" breaks off the menu. Cancel" causes the leaving of the window.

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 61 of 137

7.3

Switch point clock

Select via Modify the menu item Switch point clock. The settings of the switch point clock in the meter can be indicated and changed here.

7.3.1

Day type

Select via Modify the menu item Switch point clock -> day type.

Image 7.3-1: Menu Switch point clock

The weekdays can be summarized to corresponding groups in the field day type. The selection of the types takes place via the activation of the corresponding boxes. The fields with the designations day type 1/2/3/4 can be edited. An eight-place switch-program-number is assigned to each switch-program in the corresponding field, which can be modified. All chars, which can be displayed in the 7segment-display of the meter ( 0..9,A,C,E,F,H,J,L,P,S,V,Y), are valid. In the field comment exists the possibility to enter free text. Though, this is not written in the meter, but only in the saved file. With the command save as file the switch-program can be saved. The command read from file loads an existing switch-program (file with the ending .uhr). The command print prints the complete switch-program including day-type- and seasondefinitions.

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 62 of 137

By clicking on the button OK appears the security query Do you want to transfer the modified data to the meter?. "Yes" writes the changes into the meter, "no" breaks off the menu. Cancel" causes the leaving of the window.

7.3.2

Season change

Select via Modify the menu item Switch point clock -> Season change.

Image 7.3-2: Season change

In the field seasons the number of the seasons can be defined as well as their start date (the field of the seasons name can be edited). 1, 2 or 4 seasons can be arranged and distributed as desired over a total calendar year. They can even occur repeatedly in the total calendar year. Procedure: To register a season in the calendar, the field season 1 must be clicked (above green). Subsequently a black arrow marks the activation. Now clicking on the corresponding days must mark only the beginning and ending day of the season. With this menu structure, arises a higher flexibility, which permits for example to bind switch-programs of the season 1 within the season 3 of the 9.-16. July.

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 63 of 137

7.3.3

Tariff switch table

Select via Modify the menu item Switch point clock -> Tariff switch table.

Image 7.3-3: Switching times

In this submenu are the actual settings of the different switching times taken. In the indicated table stands T for energy tariff, M1 until M4 for the different demand tariffs, R1 and R2 for the two output relays (as far as these functions are parameterised like this). The different energy and demand tariffs can now be assigned individually to the switching times and their validity (defines over the season and the day type). The following buttons are available: Release locks: The check of alphaSET, whether T1-T4, M1-M4 and relay 1/2 are valid is unmade. Recommendation: Let this checkbox always deactivated. Accept: The changes concerning the selected switching time are transferred into the table. New: A new switching time is transferred into the table. The time of an available entry must be blocked first to be able to carry out this function. Delete: A designed entry is removed from the table. Comment: To each season and to each day type, a time entry is generated automatically at 00:00 clock. The user has to indicate the corresponding energy and/or demand tariff.

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 64 of 137

7.3.4

Holiday-list

Select via Modify the menu item Switch point clock and there the register card Holidaylist.

Image 7.3-4: Holiday-list

All defined holidays are displayed in the table. With the pull-down-menu holiday list the selection of already recalculated holidays can be activated. The number of years, which should be calculated for each holiday, is indicated in the field "years". According to the number of the switching times and holidays, ca. 15 years can be saved in advance. With the check box cyclic one receives the possibility to define recurring holidays (e.g. 01.01. -> new year). If this option is not selected, one receives the possibility to indicate day, month and year of a fixed holiday (e.g. Easter Sunday). The following buttons are available: Accept: The changes concerning the selected holiday are transferred into the table. New: A new holiday is transferred into the table. Delete: A designed entry is removed from the table.

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 65 of 137

7.3.5

Daylight saving time

Select via Modify the menu item Switch point clock -> Daylight saving time.

Image 7.3-5: Summer/winter time switch

In this menu can the summer/winter time-switch either be deactivated, aligned at the EU standard or, in the setting "user defined", be defined in the indicated tables.

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 66 of 137

7.4

Switch point clock (Update)

Select via Modify the menu item Switch point clock (Update). A second switch point clock can be defined in the meter (with FW 5.10 of A1350, FW 7.00 of A220 and the FW of AS220/AS253/AS1253/A1440.). At a predefined date the second tariff table will be activated and valid for the rest of the time. All data have to be defined in the same way as the first switch timetable.

7.4.1

Day type

Select via Modify the menu item Switch point clock (Update) -> day type.

Image 7.4-1: Second tariff table

Date of update The activation date (at 00:00) of the second tariff table has to be defined here.

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 67 of 137

7.5

Times

Select via Modify the menu item Times. Different possibilities to change the time base or communication timeout are offered:

7.5.1

Source of Times

Select via Modify the menu item Times -> Source of time.

Image 7.5-1: Real time clock

In this menu the user can define whether the network frequency or the quartz frequency is supposed to be used for the time of the internal real time clock of the meter. Notes: In general, the setting quartz is to be recommended because the quartz inserted are highly exact and temperature stable (< 5 ppm). Especially in use of a DCF-synchronization of the measuring period is it recommended to select the setting quartz. This is because the network frequency can vary and it can lead therefore to undesirable time set (in synchronization) with corresponding entries in the load profile. It is recommended to use line for meters that are not synchronized, because the temporal deviations are countervailed with the time. Therewith, the time doesnt run away. Whether these parameters are set parameters or parameterisation parameters depends on the firmware version of the meter which works at the moment with the alphaSET: Until including FW version 3.05 these are parameterisation parameters, from FW version 4.00 these are set parameters.

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 68 of 137

By clicking on the button OK appears the security query Do you want to transfer the modified data to the meter?. "Yes" writes the changes into the meter, "no" breaks off the menu. Cancel" causes the leaving of the window.

7.5.2

Display Timeouts

Select via Modify the menu item Times -> Display Times.

Image 7.5-2: Display timeouts

In this menu the user can define the display scroll time and the timeout for the alternate mode. After the alternate time out exceeds the limit, the meter goes back automatically in the scroll mode.

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 69 of 137

7.5.3

Communication Timeouts

Select via Modify the menu item Times -> Communication Times.

Image 7.5-3: GPRS communication timeout

Notes: According the IEC1107 standard the maximum communication timeout between 2 characters is 1,5s. For GPRS application the maximum timeout between 2 characters has to be increased. The suggestion is to use in that case a timeout of 6s.

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 70 of 137

7.6

Demand reset

Select via Modify the menu item demand reset.

Image 7.6-1: Demand reset

In this menu, the possible sources for the triggering of a maximum demand reset can be released or blocked. Settings, which are not selectable, have a grey background. The day within a month, at which the maxima demand reset should take place, can be defined with the button every month on the... at 0.00 PM. Moreover the duration of the reset lock time can be adjusted. The reset lock time is only active by activation over the same reset lock source. By clicking on the button OK appears the security query Do you want to transfer the modified data to the meter?. "Yes" writes the changes into the meter, "no" breaks off the menu. Cancel" causes the leaving of the window.

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 71 of 137

7.7

Demand overload

Select via Modify the menu item Demand overload. Depending on the meter firmware-version you will have up to three tabs to parametrize: Load limitation Demand overload Threshold value tan(phi)

7.7.1

Load limitation

IImage 7.7-1: Control of disconnect relay

Since firmware version 8.00 it is possible, to insert a disconnect relay. On the tab you can set the measuring value, that is responsible for the disconnection or <none>. If a value is selected, the threshold value, that causes the disconnection, can be set. With the scroll bar the delay time can be set, the measuring value can be larger than the threshold value with impunity.

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 72 of 137

7.7.2

Demand overload

IImage 7.7-2: Demand overload

The user has the possibility to configure one or two outputs of the meter, so that by exceeding of a specific demand threshold an output contact is opened and/or closed (NOT the diosconnect relay!). The overload threshold 1 refers always to the measuring channel 1 of the meter. The overload 2 can be set on every defined measuring channel of the meter. At the start of a demand period, the output contact is either opened or closed (if it is parameterised). By exceeding the threshold the output contact is closed (opened). Starting with the FW version 4.40 it is additionally possible to enter a threshold value for the tan(phi). Note: The format of the overload threshold is the same as for the demand values. Up to FW version 4.00 only one overload threshold can be parameterised, since then two. Only since firmware 4.20 is it possible to configure overload threshold 2 freely.

7.7.3

Threshold value tan(phi)

IImage 7.7-3: Threshold value tan(phi)

In this tab (available for the firmware-versions 5.31 and 9.xx) a threshold value for the tan(phi) Q1 or Q4 can be set. If exceeded, a warning can be set onto an output.

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 73 of 137

7.8

Baud rate

Select via Modify the menu item Baud rate

Image 7.8-1: Baud rate

In this menu the start baud rate or either the maximum baud rate of the meter can be selected, separated between optical or electrical interface. Further baud rates can be selected by a click on the pull-down-arrows. With the FW version 4.40 of the A1500 a second electrical interface is available. For this case it is possible to set the priorities of this interfaces (only available, if the type key at position 24 is set to T, u or X). It is also possible to choose if the meter can only be addressed with its IEC-address. Note: If the start baud rate of an interface in the meter is changed, the baud rate for the communication must be changed after writing into the meter, too. (See chapter 4.1 Communication).

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 74 of 137

7.9

DLMS Parameters

Select via Modify the menu item DLMS Parameters

Image 7.9-1: Measuring Energy / Demand

Here the DLMS parameters can be modified. The DLMS address is fixed for the Certification profile. The DLMS baud rate can be selected from the list. The Quantity of address bytes, the Inter oktett time out, the Inactivity time out and the Time window for IEC1107 communication can be modified with the arrows at the right. The changes can be saved or discarded before closing the menu. To restore factory values click the button Reset parameters to factory settings:

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 75 of 137

7.10 Synchronization
Select via Modify the menu item Synchronization.

Image 7.10-1: Synchronization

In this menu the mode of the demand period synchronisation as well as the synchronisation of the meter clock can be defined by using an integrated ripple receiver, an internal DCF77-clock or an external control input. The image offers the following adjustment possibilities: None To next interval: recommended if a control input (MPE Kl. 16) to the measuring period synchronization is used by an external synchronization pulse. To next minute: recommended with reservation if an externally produced DCF pulse is used by an external control input for the synchronization of the measuring period. With interval to reference-time: recommended in synchronization over ripple receiver. In selecting the point With interval to reference-time appears a menu, in which the reference time and the time window of the synchronization can be adjusted.

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 76 of 137

Set date/time by DCF 77-antenna input: recommended by using the pulse input 1 as a DCF77 antenna input. (A DCF77antenna must be connected to the pulse input 1). By activation of this feature the internal meter clock will by synchronized every 5 minutes after a full hour, after power up or by activation of the meter test mode. Note: After activation of the DCF 77 antenna input the meter will generate a warning FF2 1000000 until a correct time/date information is decoded. A DCF77 decoding can be activated by a formatted command too.

By clicking on the button OK appears the security query Do you want to transfer the modified data to the meter?. "Yes" writes the changes into the meter, "no" breaks off the menu. Cancel" causes the leaving of the window. Note: DCF 77 decoding is available from meter with firmware version 4.00.

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 77 of 137

7.11 Backup time of the real time clock


Select via Modify the menu item Backup time of real time clock.

Image 7.11-1: Backup time of real time clock

In order to be able to build a battery into the meter subsequently, there is the possibility to change the default settings from supercap to battery. Note: This is first possible from FW version 4.00 of the meter. The rating plate of the meter must be removed to install the Battery.

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 78 of 137

7.12 Inverting Inputs/Outputs


Select via Modify the menu item Inverting Inputs/Outputs .

Image 7.12-1: Inverting Inputs / Outputs

With this menu it is possible to invert inputs and outputs by activating the checkboxes. This is possible with firmware version 4.30 and higher.

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 79 of 137

7.13 Power quality


Select via Modify the menu item power quality.

7.13.1 Release of power quality functionality

Image 7.13-1: Release power quality values

In this menu you have the possibility to release the measurement of the power quality values, which can then be read over the service list or which or are available for the power quality profile.

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 80 of 137

7.13.2 Load profile of power quality data


In this menu the settings of the power quality monitoring can be configured.

Image 7.13-2: Power quality monitoring data

The following parameters can be assigned: Assignment of load profile channel number and quantity Storage type of every channel Average value over the period of the power quality data Minimum value inside the period of the power quality data Maximum value inside the period of the power quality data Duration of the load profile period (1..60min) Notes: The max. Duration of the load profile of the power quality data depends on the duration of the billing data load profile and cannot be changed in this menu. This duration depends on the measure period and the number of channels. The OBIS identifier for the load profile channels will be assigned automatically. The different power quality measurements have to be activated in the menu Release power quality values, to be used here.

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 81 of 137

7.13.3

Power Quality Monitoring

In this menu the settings of the power quality monitoring can be configured.

Image 7.13-3: Power quality monitoring

The following parameters can be assigned: Assignment of power quality data to a register Definition of a upper and / or lower limit Measuring interval (1..60min) The FW 5.10 and FW 4.40 offer additional features to observe the network regarding power quality issues. Therefore up to 18 different counters with up to 18 thresholds can be activated to detect the occurrence, if a power quality value is above or below a predefined threshold during a user programmable period (1, 2, 3, 4, 5, 6, 10,12, 15,20, 30, 60 minutes). Furthermore 2 log file events and 2 relay contacts can be activated if 1 or more events will be above or below the predefined threshold. Additionally with the logic OR / AND operation you are able to combine the different information of the thresholds.

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 82 of 137

7.14 Copper-/Iron-losses
In this menu the definitions for the transformer and line loss calculation can be configured. This feature is only supported with the FW 4.30 of the A1500 and A2500.

Image 7.14-1: Copper and iron losses

The following parameters can be assigned: Constant R of the transformer loss calculation Constant X of the line loss calculation Decimals for the transformer loss register Decimals for the line loss register

To display the transformer and line loss register on the LCD or optical/electrical interface the value has to be assigned to the display list. For the right function you have to select your nominal voltage and current of your meter. The internal algorithm needs this information to calculate with the decimals the overflow boundary.

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 83 of 137

7.15 Meter Access Rights


With the FW 4.40 (A1500), FW 5.20(A1350), FW 7.00(A220), FW 8.00 (AS220 / AS253) and FW 9.00 (A1440/AS1253) the meter offers an advanced access protection with the following features: Up to 3 user passwords Separate access matrix for Optical interface Electrical interface 1 Electrical interface 2 (if available)

Select via Modify the menu item Meter Access Rights:

Image 7.15-1: Password 3 is needed for this menu item

To reach the configuration matrix, type in the password 3. Then you will get a list of all functions of the meter and you are able to decide which access rights each function will have, even for each interface.

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 84 of 137

Image 7.15-2: Configuration matrix for meter access rights

If you set a cross, you have access with the right password / set mode / para button. Note: If you dont set a cross at the passwords row, you dont have access at all. In the following statement you see the logical interconnection of the passwords, set mode and para button.

This icon sets the crosses of the matrix back to the factory settings.

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 85 of 137

7.16 Display
The parameter settings of the display are divided in two menu items. Service list Dispay parameter

Note: With the FW version 4.20 a second settable display list (service list) was added to the meter.

7.16.1 Service list


Select via Modify the menu item Service list.

Image 7.16-1: Service list

This service list is additional to the alternate list. In the display of the meter you will find it via the symbol Abl-data. Basically the list is blocked, but can be released since firmware version 4.10 of the meter by selecting the checkbox "The service-list IS released. The handling of this service list is identical with chapter 7.16.2.1 Display list with the exception that there is no display of data in the scroll mode.

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 86 of 137

Explanation: No.: Me: Ch ID-Code: wU: AM: wP: SP:

Consecutive number (automatically set). medium of the displayed value channel number of the displayed value ODIS-ID (firmly assigned after standard) Display with Unit (freely selectable) Display in alternate mode (freely selectable) Display with historical billing data (freely selectable) Display (with historical values) in the display sequence (scroll-historicalValues) (freely selectable) D1: Display date/time in one line (firmly assigned through parameter set) op: Output over optical interface (freely selectable) el: Output over electrical interface (freely selectable) Description: Explanation to the display value

The following buttons are required for changing the display table:

Creating a new entry in the display table.

Copying of the marked area of the display table (also new entries can be generated on this basis) Takes the changes over into the indicated display table

Automatic sorting of the table

Deletes the marked display entry

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 87 of 137

7.16.2 Display parameter


7.16.2.1 Display list

Select via Modify the menu item Display parameter -> Display list.

Image 7.16-2: Display list

The register values with the associated IDs can be selected here. It is possible to chose scrollmode (SM), alternate mode (AM), the optical (OP) and/or electric interface (EL). The handling of this display list is identical with chapter 7.16.1 Service list with one addition: SM: Display in scroll-mode (freely selectable)

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 88 of 137

7.16.2.2

General settings of the display

Select via Modify the menu item Display parameter and there the register card Control.

Image 7.16-3: General settings of the display

In this menu you are able to set the following parameters: total number / number of digits / unit for the energy register data total number / number of digits / unit for the demand register data total number / number of digits / unit for the cumulative register data using medium&channel for OBIS identifier reading data with/without units time&date format

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 89 of 137

7.16.2.3

Configuration of historical values

Select via Modify the menu item Display parameter and there the register card Hist. Values.

Image 7.16-4: Configuration of historical values

In this menu can the maximum number of historical values and the number of values for the different medium (optical/electrical interface or alternate list) be defined.

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 90 of 137

7.17 Pulse constants


Select via Modify the menu item Pulse constants.

Image 7.17-1: Transformer ratio

The user is able to select the measurement type: secondary or primary measurement. By using the primary measurement the current and voltage transformer ratio is included in the energy and demand measurement results of the meter. Furthermore it is possible to define the pulse constant of the LED and the relay output of the meter. Additionally the pulse duration of the pulse output can be defined in multiple of 8ms.

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 91 of 137

7.18 Pulse inputs


Select via Modify the menu item pulse inputs

7.18.1 Pulse inputs tabs.


One for each available pulse input in the meter. The maximum available is 4.

Image 7.18-1: Pulse inputs

The user has, by standard, 1 pulse input at disposal (with disuse of the DCF-input). 3 further pulse inputs can be used if an optional conductor board is used in the meter. The inputs accord to the SO-standard. An own pulse constant can be assigned to the pulses of the pulse inputs. The summation of the input pulses is stored in a separate register and is included in the standard reading list of the meter. The following functions are available: Measuring period synchronization input, which must be controlled by a relay (Attention! No connection to 230V possible). Check of opening terminal cover (optional): A removing of the terminal cover can be detected with this input. A reed relay is positioned at the terminal cover, which bypasses the input. If the cover is removed, an entry in the log file occurs and the corresponding meter is incremented. A warning appears in the display, which can only be removed by using the interface. F.F.1: 00010000 Pulse input: pulse constants and number of decimals are freely selectable.

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 92 of 137

Summation to internal: The pulse input could be added to the register of measuring block 3. The pulse constant is freely selectable; measuring block 3 specifies the number of decimals.

Note: Pulse input 1 can also be used as DCF-input and is then deactivated at this place.

7.18.2 Summation tab

Image 7.18-2: Summation

Every pulse input can be configured to be added with internal measurement of +P, -P, +Q or -Q. In the upper part of this tab it is to be select, which summation block will be the used and which inputs will be added to this summation block. Additionally in every summation block an internal value can be added with the pulse inputs.

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 93 of 137

7.19 Load profile / logfile - parameter


7.19.1 Load profile parameter
Select via Modify the menu item Load profile / log-book parameter. In the first register card the measuring quantities can be assigned to the load profile channels. A plausibility check of the parameters takes place before the image appears: Are all necessary parameters for the parametrization loaded into the alphaSET? Is the load profile generally released? Is the load profile released in the type key? Is a VDEW-load profile parametrized? The form is not indicated and an error message appears instead, if one of these tests leads to a negative result.

Image 7.19-1: Load profile parameter

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 94 of 137

The final layout of the window depends on the configuration of the meter: How many and which measuring channels has the meter? Perhaps not all channels shown above (=lines) are visible! Which Quantity is measured by the meter? Perhaps not all quantities shown above (columns) are visible How much place is yet available in the display table? Possibly is the number of the channels reduced for this reason. In the upper part of the form the assignment of the channels with the measuring quantity can be done. The OBIS identifier belonging to the measuring channel are adapted automatically (and automatically registered into the display table). The OBIS identifiers ending can be chosen between 5 or 25 in average demand, or between 9 or 29 in energy per measuring period. Note: If the load profile should store energy register values the number of days of load profile is going down, because these values need more memory space. Memory Size of Load Profile: The Load profile Size for the billing data can be set here. According to VDEW Specifications at least 40 days are necessary. The remaining memory is available for the power quality monitoring. For more information see chapter 7.13.2

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 95 of 137

7.19.2 Log file parameters


At the second register card the assignment of the logfile parameters can be done.

Image 7.19-2: Log file - parameter

In addition to the standard logfile entries like power outage, power up, time&date change, etc. the user has the possibility to store the following events: Switching of energy and demand tariffs Single phase power outages Cover opening alarms

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 96 of 137

7.20 Energy / Demand measuring


Select via Modify the menu item Measuring Energy / Demand.

Image 7.20-1: Measuring Energy / Demand

In this menu the length of demand period can be defined in the range of 1 to 60 minutes. Further a choice of the detach time is possible, corresponding to the requests from 0 to 63 seconds. For the switching of demand and energy you are able to select , if it should be done immediately or delayed

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 97 of 137

7.21 Passwords
With the FW 4.40 (A1500), FW 5.20(A1350), FW 7.00(A220), FW 8.00 (AS220 / AS253) and FW 9.00 (A1440/AS1253) the meter offers an advanced access protection with up to 3 user passwords. Select via Modify the menu item Passwords:

Image 7.21-1: Passwords change 1

To get into this menu to change the password you have fist to type in the password 3.

Image 7.21-1: Passwords change 2

Here you are able to change all passwords of the meter. To download the changes to the meter you have to secure, that you have the access rights to do this. You can check this in the access matrix:

alphaSET, user manual, Version 2.07.00 7 Change of meter configuration

Page 98 of 137

7.22 Show settings


Select via Modify the menu item Show settings or the following icon:

With this function, the current state of the database of alphaSET can be indicated. All changes that you have made (and perhaps also not yet have written into the meter) are updated here.

alphaSET, user manual, Version 2.07.00 8 Formatted Meter Commands

Page 99 of 137

Formatted Meter Commands

Select the menu item Meter commands.

Image 8-1: Menu Meter commands

With this menu, formatted commands can be sent at the meter. It is distinguished in: Set commands (with use of a password) Set meter date / time Read / Set Date / Time (VDEW) Read / Set pulse constants Set outputs Control of disconnect relay Activate DCF clock Reset demand Maxima (W1 command) Reset demand Maxima (E2 command) Reset meter error state Reset power quality monitoring Reset Power Quality Supervision Counter Reset power loss power Reset terminal open counter Parameterisation commands (with use of a password and the parameterisation switch) Reset register Set register values (pulse inputs) Reset load profile and log file Note to the user profile "Railway": The meter command Set train code is supported additionally in the user profile Railway.

alphaSET, user manual, Version 2.07.00 8 Formatted Meter Commands

Page 100 of 137

8.1

Set meter date/time using the W2 command

Select via Meter commands the menu item Set meter date/time or the following icon:

Image 8.1-1: Meter date/time

In this menu date and time of the meter can be changed. The date is divided into day, month and year, the time into hour, minute and second. Furthermore is it possible to send the current time of the PC to the meter. Use manually edited time The stored PC time is sent to the meter. Use actual PC time The current PC time is sent to the meter. The clock keeps running invisible if changes in the time window are done.

The button Set accepts the adjusted data and the button "Cancel" ignores the last command and leads back to the main menu. Note: The Offset of the data transmission time of about 4 seconds is considered automatically. This process is realized with the W2-command.

alphaSET, user manual, Version 2.07.00 8 Formatted Meter Commands

Page 101 of 137

8.2

Read and Set time/date using the VDEW command

Select via Meter commands the menu item Read/Set date/time (VDEW).

Image 8.2-1: Read/Set date/time (VDEW)

In this menu, date/time can be read and/or set in accordance with VDEW-requirements (W5command) by using the R5- or W5 command. For further information see chapter 8.1 Set meter date/time.

alphaSET, user manual, Version 2.07.00 8 Formatted Meter Commands

Page 102 of 137

8.3

Setting of pulse constants

Select via Meter commands the menu item Read/Set pulse constants.

Image 8.3-1: Setting of pulse constants

In this menu, the pulse constants for outputs for the LED and the electronic outputs of the meter can be changed with use of the certified log file. Therefore the actual constant will be read, changed and downloaded to the meter. In the log file the change will be registered with time / date stamp and with old and new constants. The actual pulse constant is additionally displayed in the display. Note: The meter will accept this command only in the case if the certified log file is enabled.

alphaSET, user manual, Version 2.07.00 8 Formatted Meter Commands

Page 103 of 137

8.4

Setting of outputs

Select via Meter commands the menu item Set outputs.

Image 8.4-1: Set outputs

With the FW 7.00 (A220) the meter offers a function to set up to seven outputs of the meter. It is possible to set the output as static OFF, static ON and dynamic, with a selectable pulse length. It depends on the meter hardware and parametrization, how many outputs are available for setting.

alphaSET, user manual, Version 2.07.00 8 Formatted Meter Commands

Page 104 of 137

8.5

Control of Disconnect Relay

Select via Meter commands the menu item Control of Disconnect Relay .

Image 8.5-1: Control of Disconnect relay

If a disconnect relay is installed in the meter, it can be directly controlled with a meter command via this menu item. It can be set statically OFF or ON. Or it can be set ARMED, that means the Control of Disconnect Relay is actice, Please, look into chapter 7.7.1, "Load limitation.

alphaSET, user manual, Version 2.07.00 8 Formatted Meter Commands

Page 105 of 137

8.6

Activation of DCF 77 signal decoding

Select via Meter commands the menu item Read out DCF clock.

Image 8.6-1: Read out DCF clock

After receiving this command the meter will activate the DCF77 decoding at once. Otherwise it will be done only every 5 min after a full hour, or after a power up.

Note: The DCF77 function of the meter possesses the following characteristics: The acceptance of the DCF time follows only after a correct decoding from 2 behind another following correct time telegrams The decoding of time & date follows after power up or after every 5 min after each full hour. With an incorrect decoding a warning message appears on the display, which is automatically deleted with the next correct decoded telegram.

alphaSET, user manual, Version 2.07.00 8 Formatted Meter Commands

Page 106 of 137

8.7

Reset maximum demand (W1 or E2)

Select via Meter commands the menu item Reset demand maxima or the following icon:

Image 8.7-1: Reset demand maxima

With yes the meter will directly execute a demand reset, no causes the abort of the function and leads back to the main menu, which shows all actual data of energy and demand measurement as historical data.

alphaSET, user manual, Version 2.07.00 8 Formatted Meter Commands

Page 107 of 137

8.8

Reset meter error status

Select via Meter commands the menu item Reset meter error state or the following icon.

Image 8.8-1: Reset meter error state

With yes the error state of the meter will be reset, no causes the abort of the function and leads back to the main menu. Note: The parameterisation mode is left with this command. Fatal fault messages cannot be put back thereby!

alphaSET, user manual, Version 2.07.00 8 Formatted Meter Commands

Page 108 of 137

8.9

Reset power quality monitoring

Select via Meter commands the menu item Reset power quality monitoring:

Image 8.9-1: Reset power quality monitoring

With yes the load profile of the power quality quantities of the meter will be reset, no causes the abort of the function and leads back to the main menu. The load profile for the billing data is not influenced thereby.

alphaSET, user manual, Version 2.07.00 8 Formatted Meter Commands

Page 109 of 137

8.10 Reset power quality supervision counter


Select via Meter commands the menu item Reset power quality supervision counter:

Image 8.10-1: Reset power quality monitoring

With yes this counter will be reset, no causes the abort of the function and leads back to the main menu.

alphaSET, user manual, Version 2.07.00 8 Formatted Meter Commands

Page 110 of 137

8.11 Reset power-loss counter


Select via Meter commands the menu item Reset power-loss counter.

Image 8.11-1: Reset power loss counter

With yes the following counters (if parameterised in the meter) will be reset, no causes the abort of the function and leads back to the main menu. C7.0 C7.1 C7.2 C7.3 C.52 C.53 C.54 C.55 C.56 Number of total power losses Number of power losses in phase 1 Number of power losses in phase 2 Number of power losses in phase 3 Beginning date of the last total power loss Beginning time of the last total power loss End date of the last total power loss End time of the last total power loss Total duration of all power losses in minutes

alphaSET, user manual, Version 2.07.00 8 Formatted Meter Commands

Page 111 of 137

8.12 Reset terminal cover open counter


Select via Meter commands the menu item Reset terminal open counter.

Image 8.12-1: Reset terminal open counter

With yes this counter will be reset, no causes the abort of the function and leads back to the main menu.

alphaSET, user manual, Version 2.07.00 8 Formatted Meter Commands

Page 112 of 137

8.13 Reset register


Select via Meter commands the menu item Reset register or the following icon:

Image 8.13-1: Reset register

With yes all register values of the meter will be resetted, no causes the abort of the function and leads back to the main menu. Note: The parameterisation button must be pressed, before this function can be executed.

alphaSET, user manual, Version 2.07.00 8 Formatted Meter Commands

Page 113 of 137

8.14 Set register values (pulse inputs)


Select via Meter commands the menu item Set register values (pulse inputs).

Image 8.14-1: Set register values (pulse inputs)

The initial condition of the pulse register can be set with this menu item. The meter accepts this command only if the pulse inputs are defined as set parameters. The meter has no notarisation in this case.

alphaSET, user manual, Version 2.07.00 8 Formatted Meter Commands

Page 114 of 137

8.15 Reset load profile + logbook


Select via Meter commands the menu item Reset load profile + logbook or the following icon:

Image 8.15-1: Reset load profile + logbook

With yes is load profile and logbook reset, no causes the abort of the function and leads back to the main menu. Note: The parameterisation switch must be pressed, before this function can be executed.

alphaSET, user manual, Version 2.07.00 9 Integrated Ripple receiver (LCR)

Page 115 of 137

Integrated Ripple receiver (LCR)

Select via LCR the menu item Switch to ripple receiver

Image 9-1: Switch to ripple receiver

In this menu, the duration of LCR-mode is specified in minutes. The values of 1 to 255 minutes are allowed whereby the selection of 255 minutes means, that the optical interface is uninterrupted connected with the integrated ripple receiver (e.g. status recording with LCRSET or SCAN). The LCR-mode serves for the communication of the internal ripple receiver over the optical interface. The meter is switched in the LCR-mode for the selected time by activation of the button OK, that means, that over the optical interface can directly be communicated with the LCR. The communication with the LCR module of the meter can now take place by the parametrization software of the receiver (CFIG, LCRset). The LCR mode can be left by long pressing of the function key (> 5 s) before the end of the selected duration. The menu is left with Cancel. Remark: LCR = load control receiver or ripple receiver.

alphaSET, user manual, Version 2.07.00 10 Test

Page 116 of 137

10 Test
Select the menu item Test.

Image 10-1: Test Menu

alphaSET, user manual, Version 2.07.00 10 Test

Page 117 of 137

10.1 Read meter error


See chapter 5.8 Read meter error.

alphaSET, user manual, Version 2.07.00 10 Test

Page 118 of 137

10.2 Power-Quality
Select via Test the menu item power quality.

10.2.1 Main display

Image 10.2-1: Power quality

In this menu the service list or the register data list which includes the instantaneous values of mains quantities like current, voltage, etc. can be readout manually or automatically in a predefined time interval. It is to be regarded that the register- or service list must contain the corresponding data. The missing values are marked with ? in the preceding example. One has the possibility to read the data per button or per an automatic reading with specification of the read cycles in seconds. For commissioning documentation purposes the fields Meter Serial No. and Utiliy ID #1..(if delivered in the service list or register data) and PC time are filled automatically. Additionally the fields Customer, Technician and Comment can be filled in manually. These informations were stored automatically in the text file, if button Save is selected. Depending on the settings in tab options, an arrow appears in the background of the graphics. It will be green and clockwise, if the rotating field is correct, or red and counter clockwise, if the rotating field is wrong.

alphaSET, user manual, Version 2.07.00 10 Test

Page 119 of 137

10.2.2 Options

Image 10.2-2: Power quality, Options

The OBIS-identifiers can be adjusted via Options. If the OBIS identifiers, used with the service list or register data, are not the standards, the numbers must be corrected. Additionally the nominal voltage and current can be changed, in order to standardize the diagram correlatively: if the arrows in the main tab are out of sight or too small, these values shall be set (and saved automatically in the user INI file). If a parameter set is read before,, always THIS values are used at first entry of the menu item Power Quality.

alphaSET, user manual, Version 2.07.00 10 Test

Page 120 of 137

10.2.3 Print
With the tab Print it is possible to configure the printout of the graphics.

Image 10.2-3: Power quality, Print

alphaSET, user manual, Version 2.07.00 10 Test

Page 121 of 137

10.3 Test mode


Select via Test the menu item Test mode or the following icon:

Image 10.3-1: Test mode

With the test mode, the meter can be transferred occasionally into certain conditions in order to accelerate calibration sequences. Herewith, tariff sources can be changed or tariffs can be given directly. The pulse constants can furthermore be set to the maximal possible value, and the LED of the meter can be assigned to a measuring size. Parameterised delays are cancelled in this mode. The original settings are reconstructed after leaving the test mode. Note: The test mode is first active, if the settings were written into the meter. The command reset test mode must be sent before leaving the test mode. Alternatively to this the field test mode can be deactivated in the Test mode checkbox.

alphaSET, user manual, Version 2.07.00 10 Test

Page 122 of 137

Read settings for test mode

Set test mode

Send commands to meter: To simplify the test and/or the leaving of the test mode, a defined command sequence can be sent to the meter.

Leave this window

alphaSET, user manual, Version 2.07.00 10 Test

Page 123 of 137

10.4 Communication Protocol


See chapter 5.9 Read communication protocol.

alphaSET, user manual, Version 2.07.00 11 Modem

Page 124 of 137

11 Modem
To edit the modem menu, select via Extras the menu item Options, there in the register card Communication activate the option Phone book active. Then press OK.

Image 11-1: Settings register card Modem

A new option Phone book in the main menu appears.

Image 11-2: Settings register card Modem

alphaSET, user manual, Version 2.07.00 11 Modem

Page 125 of 137

11.1 Phone Book


Select via Phone book the menu item Edit phone book.

11.1.1 Phone book part 1


Here the user can set parameters on all modem functions of alphaSET. These are necessary for the communication over a meter modem.

Image 11.1-1: Phone book part 1

The first communications interface is the optical probe. By default is always set in the first position.

Image 11.1-2: Phone book part 1

To add a new modem, click in first left cell of an existing modem and the options for adding new rows appear. A new row below or over can be created. An existing one can be copied in a An existing Phone Book can be opened.

alphaSET, user manual, Version 2.07.00 11 Modem

Page 126 of 137

The current Phone Book can be exported into a file. The changes can be saved or discarded before closing this menu. The active communications interface is the one marked with the red arrow at the left. All of the following commands can be edited by double clicking in each of them. Modem The cross shows that the device is a Modem. Phone-No To configure the customers meter phone number. Here can the phone number be registered. If a telephone book is created, this entry automatically takes place after choice of the appropriate telephone book entry. Meter modem. To chose from a list the modem type. Modem PW To establish the modems password if any. IEC1107-Adr The communication address Util-PW To establish the utility password of the meter if any

11.1.2 Phone book part 2

Image 11.1-3: Phone book part 2

Here the settings for the communication of the modems added in the first card are configured. All of the following commands can be edited by double clicking in each of them. COM To choose the pc port in which the modem is connected. Start

alphaSET, user manual, Version 2.07.00 11 Modem

Page 127 of 137

Baud rate for the IEC1107 communication. Is mandatory for local communication, in modem mode this setting has to be done in meter modem. Reflx Enable/disable suppression of reflexions. Form Data format of the meter modem (normally 7 bits, Even, 1 stop bit). Hold Establish the time in seconds in which the connection should be maintained after the last communication from alphaSET between PC and connected modem. At the end of this timeout the connection is interrupted and the modem hangs up. Wake The characters that are required to send directly before the login to the meter. Line If necessary, take here the settings to get a local loop (e.g. 0). PC modem type Drop down menu in which the type of meter modem is selected. Locl-Bd In this drop down menu the baud rate between PC and (control point) modem can be adjusted. If its possible, select the highest one, which is supported by both. 8,N,1 Enable/disable 8 bits, no parity and 1 stop bit (8,N,1) as data format for local modem when necessary. The changes can be saved or discarded before closing this menu.

alphaSET, user manual, Version 2.07.00 11 Modem

Page 128 of 137

11.1.3 Phone book part 3

Image 11.1-4: Phone book part 3

Here is a list registered of Modems with their necessary initialization string, which is required for the communication between PC and PC-Modem. More modems can be added or edited by clicking in the left cell of any row. To restore the factory values press the factory button. The changes can be saved or discarded before closing this menu. Modem

alphaSET, user manual, Version 2.07.00 11 Modem

Page 129 of 137

11.2 Hang up
The phone connection with the selected modem ends with this activation.

alphaSET, user manual, Version 2.07.00 11 Modem

Page 130 of 137

11.3 Dial-up doesnt work! What to do?


In order to receive a functioning communication to the meter via modem, the following points to the dial-up should be checked: Is the COM-Port for the connected modem correct? Is the phone number, which is activated in the phone book, correct? Is the entered IEC-address of the meter correct? Is the initialization string of the modem, which is connected to the computer, correct? First test read register. Is the start baud rate in meter and modem the same? Does the called modem answer? Does the meter send data (see communication) ? Is the used utility-password correct ? Is the entered data format correct (7,E,1 ; 8,N,1) ?

alphaSET, user manual, Version 2.07.00 12 Extras

Page 131 of 137

12 Extras
12.1 Construction of a restricted menu system
Restricted Menu is used to generate a reduced version of alphaSET Select via Extras the menu item Restrict menu system Then select the path where the installation program is stored. Normally this program is in the installation CD.

Image 12.1-1: Construction of restricted menu. Path selecting

After selecting the path, click in save, so the application will remember the path to the installation program.

Image 12.1-2: Construction of restricted menu. Path selecting

After saving appears a Warning with the steps to follow for creating the restricted menu.

alphaSET, user manual, Version 2.07.00 12 Extras

Page 132 of 137

Image 12.1-3: Construction of restricted menu. Important information

A user profile should be chosen. This profile will be the base from which the new menu will be created.

Image 12.1-4: Construction of restricted menu. Profile selecting

After selecting the profile, every active menu of the chosen profile will be displayed in a list arranged by hierarchy.

Image 12.1-5: Construction of restricted menu. Restricted menu configuration

Each menu from the list can be enabled or disabled with the crosses, if you want to have it in

alphaSET, user manual, Version 2.07.00 12 Extras

Page 133 of 137

your new alphaSET version or not. At the bottom of the edit window is a box with the count of the active menus in the profile. It is possible to enable password protection for the new profile. Enable the check box and click in the Enter password button to give the password.

Image 12.1-6: Construction of restricted menu. Password protection

Once the new configuration is ready, the name of the user profile must be changed otherwise the base profile chosen at the beginning in the active path will be overwritten.

Image 12.1-7: Construction of restricted menu. Name of the new profile

Click OK to create the new profile. Cancel to discard the changes. With OK you get information of the path where the new version is stored. To generate an Installation CD this path should be completely copied in the CD.

Image 12.1-8: Construction of restricted menu. Making the new menu

alphaSET, user manual, Version 2.07.00 13 Help

Page 134 of 137

13 Help
In this menu you will find help for using alphaSet.

13.1 User manual alphaSet


Select via Help the menu item User manual alphaSet

Image 13.1-1: User manual alphaSet

By selecting this menu this user manual in .pdf format will be automatically opened.

13.2 How to use the new phone book


Select via Help the menu item How to use the new phone book.

Image 13.2-2: How to use the new phone book

By selecting this menu a guide of How to use the new telephone book in .pdf format will be automatically opened.

alphaSET, user manual, Version 2.07.00 13 Help

Page 135 of 137

13.3 AlphaSet Release-notes


Select via Help the menu item Release notes.

Image 13.3-1: Release notes

By selecting this menu a guide a list of the released notes will be displayed.

13.4 About alphaSet


Select via Help the menu item About alphaSet.

Image 13.4-1: About alphaSet

By selecting this menu, the information about which version of alphaSet is being used, will be displayed.

alphaSET, user manual, Version 2.07.00 14 Image index

Page 136 of 137

14 Image index
IMAGE 3.3-1: INSTALLATION CHOOSE ALPHA METER ............................................................................................... 9 IMAGE 3.3-2: INSTALLATION CHOOSE INSTALLATION .............................................................................................. 9 IMAGE 3.3-3: INSTALLATION CHOOSE LANGUAGE .................................................................................................. 10 IMAGE 3.3-4: INSTALLATION INFORMATION1......................................................................................................... 10 IMAGE 3.3-5: INSTALLATION INFORMATION2......................................................................................................... 11 IMAGE 3.3-6: INSTALLATION SELECT DESTINATION ............................................................................................... 11 IMAGE 3.3-7: INSTALLATION - PHONE BOOK ............................................................................................................. 12 IMAGE 3.3-8: INSTALLATION - PROGRESS ................................................................................................................. 12 IMAGE 3.3-9: SETUP COMPLETE.............................................................................................................................. 13 IMAGE 3.3-10: SETUP SUCCESSFUL ......................................................................................................................... 13 IMAGE 3.4-11: START - LANGUAGE ........................................................................................................................... 14 IMAGE 3.4-10: START OLD SETTINGS ..................................................................................................................... 15 IMAGE 3.4-1: INPUT USER-PROFILE ........................................................................................................................ 16 IMAGE 3.4-2: USER PROFILE ..................................................................................................................................... 17 IMAGE 3.5-1: INFORMATION SCREEN ........................................................................................................................ 21 IMAGE 4.1-1: SETTINGS REGISTER CARD COMMUNICATION ................................................................................... 22 IMAGE 4.2-1: SETTINGS REGISTER CARD FILES ....................................................................................................... 24 IMAGE 4.3-1: SETTINGS REGISTER/LOAD PROFILE TAB ........................................................................................... 25 IMAGE 4.4-1: SETTINGS REGISTER CARD GENERAL ................................................................................................ 26 IMAGE 4.6-1: IEC 1107-ADDRESS ............................................................................................................................ 28 IMAGE 4.7-1: UTILITY PASSWORD FOR COMMUNICATION ......................................................................................... 29 IMAGE 5.1-1 READ REGISTER ................................................................................................................................... 31 IMAGE 5.3-1: READ METER CONFIGURATION ............................................................................................................ 33 IMAGE 5.5-1: READ POWER QUALITY MONITORING................................................................................................... 40 IMAGE 5.5-2: GRAPHICAL DATA OF POWER QUALITY MONITORING........................................................................... 41 IMAGE 5.6-2: DATA FROM LOGFILE........................................................................................................................... 43 IMAGE 5.7-1: DATA FROM LOGFILE 2........................................................................................................................ 44 IMAGE 5.8-1: READ METER ERROR STATUS ............................................................................................................... 45 IMAGE 5.8-2: POWER QUALITY SUPERVISION ........................................................................................................... 46 IMAGE 5.8-3: READ METER ERROR MESSAGES .......................................................................................................... 47 IMAGE 5.8-4: READ METER STATUS MESSAGES ......................................................................................................... 48 IMAGE 5.8-5: SET PRINT CONFIGURATION................................................................................................................ 49 IMAGE 5.8-6: READ METER ERROR+STATUS, OPTIONS .............................................................................................. 50 IMAGE 5.9-1: READ COMMUNICATION PROTOCOL..................................................................................................... 51 IMAGE 6.1-1: FILE - READ PARAMETER..................................................................................................................... 52 IMAGE 6.4-1: DATA TRANSFER ................................................................................................................................. 56 IMAGE 7-0: MENU ITEM MODIFY........................................................................................................................... 57 IMAGE 7.1-1: IDENTIFICATIONS ................................................................................................................................ 58 IMAGE 7.2-1: TARIFF SOURCE UP TO FW 4.01........................................................................................................... 60 IMAGE 7.3-1: MENU SWITCH POINT CLOCK............................................................................................................... 61 IMAGE 7.3-3: SWITCHING TIMES ............................................................................................................................... 63 IMAGE 7.3-4: HOLIDAY-LIST ..................................................................................................................................... 64 IMAGE 7.3-5: SUMMER/WINTER TIME SWITCH ........................................................................................................... 65 IMAGE 7.4-1: SECOND TARIFF TABLE ........................................................................................................................ 66 IMAGE 7.5-1: REAL TIME CLOCK ............................................................................................................................... 67 IMAGE 7.5-2: DISPLAY TIMEOUTS ............................................................................................................................. 68 IMAGE 7.5-3: GPRS COMMUNICATION TIMEOUT ...................................................................................................... 69 IMAGE 7.6-1: DEMAND RESET ................................................................................................................................... 70 IIMAGE 7.7-1: CONTROL OF DISCONNECT RELAY ...................................................................................................... 71 IIMAGE 7.7-2: DEMAND OVERLOAD .......................................................................................................................... 72 IIMAGE 7.7-3: THRESHOLD VALUE TAN(PHI) ............................................................................................................ 72 IMAGE 7.8-1: BAUD RATE ......................................................................................................................................... 73 IMAGE 7.9-1: MEASURING ENERGY / DEMAND ......................................................................................................... 74 IMAGE 7.10-1: SYNCHRONIZATION ........................................................................................................................... 75

alphaSET, user manual, Version 2.07.00 14 Image index

Page 137 of 137

IMAGE 7.11-1: BACKUP TIME OF REAL TIME CLOCK .................................................................................................. 77 IMAGE 7.12-1: INVERTING INPUTS / OUTPUTS .......................................................................................................... 78 IMAGE 7.13-1: RELEASE POWER QUALITY VALUES ................................................................................................... 79 IMAGE 7.13-2: POWER QUALITY MONITORING DATA ................................................................................................ 80 IMAGE 7.13-3: POWER QUALITY MONITORING .......................................................................................................... 81 IMAGE 7.14-1: COPPER AND IRON LOSSES ................................................................................................................. 82 IMAGE 7.15-1: PASSWORD 3 IS NEEDED FOR THIS MENU ITEM ................................................................................... 83 IMAGE 7.15-2: CONFIGURATION MATRIX FOR METER ACCESS RIGHTS ...................................................................... 84 IMAGE 7.16-1: SERVICE LIST..................................................................................................................................... 85 IMAGE 7.16-2: DISPLAY LIST .................................................................................................................................... 87 IMAGE 7.16-3: GENERAL SETTINGS OF THE DISPLAY................................................................................................. 88 IMAGE 7.16-4: CONFIGURATION OF HISTORICAL VALUES ......................................................................................... 89 IMAGE 7.17-1: TRANSFORMER RATIO ....................................................................................................................... 90 IMAGE 7.18-1: PULSE INPUTS .................................................................................................................................... 91 IMAGE 7.18-2: SUMMATION ...................................................................................................................................... 92 IMAGE 7.19-1: LOAD PROFILE PARAMETER ............................................................................................................... 93 IMAGE 7.19-2: LOG FILE - PARAMETER ..................................................................................................................... 95 IMAGE 7.20-1: MEASURING ENERGY / DEMAND ....................................................................................................... 96 IMAGE 7.21-1: PASSWORDS CHANGE 1 ..................................................................................................................... 97 IMAGE 7.21-1: PASSWORDS CHANGE 2 ..................................................................................................................... 97 IMAGE 8-1: MENU METER COMMANDS ..................................................................................................................... 99 IMAGE 8.1-1: METER DATE/TIME ......................................................................................................................... 100 IMAGE 8.2-1: READ/SET DATE/TIME (VDEW) ........................................................................................................ 101 IMAGE 8.3-1: SETTING OF PULSE CONSTANTS ......................................................................................................... 102 IMAGE 8.4-1: SET OUTPUTS..................................................................................................................................... 103 IMAGE 8.5-1: CONTROL OF DISCONNECT RELAY..................................................................................................... 104 IMAGE 8.6-1: READ OUT DCF CLOCK ..................................................................................................................... 105 IMAGE 8.7-1: RESET DEMAND MAXIMA .................................................................................................................. 106 IMAGE 8.8-1: RESET METER ERROR STATE .............................................................................................................. 107 IMAGE 8.9-1: RESET POWER QUALITY MONITORING ............................................................................................... 108 IMAGE 8.11-1: RESET POWER LOSS COUNTER ......................................................................................................... 110 IMAGE 8.12-1: RESET TERMINAL OPEN COUNTER ................................................................................................... 111 IMAGE 8.13-1: RESET REGISTER.............................................................................................................................. 112 IMAGE 8.14-1: SET REGISTER VALUES (PULSE INPUTS) ........................................................................................... 113 IMAGE 8.15-1: RESET LOAD PROFILE + LOGBOOK ................................................................................................... 114 IMAGE 9-1: SWITCH TO RIPPLE RECEIVER ............................................................................................................... 115 IMAGE 10-1: TEST MENU ........................................................................................................................................ 116 IMAGE 10.2-1: POWER QUALITY ............................................................................................................................. 118 IMAGE 10.2-2: POWER QUALITY, OPTIONS.............................................................................................................. 119 IMAGE 10.3-1: TEST MODE...................................................................................................................................... 121 IMAGE 11-1: SETTINGS REGISTER CARD MODEM ................................................................................................. 124 IMAGE 11-2: SETTINGS REGISTER CARD MODEM ................................................................................................. 124 IMAGE 11.1-1: PHONE BOOK PART 1 ....................................................................................................................... 125 IMAGE 11.1-2: PHONE BOOK PART 1 ....................................................................................................................... 125 IMAGE 11.1-3: PHONE BOOK PART 2 ....................................................................................................................... 126 IMAGE 11.1-4: PHONE BOOK PART 3 ....................................................................................................................... 128