Characteristics Rated control supply voltage 2448 V DC, 24240 V AC Timing functions: Congurable with DIP switches behind marker label, asymmetrical ON and OFFdelay, impulseON/OFF, pulse generator starting with ON or OFF, single pulse generator, ON/OFFfunction 2 x 10 time ranges (0.05 s 300 h) Control input with voltagerelated triggering to start timing 2 remote potentiometer connections Precise adjustment by front-face operating controls Screw connection technology or Easy Connect Technology available Housing material for highest re protection classication UL 94 V-0 Tool-free mounting on DIN rail as well as demounting 2 c/o (SPDT) contacts 22.5 mm (0.89 in) width 2 LEDs for the indication of operational states
Approvals A C D K E L
UL 508, CAN/CSA C22.2 No.14 GL GOST CB scheme CCC RMRS
Marks a
b CE C-Tick
The CT-MXS.22 is a multifunctional electronic timer from the CT-S range. It provides 5 timing functions, 2 times 10 time ranges. All electronic timers from the CT-S range are available with two different terminal versions. You can choose between the proven screw connection technology (double-chamber cage connection terminals) and the completely tool-free Easy Connect Technology (push-in terminals).
Accessories
Type ADP.01 MAR.12 COV.11 MT-150B Description Adapter for screw mounting Marker label for devices with DIP switches Sealable transparent cover Remote potentiometer 50 k20 % 0.2 , degree of protection IP66 MT-250B Remote potentiometer 50 k20 % 0.2 , degree of protection IP66 MT-350B Remote potentiometer 50 k20 % 0.2 , degree of protection IP66 KA1-8029 KA1-8030 SK 615 562-87 Adaptor for reduction of 30 mm hole to 22. 5 mm Adaptor for reduction of 30 mm hole to 22. 5 mm Legend plate for remote potentiometer Symbol (see drwg. in data sheet remote potentiometer) SK 615 562-88 MA16-1060 Legend plate for remote potentiometer Legend plate for remote potentiometer scale 0 - 30 1SFA 611 940 R1060 scale 0 - 10 GJD6 155 620 R0088 GJD6 155 620 R0087 chromed metal 1SFA 616 920 R8030 black plastic 1SFA 616 920 R8029 chromed metal 22.5 1SFA 611 410 R3506 chromed plastic 22.5 1SFA 611 410 R2506 black plastic 22.5 1SVR 730 005 R0100 1SFA 611 410 R1506 Material Diameter in mm Marking Order code 1SVR 430 029 R0100 1SVR 730 006 R0000
Connection technology Maintenance free Easy Connect Technology with push-in terminals Type designation CT-xxS.yyP Approved screw connection technology with double-chamber cage connection terminals Type designation CT-xxS.yyS
Push-in terminals Tool-free connection of rigid and exible wires with wire end ferrule according to DIN 46228-1-A, DIN 46228-4-E Wire size: 2 x 0.5-1.5 mm, (2 x 20 - 16 AWG) Easy connection of exible wires without wire end ferrule by opening the terminals No retightening necessary One operation lever for opening both connection terminals For triggering the lever and disconnecting of wires you can use the same tool (Screwdriver according to DIN ISO 2380-1 Form A 0.8 x 4 mm (0.0315 x 0.157 in), DIN ISO 8764-1 PZ1 4.5 mm (0.177 in)) Constant spring force on terminal point independent of the applied wire type, wire size or ambient conditions (e. g. vibrations or temperature changes) Opening for testing the electrical contacting Gas-tight
Double-chamber cage connection terminals Terminal spaces for different wire sizes: nestrand with/without wire end ferrule: 1 x 0.5-2.5 mm (2 x 20 - 14 AWG), 2 x 0.5-1.5 mm (2 x 20 - 16 AWG) rigid: 1 x 0.5-4 mm (1 x 20 - 12 AWG), 2 x 0.5-2.5 mm (2 x 20 - 14 AWG) One screw for opening and closing of both cages Pozidrive screws for pan- or crosshead screwdrivers according to DIN ISO 2380-1 Form A 0.8 x 4 mm (0.0315 x 0.157 in), DIN ISO 8764-1 PZ1 4.5 mm (0.177 in)
Both the Easy Connect Technology with push-in terminals and screw connection technology with double-chamber cage connection terminals have the same connection geometry as well as terminal position.
Fine adjustment of the time delay 2 Rotary switch for the preselection of the time range 2 Fine adjustment of the time delay 1 Rotary switch for the preselection of the time range 1 Indication of operational states
U/T: green LED - control supply voltage / timing
2 3
2
2CDC 251 028 V0011
Application The CTS range timers are designed for use in industrial applications. They operate over a universal range of supply voltages and a large time delay range, within compact dimensions. The easytoset frontface potentiometers, with direct reading scales, provide accurate time delay adjustment. Multifunction timers are ideally suited for service and maintenance applications, because one device can replace a number of time relays with different functions, voltage and time ranges. This reduces inventory and saves money. Operating mode The CTMXS.22 with 2 c/o (SPDT) contacts offers 5 timing functions. The timing function is adjusted via the DIP switches under the marker label on the front of the unit. Two rotary switches, on the front of the unit, allow selection of one of the 2 times 10 time ranges from 0.05 s to 300 h for each time delay. The fine adjustment of the time delays is made via internal potentiometers, with direct reading scales, on the front of the unit. When external potentiometers are connected to terminals Z1Z2 and Z3Z2, the internal adjustment is disabled and external adjustment is enabled. Timing is displayed by a flashing green LED labelled U/T.
Function diagrams Remote potentiometer connection When an external potentiometer is connected to the remote potentiometer connection (terminals Z1Z2), the internal, frontface potentiometer is disabled and the time adjustment is made via the external potentiometer. AB Asymmetrical ON and OFFdelay This function requires continuous control supply voltage for timing. Closing control input A1Y1/B1 starts the ONdelay t1. When timing is complete, the output relay energizes. Opening control input A1Y1/B1 starts the OFFdelay t 2. When the OFFdelay is complete, the output relay deenergizes. Both timing functions are displayed by the flashing green LED. The ONdelay and OFFdelay are independently adjustable. If control input A1Y1/B1 opens before the ONdelay is complete (< t 1), the time delay is reset and the output relay remains deenergized. If control input A1Y1/B1 closes before the OFFdelay is complete (<t 2), the time delay is reset and the output relay remains energized. If control supply voltage is interrupted, the output relay deenergizes and the time delay is reset.
A1-A2 A1-Y1/B1 15-18, 25-28 15-16, 25-26 green LED
2CDC 252 038 F0206 2CDC 252 028 F0206
t1
t2
t1
< t2
CE ImpulseON and ImpulseOFF This function requires continuous control supply voltage for timing. If control supply voltage is applied, closing control input A1Y1/B1 energizes the output relay immediately and starts the pulse time t1. The green LED flashes during timing. When t1 is complete, the output relay deenergizes and the flashing green LED turns steady. Reopening control input A1Y1/B1 energizes the output relay immediately and starts the pulse time t2. The green LED flashes during timing. When t2 is complete, the output relay deenergizes and the flashing green LED turns steady. t 1 and t2 are independently adjustable. If control input A1Y1/B1 changes state before the pulse time is complete, the output relay deenergizes and the pulse time is reset. If control input A1Y1/B1 changes state again, the interrupted pulse time restarts. If control supply voltage is interrupted, the output relay deenergizes and the time delay is reset.
A1-A2 A1-Y1/B1 15-18, 25-28 15-16, 25-26 green LED t1 t1 = adjusted pulse time 1 t2 = adjusted pulse time 2 t2 < t1
DE Pulse generator, starting with ON or OFF This function requires continuous control supply voltage for timing. Applying control supply voltage, with open control input A1Y1/B1, starts timing with an ON time t2 first. Applying control supply voltage, with closed control input A1Y1/B1, starts timing with an OFF time t1 first. The ON / OFF times are displayed by the flashing green LED, which flashes twice as fast during the OFF time. The ON / OFF times are independently adjustable. If control supply voltage is interrupted, the output relay deenergizes and the time delay is reset.
A1-A2 A1-Y1/B1 15-18, 25-28 15-16, 25-26 t1 t2 t2 t1
2CDC 252 075 F0207 2CDC 252 044 F0206 2CDC 252 037 F0206
green LED
EC Single pulse generator, starting with OFF This function requires continuous control supply voltage for timing. Applying control supply voltage, or, if control supply voltage is already applied, opening control input A1Y1/B1 energizes the output relay after the OFF time t1 is complete. When the following ON time t2 is complete, the output relay deenergizes. The ON / OFF times are displayed by the flashing green LED, which flashes twice as fast during the OFF time. The ON / OFF times are independently adjustable. Closing control input A1Y1/B1, with control supply voltage applied, deenergizes the output relay and resets the time delay. If control supply voltage is interrupted, the output relay deenergizes and the time delay is reset.
A1-A2 A1-Y1/B1 15-18, 25-28 15-16, 25-26 green LED t1 t2 t1 t2
G ON/OFFfunction This function is used for test purposes during commissioning and troubleshooting. If the selected max. value of the time range is smaller than 300 h (frontface potentiometer T Range not 300 h), applying control supply voltage energizes the output relay immediately and the green LED is on. Interrupting control supply voltage, deenergizes the output relay. If the selected max. value of the time range is 300 h (frontface potentiometer T Range = 300 h) and control supply voltage is applied, the green LED is on, but the output relay does not energize. Time settings and operating of the control inputs have no effect on the operation.
A1-A2 15-18, 25-28 15-16, 25-26 green LED Time range 300 h Time range = 300 h
Electrical connection
A1 Z3 Y1/ B1 A1 15 Z2 15 25 Z1 25
1516/18 2526/28 A1A2 A1Y1/B1 1st c/o (SPDT) contact 2nd c/o (SPDT) contact Rated control supply voltage US 2448 V DC or 24240 V AC Control input Remote potentiometer connection Remote potentiometer connection
A2 16 28 18
18 26 26 16
28
Z1-Z2 Z3-Z2
Y1/B1 A2
Connection diagram
Wiring instructions Control input (voltagerelated triggering) The control input Y1/B1 is triggered with electric potential against A2. It is possible to use the control supply voltage from terminal A1 or any other voltage within the rated control supply voltage range.
L(+)
L(+) L(+)
A1
Y1/B1
A1
Y1/B1
A2
A2
N(-)
N(-)
L(-)
Remote potentiometer
2CDC 252 104 F0b06
L(+)
A1
Z3 Z1
A2
Z2
N(-)
DIP switches
4 ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF 3 2 1
Pulse generator, starting with ON or OFF Single pulse generator, starting with OFF Asymmetrical ON- and OFF-delay Impulse-ON and Impulse-OFF No function ON/OFF function
2CDC 252 043 F0207
Technical data Data at Ta = 25 C and rated values, unless otherwise indicated Input circuits
Supply circuit Rated control supply voltage US Rated control supply voltage US tolerance Rated frequency Frequency range Typical current / power consumption 2448V DC 24240V AC Power failure buffering time 24 V DC 230 V AC Control circuit Control input, control function Kind of triggering Restistance to reverse polarity Polarized Capable for switching a parallel load Maximum cable length to the control inputs Minimum control pulse length Control voltage potential Current consumption of the control input Remote potentiometer connection Maximum cable length to the control inputs Shield connection Timing circuit Kind of timer Multifunction timer Asymmetrical ON and OFFdelay ImpulseON and ImpulseOFF Pulse generator, starting with ON or OFF Single pulse generator, starting with OFF ON/OFFfunction Time ranges 0.05s300h Recovery time Repeat accuracy (constant parameters) Accuracy within the rated control supply voltage tolerance Accuracy within the temperature range 0.051s, 0.153s, 0.510s, 1.530s, 5100s, 15300s, 1.530min, 15300min, 1.530h, 15300h < 80 ms t < 0.2 % t < 0.004 %/V t < 0.03 %/C 24 VDC 230 VAC Z1Z2 Z3Z2 A1Y1/B1 start timing external voltagerelated triggering yes no yes 50 m 100 pF/m 20 ms see rated control supply voltage US 1.2mA 8mA 50 k 50 k 2 x 25 m, shielded with 100 pF/m Z2 2448V DC 24240V AC DC AC AC A1-A2 2448V DC, 24240V AC 15...+10% 15...+10% n/a 50/60 Hz 4763Hz 24 V DC 17mA/ on request / min. 15 ms min. 20 ms 230 V AC / 57mA/ on request 115 V AC / 33mA/ on request
User interface
Indication of operational states Control supply voltage / timing Relay status U/T: green LED U/T: green LED R: yellow LED V: control supply voltage applied W : timing V : output relay energized
Output circuits
Kind of output 1516/18 2526/28 Contact material Rated operational voltage Ue Minimum switching voltage / Minimum switching current Maximum switching voltage / Maximum switching current Rated operational current Ie (IEC/EN 6094751) AC12 (resistive) at 230 V AC15 (inductive) at 230 V DC12 (resistive) at 24 V DC13 (inductive) at 24 V AC rating (UL 508) utilization category (Control Circuit Rating Code) max. rated operational voltage max. continuous thermal current at B 300 max. making / breaking apparent power at B 300 Mechanical lifetime Electrical lifetime Maximum fuse rating to achieve short-circuit protection (IEC/EN 6094751) AC12, 230 V, 4 A n/c contact n/o contact 30 x 106 switching cycles 0.1 x 106 switching cycles 6 A fastacting 10 A fastacting 3600/360 VA 300 V AC 5A relay, 1st c/o (SPDT) contact relay, 2nd c/o (SPDT) contact Cdfree 250 V 12 V / 10 mA see Load limit curves on page 11 4A 3A 4A 2A B 300
General data
MTBF Duty time Dimensions (W x H x D) Weight net weight gross weight Mounting Mounting position Minimum distance to other units Material of housing Degree of protection housing terminals vertical horizontal product dimensions packaging dimensions on request 100 % 22.5 x 85.6 x 103.7 mm (0.89 x 3.37 x 4.08 in) 97 x 109 x 30 mm (3.82 x 4.29 x 1.18 in) Screw connection technology 0.142 kg (0.313 lb) 0.164 kg (0.362 lb) DIN rail (IEC/EN 60715), snapon mounting without any tool any not necessary not necessary UL 94 V-0 IP50 IP20 Easy Connect Technology (push-in) 0.131 kg (0.289 lb) 0.153 kg (0.337 lb)
Electrical connection
Screw connection technology Wire size finestrand with(out) wire end ferrule 1 x 0.5-2.5 mm (1 x 20-14 AWG) 2 x 0.5-1.5 mm (2 x 20-16 AWG) rigid 1 x 0.5-4 mm (1 x 20-12 AWG) 2 x 0.5-2.5 mm (2 x 20-14 AWG) Stripping length Tightening torque 8 mm (0.32 in) 0.6 - 0.8 Nm (5.31 - 7.08 lb.in) 2 x 0.5-1.5 mm (2 x 20-16 AWG) Easy Connect Technology (push-in) 2 x 0.5-1.5 mm (2 x 20-16 AWG)
Environmental data
Ambient temperature ranges Damp heat, cyclic (IEC/EN 60068230) Vibration, sinusoidal (IEC/EN 6006826) Vibration, seismic (IEC/EN 6006833) Shock, halfsine (IEC/EN 60068227) functioning resistance functioning functioning resistance operation storage 25...+60C 40...+85C 6 x 24 h cycle, 55 C, 95 % RH 40 m/s 2, 10-58/60-150 Hz 60 m/s2, 10-58/60-150 Hz, 20 cycles 20 m/s 100 m/s 2, 11 ms, 3 shocks/direction 300 m/s2, 11 ms, 3 shocks/direction
Isolation data
Rated insulation voltage Ui output circuit 1 / output circuit 2 input circuit / output circuit Rated impulse withstand voltage U imp between all isolated circuits (IEC/EN 606641) Powerfrequency withstand voltage test between all isolated circuits (test voltage) Basic insulation (IEC/EN 61140) Protective separation (IEC/EN 61140; EN 50178) Pollution degree (IEC/EN 60664-1) Overvoltage category (IEC/EN 60664-1) input circuit / output circuit input circuit / output circuit routine test: 2.0 kV; 50 Hz, 1 s type test: 2.5 kV; 50 Hz, 1 min 500 V 250 V 3 III 500 V 4 kV; 1.2/50 s 300 V
Standards
Product standard Low Voltage Directive EMC Directive RoHS Directive IEC 618121, EN 618121 + A11, DIN VDE 0435 part 2021 2006/95/EC 2004/108/EC 2002/95/EC
Electromagnetic compatibility
Interference immunity to electrostatic discharge radiated, radio-frequency, electromagnetic field electrical fast transient / burst surge conducted disturbances, induced by radio-frequency fields harmonics and interharmonics Interference emission high-frequency radiated high-frequency conducted IEC/CISPR 22, EN 55022 IEC/CISPR 22, EN 55022 IEC/EN 6100042 IEC/EN 6100043 IEC/EN 6100044 IEC/EN 6100045 IEC/EN 6100046 IEC/EN 61000413 IEC/EN 61000-6-1, IEC/EN 61000-6-2 Level 3, 6 kV / 8 kV Level 3, 10 V/m (1 GHz) / 3 V/m (2 GHz) / 1 V/m (2.7 GHz) Level 3, 2 kV / 5 kHz Level 4, 2 kV A1-A2 Level 3, 10 V Class 3 IEC/EN 61000-6-3, IEC/EN 61000-6-4 Class B Class B
resistive load
resistive load
DC current [A]
AC current [A]
AC load (resistive)
DC load (resistive)
Derating factor F
Switching cycles
1.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
Contact lifetime
6.5 0.256
62.5 2.461
2CDC 252 008 F0010 2CDC 252 020 F0011
11.5 0.453
68 2.68
60 2.362 70 2.756
4T22
19.9 0.783
22.2 0.874
Remote potentiometer
10 0.394 20 0.787
0.309
7.85
Further documentation
Document title Electronic Products and Relays CT-MXS, CT-WBS Remote potentiometer for CT-S range time relays Document type Technical catalogue Instruction manual Data sheet Document number 2CDC 110 004 C020x 1SVC 730 030 M0000 2CDC 111 108 D0201
You can find the documentation on the internet at www.abb.com/lowvoltage -> Control Products -> Electronic Relays and Controls -> Time Relays.
CAD system files You can find the CAD files for CAD systems at http://abb-control-products.partcommunity.com/PARTcommunity/Portal/ abb-control-products -> Low Voltage Products & Systems -> Control Products -> Electronic Relays and Controls -> Time Relays.
Contact us
You can find the address of your local sales organization on the ABB home page http://www.abb.com/contacts -> Low Voltage Products and Systems
Note: We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB AG. Copyright 2012 ABB All rights reserved
ABB STOTZ-KONTAKT GmbH P. O. Box 10 16 80 69006 Heidelberg, Germany Phone: +49 (0) 6221 7 01-0 Fax: +49 (0) 6221 7 01-13 25 E-mail: info.desto@de.abb.com