ENGINEERING SPECIFICATION FIRE DETECTION AND AGENT RELEASING SYSTEM PART 1.0 - GENERAL 1.1.

DESCRIPTION: This section includes the furnishing, installation, and connection of the fire alarm equipment required to form a complete coordinated agent releasing system ready for operation. It shall include, but not be limited to, alarm initiating devices, alarm notification appliances, control panel, auxiliary control devices, annunciators, power supplies, releasing devices and wiring as shown on the drawings and specified herein. A. The fire alarm system shall comply with requirements of NF A !tandard No. "# for protected premises signaling systems except as modified and supplemented by this specification. The system field wiring shall be supervised either electrically or by software$directed polling of field devices. !prin&ler system components shall be provided as specified in !ection '(()) $ fire protection. The fire alarm system shall be manufactured by an I!+ ,))' certified company and meet the requirements of %! -N,))'. AN!I/A!0* 0,))'$',,1. The FA* and peripheral devices shall be manufactured '))3 by a single 4.!. manufacturer 5or division thereof6. The system and its components shall be 4nderwriters 7aboratories, Inc. listed under the appropriate 47 testing standard as listed herein for fire alarm applications and shall be installed in compliance with the 47 listing. The installing company shall employ NI*-T 5minimum 7evel II Fire Alarm Technology6 technicians on site to guide the final chec&$out and to ensure the systems integrity. SCOPE: A new agent release system shall be provided in accordance with this specification. %asic erformance. '. #. 9. 1. Initiation 2evice *ircuits 5I2*6 shall be wired *lass A 5NF A !tyle 26. Notification Appliance *ircuits 5NA*6 shall be wired *lass A 5NF A !tyle 86. :eleasing circuits shall be arranged to supervise the solenoid coil. A single ground or open on any initiating device circuit or notification appliance circuit shall not cause system malfunction, loss of operating power or the ability to report an alarm.

%. *. 2. -.

F. 1.2. A. %.

*.

%asic !ystem Functional +peration ;hen a fire alarm condition is detected and reported by two of the system initiating devices which are cross$<oned the following functions shall immediately occur. '. #. 9. 1. (. A programmed delay timer shall be started. ;arning audible circuits shall sound. If abort is activated, the timer shall stop. =anual release shall override abort. At completion of the delay timeout, the release solenoid5s6 shall be activated.

1.3. A.

SUBMITTALS: =anufacturers -quipment. All references to manufacturer>s or supplier>s model numbers and other pertinent information herein is intended to establish minimum standards of performance, function and quality. -quivalent equipment 5compatible 47 7isted6 from other manufacturers may be substituted for the specified equipment as long as the minimum standards are met. !hop 2rawings. Include manufacturer>s name5s6, model numbers, ratings, power requirements, equipment layout, device arrangement, and complete wiring point$to$point diagrams.

%.

*.

=anuals. !ubmit simultaneously with the shop drawings, complete operating and maintenance manuals listing the manufacturer>s name5s6 including technical data sheets 5indicate which model numbers are to be used6.

2.

*ertifications. '. Together with the shop drawing submittal, submit a certification from the ma?or equipment manufacturer indicating that the proposed supervisor of installation and the proposed performer of contract maintenance is an authori<ed representative of the ma?or equipment manufacturer.

1.4. A.

GUARANTY: All wor& performed and all material and equipment furnished under this contract shall be free from defects and shall remain so for a period of at least one 5'6 year from the date of acceptance. POST CONTRACT MAINTENANCE:

1.5.

*omplete maintenance and repair service for the fire alarm system shall be available from a factory trained authori<ed representative of the manufacturer of the ma?or equipment for a period of five 5(6 years after expiration of the guaranty 1.6. APPLICABLE PUBLICATIONS: The publications listed below form a part of this specification. A. National Fire rotection Association 5NF A6 $ 4!A. No. '# No. '#A No. '#% No. '" No. '"A No. #))' No. "# No. ')'$,' No. "#) %. *+# -xtinguishing !ystems 5@igh ressure +nly6 @alon '9)' -xtinguishing !ystems @alon '#'' -xtinguishing !ystems 2ry *hemical -xtinguishing !ystems ;et *hemical -xtinguishing !ystems *lean Agent Fire -xtinguishing !ystems National Fire Alarm *ode 7ife !afety *ode *arbon =onoxide 5*+6 ;arning -quipment

4nderwriters 7aboratories Inc. 5476 $ 4!A. No. #AB No. BA1 No. 1A1 No. ',"' No. 9B '. !mo&e 2etectors for Fire rotective !ignaling !ystems. *ontrol 4nits for Fire rotective !ignaling !ystems. Audible !ignaling Appliances. Cisual !ignaling Appliances. =anually Actuated !ignaling %oxes.

The FA* shall be 47 BA1, ,th -dition 7isted. !ystems listed to 47 BA1, Bth edition 5or previous revisions6 shall not be accepted.

*. 2. 1.7.

7ocal and !tate %uilding *odes. All requirements of the Authority @aving Durisdiction 5A@D6. APPROVALS: -ach system must have proper listing and/or approval from the following nationally recogni<ed agencies. 47 4nderwriters 7aboratories Inc F= Factory =utual 47* 4nderwriters 7aboratories *anada =-A =aterial -quipment Acceptance 5NE*6 *!F= *alifornia !tate Fire =arshal

PART 2.0 - PRODUCTS 2.1. E UIPMENT AND MATERIAL! GENERAL:

A. %. *.

All equipment and components shall be new, and the manufacturer>s current model. All equipment and components shall be installed in strict compliance with manufacturers> recommendations. All -quipment shall be attached to walls and ceiling/floor assemblies and shall be held firmly in place. 5e.g., detectors shall not be supported solely by suspended ceilings6. Fasteners and supports shall be adequate to support the required load. CONDUIT AND "IRE: *onduit. '. #. 9. *onduit shall be in accordance with The National -lectrical *ode 5N-*6, local and state requirements. *onduit fill shall not exceed 1) percent of interior cross sectional area where three or more cables are contained within a single conduit. *able must be separated from any open conductors of ower, or *lass ' circuits, and shall not be placed in any conduit, ?unction box or raceway containing these conductors, as per N-* Article "A).

2.2. A.

%.

;ire. '. #. All fire alarm system wiring shall be new. ;iring shall be in accordance with local, state and national codes 5e.g., N-* Article "A)6. Number and si<e of conductors shall be as recommended by the fire alarm system manufacturer, but not less than 'B A;F 5'.)# mm6 for initiating device circuits and '1 A;F 5'.A9 mm6 for notification device circuits. All wire and cable shall be listed and/or approved by a recogni<ed testing agency for use with a protective signaling 5fire alarm6 system.

9. *.

Terminal %oxes, Dunction %oxes and *abinets. '. All boxes and cabinets shall be 47 listed for their use and purpose.

2.

The *ontrol anel shall be connected to a separate dedicated branch circuit, maximum #) amperes. This circuit shall be labeled at the main power distribution anel as fire extinguishing control. *ontrol panel primary power wiring shall be '# A;F. The control panel cabinet shall be grounded securely to either a cold water pipe or grounding rod. CONTROL PANEL: The control panel shall be a Notifier model : $#))# and shall communicate with and control the following types of equipment used to ma&e up the system. smo&e detectors,

2.3. A.

manual release/abort stations, alarm notification appliances, releasing components and other system controlled devices. '. #. The control panel shall be a 47 listed and F= approved microprocessor controlled agent releasing *ontrol anel. Function. The control panel shall perform the following functions. a. b. c. !upervise and monitor all initiating device circuits and alarm notification circuits for trouble and alarm conditions. !upervise the release solenoid5s6. 2etect the operation of any initiating device circuit and the location of the alarm condition. +perate all notification appliances and release devices as designed. Cisually and audibly annunciate any trouble, supervisory or alarm condition on panel display.

d. %.

!ystem *apacity The *ontrol anel shall include six programmable initiating device circuits, four programmable output circuits, three programmable Form$* relays, A ".) Amp integral power supply and B) character 7*2. '. The I2*s 5Initiating 2evice *ircuits6 shall be individually programmable as conventional two$wire smo&e detector circuits, as well as any dry contact input device. -xamples of dry contact input devices include four$wire smo&e detectors, manual pull stations, abort switches, heat detectors, pressure switches, and waterflow switches. The I2*s shall support !tyle 2 5*lass A6 operation by adding an expansion board. The I2*s shall support conventional two$wire smo&e detectors as well as conventional smo&e detectors capable of generating a maintenance signal when the detector becomes dirty and a separate supervisory >free<e> signal when ambient temperature falls below the detector rating of approximately 1' degrees F. The four programmable outputs shall be individually programmable as conventional supervised NA*s 5Notification Appliance *ircuits6 or for releasing solenoids. -ach NA* may be individually programmed as any of the following. !ilence Inhibit, Auto$!ilence, !trobe !ynchroni<ation, !elective !ilence 5horn$ strobe mute6, Temporal or !teady !ignal, !ilenceable or Non$silenceable, or :elease !tage !ounder. The system shall also provide resettable and non$ resettable output power for general use. The three programmable relays shall be individually programmable as Alarm, Trouble, !upervisory, 2ischarge, and A* ower 7oss. ;hen programmed as a Trouble relay, the relay shall be fail$safe. The on board power supply shall be capable of ".) Amps of regulated, filtered

#.

9.

1.

power. *. !ystem 2isplay The system shall have eight 7-2 indicators as well as an B) character 7*2 57iquid *rystal 2isplay6. The 7*2 shall be capable of displaying a custom description for each input and output circuit. The system 7-2s shall indicate the status of the following system parameters. Fire Alarm !upervisory Trouble A* ower Alarm !ilence 2ischarge re$2ischarge Abort '. :ed 7-2 Eellow 7-2 Eellow 7-2 Freen 7-2 Eellow 7-2 :ed 7-2 :ed 7-2 Eellow 7-2

The main system display shall be an integral, eighty character 7*2 with a &eypad. The &eypad shall have full programming capability without requiring the use of a laptop computer. The FA* shall include a history log with a #(A event storage. The history shall be accessible from the main system display. The system shall include a real$time cloc&/calendar with daylight savings time control.

#. 9. 2.

!ystem *ontrol !witch +peration. '. Tone !ilence !witch. Activation of the control panel tone silence switch in response to alarms troubles and supervisory conditions shall silence the local panel pie<o electric signal and change the 7-2 from flashing mode to steady$+N mode. +ccurrence of any new conditions in the system shall cause the control panel to resound the 7ocal ie<o sounder and repeat the alarm, trouble, or supervisory sequences. Alarm !ilence !witch. Activation of the alarm signal silence switch shall cause all alarm notification appliances to return to the normal condition after an alarm condition. !ystem :eset !witch. Activation of the !ystem :eset !witch shall cause all electronically$latched initiating devices, as well as all associated output devices and circuits, to return to their normal condition. @olding system reset switch down shall perform a 7A= T-!T function and will activate the pie<o sounder. Alarm Activate !witch. The alarm activate switch shall activate both notification circuits and alarm relays in the system. Alarm activate shall be a latching function.

#.

9.

1. -.

!ystem +peration

'.

8one !tatus 7-2s. The alarm, supervisory, or trouble 7-25s6 shall flash until event5s6 have been ac&nowledged 7-25s6 shall then illuminate steady. Any subsequent alarm, supervisory or trouble will flash the new event only. !upervisory. A short circuit on this <one shall cause the supervisory 7-2 and <one 1 yellow 7-2 to flash, and shall activate the supervisory notification circuit. An open circuit shall report as a <one trouble. 8one 2isable. 2isable/-nable shall be accomplished for any input circuit by a special sequence of the 1 control switches. If a <one has been disabled, an alarm shall activate the red <one 7-2, but not the pie<o or any output circuit.

#.

9.

F.

rogramming and !ystem *ommissioning '. The FA* shall have a configuration option which allows the user to program the FA* with one of thirteen factory preprogrammed templates or one custom template which can be programmed by the user. Templates shall include. *:+!!$8+N- !E!T-= ;IT@ @+:N !INF7- 8+N- !E!T-= ;IT@ @+:N !INF7- @A8A:2 *:+!!$8+N!INF7- @A8A:2 $ *+4NT +N!INF7- @A8A:2 $!INF7- 2-T-*T+:, *:+!!$8)N- NA* !INF7- @A8A:2 $ *:+!!$8+N- NA* *:+!!$8+N- !E!T-= $ %-77/@+:N/!T:+%!INF7- @A8A:2, !INF7- 2-T-*T+: $ %-77/@+:N/!T:+%24A7 @A8A:2 $ *:+!!$8+N24A7 @A8A:2 $ !INF7- 2-T-*T+: AF-NT/;AT-:F7+; $ *:+!! 8+NAF-NT/;AT-:F7+; $ !INF7- 2-T-*T+: @p *+# !INF7- 2-T-*T+:

F.

The control panel shall support the following modules. '. #. 9. 1. (. A. B) character :emote 7*2 Annunciator which mimics the FA* main display. I/+ 7-2 2river which provides 7-2 outputs for connection to a custom graphics annunciator. rinter =odule which provides a serial output for connection to a 47 listed event printer. :elay =odule which provides ') programmable form * relays. 7-2 Annunciator =odule which mounts on the FA* door and provides three 7-2s for each <one. Alarm, Trouble and !upervisory. +ptional 2igital *ommunicator 5complies with NF A "#6.

". @.

+ptional transmitter module which complies with NF A$"# Auxiliary and :emote !tation rotective !ignaling systems.

The control panel shall also include the following functions. '. #. 9. 1. (. A. ". +utput circuits shall be protected against false activations by using a #$step electronic activation circuit. %attery/-arth fault supervision shall be provided. Ad?ustable pre discharge timer shall be available, )) to A) seconds. Ad?ustable discharge timer shall be available, Galways onG or )'$#) minutes. Four abort functions options shall be selectable. 5'6 !tandard 47 methodH 5#6 I:I methodH 596 NE* method, and 516 local A@D method. " A@ to #A A@ battery options shall be available, providing up to ,) hours standby. ;atchdog timer to supervise microprocessor shall be provided.

I.

:emote Field *harging ower !upply '. The remote field charging power supply shall be a N+TIFI-: F* !$#1!A or F* !$#1!B. The F* !$#1!A/B shall be used to provide power to audio visual devices or any other device on the system whenever the power requirements exceed those provided by the FA* . The F* !$#1!A shall offer up to A.) amps continuous current of regulated, filtered, #1 volt power. It shall include an integral charger designed to charge ".) to 'B.) amp hour batteries and to support A) hour standby. The F* !$#1!B shall offer up to B.) amps continuous current of regulated, filtered, #1 volt power. It shall include an integral charger designed to charge ".) to 'B.) amp hour batteries and to support A) hour standby. The Field *harging ower !upply shall provide regulated and filtered #1 C2* power to four notification appliance circuits configured as either four *lass % 5!tyle E6 or *lass A 5!tyle 8, with 8NA*$1 option module6. Alternately, the four outputs may be configured as all non$resettable, all resettable, or two non$resettable and two resettable. The Field *harging ower !upply shall include an attractive surface mount bac&box. The Field *harging ower !upply shall include the ability to delay the A* fail delay per NF A requirements. The Field *harging ower !upply shall include power limited circuitry, per 47

#.

9.

1.

(. A. ".

standards. B. D. The Field *harging ower !upply shall provide 47$7isted NA* synchroni<ation using !ystem !ensor, ;heeloc&, or Fentex G*ommanderIG appliances.

!tand Alone Coice -vacuation *ontrol anel '. #. 9. A stand alone Coice -vacuation *ontrol anel shall be available from the same manufacturer of the main fire alarm system. This Coice *ontrol anel shall wor& stand alone or as a slave to the =ain *ontrol anel. !hall have as minimum requirements. a. b. c. Integral #( ;att, #( Crms audio amplifier. !pea&er circuit that can be wired both *lass A or %. Integral 2igital =essage Fenerator with a capacity of up to A) seconds. The 2igital =essage Fenerator shall be capable of primary and secondary messages 59) seconds each6. These messages shall field programmable without the use of additional equipment. %uilt in alert tone generators with steady, slow woop, high/low and chime tone field programmable. Integral 2iagnostic 7-2s for ower, !ystem Trouble, =essage Fenerator Trouble, Tone Fenerator Trouble, and Alarm.

d. e. 1. (. J.

The Coice *ontrol anel shall be fully supervised including microphone, amplifier output, message generator, spea&er wiring, and tone generators. !pea&er outputs shall be fully power$limited.

ower !upply '. #. The power supply for the control panel shall be integral to the control panel itself, and shall provide all control panel and peripheral device power needs. Input power shall be '#) CA*, A) @8. The power supply shall provide an integral battery charger for use with batteries up to #A A@. The FA* shall also be available in ##)/#1)CA*, A) @<. It shall provide ".) amperes of regulated #1 C2* power for release solenoids and notification devices, Four$;ire smo&e detector power #1 C2* up to 1)) mA, non resettable power #1 C2* up to 1)) mA. The power supply shall be designed to meet 47 and NF A requirements for power$

9.

1.

limited operation on all notification and initiating circuits. (. 7. ositive$temperature$coefficient thermistors, circuit brea&ers, fuses, or other over$ current protection shall be provided on all power outputs.

=echanical 2esign. The control panel shall be housed in a cabinet designed for mounting directly to a wall or vertical surface. The bac& box and door shall be constructed of ).)A) steel with provisions for electrical conduit connections into the sides and top. The door shall provide a &ey loc& and shall include a glass or other transparent opening for viewing of all indicators. The cabinet shall be approximately (.#( inches 5'9.91 cm6 deep and 'A.B inches 51#.A" cm6 wide. @eight shall be approximately ',.#( inches 51B.,) cm6. An optional trim ring shall be used for flush mounting of cabinet. !pace shall be provided in the cabinet for " A@ or 'B A@ batteries. If #A A@ batteries are used, a separate battery enclosure shall be available from the same manufacturer.

2.4. A. %. *. 2.5. A.

BATTERIES !hall be '# volt, Fell$*ell type 5# required6. %attery shall have sufficient capacity to power the fire alarm system for not less than ninety hours plus ( minutes of alarm upon a normal A* power failure. The batteries are to be completely maintenance free. No liquids are required. Fluid level chec&s refilling, spills and lea&age shall not be required. SYSTEM COMPONENTS: @orns, !trobes, and @orn/!trobes '. Feneral All horns, strobes and horn/strobes shall be !ystem !ensor !pectrAlert Advance series. @orns, strobes and horn/strobes shall mount to a standard 1 K 1 K 'L$inch bac& box, 1$inch octagon bac& box or double$gang bac& box. Two$wire products shall also mount to a single$gang # K 1 K ' "/B$inch bac& box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Indoor !pectrAlert Advance products shall operate between 9# and '#) degrees Fahrenheit from a regulated 2*, or full$wave rectified, unfiltered power supply. !trobes and horn/strobes shall have field$selectable candela settings including '(, '(/"(, 9), "(, ,(, ''), ''(, '9(, '(), '"", 'B(. #. !ynchroni<ation :equirements All @orns, !trobes, and @orn/!trobes shall be synchroni<ed without the need for additional synchroni<ation hardware or modules. !ynchroni<ation shall be provided by the : $#))# FA* ower !upply or from an additional field power supply. All @orns, !trobes, and @orn/!trobes shall be synchroni<ed at '@< and

horns at temporal three. Also, while operating the strobes, the FA* shall silence the horns on horn/strobe models over a single pair of wires. 9. !trobes The strobe shall be a !ystem !ensor !pectrAlert Advance =odel !: listed to 47 ',"' and shall be approved for fire protective service. The strobe shall be wired as a primary$signaling notification appliance and comply with the Americans with 2isabilities Act requirements for visible signaling appliances, flashing at '@< over the strobe>s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. 1. @orn/!trobe *ombination The horn/strobe shall be a !ystem !ensor !pectrAlert Advance =odel #: listed to 47 ',"' and 47 1A1 and shall be approved for fire protective service. The horn/strobe shall be wired as a primary$signaling notification appliance and comply with the Americans with 2isabilities Act requirements for visible signaling appliances, flashing at '@< over the strobe>s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have three audibility options and an option to switch between a temporal three$pattern and a non$temporal 5continuous6 pattern. These options are set by a multiple position switch. +n four$wire products, the strobe shall be powered independently of the sounder. The horn on horn/strobe models shall operate on a coded or non$coded power supply. (. +utdoor @orns, !trobes, and @orn/!trobes !pectrAlert Advance outdoor horns, strobes and horn/strobes shall be listed for outdoor use by 47 and shall operate between minus 1) degrees and '(' degrees Fahrenheit. The products shall be listed for use with a !ystem !ensor outdoor/weatherproof bac& box with half inch and three$fourths inch conduit entries. %. =anual Fire Alarm !tations '. =anual Fire Alarm !tations shall be N+TIFI-: N%F$'#7 and be non$code, with a &ey$ or hex$operated reset loc& in order that they may be tested, and so designed that after actual -mergency +peration, they cannot be restored to normal except by use of a &ey or hex. An operated station shall automatically condition itself so as to be visually detected as activated. =anual stations shall be constructed of red colored 7-MAN 5or polycarbonate equivalent6 with clearly visible operating instructions provided on the cover. The word FI:- shall appear on the front of the stations in white letters, '.)) inches 5#.(1 cm6 or larger. !tations shall be suitable for surface mounting on matching bac&box !%$') or !%$ I/+H or semi$flush mounting on a standard single$gang, double$gang, or 1G 5').'A

#.

9.

cm6 square electrical box, and shall be installed within the limits defined by the Americans with 2isabilities Act 5A2A6 or per national/local requirements. =anual !tations shall be 4nderwriters 7aboratories listed. *. *onventional hotoelectric Area !mo&e 2etectors '. !mo&e detector shall be a !ystem !ensor i9 !eries conventional photoelectric smo&e detector, listed to 4nderwriters 7aboratories 47 #AB for Fire rotection !ignaling !ystems. The detector shall be a photoelectric type 5=odel #;$%, 1;$%6 or a combination photoelectric/thermal 5=odel #;T$%, 1;T$%6 with thermal sensor rated at '9(NF 5(".#N*6. The detector shall include a mounting base for mounting to 9L$inch and 1$inch octagonal, single gang, and 1$inch square bac& boxes with a plaster ring. ;iring connections shall be made by means of !-=! screws. The detector shall allow pre$wiring of the base and the head shall be a plug$in type. The detector shall have a nominal sensitivity of #.( percent$per$foot nominal as measured in the 47 smo&e box. The detector shall be capable of automatically ad?usting its sensitivity by means of drift compensation and smoothing algorithms. The detector shall provide dual color 7-2 indication which blin&s to indicate power up, normal standby, out of sensitivity, alarm, and free<e trouble 5=odel #;T$%, 1;T$%6 conditions. Two$wire models shall include a maintenance signal to indicate the need for maintenance at the alarm control panel, and shall provide a loop testing capability to verify the circuit without testing each detector individually.

#.

9.

1.

2.

*onventional Ioni<ation Type Area !mo&e 2etectors '. !mo&e detector shall be a !ystem !ensor '1(' conventional ioni<ation plug$in smo&e detector, listed to 4nderwriters 7aboratories 47 #AB for Fire rotection !ignaling !ystems. Ioni<ation type smo&e detectors shall be a two wire, #1 C2* type using a dual unipolar chamber. -ach detector shall contain a remote 7-2 output and a built$in test switch. 2etector shall be provided on a plug$in twist$loc& mounting base. It shall be possible to perform a calibration sensitivity and performance test on the detector without the need for the generation of smo&e. A visual indication of an alarm shall be provided by dual latching 7ight -mitting 2iodes 57-2s6 over 9A) degrees, on the detector, which may be seen from ground level. This 7-2 shall flash every ') seconds, indicating that power is applied to the detector. The detector shall not alarm when exposed to air velocities of up to ',#)) feet

#. 9. 1. (. A.

".

59A(."A m6 per minute. The detector screen and cover assembly shall be easily removable for field cleaning of the detector chamber. B. -. All field wire connections shall be made to the base through the use of a clamping plate and screw.

2uct !mo&e 2etectors '. #. The air duct smo&e detector shall be a !ystem !ensor =odel 2# or 21'#) !eries 2uct !mo&e 2etector. The detector housing shall be 47 listed per 47 #ABA specifically for use in air handling systems. The detector shall operate at air velocities of ')) feet per minute to 1))) feet per minute 5).( to #).9# m/sec.6. It shall be capable of local testing via magnetic switch or remote testing using the :T!'1('J-E :emote Test !tation. The unit shall be reset by local reset button or :T!'1('J-E. The duct detector housing shall incorporate an airtight smo&e chamber in compliance with 47 #ABA, !tandard for !mo&e 2etectors for 2uct Applications. The housing shall be capable of mounting to either rectangular or round ducts without adapter brac&ets. An integral filter system shall be included to reduce dust and residue effects on detector and housing, thereby reducing maintenance and servicing. !ampling tubes shall either be plastic or be easily installed after the housing is mounted to the duct by passing through the duct housing. The enclosure shall meet all applicable N-* and NF A standards regarding electrical ?unction boxes. Terminal connections shall be of the strip and clamp method suitable for '#$'B A;F wiring.

9.

1.

(.

F.

ro?ected %eam 2etectors '. #. 9. 1. (. The ro?ected %eam 2etector shall be a !ystem !ensor =odel %-A='##1! 1$wire conventional reflected beam smo&e detector, listed to 47 standard #AB. The %eam 2etector shall be single$ended reflected design. All wiring shall only be necessary on the transmitter/receiver end of the detector. %eam 2etector alignment shall quic&ly accomplished via an optical sight and a #$ digit signal strength meter incorporated into the product. The %eam 2etector shall be listed for operation from $##NF to '9'NF 5$9)N* to ((N*6. The %eam 2etector shall have four standard sensitivity selections along with two Acclimate settings. ;hen either of the two Acclimate settings is selected the detector will automatically ad?ust its sensitivity to select the optimum sensitivity for the specific environment.

A.

The %eam 2etector shall be equipped with an integral sensitivity test feature that meets the annual maintenance and test requirements of NF A "#. This test feature shall be initiated via a &ey switch. The pro?ected beam type shall be a 1$wire #1 C2* device. The unit shall be both ceiling and wall mountable.

". B. F.

Automatic *onventional @eat 2etectors '. =echanical heat detector shall be a !ystem !ensor (A)) series model, listed to 4nderwriters 7aboratories 47 (#' for @eat 2etectors for Fire rotective !ignaling !ystems. The detector shall be either a single$circuit or a dual$circuit type, normally open. The detector shall be rated for activation at either '9(NF 5("N*6 or ',1NF 5,)N*6, and shall activate by means of a fixed temperature thermal sensor, or a combination fixed temperature/rate$of$rise thermal sensor. The rate$of$rise element shall be activated by a rapid rise in temperature, approximately '(NF 5B.9N*6 per minute. The detector shall include a reversible mounting brac&et for mounting to 9L$inch and 1$inch octagonal, single gang, and 1$inch square bac& boxes with a square to round plaster ring. ;iring connections shall be made by means of !-=! screws that shall accommodate '1$##A;F wire. The detector shall contain alphanumeric mar&ings on the exterior of the housing to identify its temperature rating and activation method. The rate$of$rise element of combination fixed temperature/rate$of$rise models shall be restorable, to allow for field$testing. The detectors shall include an external collector that shall drop upon activation to identify the unit in alarm.

#.

9.

1. (.

@.

;aterflow !witches. '. #. ;aterflow !witches shall be an integral, mechanical, non$coded, non$accumulative retard type. ;aterflow !witches shall have an alarm transmission delay time which is conveniently ad?ustable from ) to A) seconds. Initial settings shall be 9)$1( seconds. All waterflow switches shall come from a single manufacturer and series. ;aterflow switches shall be provided and connected under this section but installed by the mechanical contractor. ;here possible, locate waterflow switches a minimum of one 5'6 foot from a fitting which changes the direction of the flow and a minimum of three 596 feet from a

9. 1. (.

valve. I. !prin&ler and !tandpipe Calve !upervisory !witches. '. -ach sprin&ler system water supply control valve riser, <one control valve, and standpipe system riser control valve shall be equipped with a supervisory switch. !tandpipe hose valves, and test and drain valves shall not be equipped with supervisory switches. IC 5post indicator valve6 or main gate valves shall be equipped with a supervisory switch. The switch shall be mounted so as not to interfere with the normal operation of the valve and ad?usted to operate within two revolutions toward the closed position of the valve control, or when the stem has moved no more than one$fifth of the distance from its normal position. The supervisory switch shall be contained in a weatherproof aluminum housing, which shall provide a 9/1 inch 5', mm6 conduit entrance and incorporate the necessary facilities for attachment to the valves. The switch housing shall be finished in red ba&ed enamel. The entire installed assembly shall be tamper proof and arranged to cause a switch operation if the housing cover is removed, or if the unit is removed from its mounting. Calve supervisory switches shall be provided and connected under this section and installed by mechanical contractor.

#. 9.

1.

(. A.

". D.

*arbon =onoxide 2etector '. *arbon monoxide detector shall be a !ystem !ensor model number *+'##1T, listed to 4nderwriters 7aboratories 47 #)"( for Fas and Capor 2etectors and !ensors. The detector shall be equipped with a sounder and a trouble relay. The detector>s base shall be able to mount to a single$gang electrical box or direct 5surface6 mount to the wall or ceiling. ;iring connections shall be made by means of !-=! screws. The detector shall provide dual color 7-2 indication, which blin&s to indicate normal standby, alarm, or end$of$life. ;hen the sensor supervision is in a trouble condition, the detector shall send a trouble signal to the panel. ;hen the detector gives a trouble or end$of$life signal, the detector shall be replaced.

#. 9.

1.

PART 3.0 - E#ECUTION 3.1. INSTALLATION:

A. %.

Installation shall be in accordance with the N-*, NF A "#, local and state codes, as shown on the drawings, and as recommended by the ma?or equipment manufacturer. All conduit, ?unction boxes, conduit supports and hangers shall be concealed in finished areas and may be exposed in unfinished areas. !mo&e detectors shall not be installed prior to the system programming and test period. If construction is ongoing during this period, measures shall be ta&en to protect smo&e detectors from contamination and physical damage. All fire detection and alarm system devices, control panels and remote annunciators shall be flush mounted when located in finished areas and may be surface mounted when located in unfinished areas. At the final inspection a factory trained representative of the manufacturer of the ma?or equipment shall perform the tests in !ection 9.# T-!T!. TEST: rovide the service of a competent, factory$trained engineer or technician authori<ed by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the ad?ustments and tests for the system. '. #. 9. 1. (. A. ". B. ,. '). ''. %efore energi<ing the cables and wires, chec& for correct connections and test for short circuits, ground faults, continuity, and insulation. *lose each sprin&ler system flow valve and verify proper supervisory alarm at the FA* . Cerify activation of all flow switches. +pen initiating device circuits and verify that the trouble signal actuates. +pen and short notification appliance circuits and verify that trouble signal actuates. Fround device circuits and verify response of trouble signals. +pen release solenoids and verify response of trouble signals. *hec& presence and audibility of tone at all alarm notification devices. *hec& installation and supervision of heat detectors to ascertain that they will function as specified. *onduct tests to verify trouble indications for common mode failures, such as alternating current power failure. -ach of the alarm conditions that the system is required to detect should be

*.

2. 3.2.

introduced on the system. Cerify the proper receipt and that the release solenoid5s6 will activate. 3.3. FINAL INSPECTION: At the final inspection a factory trained representative of the manufacturer of the ma?or equipment shall demonstrate that the systems function properly in every respect. 3.4. INSTRUCTION: rovide instruction as required to the building personnel. G@ands$onG demonstrations of the operation of all system components and the entire system shall be provided.