Professional Documents
Culture Documents
R=/A(3.14/A)
Where =Resistivity of Soil ( Meter), A=Area of both side of Plate (m2), Example: Calculate Number of CI Earthing Plate of 600600 mm, System has Fault current 65KA for 1 Sec and Soil Resistivity is 100 -Meters. Current Density At The Surface of Earth Electrode (As per IS 3043): Max. Allowable Current Density I = 7.571000/(xt) A/m2 Max. Allowable Current Density = 7.571000/(100X1)=757 A/m2 Surface area of both side of single 600600 mm Plate= 2 x lxw=2 x 0.060.06 = 0.72 m2 Max. current dissipated by one Earthing Plate = Current Density x Surface area of electrode Max. current dissipated by one Earthing Plate =7570.72= 545.04 Amps Resistance of Earthing Plate (Isolated)(R)=/A(3.14/A) Resistance of Earthing Plate (Isolated)(R)=100/0.72x(3.14/.072)=290.14 Number of Earthing Plate required =Fault Current / Max.current dissipated by one Earthing Pipe. Number of Earthing Plate required= 65000/545.04 = 119 Nos. Total Number of Earthing Plate required = 119 Nos. Overall resistance of 119 No of Earthing Plate=290.14/119= 2.438 .