You are on page 1of 28

Zoning

Design Guide
Zone
Zone

8500 NW River Park Drive • Parkville , MO 64152


PH: (816) 505-1100 • FX: (816) 505-1101 • E-mail: mail@wattmaster.com
Visit our website at www.wattmaster.com
Form: WM-AZA-ZDG-01B Copyright 2001 WattMaster Controls, Inc.
Auto-Zone & System Manager are registered trademarks of WattMaster Controls, Inc.

WattMaster Controls assumes no responsibility for errors, or omissions.


This document is subject to change without notice. All rights reserved.
Table Of Contents
How Auto-Zone Works .......................................................................................................... 5
Why Should I Use Auto-Zone? .............................................................................................. 6
What Is Unique About Auto-Zone? .................................................................................... 6-8
Zoning Systems Versus True VAV Systems .......................................................................... 9
Basics Of Designing A Zoning System ................................................................................ 10
Design Considerations ................................................................................................... 11-12
Zoning Design Procedures ............................................................................................. 13-21
System Installation ......................................................................................................... 22-26
Application Notes ................................................................................................................ 27

Table Of Figures & Tables


Figure 1-1: Auto-Zone Plus System Overview .................................................................... 5
Figure 1-2: Zones Affected By Outdoor Load .................................................................. .13
Figure 1-3: Zone Layout With External Zones Only ......................................................... .14
Figure 1-4: Zones With North And South Exposures ....................................................... .14
Figure 1-5: Zoning And Constant Volume Units ............................................................... .14
Figure 1-6: Round Bypass Damper .................................................................................. .16
Figure 1-7: Rectangular Bypass Damper & Kit ................................................................ .16
Figure 1-8 Preferred Sensor Location .............................................................................. 17
Figure 1-9: Acceptable Sensor Location ........................................................................... 17
Figure 1-10: Least Desirable Sensor Location .................................................................... 17
Figure 1-11: Pressure Dependent Damper ......................................................................... 18
Figure 1-12: Pressure Independent Damper ....................................................................... 18
Figure 1-13: WattMaster Communications Wire ................................................................. 23
Figure 1-14: Auto-Zone Basic System Communications Loop Wiring ................................ 24
Figure 1-15: Auto-Zone Plus System Communications Loop Wiring .................................. 24
Figure 1-16: Transformer & Wire Sizing Considerations ..................................................... 26
Table 1-1: Round Damper Selection Data .......................................................................... 19
Table 1-2: Rectangular Damper Selection Data ................................................................. 20
Zoning Design Guide

How Auto-Zone Works


The Auto-Zone control system converts single-zone First the zone must initiate a vote to the HVAC unit.
constant volume rooftop packaged or split system This occurs when a zone becomes more than 1 degree
HVAC units into variable air volume/variable tempera- off setpoint. At this time a vote is placed for heating or
ture multiple zone systems. The microprocessor based cooling. Next the controller evaluates the total cooling
Zone Manager calculates the heating and cooling re- demand or heating demand within the entire building
quirements for each zone based on real time informa- to see which requirement is more critical. Finally, the
tion received from each Zone Controller/Damper. The system looks for any priority conditions, which would
Zone Manager then directs the HVAC unit to provide take precedence over other zones. All three of these
the appropriate amount of heating, cooling, and venti- elements working together provide accurate and stable
lation to satisfy each zone’s requirements. A bypass control of comfort.
damper controlled, by a static air pressure sensor, modu-
lates a bypass damper to maintain constant duct pres- Additional control features are taken into account to
sure. provide a very effective control of the system. Some of
these include priority override, supply air temperature
The Auto-Zone system uses a unique 3 tier approach to limits, outside air temperature lockouts, and min./max.
controlling the system: control over damper position.

• Voting Zones Substantial savings can be realized using the Auto-Zone


Zoning system instead of having to install multiple roof-
• System Demand top units to accommodate multiple zone requirements.
• Priority The Auto-Zone Zoning system is versatile and can be
used with any packaged roof top unit or split system. It
This 3 tier system works in an integrated fashion to controls a variety of terminal unit functions including
maintain proper control of the equipment and effective single duct pressure dependent, pressure independent,
control of comfort in the zone. series fan and parallel fan terminals.
H C
FAN E F
CONTROL CABLE O I
A O L
T L T MIXED
I I AIR OUTSIDE AIR
E
N N
R
G G EXHAUST AIR

AVOID SUPPLY AIR


DIRECT TEMPERATURE
SUNLIGHT SENSOR
RETURN AIR
2 CONDUCTOR 2 CONDUCTOR
24 GA. 24 GA.
MODULATING
BYPASS DAMPER RETURN AIR SENSOR
2 CONDUCTOR
OUTSIDE AIR 24 GA.
SENSOR 3 CONDUCTOR
24 GA. STATIC PRESSURE SENSOR CONNECT TO OTHER
& PICKUP TUBE ZONE CONTROLLERS
OR CV UNITS
LO HI
NETWORK COMM LOOP
CONNECT TO OTHER SUPPLY AIR DUCT
ZONE MANAGERS

AC LINE
VOLTAGE 24 VAC
GROUND
MODULATING MODULATING
DAMPER DAMPER

COMPUTER
(OPTIONAL)

ZONE ZONE
CONTROLLER CONTROLLER

ZONE MANAGER NORMAL


WARMER

COOLER

Auto-Zone CV OVR

07/20/98 02:38PM MON


OCCUPIED
NO ALARMS SYSTEM MANAGER
Alarm

1 2 3 Menu Esc

LOCAL COMM LOOP


Communication

4 5 6
ZONE 1 ZONE 2
Override

7 8 9
Dec.
* 0 Minus Clear Enter
WATTMASTER CONTROLS INC.
TEMPERATURE SENSOR TEMPERATURE SENSOR
COMM LINK II
120/24 VAC
W/OVERRIDE AND SETPOINT ADJUST
SYSTEM MANAGER
Remote Link

120/9 VAC C O N T R O L S
C O N T R O L S

TRANSFORMER
TRANSFORMER REMOTE LINK COMM LINK II UP TO 16 ZONES
(OPTIONAL MODEM) INTERFACE
( OPTIONAL )

Figure 1-1: Auto-Zone Plus System Overview


Auto-Zone Systems 5
Zoning Design Guide

Why Should I Use Auto-Zone?


Auto-Zone is a proven system with a long history of on real world experience not from tinkering with equip-
successful installations. Our systems have been refined ment in an isolated lab environment. This real world
over the years with the help of feedback from people in approach provides engineers, contractors, and end us-
the field who work and live with these systems on a ers with a zone control system that is efficient, reliable,
daily basis. Our success is greatly due to the fact that and most importantly, keeps the customers comfortable!
we have implemented changes and enhancements based

What Is Unique About Auto-Zone?


Auto-Zone is unique because it has many features not One System for Zoned or Single Zone
found on other systems. These features include Systems
Not only does Auto-Zone provide a networked zone
Non-Proprietary Design control system for one or multiple zoned HVAC units,
Auto-Zone will work on any manufacturers HVAC you can also connect individual single zone units to the
equipment that will accept a standard thermostat con- system eliminating the need to use programmable ther-
nection. This protects the end user from being locked in mostats.
to one source for service and support. In addition, Auto-
Zone Systems include very comprehensive documenta- Easy to Configure
tion, which was written in a format specifically for a Since Auto-Zone components are grouped into pack-
“non-controls technician”. Because the manuals are so ages, configuring a system has been simplified. This
user friendly, it prevents the end user from being reduces the chance of ordering errors and makes sys-
“locked-in” to one contractor for service. Any new con- tem layout effortless!
tractor needs only a copy of the system manual to have
as much technical information as any previous contrac- User Friendly Set Up
tor.
Since the Auto-Zone comes with menu driven, fill in
Pre-Engineered Software the blank programming, system setup is simple. The
system manual takes you step by step through the set
System design, software, and documentation has already up process. Default parameter values are programmed
been done for you. This eliminates the costly expense into permanent memory so the system can be opera-
usually associated with conventional DDC systems, tional at start-up. Specialized training is not required.
making the Auto-Zone system more competitive and
easier to install and operate.

6 Auto-Zone Systems
Zoning Design Guide

True Network Communications CommLink II communications interface and a local


The Auto-Zone uses a three wire, RS-485 loop for com- phone line. With the Remote Link, the Auto-Zone sys-
munication between all controllers in the system. This tem can be monitored and controlled from a remote lo-
provides a very reliable form of communication with cation, using a computer and the ZoneView AZ or Plus
flexibility of installation. The loop can be wired in a software packages.
“daisy chain” or “star” configuration. Many other zon-
ing systems utilize “home run” wiring that requires all Memory Backup
communication cables to be brought back to a central Instead of batteries, which have to be replaced, Auto-
point adding additional cost to the project and compli- Zone utilizes super capacitors to provide power for
cating wiring. memory backup during power outages. The major ad-
vantages to this approach is that super capacitors are
High Integrity Communications more reliable than batteries and they recharge in a mat-
Many communicating control systems are susceptible ter of seconds instead of hours. Typical memory backup
to electrical interference. One major manufacturer of is good for a minimum of 10 days.
zoning systems recommends that their communication
cable should not be strapped to conduit because of po- Modulating, Heavy Duty Actuators with
tential interference. The Auto-Zone Systems have a Real Time Feedback
communication bus that is almost immune to any noise All Auto-Zone actuators utilize true modulating con-
problems that may be found in most commercial facili- trol unlike many systems, which are two position. This
ties. gives the system-improved control, which translates, to
better comfort levels. Our actuators are also rated for
Microprocessor Controllers 2-½ million cycles, making our actuators some of the
All controllers in the Auto-Zone have an on board most reliable in the industry. One other critical feature
microprocessor. This is what gives the Auto-Zone its is the real time feedback. Many other systems have no
powerful features and capabilities not found in other feedback at all. They blindly estimate the travel time of
systems. their actuator, which, in the real world, is not a very
repeatable estimate. To help correct the problems in-
Stand Alone Systems herent with this approach, they recycle all the actuators
in the system once or twice a day. They may save a few
All Auto-Zone Systems are true stand-alone and do not
dollars by not including feedback but they sacrifice sys-
require a computer to operate. Unit controllers main-
tem performance. Not so with Auto-Zone.
tain their own 7 day time clock, 365 day holiday sched-
uling, and setpoints within each controller.
Commercial Grade – Insulated Round
Zone Dampers
Menu Driven Operators’ Interface
Auto-Zone only uses commercial grade zone dampers,
All Auto-Zone systems have an operators’ keypad and
not cheap, flimsy, “light commercial” or “residential”
display terminal. This gives you access to system sta-
style dampers like many other manufacturers. Our round
tus and parameter values without the need for a com-
damper is ARI certified and comes from the factory
puter. The 4 line by 20 character display is backlighted
fully insulated. Why? When many zone dampers are
making it easy to read even in low light environments.
installed they are improperly insulated or not insulated
Menu driven programming makes the system extremely
at all. This can cause problems with the damper “sweat-
user friendly. In addition, the interface panel is pass-
ing” from condensation. With factory insulated zone
word protected to keep unauthorized users from access-
dampers, we eliminate a common problem for the con-
ing the system.
tractor while insuring the end user will not have prob-
lems with condensation dripping down onto the ceil-
Communications Via Optional Modem
ing.
The Remote Link is used for achieving remote commu-
nications with the Auto-Zone system. It connects to the

Auto-Zone Systems 7
Zoning Design Guide

What Is Unique About Auto-Zone?


Rectangular Dampers hundreds. ZoneView is not copy protected so it can be
Auto-Zone uses only top of the line, aluminum air foil installed on multiple PC’s’ without additional expense.
rectangular control dampers. No other zone system on Just some of its many features include but are not lim-
the market today utilizes a damper of this quality and ited to:
performance! • Pre-designed status screens for all controllers

Patented Flush Mount Room Sensors • Alarm dial out capability


Our flush mount room sensors are so unique, they are • Programming of all system parameters
patented (U.S. Patent No. 4,659,236). Even though part
of the sensor is recessed into the wall to provide an • Trend logging to Excel™ spreadsheets
attractive yet tamper proof flush mounting, internal wall
temperatures do not influence the sensor. A special plate • Alarm Handling
on the face of the sensor accurately senses space tem- • Custom graphics capability
perature. Even though the attractive off white plastic
housing is a preferred color, the sensor housing can be
painted or wallpapered to blend with room decor with-
out affecting sensor performance. The sensors are of-
fered in four different configurations:
• Sensor
• Sensor w/override
• Sensor w/setpoint adjustment
• Sensor w/setpoint adjustment & override

Modular Connections
Many Auto-Zone auxiliary devices are connected to the
controllers via modular plugs like the ones used on tele-
phones. This simplifies installation and eliminates the
possibility of wiring errors. The devices, which utilize
this method, are damper actuators for zone and bypass
control, auxiliary relay boards, and static pressure/air
flow sensors. There is one interesting side note about
the auxiliary relay board and airflow sensors. These
devices are typically used on the zone controllers in the
Auto-Zone Basic & Plus systems. When the system is
powered up, it automatically looks to see if these de-
vices are connected to the controller. If they are, the
controller automatically reconfigures itself to utilize
these devices and activates the appropriate set up screens
back at the operators interface. Pretty neat don’t you
think! Open Protocol System
Auto-Zone is an open protocol based system allowing
FREE! Windows™ Graphics Software other manufacturers to develop direct interfaces to the
Each Auto-Zone system can be monitored on site or communications loop. This gives you the ability to in-
remotely using a PC and our ZoneView Plus™ Win- tegrate the Auto-Zone system into products from other
dows 98 software. This full-featured package is very vendors. Our engineering staff will be glad to assist any
user friendly and can be used to monitor one system or vendor in this process.

8 Auto-Zone Systems
Zoning Design Guide

Zoning Systems Versus True VAV Systems


General Auto Zone Systems
Even though there are some similarities between zone The Auto-Zone zoning system is completely different
control systems and Variable Air Volume (VAV) sys- in operation and design from the VAV system previ-
tems, there are some major differences. In many cases ously discussed. One of the major differences between
systems will be called VAV when in fact they are really the zoning system and a true VAV system is that the
a zoning system or are referred to as a zoning system HVAC unit used on a zoning system utilizes a constant
when they are really a VAV system. Always make sure volume fan. Air volume control of the zoning system is
that you do not try to adapt a zoning system to a VAV achieved by bypassing air from the HVAC unit supply
design system. Understanding the differences will help duct back into the HVAC unit return air duct on the unit
you to prevent misapplication of the Auto-Zone zoning inlet. This bypass air is controlled based on a static pres-
system. In the paragraphs that follow we will try to ex- sure sensor located in the supply air duct downstream
plain the differences, advantages and disadvantages of of the unit supply air discharge. The bypass damper
each and explain their operation. modulates open and closed based on the static pressure
in the duct. The temperature at the HVAC unit discharge
VAV Systems varies in relation to the demand from the zones. Typi-
These systems consist of an HVAC unit that is gener- cally the HVAC units used for the zoning system will
ally a cooling only unit and VAV terminal units located have both heating and cooling capabilities. The fan sup-
in the downstream ductwork that are used to control plies a constant volume of cold or hot air to the duct
the amount of constant temperature air delivered to the system and which is fed to the individual zones by modu-
various building zones. Sometimes the HVAC unit may lating zone dampers. Each zone controller relays its heat-
have gas or electric heat, but it is typically sized and ing or cooling demand to the HVAC unit controller. The
applied for morning warm-up purposes. The HVAC unit HVAC unit controller determines its mode of operation
is designed to vary the volume of air that is supplied to (heating, cooling or vent mode) depending on the de-
the duct system by using either inlet vanes or an elec- mand from the zone controllers. The unit controller uti-
tronic variable frequency drive. These devices modu- lizes a voting system to determine the correct mode of
late to control the air flow through the supply fan in operation. Each zone controller determines (based on
response to the static pressure in the duct system. VAV its heating and cooling setpoints) whether or not to use
systems typically use high velocity VAV terminal units the air being supplied by the HVAC unit. For example,
to distribute the air to the zones. As the various VAV one of the zones is calling for cooling when the tem-
terminal units in the different zones open and close to perature in the duct is above the zones cooling setpoint.
supply the constant temperature air to the spaces, the This zone will move to its minimum cooling position
HVAC unit varies the volume of constant temperature to prevent warm air being introduced into the space.
air based on the static pressure in the ductwork. The With the zoning system the zone dampers are generally
HVAC unit is designed to maintain a constant cold sup- pressure dependent. Pressure independent operation is
ply air temperature regardless of the air flow volume in available but is not very common. Reheat and/or fan
the system. The HVAC unit cycles it’s cooling stages powered terminal units can be used but aren’t commonly
to maintain a constant predetermined supply air tem- part of the typical zoning system.
perature. It typically runs continuously based on a sched-
ule. For perimeter zones requiring heat, reheat coils Conclusion
(electric or hot water) located in the terminal units are In many cases VAV systems go over budget because of
used to supply heated air to the space. Many times fan the increased cost of a VAV, HVAC unit and the expen-
powered terminal boxes are used and in many cases sive VAV controls associated with the system. Many
also incorporate electric or hot water heating coils to times the system can be redesigned to a zoning system
provide perimeter zone heating. In summary a true VAV using Auto-Zone controls with a significant cost sav-
system uses a variable volume fan supplying constant ings and equal or better performance and comfort than
temperature air to the system with variable volume ter- the VAV system would provide. Be sure to follow the
minal units used to control the volume of constant tem- instructions in this design guide for your zoning sys-
perature air delivered to the space. Generally these sys- tem.
tems use pressure independent damper control.
Auto-Zone Systems 9
Zoning Design Guide

Basics of Designing A Zoning System


This is a summary of the key items you need to con- • If you have electric reheat coils mounted on
sider for the design and layout of a successful zoning
system. VAV boxes, it is recommended that a fan
powered box be used. Consult the factory for
It is important that you study the design guide for a further details concerning this application.
more in depth understanding of proper system design.
• If there is an economizer on the HVAC unit,
By following the design guide and these tips you can
eliminate many unnecessary headaches that occur when it is highly recommended, though not
the basic rules of zoning are not followed. Always con- required, that the Zone Manager control the
tact WattMaster Controls if you have any questions. economizer.

• Always group zones with similar load • Pressure Independent Zones must always use
profiles on the same HVAC unit. round dampers or VAV boxes, never
rectangular - no exceptions!
• Never mix perimeter zones with interior
zones on the same HVAC unit. • Never attempt to use a zone control system
on a true VAV application. See “ Zoning
• Each zoned HVAC unit should have a
Systems Versus True VAV Systems” on page
minimum of 3 to 4 zones. Any less and you
9 of this guide for detailed information.
should consult the factory.
• Bypass dampers should always be sized for
• Each zoned HVAC unit can support a
60%-70% of the HVAC units rated CFM.
maximum of 16 voting zones. Any more
zones and you should contact the factory. • Even though the Auto-Zone system has
certain features to help protect your
• When using auxiliary heat for individual
equipment, never override or disconnect any
zones, perimeter heat such as baseboard is
safety devices associated with the HVAC
always preferred and more economical to
unit.
operate than a fan terminal unit with reheat.

10 Auto-Zone Systems
Zoning Design Guide

Design Considerations
Load Diversity on utilities and provide comfort under conditions when
A zoning system is designed to improve tenant comfort it is not possible to operate the mechanical cooling sys-
by dynamically rebalancing the air distribution when tem.
used with a typical constant volume rooftop heating/
cooling unit. If zones with extremely different load con- 2.) Low Supply Air Temperatures. Under lightly
ditions are serviced by a single rooftop unit, the result loaded conditions much of the supply air may be by-
will be poor control and excessive wear due to cycling passed back into the return air side of the HVAC unit.
of the equipment. This bypassing will result in the lowering of the supply
air temperature, which may result in the supply air tem-
It is especially important to avoid mixing interior zones perature reaching the low temperature safety limit. If
(which require cooling all year) with exterior zones the supply air low temperature safety limit is exceeded,
(which may require constant heat during winter months). the control system will “cut off” the mechanical cool-
If you must mix zones under these conditions, consider ing to protect it from damage. Excessive cycling of the
using either VAV boxes with heat or separate external mechanical system will result if this condition persists.
heat on perimeter zones. Auto-Zone Zoning systems Comfort may also suffer if the system cannot run long
offer a variety of methods to control additional zone enough to satisfy cooling demands.
heat to help you avoid problems.
A number of things can be done to reduce this problem.
Group similar loads on an individual unit and use more Some of these things depend upon the type of installa-
than one zoned unit if required. Any special loads can tion.
be handled by using separate constant volume units.
Avoid oversizing the unit. Do your all load calculations
The Auto-Zone Plus system offers the designer consid- carefully. Since the zoning system directs the heating
erable flexibility by allowing both multiple-zoned units or cooling to the zones which require it, you may find
and single-zone units to be connected within a single that you can use a smaller unit in many cases. Oversizing
simple system. is the number one cause of excessive low supply air
temperature cycling.
Cooling - Partial Load Conditions
Use an economizer. Although this is not a cure-all, it
The engineer must be aware of several potential prob-
greatly improves operation during cool weather when
lems when applying a zoning system for cold weather
cooling loads are minimal. Using an economizer also
operation.
improves ventilation and lowers operating costs.
1.) Low Ambient Temperature Lockout. During very
Increase cooling minimum airflow. Increase your cool-
cold weather it is common for mechanical systems to
ing minimum airflow or damper position settings to al-
have “low temperature lockouts” which protect equip-
low more air during cooling operation. Be careful to
ment from damage if operated under these conditions.
avoid minimum settings that are so high they may cause
Auto-Zone also provides user programmed lockouts for
over cooling of the spaces.
protection purposes, although mechanical safeties
should always be used as the final stage of protection.
Bypass the air into the ceiling plenum. If you have a
system without ducted return, bypass the air into the
If the rooftop unit services interior zones with thermal
ceiling plenum instead of into the return air intake. Be
loads, which require cooling when outside temperatures
careful if you use this method since you may get “dump-
are below the safe operating limits for your equipment,
ing” of cold air from your return air grilles. This method
you should seriously consider installing an economizer
works best with plenum returns. Do not use this method
on your rooftop unit. The Auto-Zone control system is
with ducted returns.
designed to take advantage of an economizer if it is
installed. The use of an economizer will save money

Auto-Zone Systems 11
Zoning Design Guide

Design Considerations
Increase your static pressure setpoint. This will help method works best with plenum returns. Do not use
reduce the amount of air being bypassed. Be aware of this method with ducted returns
increased noise levels and the cost of operation if you
use excessive static pressures. This will not work if you Use auxiliary heat . Use an auxiliary heat source in
are using pressure independent zone controllers, since either your VAV boxes or use baseboard heaters.
they will maintain a constant flow of air to the zones
regardless of duct static pressure. This technique will Auto-Zone has a number of auxiliary heat control op-
likely cause over cooling of the spaces due to increased tions which provide solutions to most problems. Refer
airflow at minimum positions. to the Auxiliary Heat Control Options topic near the
end of this section.
Warning:
Override Conditions
If the fan system has the capability of producing static After-hours overrides can produce aggravated partial
pressures which could damage ductwork you must pro- load conditions in both the heating and cooling modes.
vide a manual reset, high pressure limit switch (Dwyer A single zone being overridden for after-hours use most
1900-5-MR or equal) to cut off the fan system in the commonly causes the problem. This causes the rooftop
event of high duct static. Do not use your Auto-Zone equipment to operate for only one zone. The Auto-Zone
Zoning system as a safety device! system offers an improved solution to this common
problem by allowing a single override to trigger a group
of zones via a “global” override. This allows the sys-
Heating - Partial Load Conditions
tem to operate with sufficient load to reduce cycling
Heating difficulties are less common than cooling dif- caused by light load conditions.
ficulties. They are similar in nature, however, and the
cures are generally the same. Again, a number of things Building Pressurization
can be done to reduce the effects of this problem.
If you are using an economizer, building pressurization
must be addressed. Failure to properly handle building
Increase heating minimum airflow. Increase your heat-
pressurization may result in doors remaining open when
ing minimum airflow or damper position settings to
the economizer is operating. Pressurization problems
allow more air during heating operation. Be careful to
can render economizer operation useless. The follow-
avoid minimum settings that are so high they may cause
ing suggestions will help to avoid potential problems.
over heating of the spaces.
Use powered exhaust. A power exhaust fan(s) must be
Increase the static pressure. Set the static pressure
used when the system utilizes ducted returns. The re-
setpoint to be as high as practical. Increasing static pres-
turn duct pressure drop will cause most barometric re-
sure does not help if you are using pressure indepen-
lief dampers to function poorly or not at all. Auto-Zone
dent control operation.
has the ability to control a powered exhaust whenever
the economizer is operating.
Avoid oversizing the unit. Do your all load calculations
carefully. Since the zoning system directs the heating
Use a separate building pressure control. Use a con-
or cooling to the zones which require it, you may find
trol that operates a relief fan or dampers to relieve build-
that you can use a smaller unit in many cases.
ing pressure
Bypass the air into the ceiling plenum. If you have a
system without ducted return, bypass the air into the
ceiling plenum instead of into the return air intake. This

12 Auto-Zone Systems
Zoning Design Guide

Zoning Design Procedures


General on the wall, ceiling and floor material and location
There are six basic steps to designing an Auto-Zone within the building (e.g. top or middle floor), a typical
Zoning system: floor of a building usually has several distinct tempera-
ture or control zones that are affected uniquely by the
1.) Determining the number and location of zones outdoor load. These zones are depicted in Figure 1-2.
Depending on the size of the building and partition lay-
2.) Sizing the central unit out, some of these zones may overlap or be insignifi-
cant from a zoning standpoint. For example, Zone 11
3.) Duct Considerations could be multiple conference or computer rooms where
additional zoning would be required, or it could be as
4.) Room air motion and diffuser selection small as a corridor where no zoning is required. Simi-
larly, zones 7 and 8 could have no external windows
5.) Bypass damper sizing and no partitions between them and could be consid-
ered a single zone. Some zones could be divided into
6.) Sizing the zone dampers multiple offices with full partitions between them, thus
requiring separate Zone Controllers because of differ-
ent internal loads, but the same external load.
Step #1 - Determining The Number And
Location Of Zones Generally, the greater the number of individual Zone
Controllers, the greater the comfort. The designer will
A single air handler unit can have no more than sixteen have to look at the specific building, balancing the costs
zones and no fewer than 3 zones. If the number of zones of multiple zones with the added comfort possible with
exceeds sixteen then more than one Zone Manager will multiple zones, to match the owner’s requirements.
be required.
It is important to recognize that there are purely inter-
The primary precaution to be taken in applying the Auto- nal zones, such as Zone 11 in Figure 1-2, which may
Zone Zoning System is to select the zoning so that no contain separate offices/conference/computer rooms.
zone will be at maximum (design) heating (or cooling) These internal zones could easily have high cooling re-
load when any other zone requires the opposite tem- quirements while external zones (1,2,3, etc.) could be
perature air to satisfy its load. For example, depending at or near design heating load. This is a misapplication
of the Auto-Zone, zoning (or any heating/cooling
change-over) system. The interior zones with cooling
only loads should be served by a separate single zone
 rooftop HVAC unit (that could be zoned between mul-
tiple rooms with a similar load profile). Supplemental
heat could be added to the perimeter zones and con-
   trolled with the auxiliary heat control board from the

Zone Controller. System performance will generally be
compromised and frequent change-over from the heat-
ing to the cooling mode will occur during the heating
  season if purely internal zones are combined on the same
 air-conditioning unit serving perimeter zones. The ex-
posure to the sun has a large affect on the loading of the
building. With the building zoned as shown below, for
    the best control, zones 6, 7, 8, 9 and 10 should be put
on one HVAC unit, and zones 1, 2, 3, 4 and 5 on an-
other HVAC unit. Zone 11 should be on a separate single
Figure 1-2: Zones Affected by the Outdoor Load zone constant volume HVAC unit.

Auto-Zone Systems 13
Zoning Design Guide

Zoning Design Procedures


Here is another example of the building’s exposure af-
fecting the zoning. Figure 1-3 below shows a building 
layout with 7 zones, it has 3 zones with an eastern ex-
posure, 4 zones with a western exposure and two each
north and south exposures. This building can be con-
trolled from a single, constant volume air handler. All
of the zones have exterior surfaces and there are no
totally internal zones, so they will have similar load    
requirements.

    

 Figure 1-4: Zones With North And South Exposures.

  


Figure 1-3: Zone Layout With External Zones Only.

Figure 1-4 shows a building with 7 zones, 4 of the zones  


have a north exposure and the other 3 have a south ex-
posure. Since there is a big difference in the affect on
the building between north and south exposures, this  
situation should use two zoned HVAC units.

Figure 1-5 shows a combination manufacturing 
facility and office area. The space temperature in the  
individual zones numbered 1 through 7, would all be
controlled by a single HVAC unit. A single constant 

volume HVAC unit would be used for each of the
zones 8 through 12.
Figure 1-5: Zoning And Constant Volume Units

14 Auto-Zone Systems
Zoning Design Guide

Step #2 - Sizing the Central Unit Note For pressure independent terminal units
Because the zones are controlled with variable air vol- with velocity sensors and conventional
ume, it is unlikely that all zones will be at design load “VAV” boxes properly selected for
at the same time. The zoning allows for the diversity of “quiet” operation, this 2000 FPM rule
loads to be taken into account and will often provide
can be exceeded by up to 50 percent. The
better comfort with a smaller HVAC unit.
designer, however, should be very
experienced in VAV system design before
In sizing the system, the individual zone loads should
be calculated using any dependable load estimating pro- considering modification of this general
gram. Because of diversity, the central unit should be rule.
selected for the instantaneous peak load, not the sum of
the peak loads, as would be done with a constant vol- Typical VAV systems with pressure independent termi-
ume single zone system. Consider the following when nals use the static regain method for sizing ducts. The
sizing the central unit. typical Auto-Zone Zoning system is a low-pressure,
pressure dependent system that utilizes conventional
• Size the peak cooling load based on the unitary air-conditioning units. These systems should use
month day hour of the greatest total building the equal-friction method of sizing the ducts, and use
system load the maximum loss of 0.1 inch per 100 feet as described
above.
• Heating should be sized for the lowest design
temperature with an additional margin for Step #4 - Air Motion/Diffuser Selection
morning “pickup”. This margin is generally Air motion is a consideration for occupant comfort. The
recommended to be 20 to 25 percent of base selection of diffusers for an Auto-Zone Zoning system
design. requires more care than a constant volume system due
to varying flow of air into the zones. Slot diffusers are
Step #3 - Duct Design Considerations recommended due to their superior performance at low
The Auto-Zone system uses a typical low pressure duct airflows. Because the zone airflow is variable volume,
design. To reduce noise problems duct pressures should lower cost round or rectangular diffusers that were sat-
not exceed 1 inch W.C. isfactory for constant volume may prove unsatisfactory
with an Auto-Zone Zoning system. These diffusers may
Primary trunk ducts should not be “undersized.” This result in “dumping” of the cold air at low flows in the
is especially true for “pressure dependent” systems. cooling mode, and insufficient room air motion at low
Pressure dependent refers to the typical Auto-Zone, air flows in the heating mode. Although high air mo-
Zone Controller without the airflow sensor. With larger tion in the heating mode can be undesirable, a slot dif-
trunk ducts, it is easier to assure relatively constant pres- fuser with a high induction ratio generally helps to re-
sure to each zone. Runs should be as short as possible, duce room air “stratification” when the heating comes
and the trunk duct system kept as symmetrical as pos- from a ceiling diffuser. Linear slot diffusers should be
sible to facilitate system balancing. Wherever possible, properly selected for the airflow and “throw” suited to
run the trunk ducts above corridors and locate the zone the specific installation or zone.
dampers above corridors to reduce the noise in the space
and facilitate service of the units. Trunk ducts should Additional factors to consider in diffuser selection is
be sized for no more than 0.1 inch W.C. drop per 100 sound level and throw at design flow. Generally, mul-
feet., and a maximum duct velocity of 2000 FPM. tiple diffusers will result in lower sound levels in the
space, but this must be balanced with the additional
hardware and installation costs. It is commonly recom-

Auto-Zone Systems 15
Zoning Design Guide

Zoning Design Procedures


mended that slot diffusers be located near the perim- setpoint, then the damper opens to bypass more air, and
eter or outside wall with the airflow directed into the if the static pressure drops below the setpoint, it closes
room. Consult your diffuser supplier or catalog for to bypass less air.
proper diffuser sizing and location. Using a load calculation program, the bypass damper
should be sized to give you the maximum CFM of air
Series fan boxes may be used instead of zone dampers to be bypassed, typically 60 to 70 percent of the HVAC
where higher induction rates are desirable. If the heat units rated capacity.
loss on perimeter walls is high, such as large areas of
glass, the use of Series Fan Boxes may be indicated to To size the damper, select a damper from the table based
maintain higher induction rates to offset “downdrafts.” on calculated bypass CFM and a maximum velocity
If the heat loss is greater than 275 BTUH/LINEAR between 1750-2250 FPM. When determining the by-
FOOT, you should use high quality slot diffusers next pass duct size, be sure to take into account any transi-
to the outer wall with the airflow directed inward to tion fittings and associated pressure drops. (See Tables
counteract downdrafts during heating. Serious 1-1 & 1-2: Damper Sizing Charts)
downdraft problems occur when heat losses exceed 400
BTUH/linear foot and both high induction diffusers and Whenever possible, use a single bypass damper and
series fan boxes are recommended. round duct for the bypass. If space limitations or total
airflow requires it, multiple bypass dampers can be con-
Step #5 - Bypass Damper Sizing trolled in parallel or a rectangular damper may be used.
The function of the bypass damper is to allow a con- For proper control of the Bypass Damper, the static pres-
stant volume air handling unit to be used with variable sure sensor location is very important. Refer to Fig-
volume zone dampers. The bypass damper modulates ures 1-8 Thru 1-10 for proper sensor installation loca-
on a signal from a duct static pressure sensor to “by- tion information and guidelines.
pass” air from the supply duct back into the return air
duct. If the duct static pressure exceeds the adjustable

Figure 1-6: Round Bypass Damper Figure 1-7: Rectangular Bypass Damper & Kit

16 Auto-Zone Systems
Zoning Design Guide

Fan
Fan

RA Sensor
SA Sensor Bypass Damper
RA Sensor
SA Sensor
Supply Air Duct
SP Pickup
Return Air Duct Return Air Duct
Supply Air Duct

Bypass Damper SP Sensor

SP Pickup SP Sensor

3D 2D
Min. Min.
Figure 1-10: Least Desirable Sensor Location
Figure 1-8: Preferred Sensor Location If the supply duct comes directly from the unit and im-
mediately splits in opposite directions, the pressure
If the trunk ducts are properly sized for minimum pres- pickup should be located ahead of the split, or as close
sure drop, the location of the static pickup probe is not to it as possible, even if the bypass damper(s) are lo-
particularly critical. It should ideally be located at right cated downstream of the split.
angles to the airflow in a straight section of the supply
duct approximately 2/3 the distance of the total length Step #6 - Sizing the Zone Damper
of the supply duct. Also the probe should be located
Use a load program to determine the peak load for each
not less than 3 duct diameters downstream and 2 duct
zone. These calculations will be used in selecting the
diameters upstream of any elbow or takeoff. See Fig-
appropriate zone damper sizes.
ure 1-8.
Using the maximum acceptable velocity for a branch
duct (typically 1000-1500 FPM for minimal noise), find
Fan
the smallest damper that will deliver the required CFM
as determined by the load program.
RA Sensor
Bypass Damper

Supply Air Duct Locate the branch velocity used in the duct design pro-
Return Air Duct
Tubing To Be Equal gram on the left hand column of the damper sizing chart
Length And Size
SA Sensor
(Table 1-1). Move across the chart and find the damper
which will provide the acceptable CFM to meet your
specific zone requirements.
SP Pickups SP Sensor

Note Compare the damper size selected against


Figure 1-9: Acceptable Sensor Location the duct size to determine if the next size
up or down will provide acceptable
performance without requiring a transi-
Since the “ideal” location is often difficult to find in an
installation, a location in the main trunk where the tip tion fitting.
is not in a “negative pressure area” (e.g. just downstream
of the inside curve of an elbow) or an area where the One additional damper may be slaved together for large
tube opening is directly impacted by the velocity of the zones. See zone wiring diagram for details. This should
supply air. See Figure 1-9. be reserved for situations when it is not practical to use
a single large damper. Round zone dampers can be speci-
fied to be either pressure dependent or independent.

Auto-Zone Systems 17
Zoning Design Guide

Zoning Design Procedures


Pressure Dependent Dampers dent operation. Pressure independent operation is avail-
With pressure dependent (PD) dampers, the minimum able for round zone dampers only. Pressure indepen-
and maximum airflow is set based on damper position. dent rectangular dampers are not available. See Figure
During the final commissioning of the system, each zone 1-12 for a diagram of a typical pressure independent
is typically balanced with a flow hood and the min/max zone damper.
position is fixed either mechanically or the preferred
method, in the controller software. Since this min/max When pressure independent dampers are used they must
setting is based only on position, as the static pressure be field calibrated so the CFM of airflow for the mini-
fluctuates it will cause the actual airflow at the zone mum and maximum airflow setpoints will be correct.
damper to increase or decrease. Therefore the name, This should be done by the field technician during the
pressure dependent since the airflow is dependent on commissioning portion of the system installation. The
the static pressure. Pressure dependent dampers are K-factor is the amount of airflow in CFM that the spe-
available in round or rectangular configurations. See cific damper will produce with 1” W.C. duct static pres-
Figure 1-11 for a diagram of a typical pressure depen- sure on the damper flow sensor. This K-factor is used
dent zone damper. by the controller software to maintain the correct mini-
mum or maximum airflow setpoint regardless of the
static pressure at the flow sensor. The K-factor and the
minimum and maximum damper CFMs can be entered
at the Zone Manager on Basic systems, or using the
System Manager on Auto-Zone Plus systems. K-fac-
tors can also be entered using a personal computer with
the ZoneView computer front end software installed.
The K-factors for each damper size are listed in Table
1-1: Round Air Damper Selection. Once the correct K-
factors and minimum and maximum damper CFM
setpoints are entered, the damper will modulate to try
to maintain these CFM airflows during damper opera-
tion. If zone dampers or fan terminal units manufac-
tured by others are used, the correct K-factors must be
obtained from the equipment manufacturer.

Figure 1-11: Pressure Dependent Damper

Pressure Independent Dampers


When using pressure independent (PI) dampers this
minimum and maximum is set based on actual CFM of
airflow through the damper. Airflow is measured using
a pickup tube mounted in the zone damper and an elec-
tronic air flow sensor. Using this method you always
know the actual airflow through each zone damper in-
stead of just the damper percentage open. The mini-
mum and maximum settings are based on this actual
airflow reading. As the static pressure fluctuates, the
flow sensor reads the variation and automatically repo-
sitions the damper to maintain the minimum or maxi-
mum flow setpoints. Since the minimum or maximum
airflow is maintained independently of the static pres- Figure 1-12: Pressure Independent Damper
sure available in the duct it is called pressure indepen-

18 Auto-Zone Systems
Zoning Design Guide

Round Damper Round Damper


Blade Assembly Blade Assembly
Zone Controller

1/2" Foil Faced 1/2" Foil Faced


Insulation Insulation

W
O

A
FL

IR
W

IR

FL
O

A
AI

O
FL

W
R
R

FL
AI

O
W

Actuator Actuator

Control Enclosure Control Enclosure


(Cover Removed) (Cover Removed)
Bypass & Slave Interface

Bypass & Slave Dampers Zone Dampers

Table 1-1: Round Damper Selection Data


Damper Round Duct Size 6” 8” 10” 12” 14” 16”
(Area Ft2)
(0.188) (0.338) (0.532) (0.769) (1.050) (1.375)

CFM @ 1” Velocity Pressure


Air Flow Probe “K” Factor- For Pressure 474 950 1417 2120 2908 3700
Independent Applications Only

Velocity Through Zone Damper Airflow Through Zone Damper - CFM


FPM (∆PS inches W.C. With Air Damper Full Open)

141 254 399 577 788 1031


750 - Zone
(0.03) (0.02) (0.01) (0.02) (0.01) (0.01)
188 338 532 769 1050 1375
1000 - Zone
(0.05) (0.03) (0.02) (0.03) (0.02) (0.01)
235 423 665 961 1313 1718
1250 - Zone
(0.07) (0.04) (0.03) (0.04) (0.03) (0.02)
282 507 798 1154 1575 2062
1500 - Zone
(0.09) (0.06) (0.04) (0.05) 0.04) (0.03)
329 592 931 1346 1838 2405
1750 – Bypass Only
(0.12) (0.08) (0.06) (0.06) (0.05) (0.04)
376 676 1064 1538 2100 2749
2000 – Bypass Only
(0.15) (0.10) (0.07) (0.07) (0.07) (0.05)
423 761 1197 1730 2363 3094
2250 – Bypass Only
(0.18) (0.13) (0.09) (0.09) (0.08) (0.06)
WattMaster reserves the right to change specifications without notice

Rectangular Dampers can cause air flow problems. These slide-in dampers
Auto-Zone rectangular dampers are high quality alu- require that the damper frame be inside the duct. Imag-
minum construction with opposed/air foil designed ine an 8 x 10 rectangular duct using a slide in damper
blades for superior control and have both blade and jamb with a frame thickness of 1”. The frame alone would
seals for tight shut off. The dampers are installed using reduce the opening to 6 x 8.
a mounting flange. The purpose for the flange mount-
ing is to allow as much unrestricted free space within Another possible problem encountered with rectangu-
the duct as possible. lar dampers is the blade width. Many damper manufac-
turers supply dampers with 6” or 8” dampers blades.
Many companies utilize slide-in type dampers which This can become a major problem, for example, if the
Auto-Zone Systems 19
Zoning Design Guide

Zoning Design Procedures


damper has a height of 10”. In this case the damper
would utilize an 8” blade and a 2” blade stop or dam
would be installed across the base of the damper. Tak-
ing into consideration the “blade stop” and the frame, a
10 x 10 damper would have a reduced opening of 6 x 8
inside the duct. Many contractors have experienced low
air flow problems on projects only to discover this hid-
den problem of the dampers actually creating the re-
striction. Auto-Zone utilizes a variety of blade widths
in order to accommodate the size of the damper instead
of the damper trying to accommodate the size of the
blade.
Rectangular Dampers

Table 1-2: Rectangular Damper Selection Data


Damper
Height 8” 10” 12” 14” 16” 18” 20” 22” 24” 26” 28” 30” 32” 34” 36”
“B”

Damper Airflow Data with Full Open Damper – CFM @ 1000 FPM Velocity
Width (∆PS - inches W.C. @ 1000 FPM Velocity)
“A” For airflow CFM at other velocities use these multipliers: 750 FPM = 0.75, 1250 FPM = 1.25, 1500 FPM = 1.5, 2000 = 2.0, 2250 = 2.25

8” 410 530 640 740 850 970 1080 1190 1300 1410 1520 1630 1740 1850 1970
(0.16) (0.10) (0.07) (0.05) (0.04) (0.03) (0.03) (0.02) (0.02) (0.02) (0.01) (0.02) (0.01) (0.01) (0.01)
10” 510 590 690 800 910 1030 1150 1260 1380 1500 1610 1730 1840 2000 2080
(0.10) (0.07) (0.05) (0.03) (0.03) (0.02) (0.02) (0.01) (0.01) (0.01) (0.01) (0.01) (0.01) (0.01) (0.01)
12” 560 650 730 850 970 1090 1210 1330 1460 1580 1700 1820 1940 2060 2190
(0.07) (0.05) (0.03) (0.02) (0.02) (0.01) (0.01) (0.01) (0.01) (0.01) (0.01) (0.01) (-) (-) (-)
14” 660 770 880 1030 1180 1330 1480 1630 1760 1910 2060 2210 2360 2510 2640
(0.05) (0.03) (0.02) (0.02) (0.01) (0.01) (0.01) (0.01) (0.01) (0.01) (-) (-) (-) (-) (-)
16” 750 890 1030 1200 1370 1540 1710 1880 2060 2230 2400 2570 2740 2910 3090
(0.04) (0.03) (0.02) (0.01) (0.01) (0.01) (0.01) (0.01) (-) (-) (-) (-) (-) (-) (-)
18” 770 980 1180 1380 1580 1780 1980 2180 2350 2550 2750 2950 3150 3350 3540
(0.03) (0.03) (0.01) (0.01) (0.01) (0.01) (0.01) (-) (-) (-) (-) (-) (-) (-) (-)
20” 850 1090 1330 1550 1770 1990 2210 2430 2650 2870 3090 3310 3530 3750 3990
(0.03) (0.02) (0.01) (0.01) (0.01) (0.01) (-) (-) (-) (-) (-) (-) (-) (-) (-)
22” 930 1210 1480 1730 1980 2230 2480 2730 2950 3200 3450 3700 3950 4200 4440
(0.02) (0.01) (0.01) (0.01) (0.01) (-) (-) (-) (-) (-) (-) (-) (-) (-) (-)
24” 950 1290 1630 1900 2170 2440 2710 2980 3250 3520 3790 4060 4330 4600 4880
(0.02) (0.01) (0.01) (0.01) (-) (-) (-) (-) (-) (-) (-) (-) (-) (-) (-)
26” 990 1390 1780 2080 2380 2680 2980 3280 3550 3850 4150 4450 4750 NA NA
(0.02) (0.01) (0.01) (0.01) (-) (-) (-) (-) (-) (-) (-) (-) (-)
28” 1070 1500 1930 2250 2570 2890 3210 3530 3850 4170 4500 4820 NA NA NA
(0.01) (0.01) (0.01) (-) (-) (-) (-) (-) (-) (-) (-) (-)
30” 1020 1550 2080 2430 2780 3130 3480 3830 4150 4500 4850 NA NA NA NA
(0.01) (0.01) (0.01) (-) (-) (-) (-) (-) (-) (-) (-)
32” 1090 1660 2230 2600 2970 3340 3710 4080 4450 4820 NA NA NA NA NA
(0.01) (0.01) (-) (-) (-) (-) (-) (-) (-) (-)
34” 1150 1770 2380 2780 3180 3580 3980 4370 4750 NA NA NA NA NA NA
(0.01) (0.01) (-) (-) (-) (-) (-) (-) (-)
36” 1060 1790 2520 2670 3090 3510 3930 4350 5040 NA NA NA NA NA NA
(0.01) (0.01) (-) (-) (-) (-) (-) (-) (-)
WattMaster reserves the right to change specifications without notice

20 Auto-Zone Systems
Zoning Design Guide

Auxiliary Heat Control Options Relay Expansion Board Outputs


The Auto-Zone Zoning system offers the user a variety The following describes the operation of each of the
of methods to deal with zone heating requirements. In relays on the optional relay expansion board. The user
order to control zone heat, an optional Relay Expan- can choose the appropriate relays for any given appli-
sion Board is required. When deciding how to handle cation.
zone heating requirements the user should consider the
following: Relay #1 - Parallel Fan
If the Zone is in cooling or vent mode, the parallel fan
• Does the rooftop unit have heat? can activate anytime the zone temperature drops 0.5° F
• Are you using fan-powered boxes with reheat? below the heating setpoint. It deactivates when the tem-
• Is auxiliary heat such as baseboard or radiant perature rises above the heating setpoint.
ceiling panels used?
Relay #2 - Box Heat
If the zone has some type of heat, the user must con- If the zone is in cooling or vent mode then the box heat
sider how the heat is to be used. Typical questions that can activate anytime the zone temperature drops 1.5° F
should be asked: below the heating setpoint. It deactivates when the tem-
perature rises to within 1.0° F of the heating setpoint.
Q: Should the zone heat be used as a first stage where Box heat is not allowed to activate in the heating mode
it will become active before a heating demand is when there is hot air being supplied by the air handling
created at the rooftop unit? unit. This output was intended to allow zone reheat
while the Zone Manager is satisfying cooling demands
A: This mode is useful if you expect to have both in other zones.
heating and cooling demands at the same time. The
zone will use it’s own heat and allow the rooftop Relay #3 - Aux. Heat
unit to continue to provide cooling for other zones. In the occupied mode, the aux heat can activate any-
This mode is also useful if the roof top unit does time the zone temperature is 0.5° F below the aux heat
not have any heating capabilities. setpoint. It deactivates when the temperature rises 0.5°
F above the aux heat setpoint. In the unoccupied mode,
Q: Is the zone heat only to be used as a second stage, the aux heat uses the unoccupied heating setpoint with
where it will be activated only if the roof top unit the same deadband values mentioned above. This pre-
cannot maintain the space temperature, such as vents the zone from maintaining the same aux heat
during very cold weather? setpoint at night that it does during the daytime. The
Parallel Fan and Box Heat are prevented from coming
A: In this mode of operation the rooftop will examine on until the aux heat is energized.
the heating and cooling demands and try to satisfy
all of the zones by switching between heating and This output was intended to allow zone heating to aug-
cooling as required. The zone heat will only be ment the normal heating mode and also to allow a zone
activated if the zone temperature falls below a an attempt to satisfy its own heating needs before cre-
selected limit. ating a heating demand at the Zone Manager.

Q: Should the zone heat be locked out if the rooftop Relay #4 - Series Fan
unit is supplying warm air? The series fan runs anytime the main fan is running.
This includes occupied and unoccupied modes. The fan
A: Many times it is desirable to use the rooftop can only start running when the zone damper is closed,
heating whenever possible and only use zone heat so it determines that the damper is closed before start-
when the rooftop unit is in cooling. This mode of ing the fan.
operation will lockout zone heat if the rooftop is
delivering heated air.

Auto-Zone Systems 21
Zoning Design Guide

System Installation
Mounting Of Controllers device. Possible problems you may encounter using
All Auto-Zone Round Dampers or Rectangular Damper common transformers to power multiple devices are:
Kits have the required controllers, actuators etc. fac-
tory mounted in an indoor rated control enclosure. If • If polarity is not maintained between devices,
you wish to use another manufacturers dampers for zon- shorting of the transformer will occur resulting
ing control you must purchase Zone or Bypass Pack- in damage to the electronics.
ages from WattMaster. These are furnished without a
mounting enclosure. Most local codes require these • When using one transformer to power multiple
components be mounted in an enclosure. If yours does devices it is possible to lose most or all of your
not require this it is still strongly recommended that system if the transformer fails.
you do mount them in an enclosure. Components that
are not in an enclosure are in danger of being damaged, • It is important when powering multiple devices
and are susceptible to dirt and moisture contamination. from one transformer that total VA load and
You may furnish your own enclosure or one is avail- wiring voltage drops be taken into account for
able from WattMaster. The part number for the proper sizing of the transformer and wire.
WattMaster enclosure is EE000075-01. This is an in- (See Table 3 on page 23)
door rated enclosure. If the zone mounting location is
susceptible to water damage, watertight enclosures can It is therefore recommended that in most installations
be purchased at any local electrical supply. Mounting individual transformers be installed for each device.
location for the controllers should not violate any lo- This will greatly reduce the possibility of errors and
cal, state or national codes. possible damage to the system.

System Wiring Power wiring should always be done in accordance with


Wiring requirements for Auto-Zone systems can be bro- any local, state, or national codes.
ken down into four main categories:
It is also important to note that THE HVAC UNITS
1.) Power Wiring FACTORY TRANSFORMER SHOULD NEVER
BE USED TO POWER Auto-Zone devices! Normally
2.) Communications Wiring transformers on typical HVAC units are sized to only
handle the load of the units factory installed controls.
3.) Controller Wiring A separate transformer must be used.

4.) Sensor Wiring Communication Loops


The Auto-Zone system utilizes two different commu-
Each category should be thoroughly understood and nications loops. The Basic system uses a 9600 Baud
implemented in order to have a trouble free installa- RS-485 communications loop (Local Loop) only. The
tion. Plus system uses two different communications loops.
It has a 9600 Baud RS-485 communications loop (Lo-
Power Wiring cal Loop) like the Basic system but also has an RS-485
All Auto-Zone devices are powered by 24 VAC. It is 19200 baud communication loop (Network Loop) that
possible to power the system using one or more com- connects the Zone Managers together and connects the
mon transformers or individual transformers for each CommLink II communications interface.

22 Auto-Zone Systems
Zoning Design Guide

WattMaster requires that all communication wire be 18 should be color coded to facilitate error free wiring.
gauge minimum, two wire shielded cable, Belden The communication loops will not work if any of the
#82760 or equivalent. WattMaster offers AZWR series wires are reversed or otherwise landed incorrectly. Com-
communications cable for this purpose. The 18 gauge munications loops can be run up to a maximum of ap-
color coded and labeled wire is available for the local proximately 4000 ft. in total length. If your system ex-
loop and the network loop communications wiring. The ceeds this length, please consult the WattMaster fac-
local loop wire is supplied in 1000 ft. spools and is la- tory for more information regarding extended commu-
beled “Local Loop” with a green candy stripe. The nication loop lengths and solutions.
network loop wire is supplied in 500 ft. spools and is
labeled “Network Loop” with a red candy stripe. Caution: Unless the communications loop
is installed in conduit, be careful to
position the cable away from high
noise devices like fluorescent
lights, transformers, VFD’s, etc.
Conduit is not required for com-
munications loop wiring unless
required by local codes.

Tip: Incorrect wiring of the communications


loop is the most common mistake made
during installation. Before beginning
installation, write down the wire color
Local Loop Wire Network Loop Wire used on each terminal connection and
consistently maintain that color code. It
Figure 1-13: WattMaster Communications Wire is recommended that a continuous wire
run be made between devices. Anytime
The loop is best connected in a daisy chain configura- a splice is made in the cable you increase
tion, meaning the loop is connected from one control- your chance of problems. If a splice must
ler to another. It is not necessary to sequentially ad- be made, Never use wire nuts! Cable
dress the zone controllers in relation to their location should be soldered and wrapped or if
on the loop. soldering is not possible use butt splice
crimp connectors and wrap tightly with
Even though the daisy chain configuration is preferred,
electrical tape.
the star configuration can also be used. If required, a
combination of the two can also be used. Remember,
the best communications loop wiring is the one which
Caution: Make sure when you are inserting
utilizes the minimum number of ends while using the
wires into the terminal blocks that
shortest wiring path.
strands of wire do not stick out and
Communication Wiring terminals on most Auto-Zone touch the adjacent terminals. If
controllers are marked “T”, “R” and “SHLD” (Note: adjacent wires touch each other or
instead of SHLD the CommLink is marked “G” and another terminal, shorting and
the Basic Zone Manager is marked “SH”). All wiring subsequent damage to the circuit
should be connected T to T, R to R and SHLD to SHLD board could result
throughout the entire loop system. Communication wire

Auto-Zone Systems 23
Zoning Design Guide

System Installation
Computer
(Optional)

CO
MM
LIN
K II Zone Controllers Occupy
HVAC Unit Addresses 1 through 16.
L
O C
O O
P M
M O
P D

24VAC
E
M

Zone Manager
WATTM
AST

Zone
ER
CON

Zone
TRO
LS,
INC

CommLink II Controller #1 Controller #16


(Optional)
AUTO-ZONE
RAM RAM
8K 32K 8K 32K

R34

R18

R34

R18
FLOW CX4 FLOW CX4
CX3 CX1 CX3 CX1
CX8 U4 U3 CX8 U4 U3

U8

U8
RN1 RN1

U1

U1
1 1

TCU32K2V

TCU32K2V
MS6264L-70PC

MS6264L-70PC
V4.00F C094

V4.00F C094
B31920PS
74HC573N

B31920PS
74HC573N
AZZONE

AZZONE
9936

9936
D5 D5

R27

R27
16L8 16L8
AUTO ZONE CX9 U9 R1
CX9 U9 R1

C13

C9

C13

C9
WED JANUARY11 2001

LMC662

LMC662
R2 R2
RAM EPROM R3 RAM EPROM R3

C8

C8
OCCUPIED 80C55 80C55

C14 ADJ

C14 ADJ
R22 R22
2 CX2 2 CX2
D5 D5
P.U. P.U.

VREF

VREF
Q1

Q1
R32 R32

C10

C10
PHILIPS

PHILIPS
R23 R23

X1

X1
PCB80C552-5-16WP

PCB80C552-5-16WP
B31920PS
74HC259

B31920PS
74HC259
T'STA T'STA

C1

U2

C1

U2
T R24 T R24

R28

R28
DFD9940SM

DFD9940SM
500650=1/3

500650=1/3
U11

U11
C2

C2
R19

R19
C11

C11
R20

R20
PHILIPS

PHILIPS
R4 R4

C15

C15
CX5

CX5
EWDOG

EWDOG
D7
R25 R5 D7
R25 R5

U5

U5
ADDRE R6 ADDRE R6
SS ADD R7 SS ADD R7
CX10 CX10
1 1

PJ1

PJ1
93C46

93C46
U6

U6
2 2

SION
EXPAN

SION
EXPAN
R8

R8
4 4

COMM

COMM
75176

75176
8 8

SW1

SW1
CX6

CX6
U10

C3

U10

C3
16 16
32 32
LD3 LD3
TOKEN TOKEN
Sy

POWER

POWER
C5

C5
C4

C4
ch NET NET

R100

R100
ro

PJ2

PJ2
R26 R26
no

R13

R13
TOR
ACTUA

TOR
ACTUA
R14

R14
us 250 250

V1

V1
Da D4 D4
ta
Lin F1 F1

LD2

LD1

LD2

LD1
R21

R21
k

R9

R9
C6

C6
562
YS101

562
YS101
SIG

REV. 2

REV. 2
SCAN REC SCAN REC
fTimes New fTimes New
DET

R12
R11
R10

R12
R11
R10
Roman|b0|i0| Roman|b0|i0|
RDY

fTimes New fTimes New

L1

L1
Roman|b0|i0|c0|p18; Roman|b0|i0|c0|p18;
c0|p18;OMRON c0|p18;OMRON
SND

G5L-114P-PS G5L-114P-PS
24VDC 24VDC
REC

CONTACT: CONTACT:
PWR

MDL MDL
UL / CSA 5A250VAC UL / CSA 5A250VAC

Q2

Q2
VR1

VR1
D1
K1

D1
K1
D3 D3
C
O
T C7 fTimes New T C7 fTimes New
24VAC Roman|b0|i0| 24VAC Roman|b0|i0|
7824C 7824C
fTimes New fTimes New

7824

7824
R15

R15
N
T
Roman|b0|i0|c0|p18; Roman|b0|i0|c0|p18;
c0|p18;OMRON c0|p18;OMRON
R M 9936 M 9936
O
64A
G5L-114P-PS 64A
G5L-114P-PS

RS485 Loop
L
24VDC 24VDC
MC340 MC340
S

CONTACT: CONTACT:
UL / CSA 5A250VAC UL / CSA 5A250VAC

Q3

Q3
U7

U7
R16

D2

R16

D2
R17

R17
K2

K2
GND GND

Remote Link
V2 V2

(Optional)

RS485 Loop 24VAC 24VAC

Figure 1-14: Auto-Zone Basic System Communication Loop Wiring

Zone Controllers Occupy Constant Volume


Addresses 1 through 16. Controller
24VAC HVAC Unit #1 Zone Zone
CV Controllers And Other (Addresses Start At 18)
Add On Devices, Occupy
Zone Manager Controller #1 Controller #16
Addresses 18 trough 30 RAM
8K 32K
RAM
8K 32K
32K
R34

R18

R34

R18

FLOW CX4 FLOW CX4


CX3 CX1 CX3 CX1
CX8 CX8
U4 U3 U4 U3 8K
U8

U8

RN1 RN1
U1

U1

1 1
COMM
TCU32K2V

TCU32K2V

RELAY
MS6264L-70PC

MS6264L-70PC
V4.00F C094

V4.00F C094
B31920PS
74HC573N

B31920PS
74HC573N
AZZONE

AZZONE
9936

9936

D5 D5 T OUTPUT
COM
SHLD 1-3
R27

R27

OUT
16L8 16L8
CX9 CX9
R
U9 U9
R1 R1
1
C13

C9

C13

C9
LMC662

LMC662

R2 R2
RAM EPROM R3 RAM EPROM R3 OUT
C8

C8

LD4 485 RAM EPROM 2

Computer
80C55 80C55
C14 ADJ

C14 ADJ

R22 R22
2 CX2 2 CX2 COMM
D5
P.U.
D5
P.U. OUT
VREF

VREF
Q1

Q1

R32 R32 3
REC.
C10

C10
PHILIPS

PHILIPS

R23 R23
OUT
X1

X1
PCB80C552-5-16WP

PCB80C552-5-16WP
B31920PS
74HC259

B31920PS
74HC259

T'STA T'STA 4
C1

U2

C1

U2

T R24 T R24
R28

R28
DFD9940SM

DFD9940SM

OUT

(Optional)
500650=1/3

500650=1/3
U11

U11
C2

C2
R19

R19

5
C11

C11
R20

R20
PHILIPS

PHILIPS

R4 R4
C15

C15

COM
CX5

CX5
EWDOG

EWDOG

R25 R5 R25 R5
D7 D7
4-5
U5

U5

COMM
ADDRE R6 ADDRE R6
SS ADD SS ADD

RS485
R7 R7
CX10 CX10
1 1
PJ1

PJ1
93C46

93C46
U6

U6

2 2
SION
EXPAN

SION
EXPAN
R8

R8

4 4
COMM

COMM
75176

75176

8 8
12V TEST
SW1

SW1
CX6

CX6
U10

C3

U10

C3

16 16
ADDRESS ADD
LD3
32
TOKEN
LD3
32
TOKEN AIN
1
POWER

POWER
C5

C5

Network Loop
C4

C4

NET NET
R100

R100
PJ2

PJ2

R26 R26
AIN
R13

R13
TOR
ACTUA

TOR
ACTUA
R14

R14

250 250
V1

V1

2
EWDOG

D4 D4
F1 F1
LD2

LD1

LD2

LD1

AIN
R21

R21

3
R9

R9
C6

C6
562
YS101

562
YS101
REV. 2

REV. 2

SCAN REC SCAN REC


fTimes New fTimes New AIN
R12
R11
R10

R12
R11
R10

Roman|b0|i0|
fTimes New Roman|b0|i0|
fTimes New
4
L1

L1

Roman|b0|i0|c0|p18; Roman|b0|i0|c0|p18;
c0|p18;OMRON
G5L-114P-PS c0|p18;OMRON
G5L-114P-PS

MDL
24VDC
CONTACT:
UL / CSA 5A250VAC
MDL
24VDC
CONTACT:
UL / CSA 5A250VAC
AIN
5
Q2

Q2
VR1

VR1
D1
K1

D1
K1

D3 D3

19200 Baud
24VAC
T
7824C
C7 fTimes New
Roman|b0|i0|
fTimes New 24VAC
T
7824C
C7 fTimes New
Roman|b0|i0|
fTimes New GND
7824

7824
R15

R15

Roman|b0|i0|c0|p18; Roman|b0|i0|c0|p18;
c0|p18;OMRON c0|p18;OMRON
M 9936 M 9936
64A
G5L-114P-PS 64A
G5L-114P-PS
24VDC 24VDC
GND
MC340 MC340
CONTACT: CONTACT:
UL / CSA 5A250VAC UL / CSA 5A250VAC
Q3

Q3
U7

U7

VDC
R16

D2

R16

D2

0-5
R17

R17
K2

K2

GND GND

V2 V2
AOUT
PWR
PRESSURE GND
SENSOR
VDC
0-1

YS101564

24VAC

9600 Baud RS485 Local


24VAC 24VAC 24VAC
Loop #1
To Any Other
CV Controllers
Or Add On Devices
The Loop Does Not
CO
MM
LIN
K
II
Have To Follow The Board
Address Sequence
L
O C
O

Constant Volume
O M
P M O
P D
E
M

WATTM

Controller
AST
ER
CON

HVAC Unit #2 Zone Zone


TRO
LS,

24VAC
INC

CommLink II Zone Manager Controller #1 Controller #16 (Addresses Start At 18)


RAM RAM
8K 32K 8K 32K
32K
R34

R18

R34

R18

FLOW CX4 FLOW CX4


CX3 CX1 CX3 CX1
CX8 CX8
U4 U3 U4 U3 8K
U8

U8

RN1 RN1
U1

U1

1 1
COMM
TCU32K2V

TCU32K2V

RELAY
MS6264L-70PC

MS6264L-70PC
V4.00F C094

V4.00F C094
B31920PS
74HC573N

B31920PS
74HC573N
AZZONE

AZZONE
9936

9936

D5 D5 T OUTPUT
COM
SHLD 1-3
R27

R27

CX9
16L8
CX9
16L8
OUT
R
U9 U9
R1 R1
1
C13

C9

C13

C9
LMC662

LMC662

R2 R2
RAM EPROM R3 RAM EPROM R3 OUT
C8

C8

80C55 80C55 LD4 485 RAM EPROM 2


C14 ADJ

C14 ADJ

R22 R22
2 CX2 2 CX2 COMM
D5
P.U.
D5
P.U. OUT
VREF

VREF
Q1

Q1

R32 R32 3
REC.
C10

C10
PHILIPS

PHILIPS

R23 R23
OUT
X1

X1
PCB80C552-5-16WP

PCB80C552-5-16WP
B31920PS
74HC259

B31920PS
74HC259

T'STA T'STA 4
C1

U2

C1

U2

T R24 T R24
R28

R28
DFD9940SM

DFD9940SM

OUT
500650=1/3

500650=1/3
U11

U11
C2

C2
R19

R19

5
C11

C11
R20

R20
PHILIPS

PHILIPS

R4 R4
C15

C15

COM
CX5

CX5
EWDOG

EWDOG

R25 R5 R25 R5
D7 D7
4-5
U5

U5

COMM
ADDRE R6 ADDRE R6
SS ADD R7 SS ADD R7
CX10 CX10
1 1
PJ1

PJ1
93C46

93C46
U6

U6

2 2
SION
EXPAN

SION
EXPAN
R8

R8

4 4
COMM

COMM
75176

75176

8 8
12V TEST
SW1

SW1
CX6

CX6
U10

C3

U10

C3

16 16
ADDRESS ADD
Sy
LD3
32
TOKEN
LD3
32
TOKEN AIN
1
POWER

POWER
C5

C5
C4

C4

ch NET NET
R100

R100

ro
PJ2

PJ2

R26 R26
no
AIN
R13

R13
TOR
ACTUA

TOR
ACTUA
R14

R14

us 250 250
V1

V1

Da
2
EWDOG

D4 D4
ta
Lin F1 F1
LD2

LD1

LD2

LD1

AIN
R21

R21

k
3
R9

R9
C6

C6
562
YS101

562
YS101
SIG

REV. 2

REV. 2

SCAN REC SCAN REC


fTimes New fTimes New AIN
DET

R12
R11
R10

R12
R11
R10

Roman|b0|i0| Roman|b0|i0|
RDY

fTimes New fTimes New


4
L1

L1

Roman|b0|i0|c0|p18; Roman|b0|i0|c0|p18;
c0|p18;OMRON c0|p18;OMRON
SND

G5L-114P-PS G5L-114P-PS
24VDC 24VDC
AIN
REC

CONTACT: CONTACT:
PWR

MDL MDL
UL / CSA 5A250VAC UL / CSA 5A250VAC
5
Q2

Q2
VR1

VR1
D1
K1

D1
K1

D3 D3
C
O

24VAC
T
7824C
C7 fTimes New
Roman|b0|i0|
fTimes New 24VAC
T
7824C
C7 fTimes New
Roman|b0|i0|
fTimes New GND
7824

7824
R15

R15

N
T
Roman|b0|i0|c0|p18; Roman|b0|i0|c0|p18;
c0|p18;OMRON c0|p18;OMRON
R M 9936 M 9936
O
64A
G5L-114P-PS 64A
G5L-114P-PS

GND
L
24VDC 24VDC
MC340 MC340
S

CONTACT: CONTACT:
UL / CSA 5A250VAC UL / CSA 5A250VAC
Q3

Q3
U7

U7

VDC
R16

D2

R16

D2

0-5
R17

R17
K2

K2

GND GND
AOUT

Remote Link
V2 V2
PWR
PRESSURE GND
SENSOR
VDC
0-1

YS101564

(Optional) 24VAC

Network Loop RS485 Local 24VAC 24VAC 24VAC


To Other Zone Loop #2
To Any Other
Managers
CV Controllers
Or Add On Devices

Figure 1-15: Auto-Zone Plus System Communication Loop Wiring

24 Auto-Zone Systems
Zoning Design Guide

Controller Wiring Zone Controller


All controller wiring should be in accordance with all • 24 VAC Supply Voltage (10 VA)
local, state, and national codes. It is recommended that (2) Conductors - Determine minimum
all wire be a minimum of 18 AWG unless otherwise wire size from Figure 1-16 on page 26.
specified in the charts below. Controller connections
and wire sizing is as follows: • Communications Loop
(2) Conductors 18 gauge minimum
Zone Manager twisted pair with shield
• 24 VAC Supply Voltage (25 VA) (WattMaster communication wire,
(2) Conductors - Determine minimum Belden #82760 or equal)
wire size from Figure 1-16 on page 26. • Room Sensor
• Communications Loop (2) Conductors 24 gauge minimum
(2) Conductors 18 gauge minimum (3) Conductors if using optional slide
twisted pair with shield Sensor Wiring
(WattMaster communication wire, Auto-Zone temperature sensors utilize a type III ther-
Belden #82760 or equal) mistor element that is one of the most commonly used
• Supply Air Temperature Sensor sensors in the building controls industry. Sensor wire
(2) Conductors 24 gauge minimum should be a minimum of 24 gauge however larger wire
such as 18 gauge is commonly used.
• Return Air Temperature Sensor
(2) Conductors 24 gauge minimum
Conventional thermostat cable is acceptable in most
• Outside Air Sensor commercial and institutional installations. In some in-
(2) Conductors 24 gauge minimum stallations which have the potential for high electrical
noise, such as broadcast facilities (radio, TV, etc.), heavy
• Supply Static Pressure Sensor industrial (machinery, welding equipment, etc.), and
(2) Conductors 24 gauge minimum medical (x-ray, scanning, etc.), it is advisable to use
• Bypass Damper shielded cable on sensors which are located in or close
(4) Conductors 24 gauge minimum to these environments. The same cable used for the com-
munication bus can be used in these situations.
• HVAC Unit Control Wiring
(6) Conductors 24 gauge minimum Sensor requirements are:
R (Common), G (Fan), Y1 (Cool 1), • Supply Air Sensor
Y2 (Cool 2), W1 (Heat 1), W2 (Heat 2) (2) Conductors 24 gauge minimum
For Auto-Zone Plus System With
Optional Staging Expansion Board up to • Return Sensor
an additional (8) conductors Y3 through (2) Conductors 24 gauge minimum
Y6, W3 Through W6 • Outside Air Sensor
(2) Conductors 24 gauge minimum
System Manager
• 24 VAC Supply Voltage (25 VA) • Room Sensor
(2) Conductors - Determine minimum (2) Conductors 24 gauge minimum
wire size from Figure 1-16 on page 26. (3) Conductors if using optional slide
adjust
• Communications Loop
(2) Conductors 18 gauge minimum
twisted pair with shield
(WattMaster communication wire,
Belden #82760 or equal)

Auto-Zone Systems 25
Zoning Design Guide

System Installation
24VAC Power - Transformer & Wire Sizing Considerations
Some installers like to use one large 24VAC transformer to power several controllers. This is allowable as long as polarity is maintained to each
controller on the transformer circuit. Warning: If polarity is not maintained, severe damage to the controllers may result. WattMaster Controls
recommends using a separate transformer for each controller in order to eliminate the potential for damaging controllers due to incorrect
polarity. Using separate transformers also allows redundancy in case of a transformer failure. Instead of having 8 controllers inoperative because of a
malfunctioning transformer you have only 1 controller off line. If the installer does decide to use a large transformer to supply power to several
controllers, the following transformer and wire sizing information is presented to help the installer correctly supply 24VAC power to the controllers.
Following is a typical example to help the installer to correctly evaluate transformer and wiring designs.

Each Zone Controller with actuator requires 10 VA @ 24VAC power. In the examples below we have a total of 8 Zone Controllers.
8 Zone Controllers @ 10VA each................ 8 x 10VA = 80VA.
The above calculation determines that our transformer will need to be sized for a minimum of 80VA if we are to use one transformer to power all the
controllers.
Next we must determine the maximum length of run allowable for the wire gauge we wish to use in the installation. Each wire gauge below has a
voltage drop per foot value we use to calculate total voltage drop.
18ga wire.................................0.00054 = voltage drop per 1’ length of wire
16ga wire.................................0.00034 = voltage drop per 1’ length of wire
14ga wire.................................0.00021 = voltage drop per 1’ length of wire
For our example we will use 18 gauge wire. WattMaster recommends 18 gauge as a minimum wire size for all power wiring.

Next use the voltage drop per foot value for 18 gauge wire from the list above and multiply by the total VA load of the 8 controllers to be installed.
0.00054 (Voltage drop per foot for 18 gauge wire) x 80VA controller load = 0.0432 Volts/Ft.
WattMaster controllers will operate efficiently with a voltage drop no greater than 2 Volts. Divide the total allowable voltage drop of 2 Volts by the
number you arrived at above and you have the maximum number of feet you can run the 18 gauge wire with an 80VA transformer with no more than a
2 Volt drop at the farthest controller from the transformer..
2 (Volts total allowable voltage drop)
= 46.30 feet
0.0432 (Voltage drop per 1 ft. @ 80VA load)
Parallel circuiting of the wiring instead of wiring all 8 controllers in series allows for longer wire runs to be used with the same size wire (as shown in
our examples below). It is often necessary for the installer to calculate and weigh the cost and installation advantages and disadvantages of wire size,
transformer size, multiple transformers, circuiting, etc., when laying out an installation. No matter what layout scheme is decided upon, it is mandatory
that the farthest controller on the circuit is supplied with a minimum of 22 Volts.

ZONE ZONE
ZONE ZONE CONTROLLER CONTROLLER ZONE ZONE
CONTROLLER CONTROLLER ZONE ZONE
CONTROLLER CONTROLLER CONTROLLER CONTROLLER

B C
B B C D E
A
ZONE ZONE
ZONE ZONE CONTROLLER CONTROLLER ZONE ZONE
CONTROLLER CONTROLLER ZONE ZONE
CONTROLLER CONTROLLER CONTROLLER CONTROLLER

120 / 24VAC

ZONE ZONE
ZONE ZONE CONTROLLER CONTROLLER
CONTROLLER CONTROLLER

ZONE ZONE
ZONE ZONE CONTROLLER CONTROLLER
CONTROLLER CONTROLLER
A
120 / 24VAC

A Distance from A to B cannot exceed 185.20 Ft.


120 / 24VAC
Distance from A to C cannot exceed 185.20 Ft.
Distance A to B cannot exceed 46.30 Ft. Distance from A to B cannot exceed 92.60 Ft. Distance from A to D cannot exceed 185.20 Ft.
Distance from A to C cannot exceed 92.60 Ft. Distance from A to E cannot exceed 185.20 Ft.

JOB NAME
Component Power Requirements
System Manager ......................25VA GPC Controller .........................20VA
FILENAME
Zone Manager ..........................25VA Wetbulb Module .......................20VA
WIRSIZ1.CDR C O N T R O L S
Zone Controller ........................10VA Lighting Panel Controller ..........25VA
DATE: 11/30/99 DRAWN BY: B. CREWS
CV Controller............................20VA Zone Relay Expansion Board ...10VA
PAGE DESCRIPTION:
CV-C Controller ........................20VA Staging Expansion Board .........20VA
Auto-Zone
Optimal Start Scheduler ...........25VA 1 Wire & Transformer Sizing
Figure 1-16: Transformer And Wire Sizing Considerations

26 Auto-Zone Systems
Zoning Design Guide

Application Notes:
Zoning 30 And 40 Ton Units • Bypass dampers should be sized for 60 to
When using large HVAC units for zoning applications, 70% of the rated CFM of the unit. Because of
several rules must be considered to prohibit potential the large air volumes involved, rectangular
problems. dampers should be used instead of round
dampers. Consult the rectangular damper
Because of the large air flow capacities of the 30 and sizing guide (Table 1-2 on page 25), for CFM
40 ton units, great care must be taken in sizing zone ratings.
and bypass dampers.
• Large units should always have a minimum
Use these guidelines to help keep you out of trouble. of 6 zones due to the high air flow capacities.

• Always use the Auto-Zone Plus system even • To prevent excessive noise in the system,
if you only have one unit that you are zoning. zone damper total minimum airflow settings
should be equal to or preferably greater than
• Generally you should use constant volume 30% of the units rated CFM.
units in your zoning system design. If your
units are to be equipped with variable As an added precaution, we recommend a high duct
frequency drives or inlet vanes, please static safety switch be installed (Dwyer Model 1900-
consult WattMaster Controls for assistance. 5-MR or equal) to prevent over pressurization of the
ductwork.
• The OE340-10-AGSTG relay expansion card
is usually required for each Zone Manager
controlling two or more stages of cooling.

Auto-Zone Systems 27
Form: WM-AZA-ZDG-01B Printed in the USA October 2001
All rights reserved Copyright 2001
WattMaster Controls Inc. • 8500 NW River Park Drive • Parkville MO • 64152
Phone (816) 505-1100 E-mail: mail@wattmaster.com Fax (816) 505-1101

You might also like