You are on page 1of 1

ducts and accessories

ALU-COUSTIC ALU-PHONIC

Alu-Coustic 25 M0 / M1
advantages
Phonic attenuation.

acoustic semi-rigid duct

Alu-Phonic 25 M0 / M0
advantages
Phonic attenuation.

acoustic semi-rigid duct

 Reducing of the condensation and the heat losses.

 Reducing of the condensation and the heat losses. Possibility of building around the duct.

range
Diameters : 100 to 500 mm.

 range
Diameters : 100 to 400 mm.

application
Installations of ventilation, air conditioning and CMV.

application
 Installation of hot water, ventilation, air conditioning and CMV.

construction / composition
Microperforated semi-rigid aluminium interior duct. Glasswool mattress (thickness : 25 mm, density : 16 kg/m3). Steam barrier aluminium/Polyester.

construction / composition
Microperforated semi-rigid aluminium interior duct. Glasswool mattress (thickness : 25 mm, density : 16 kg/m3). Steam barrier.

packaging
Length of 3 m compressed to 1,5 m up to 315 mm. superior to 315 mm not compressed. In individual cartons.

packaging
Length of 3 m not compressed.

specications
T  he valves will be connected to the main network by a circular semi-rigid duct in microperforated aluminium, phonically isolated by 25 mm of glasswool with exterior semi-rigid aluminium coating. The semi-rigid duct will have fire grading M0/M0. Type Alu-Phonic, France Air brand.

specications
T  he valves will be connected to the main network by a circular semi-rigid duct in microperforated aluminium, phonically isolated by a glasswool mattress with exterior multi-layer aluminium coating. The semi-rigid duct will have fire grading M0/M1. Type Alu-Coustic, France Air brand.

technical description
Fire grading
M0/M1 : product M1 with interior duct is classified M0.

technical description
Fire grading
 M0/M0 : interior duct, glasswool and exterior duct classified MO.

Limits of use
Temperature : - 30 C to + 250 C. Maximum temperature : 300 C. Maximum pressure : 2 000 Pa - > 400 : 1000 Pa.

Limits of use
Temperature : - 30 C to + 250 C. Maximum temperature : 300 C. Maximum pressure : 3 000 Pa.

Features
A  coustic attenuations (according to norm NF ISO 7235 August 1995) : tolerance of 0,5 dB for 1 linear metre of Alu-Coustic duct.
Diameter (mm) 80 100 125 160 200 250 315 400 500 Frequency (Hz) 63 10 7 5 4 3 2 1 1 1 125 8 7 5 4 3 2 2 2 1 250 13 11 9 6 5 4 3 3 2 500 13 12 11 11 10 9 9 8 8 1000 32 30 28 25 22 21 19 18 16 2000 45 45 45 36 31 22 17 13 10 4000 35 28 24 19 15 13 10 9 7 8000 30 23 17 14 13 9 7 5 4

 Features
A  coustic attenuations (according to norm NF ISO 7235 August 1995) : tolerance of 0,5 dB for 1 linear metre of Alu-Phonic duct.
Diameter (mm) 80 100 125 160 200 250 315 400 500 Frequency (Hz) 63 10 7 5 4 3 2 1 1 1 125 8 7 5 4 3 2 2 2 1 250 13 11 9 6 5 4 3 3 2 500 13 12 11 11 10 9 9 8 8 1000 32 30 28 25 22 21 19 18 16 2000 45 45 45 36 31 22 17 13 10 4000 35 28 24 19 15 13 10 9 7 8000 30 23 17 14 13 9 7 5 4

tting and connection


 The ducts must be cut with a metal saw or with a sharp blade.  Use a male-male connection (RM) for assembly of 2 lengths.  Ensure airtightness between the interior duct and the connection with a Alu Butyl, Fib-Air or sheeted FA 52 strip. Push the glasswool a few centimeters back.  Tighten the exterior duct and ensure the airtightness with an aluminium strip Fib-Air, then complete with flat collar Multidiam or Monofil.

168

www.france-air.com

Guide created by France Air 2010. All rights reserved.