You are on page 1of 19

14th U.S.

-Japan Workshop on Improvement of Structural Design and Construction Practices

Nobuyuki KURAUCHI AZUSA SEKKEI Co.,Ltd. Osaka , Japan

Why was needed the seismic retrofit ?


Improvement of the seismic retrofit of this building was needed, the controller escaped by intense fear in the Great East Japan Earthquake.

The important facility as the main gate of Japan.


Preparation for Tokyo metropolitan earthquake

which may happen from now on.

14th U.S.-Japan Workshop on Improvement of Structural Design and Construction Practices December, 2012

Why adopted the damping structure?


The reinforcement work must be done while the building is being used.
No change was allowed concerning

the main electric cables and building equipment.


The cost of the seismic retrofit must be kept in

the limited budget.

14th U.S.-Japan Workshop on Improvement of Structural Design and Construction Practices December, 2012

Existing Building Outline-1

Airport Administration Building


6

Connecting bridge Control Tower

SITE
14th U.S.-Japan Workshop on Improvement of Structural Design and Construction Practices December, 2012

Existing Building Outline-2


Location : Chiba , Japan Building area : 241.43 Total floor area : 1778.26 Standard floor area : 169.74(13.16 sq. meters) Number of floors : L21

Structure : S , partly SRC or RC Foundation : pile

Y3

13.16m 4.16 4.84 4.16

Y4

13.16m 6.58 6.58

87.3m

Height of building : 87.3

Y2

Y1

X1

X2

X3

SRC,RC
December, 2012

14th U.S.-Japan Workshop on Improvement of Structural Design and Construction Practices

Structural Planning-Structural design of Existing Building


Frame Form Main Frame : S , Moment Frame with braces (L2~ ) SRC , Box-frame construction(L1) : Column section is a shape of 550mm-box and a shape of 450mm-diameter-pipe. Maximum depth of H-Beam is 700mm. Maximum depth of H-Brace is 400mm. Thickness of bearing wall is 900mm. Foundation : Mat slab form(Thickness is 5m) Cast-in-place concrete pile(Diameter is 1.5m) Material Strength : Tensile strength of Steel is 490N/mm2 . Compressive strength of concrete is 21N/mm2. Tuned liquid damper(TLD)is installed on the L15

Situation of installed TLD (L15)


14th U.S.-Japan Workshop on Improvement of Structural Design and Construction Practices December, 2012

Structural Planning-Application design of viscous dampers


Y4 Y3

Y2 Y1

X1

X2

X3

Y Fig. Beam plan X


:Viscous Damper :Brace :Reinforcement Beam

Y1,4

Y2,3

X2

Fig. Section plan for disposition of viscous dampers


14th U.S.-Japan Workshop on Improvement of Structural Design and Construction Practices December, 2012

Structural Planning-type-1 of viscous dampers

For example
[leaned arrangement type(Y2 L2-3)]
14th U.S.-Japan Workshop on Improvement of Structural Design and Construction Practices December, 2012

Structural Planning-type-2 of viscous dampers

For example of installing out-frame


[Amplification mechanism type(X2 L9-11)]
14th U.S.-Japan Workshop on Improvement of Structural Design and Construction Practices December, 2012

Dynamic characteristics of existing building


VFR Room

Fig. Free vibration of horizontal motion Table. 1st natural period and damping coefficient
Damping Natural period(s) coefficient(%)

Fig. Seismographs arrangement Before installing TLD

1st(1992) 2nd(1992) 3rd(1993)

After installing TLD

4th(1994) 5th(1998) 6th(2004)

14th U.S.-Japan Workshop on Improvement of Structural Design and Construction Practices December, 2012

Structural Design Criteria1000


cm 00 10
2

Selection of Input Earthquake Motion


Level-2 KOBE Phase(Foundation position)
500

10 0c m

Acceleration(cm/s )

10 00 0g al

Velocity Response Spectra(cm/s

Maximum-387.82(cm/s2)
Level-2 KOBE Phase(Foundation position) 0 10 20 30 40 50 60

100

Level-2(three kinds of phase)


al

-500

10

g 00

10

Acceleration(cm/s )

l ga 0 50

Level-1(three kinds of phase)


10 . 0c m
500

Level-2 HACHINOHE Phase(Foundation position)

Maximum-316.58(cm/s2)

1. m 0c

l ga 0 10

10 g

0.

1 0.

al

1g al

1 0.1

05 cm

Level-2 HACHINOHE Phase(Foundation position) 0 10 20 30 40 50 60

cm

-500

Period(s)

10

(h=5%)

Second(s)

14th U.S.-Japan Workshop on Improvement of Structural Design and Construction Practices December, 2012

Structural Design CriteriaStructural design criteria of seismic retrofit building


Table. Structural Design Criteria of seismic retrofit building

* The top of building partly cannot meet the design criteria of Inter-story drift angle. Therefore, total inter-story drift is divided into bending deformation and shear deformation and, paying attention to shear deformation, breakage and fall of the exterior are checked

A D C b D

s
C

A B

Total inter-story drift ;

rotational moment of floor horizontal displacement of floor Bending deformation ; b shear deformation ; s

Figure . Outline of Inter-Story Drift Angle


14th U.S.-Japan Workshop on Improvement of Structural Design and Construction Practices December, 2012

Structural Modeling and Analysis Method(1)


1) Boundary condition: bottom of column installed on the L1 is Pin support 2) Node has six degrees of freedom, while node installed on the slab has three degrees of freedom 3) restoring force characteristics of structural element Beam bending: end of member has rotational spring (Fig. a) Restoring force characteristics is Bi-linear Type Shear : center of member has shear spring (Fig. b) Restoring force characteristics is Bi-linear Type Brace : Axial direction spring (Fig c) Restoring force characteristics is Bi-linear Type Column, wall : fiber (MS) model (Fig. d)

Fig a. Beam bending model

Fig b. Beam shear model Fig c. Axial direction spring Fig d. Fiber model Fig. Analysis model
December, 2012

14th U.S.-Japan Workshop on Improvement of Structural Design and Construction Practices

Structural Modeling and Analysis Method(2)


Viscous damper : Maxwell Model.(Fig e) )Type-1 (Leaned Arrangement Type) Damping coefficient ; C1 , C2 =750, 14.4[kNsec/cm] Stiffness coefficient ; K=5800[kN /cm], constant value )Type-2 (Amplification Mechanism Type) Damping coefficient ; C1 , C2 =120, 4.0[kNsec/cm] Stiffness coefficient ; K=2352[kN /cm], constant value Axial stiffness of brace is slip model in consideration of a displacement loss
2000kN Viscous damperLeaned arrangement type 2500 1000 Maximum force Damping forcekN 800 600 400 200 0 5 10 15 20 Velocitycm/s 25 30 0 Maximum force 800kN Viscous damper(Amplication mechanism type)

Damping forcekN)

2000 1500 1000 500 0

C2

Product Error : 10%

C2

Product Error : 10%

Inter Node Fig e. Maxwell Model

C1
0

C1
20 40 Velocitycm/s 60 80

4) Damping; Structural Damping is type of internal viscous damping of initial stiffness coefficient and first mode damping ration(=h1) is =0.01. 5) Stiffness;

Fig . Nonlinear curve (type-1)

Fig . Nonlinear curve (type-2)

Shear deformation for junction of the intersection portions of column and beam must be taken into consideration. The rigidity of beam bending must be increased by slab. ( =1.3:single-sided slab, =1.5:both-sides slab)
14th U.S.-Japan Workshop on Improvement of Structural Design and Construction Practices December, 2012

Analysis ResultComparison Comparison of of Maximum Maximum Response Response based based on on damper damper disposition disposition
Y1,4 Y2,3 Y1,4 Y2,3 Y1,4 Y2,3
Maximum inter-story drift angle 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 Case-1 4 3 Case-2 2 Case-3 1 0 0.000 0.005 0.010 0.015 Inter-story drift angle(rad)

[CASE-2] [CASE-3] [CASE-1] Fig. Damper disposition proposal of X-direction X2 X1 X3 X2 X1 X3

Floor

21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

Maximum inter-story drift angle

Fig. damper disposition

Floor

Table . 1st Natural period(s)


Exsiting Case-1 Case-2 Case-3 Model 1.31 1.41 1.31 X-direction 1.31 1.30 1.30 1.30 Y-direction

Case-1 Case-2 0.005 0.010 0.015 Inter-story drift angle(rad)

[CASE-1] [CASE-2] Fig. Damper disposition proposal of Y-direction

0.000

14th U.S.-Japan Workshop on Improvement of Structural Design and Construction Practices December, 2012

Analysis Result-Effect of viscous dampers(1)


Maximum inter-story drift angle 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 0 Maximum story share force Existing model Retrofit model

Average; about 38%


Floor

Average; about 35%

Existing model Retrofit model

0.000 0.005 0.010 0.015 0.020 Inter-story drift anglerad

Maximum acceleration response 21 20 19 18 17 16 15 14 13 12 11 10 Average; about 25% 9 8 7 6 5 4 Existing model 3 2 Retrofit model 1 0 0 1000 2000 3000 Acceleration responsecm/s2

Floor

10000 20000 30000 story share forcekN

Fig. Maximum Response of X-direction


14th U.S.-Japan Workshop on Improvement of Structural Design and Construction Practices December, 2012

Floor

Analysis Result-Effect of viscous dampers(1)


Maximum inter-story drift angle 21 20 19 18 17 16 15 14 13 12 11 10 9 Average; about 9% 8 7 6 5 4 Existing model 3 Retrofit model 2 1 0 0.000 0.005 0.010 0.015 0.020 Inter-story drift anglerad

Maximum story share force 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 0

Maximum acceleration response 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

Existing model Retrofit model

Floor

Floor

Floor

Average; about 7%

Average; about 7%

Existing model Retrofit model 0 1000 2000 3000 Acceleration responsecm/s2

10000 20000 30000 story share forcekN

Fig. Maximum Response of Y-direction


14th U.S.-Japan Workshop on Improvement of Structural Design and Construction Practices December, 2012

Analysis Result-Effect of viscous dampers(2)


X-Direction 2000.00 1500.00 1000.00 500.00 0.00 -500.00 -1000.00 -1500.00 -2000.00 0.00 10.00 20.00 30.00

X-Direction 500.00
Existing model Retrofit model

floor acceleration response(cm/s2)

floor acceleration response(cm/s2)

Existing model Retrofit model

0.00

The highest response; about 18%


40.00 Second(s) 50.00 60.00 70.00 80.00

-500.00 60.00 70.00 Second(s) 80.00

Fig. Time History of Response acceleration (X-direction / L20)


Y-Direction 2000.00 1000.00 500.00 0.00 -500.00 -1000.00 -1500.00 -2000.00 0.00 10.00 20.00 30.00 40.00 Second(s) 50.00 60.00 70.00 80.00

Y-Direction 500.00 floor acceleration response(cm/s2)


Existing model Retrofit model

1500.00 floor acceleration response(cm/s2)

Existing model Retrofit model 0.00

The highest response; about 5.5%

-500.00 60.00 70.00 Second(s) 80.00

Fig. Time History of Response acceleration (Y-direction / L20)


14th U.S.-Japan Workshop on Improvement of Structural Design and Construction Practices December, 2012

Conclusions
Earthquake-proof performance was improved with the proposed seismic retrofit using viscous dampers, in compliance with structural design criteria.

After this reinforcement work ended, we are scheduled to experiment on dynamic characteristics based on microtremor measure and free vibration test.

14th U.S.-Japan Workshop on Improvement of Structural Design and Construction Practices December, 2012