You are on page 1of 46

Fire Prevention Book – Table of Contents

(October 2, 2009)

• Automatic Sprinkler System – Weekly


• Automatic Sprinkler System – Monthly
• Automatic Sprinkler System – Every 2 Months
• Automatic Sprinkler System – Every 3 Months
• Automatic Sprinkler System – Every 6 Months
• Automatic Sprinkler System – Annually
• Automatic Sprinkler System – As Required
• Automatic Sprinkler System – Every 15 Years

• Emergency Lighting Systems - Monthly


• Emergency Lighting Systems – Annually

• Emergency Power Systems – Weekly


• Emergency Power Systems – Every 6 Months
• Emergency Power Systems – Annually
• Emergency Power Systems – Every 2 Years
• Emergency Power Systems – Every 3 Years
• Emergency Power Systems – Every 5 Years

• Fire Alarm Inspection Log – Monthly

Fire Department Access - As Required

• Fire Protection System for Commercial Cooking Equipment – Weekly


• Fire Protection System for Commercial Cooking Equipment – Monthly
• Fire Protection System for Commercial Cooking Equipment – Every 6 Months
• Fire Protection System for Commercial Cooking Equipment – As Required

• Fire Separations – Monthly


• Fire Separations – As Required

• Means of Egress and Exit Signs - As Required


• Portable Fire Extinguishers – Monthly
• Portable Fire Extinguishers – Annually
• Portable Fire Extinguishers - Every 5 Years
• Portable Fire Extinguishers - Every 6 Years
• Portable Fire Extinguishers - Every 12 Years
• Portable Fire Extinguishers - As Required

• Standpipe and Hose systems – Annually


• Standpipe and Hose Systems – Monthly
• Standpipe and Hose systems – Annually
• Standpipe and Hose systems – After Each Use
• Standpipe and Hose systems – As Required

• Water Supply for Fire Fighting – Daily


• Water Supply for Fire Fighting – Weekly
• Water Supply for Fire Fighting – Monthly
• Water Supply for Fire Fighting – Annually
• Water Supply for Fire Fighting – Every 2 Years
• Water Supply for Fire Fighting – Every 5 Years
Fire Department Access - As Required

Requirement: X = Satisfactory
O = Unsatisfactory
Check fire access routes and access panels or windows
provided to facilitate access by fire fighting operations to ensure
that they are not obstructed by vehicles, gates, fences, building
materials, vegetation, signs or any other form of obstruction.
Location Condition Inspected by (LKDSB) Date
Means of Egress and Exit Signs - As Required

Requirement: X = Satisfactory
O = Unsatisfactory
Check that required exit signs are maintained to ensure they are
clearly visible, clean and legible.
Location Condition Inspected by (Custodian) Date
Portable Fire Extinguishers – Monthly
Reference should be made to NFPA 10-2002 for exact details.
(in accordance with Subsection 6.2.7.) – Inspection, Testing and Maintenance)

Requirement: X = Satisfactory
O = Unsatisfactory
Inspect all portable extinguishers.
Location J F M A M J J A S O N D Inspected by Date
(Custodian)
Portable Fire Extinguishers – Annually
Reference should be made to NFPA 10-2002 for exact details.
(in accordance with Subsection 6.2.7.) – Inspection, Testing and Maintenance)

Requirement: X = Satisfactory
O = Unsatisfactory
Maintain and test all portable extinguishers in conformance with
NFPA 10.
Location Serial # Condition Inspected by (Access) Date
Portable Fire Extinguishers - Every 5 Years
Reference should be made to NFPA 10-2002 for exact details.
(in accordance with Subsection 6.2.7.) – Inspection, Testing and Maintenance)

Requirement: X = Satisfactory
O = Unsatisfactory
Hydrostatically test carbon dioxide and water type extinguishers.
Location Condition Inspected by (Access) Date
Portable Fire Extinguishers - Every 6 Years
Reference should be made to NFPA 10-2002 for exact details.
(in accordance with Subsection 6.2.7.) – Inspection, Testing and Maintenance)

Requirement: X = Satisfactory
O = Unsatisfactory
Empty stored pressure type extinguishers and repair or replace if
necessary.
Location Condition Inspected by (Access) Date
Portable Fire Extinguishers - Every 12 Years
Reference should be made to NFPA 10-2002 for exact details.
(in accordance with Subsection 6.2.7.) – Inspection, Testing and Maintenance)

Requirement: X = Satisfactory
O = Unsatisfactory
Hydrostatically test dry chemical type extinguishers.
Location Serial # Condition Inspected by (Access) Date
Portable Fire Extinguishers - As Required
Reference should be made to NFPA 10-2002 for exact details.
(in accordance with Subsection 6.2.7.) – Inspection, Testing and Maintenance)

Requirement: X = Satisfactory
O = Unsatisfactory
Replace or recharge portable fire extinguishers after use in
conformance with instructions given on the extinguisher
nameplate or as indicated by an inspection or when performing
maintenance.
Location Serial # Condition Inspected by (Access) Date
Emergency Lighting Systems - Monthly

Requirement: X = Satisfactory
O = Unsatisfactory
Test emergency lighting units to ensure emergency lights will
function upon failure of the primary power supply.
Location J F M A M J J A S O N D Inspected by Date
(Custodian)
Emergency Lighting Systems – Annually

Requirement:

Test emergency lighting units to ensure unit will provide


emergency lighting for a duration equal to the design criteria X = Satisfactory
under simulated power failure conditions. O = Unsatisfactory
(After completion of the test, the charging conditions for voltage
and current and the recovery period shall be tested to ensure
that the charging system is in accordance with the
manufacturer’s specifications.)
Location Condition Inspected by (Access) Date
Fire Separations – Monthly

Requirement: X = Satisfactory
O = Unsatisfactory
Inspect all doors in fire separations.
Location J F M A M J J A S O N D Inspected by Date
(LKDSB)
Fire Separations – As Required

Requirement: X = Satisfactory
O = Unsatisfactory
Check doors in fire separations to ensure that they are closed.
Location Condition Inspected by (LKDSB) Date
Fire Protection System for Commercial Cooking Equipment – Weekly
Reference should be made to NFPA 96 for exact details.

Requirement: X = Satisfactory
O = Unsatisfactory
Check hoods, filters and ducts in ventilation systems subject to
the accumulation of combustible deposits.
Location Condition Inspected by (Kitchen Staff) Date
Fire Protection System for Commercial Cooking Equipment – Monthly
Reference should be made to NFPA 96 for exact details.

Requirement: X = Satisfactory
O = Unsatisfactory
Inspect system for obvious or mechanical damage.
Location J F M A M J J A S O N D Inspected by Date
(Kitchen Staff)
Fire Protection System for Commercial Cooking Equipment – Every 6 Months
Reference should be made to NFPA 96 for exact details.

Requirement: X = Satisfactory
O = Unsatisfactory
Inspect and maintain exhaust and fire protection system for
commercial cooking equipment.
Location Condition Inspected by (Access) Date
Fire Protection System for Commercial Cooking Equipment – As Required
Reference should be made to NFPA 96 for exact details.

Requirement: X = Satisfactory
O = Unsatisfactory
Clean hoods, filters, ducts when accumulation of combustible
deposits creates a fire hazard.
Location Condition Inspected by (Kitchen Staff) Date
Automatic Sprinkler System – Weekly
Reference should be made to NFPA 13 for exact details

Requirement: X = Satisfactory
O = Unsatisfactory
Check to ensure that valves that are not electrically supervised
and control water supplies to sprinklers and alarm connections
(e.g. control valves), are in the open position.
Location Condition Inspected by (LKDSB – C1) Date
Automatic Sprinkler System – Monthly
Reference should be made to NFPA 13 for exact details

Requirement: X = Satisfactory
O = Unsatisfactory
Test the sprinkler system alarm using alarm test connection
located at the sprinkler valve.
Location J F M A M J J A S O N D Inspected by Date
(LKDSB – C1)
Automatic Sprinkler System – Every 2 Months
Reference should be made to NFPA 13 for exact details

Requirement: X = Satisfactory
O = Unsatisfactory
Test the sprinkler supervisory transmitters and water flow
devices.
Location Condition Inspected by (LKDSB – C1) Date
Automatic Sprinkler System – Every 3 Months
Reference should be made to NFPA 13 for exact details

Requirement: X = Satisfactory
O = Unsatisfactory
Inspect the priming water level for dry-pipe systems to ensure
proper levels are maintained.
Location Condition Inspected by (LKDSB – C1) Date
Automatic Sprinkler System – Every 6 Months
Reference should be made to NFPA 13 for exact details

Requirement: X = Satisfactory
O = Unsatisfactory
Test gate valve supervisory switches and other sprinkler and fire
protection system supervisory devices.
Location Condition Inspected by (Contracted – Date
TBD New Tender)
Automatic Sprinkler System – Annually
Reference should be made to NFPA 13 for exact details

Requirement: X = Satisfactory
O = Unsatisfactory
Check exposed sprinkler system pipe hangers to ensure they are
in good repair.
Location Condition Inspected by (Contracted – Date
TBD New Tender)
Automatic Sprinkler System – Every 15 Years
Reference should be made to NFPA 13 for exact details

Requirement: X = Satisfactory
O = Unsatisfactory
Inspect the dry pipe systems for obstructions and flush the entire
system where necessary.
Location Condition Inspected by (Contracted – Date
TBD New Tender)
Automatic Sprinkler System – As Required
Reference should be made to NFPA 13 for exact details

Requirement: X = Satisfactory
O = Unsatisfactory
Check dry pipe valve rooms or enclosures during freezing
weather to ensure the system does not freeze.
Location Condition Inspected by (LKDSB-C1) Date
Water Supply for Fire Fighting – Daily

Requirement: X = Satisfactory
O = Unsatisfactory
Check the temperature of pump room during freezing weather.
Location Condition Inspected by (LKDSB-C1) Date
Water Supply for Fire Fighting – Weekly

Requirement: X = Satisfactory
O = Unsatisfactory
Inspect valves controlling fire protection water supply to ensure
they are wide open and sealed or locked in that position.
Location Condition Inspected by (LKDSB-C1) Date
Water Supply for Fire Fighting – Monthly

Requirement: X = Satisfactory
O = Unsatisfactory
Inspect water level in gravity tanks.
Location J F M A M J J A S O N D Inspected by Date
(LKDSB-C1)
Water Supply for Fire Fighting – Annually

Requirement: X = Satisfactory
O = Unsatisfactory
Inspect fire protection water supply tanks, supporting structures
and supply systems.
Location Condition Inspected by (LKDSB- TBD) Date
Water Supply for Fire Fighting – Every 2 Years

Requirement: X = Satisfactory
O = Unsatisfactory
Check steel on inside and outside of fire protection water supply
tanks for corrosion.
Location Condition Inspected by (LKDSB) Date
Water Supply for Fire Fighting – Every 5 Years

Requirement: X = Satisfactory
O = Unsatisfactory
Inspect fire protection water tanks connected to potable water,
scrape and repaint as required.
Location Condition Inspected by (LKDSB) Date
Emergency Power Systems – Weekly
Reference should be made to CAN/CSA C282-M89 for exact details

Requirement: X = Satisfactory
O = Unsatisfactory
Check all components of the system, operate the generator set
under at least 50% of rated load for 30 minutes.
Location Condition Inspected by (LKDSB – N/A Date
School by School)
Emergency Power Systems – Every 6 Months
Reference should be made to CAN/CSA C282-M89 for exact details

Requirement: X = Satisfactory
O = Unsatisfactory
Check and clean crankcase breathers, governors and linkages
on emergency generators.
Location Condition Inspected by (LKDSB – N/A Date
School by School)
Emergency Power Systems – Annually
Reference should be made to CAN/CSA C282-M89 for exact details

Requirement: X = Satisfactory
O = Unsatisfactory
Inspect and service generator and generator set.
Location Condition Inspected by (LKDSB – N/A Date
School by School)
Emergency Power Systems – Every 2 Years
Reference should be made to CAN/CSA C282-M89 for exact details

Requirement: X = Satisfactory
O = Unsatisfactory
Check torque and valve adjustments for engines.
Location Condition Inspected by (LKDSB – N/A Date
School by School)
Emergency Power Systems – Every 3 Years
Reference should be made to CAN/CSA C282-M89 for exact details

Requirement: X = Satisfactory
O = Unsatisfactory
Inspect and service injector nozzles and valve adjustments on
diesel engines.
Location Condition Inspected by (LKDSB – N/A Date
School by School)
Emergency Power Systems – Every 5 Years
Reference should be made to CAN/CSA C282-M89 for exact details

Requirement: X = Satisfactory
O = Unsatisfactory
Check insulation of generator windings.
Location Condition Inspected by (LKDSB – N/A Date
School by School)
Standpipe and Hose systems – Annually
Reference should be made to NFPA 25 for exact details.

Requirement: X = Satisfactory
O = Unsatisfactory
Plugs and caps to be removed annually and the fire department
connections inspected for wear, rust, or obstruction.
Location Condition Inspected by (LKDSB) Date
Standpipe and Hose Systems – Monthly
Reference should be made to NFPA 25 for exact details.

Requirement: X = Satisfactory
O = Unsatisfactory
Hose stations are to be checked to ensure they are in the
proper location and all the equipment is in place and operable.
Location J F M A M J J A S O N D Inspected by Date
(LKDSB)
Standpipe and Hose systems – Annually
Reference should be made to NFPA 25 for exact details.

Requirement: X = Satisfactory
O = Unsatisfactory
Hose valves are to be inspected annually to ensure there is no
leakage.
Location Condition Inspected by (LKDSB) Date
Standpipe and Hose systems – After Each Use
Reference should be made to NFPA 25 for exact details.

Requirement: X = Satisfactory
O = Unsatisfactory
Inspect hose and replace on the rack.
Location Condition Inspected by (LKDSB) Date
Standpipe and Hose systems – Annually and After Each Use
Reference should be made to NFPA 25 for exact details.

Requirement: X = Satisfactory
O = Unsatisfactory
Inspected hose shall be replaced so that the folds are not in the
same places.
Location Condition Inspected by (LKDSB) Date
Standpipe and Hose systems – As Required
Reference should be made to NFPA 25 for exact details.

Requirement: X = Satisfactory
O = Unsatisfactory
Inspection, testing and maintenance shall conform to NFPA 25
“Standard for the Inspection, Testing and Maintenance of Water-
Based Fire Protection Systems.”
Location Condition Inspected by (LKDSB) Date
Fire Alarm Inspection Log – Monthly
Mark “X” for Satisfactory and “O” for Unsatisfactory

Date Pull Station Results Audible Signal Results Annunciator Results Battery Trouble Signature of Certified
Location Appliance Readings Signal Technician (where
Location applicable)