Protection and control IED manager PCM600 Communication and project setup

SA-T Training October 20, 2010 | Slide 1 1MRG003731

Contents

Section 3

Communication setup at

IED side PC side

PCM600 project handling


Creation/deletion of projects Handling of IED objects License Update (read order options) Technical key (only for 650 series) Export/Import Report parameters

HW tool

SA-T Training October 20, 2010 | Slide 2 1MRG003731

What to learn with this chapter


Section 3

With this presentation You will learn


What is needed to establish the communication between the physical IED and PCM600.

How to set IP addresses for the IED objects in PCM600 and also for the engineering PC itself running PCM600 Impact of sub networks

How to manage projects with PCM600


Creation of projects Deletion of projects Import/export functionality

Basic HW configuration done with the HW tool

SA-T Training October 20, 2010 | Slide 3 1MRG003731

Communication setup IED PC

Section 3

Communication protocols

TCP/IP

IEC61850 communication connectivity package used

SPA (only 670 series) LON (only 670 series)

IED Ethernet ports


Front port

Galvanic

Rear port(s)

Optic

Two channels possible for 670 series One channel only for 650 series

SA-T Training October 20, 2010 | Slide 4 1MRG003731

Ethernet IED Front connection

Section 3

IED Front port


Default IP address 10.1.150.3 Default Subnet mask 255.255.255.0

PC port setting

IP address 10.1.150.1 up to 254 Subnet mask 255.255.255.0

Crossed over Ethernet cable


If direct connection from PC to IED

IED Front has DHCP server


Dynamically assign IP address to the PC

SA-T Training October 20, 2010 | Slide 5 1MRG003731

Ethernet Optic network


IP: 172.16.0.11 Mask: 255.255.0.0

Section 3

IED Rear port


Default IP address 192.168.1.10 Default Subnet mask 255.255.255.0

IP: 172.16.0.10 Mask: 255.255.0.0

Optical cable
RX TX RX TX

This is an example of Class B network addressing concept


The two first segments


Ethernet switch

Defines the Network

The two last segments


IP: 172.16.0.13 Mask: 255.255.0.0

Define the Nodes

Rear Ethernet port NO DHCP server

IP: 172.16.0.12 Mask: 255.255.0.0

Note! All devices that shall communicate with each other must belong to the same sub network

SA-T Training October 20, 2010 | Slide 6 1MRG003731

Ethernet port settings at PC side

Section 3

No settings in PCM600 for Ethernet port of PC, use WINDOWS control panel

Set TCP/IP properties on the connection to be used for the PCM600/IED communication

SA-T Training October 20, 2010 | Slide 7 1MRG003731

IED Ethernet port settings


Section 3

The IP address of the IED object in PCM600 can be set in two ways;

When creating the IED object in PCM600, the IP address can be set in the Configuration Wizard Opening Properties at IED level object and changing the IP Address property

SA-T Training October 20, 2010 | Slide 8 1MRG003731

Section 3

PCM600 project handling


Manage projects Create the plant structure Create the IED objects

SA-T Training October 20, 2010 | Slide 9 1MRG003731

Manage Projects

Section 3

Open/Manage projects

Create projects Delete projects Export projects


All data within the PCM600 project is exported to a file with extension .pcmp. Used for back-up purposes.

Import projects

Use earlier exported .pcmp file

Rename projects

SA-T Training October 20, 2010 | Slide 10 1MRG003731

Create the Plant Structure


Section 3

Two ways to create objects;


Drag and drop from object types Right click on object, select New

When creating IED objects, the configuration wizard is automatically started

Note: Only one substation level is allowed

SA-T Training October 20, 2010 | Slide 11 1MRG003731

Create the IED objects

Section 3

Configuration modes

Online configuration

IED available

Select the protocol to use for the PCM600/IED communication


Note: Not possible to communicate between PCM600 and IED via SPA and LON for the 650 series

Offline configuration

No IED available Use order files

SA-T Training October 20, 2010 | Slide 12 1MRG003731

Create the IED objects, Online configuration

Section 3

Set IP address to use Different default values for Front and Rear port, otherwise no meaning with the Port selection

IED type, version, display type (Local HMI) and housing (size of the IED) is automatically detected in online mode (Use the Scan button)

SA-T Training October 20, 2010 | Slide 13 1MRG003731

Create the IED objects, Offline configuration


Section 3

IED version must be selected manually Order option file available


Enables only ordered SW and HW in PCM600


No need to synchronize PCM600 and physical IED

No order option file available


Enables all functionality in PCM600


Need to synchronize PCM600 and physical IED, use the License Update Tool Possible to configure functionality in PCM600 that later will not be accepted by the IED

SA-T Training October 20, 2010 | Slide 14 1MRG003731

Plant Structure, basics

Section 3

Two main sections


IED configuration structure


Contains basic functionality such as for example communication addresses and HW

Application configuration structure


Contains the configuration data configured with ACT. Synchronized with the Main Application structure configured with ACT.

SA-T Training October 20, 2010 | Slide 15 1MRG003731

License update Tool

Section 3

Synchronizes PCM600 IED object with physical IED capabilities when it comes to;

Function options Hardware options

SA-T Training October 20, 2010 | Slide 16 1MRG003731

Technical Key (not applicable for 670 series)


Section 3

Is used for security reasons, more difficult to communicate with the wrong IED since the technical key at IED object in PCM600 and in physical IED must match. Unique identifier for each object in the Plant Structure

Is set automatically by PCM600 Can be modified by the user

To synchronize PCM600 and IED technical key, use the Set Technical Key Tool To change the technical key in PCM600 only, go to object properties for the IED object

SA-T Training October 20, 2010 | Slide 17 1MRG003731

Set Technical Key

Section 3

Technical key options


Use IED Technical key Use PCM600 Technical key User-defined Technical key

No special characters Max length 13 characters No numbers in the beginning

Note that changing the Technical key might have an impact on the IEC61850 configuration in your system

SA-T Training October 20, 2010 | Slide 18 1MRG003731

Export IED object


Section 3

Purpose: Make backup of and reuse a configured IED Contains all configured data for the IED

Application Configuration Signal Matrix Parameter Setting Graphical Display Communication Management (DNP) SCL information Hardware configuration

File extension is .pcmi

SA-T Training October 20, 2010 | Slide 19 1MRG003731

Import IED object

Section 3

Purpose: To reuse a previously configured IED object (pcmi file) Import of pcmi files can be made at the Bay level object in PCM600

SA-T Training October 20, 2010 | Slide 20 1MRG003731

Create Template

Section 3

Purpose: To reuse a configured IED


In a pre-defined place For quick access

Creation of template

Right click IED object Creates a .pcmt file Ends up in PCMDatabases\Templates

Contains all configured data


Same contents as the pcmi file

SA-T Training October 20, 2010 | Slide 21 1MRG003731

Create new IED object from Template


Section 3

Purpose: To reuse a configured IED Initiated from the Bay level object

New->Create from Template

Templates structured based on IED type

SA-T Training October 20, 2010 | Slide 22 1MRG003731

IEC 61850 configuration SCD

Section 3

SCD file

Substations Configuration Description

Contents

SCL information for all IEDs within the substation

Export/Import of SCD file


Done at Substation level SCL engineering done outside PCM600, export/import functionality needed.

Note! When importing SCL files to PCM600, be sure to import an SCL file that correlates with the PCM600 project or you might loose data
SA-T Training October 20, 2010 | Slide 23 1MRG003731

IEC 61850 configuration ICD

Section 3

ICD file

IED Capability Description

Contents

All thats configured in the IED before the system configuration No SA Section No Communication section IEDName = TEMPLATE

Usage

System engineering

Merging to an SCD file

Export/Import of ICD file


At IED level

SA-T Training October 20, 2010 | Slide 24 1MRG003731

IEC 61850 configuration CID


Section 3

CID file

Configured IED Description

Contents

Extract of the SCD file SCL information for one specific IED

Export/Import of ICD file


At IED level

SA-T Training October 20, 2010 | Slide 25 1MRG003731

Report Parameters

Section 3

Footer information for printouts


Application configuration Local display, Graphical display editor Parameter settings Communication management

SA-T Training October 20, 2010 | Slide 26 1MRG003731

Hardware Configuration

Section 3

Possible to manually configure HW/slot positions


This information is already available if you have created the IED object in online mode

Select correct card type in correct slot position

SA-T Training October 20, 2010 | Slide 27 1MRG003731

Hardware Configuration

Section 3

Compare configuration

Reads hardware configuration from the IED and compares with the HW configuration made in PCM600 Make sure that the HW configuration matches with your physical IED before you do any other configuration e.g. with ACT or SMT otherwise you might need to spend time on reconfiguration.

SA-T Training October 20, 2010 | Slide 28 1MRG003731

Hardware Configuration, parameterization

Section 3

Parameter Setting

Short-cut to parameters/settings for the HW when HW tool is open Select HW module from hardware configuration list

Press Parameter Setting button in toolbar menu that will issue the PST Only change of parameters possible when opening PST from the HW tool. Read/Write with the IED done from ordinary PST, e.g. open PST from the Plant Structure.

SA-T Training October 20, 2010 | Slide 29 1MRG003731

Time for exercise! Ex 2

Section 3

SA-T Training October 20, 2010 | Slide 30 1MRG003731

Section 3

SA-T Training October 20, 2010 | Slide 31 1MRG003731