technical data
ERHQ011-016AA
Altherma

Altherma

Altherma

Daikins unique position as a manufacturer of air conditioning equipment, compressors and refrigerants has led to its close involvement in environmental issues. For several years Daikin has had the intention to become a leader in the provision of products that have limited impact on the environment. This challenge demands the eco design and development of a wide range of products and an energy management system, resulting in energy conservation and a reduction of waste.

Het ISO14001 assures an effective environmental management system in order to help protect human health and the environment from potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment.

Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product.

The present publication is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this publication to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein. Specifications are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, In the broadest sense, arising from or related to the use and/or interpretation of this publication. All content is copyrighted by Daikin Europe N.V..

Daikin units comply with the European regulations that guarantee the safety of the product.

Naamloze Vennootschap Zandvoordestraat 300 B-8400 Ostend, Belgium www.daikin.eu BTW: BE 0412 120 336 RPR Oostende

Daikin Europe N.V. participates in the Eurovent Certification Programme for Air Conditioners (AC), Liquid Chilling Packages (LCP) and Fan Coil Units (FC); the certified data of certified models are listed in the Eurovent Directory.

EEDEN0 8 - 7 2 0

EEDEN08-720 - 06/2008 Printed in Belgium by Goekint Graphics Copyright Daikin

EEDEN08-720

technical data
ERHQ011-016AA
Altherma

Altherma

Outdoor units ERHQ011-016AA

TABLE OF CONTENTS ERHQ011-016AA

1 2

Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6 6 8

Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Cooling capacity tables Heating capacity tables
.............................................. 9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 11


Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11 12

5 6

Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14


Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
14 15

Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Sound pressure spectrum quiet mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
16 17 18

8 9

Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Service space

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 19

Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Altherma Outdoor units

Outdoor units ERHQ011-016AA

1
A iA n6 1u 0 a - r m 1 o r 1 o e 0 dh Q t H ulR OEA

Features
Cost effective alternative to a fossil fuel boiler Low energy bills and low CO2 emissions

Easy to install Total solution for year round comfort

1
1

Altherma Outdoor units

Outdoor units ERHQ011-016AA

Specifications

2-1 NOMINAL CAPACITY AND NOMINAL INPUT


For combination Indoor Units indoor units + outdoor units Condition 1 Heating capacity Nominal Heating PI COP Nominal Capacity Heating PI COP For combination Indoor Units indoor units + outdoor units Condition 1 Heating capacity Nominal Cooling capacity Nominal Heating PI Cooling PI COP EER Nominal Capacity Nominal Nominal Nominal Nominal kW kW kW kW kW kW kW kW Nominal Nominal kW kW Nominal Nominal kW kW

ERHQ011AA

ERHQ014AA

ERHQ016AA

3 1
2

EKHBH016AB

11.2 2.46 4.55 10.3 3.06 3.37

14.0 3.17 4.42 13.1 3.88 3.38 EKHBX016AB

16.0 3.83 4.18 15.2 4.66 3.26

Heating capacity Nominal

11.2 13.9 2.46 3.79 4.55 3.67 10.3 10.0 3.06 3.60 3.37 2.78

14.0 17.3 3.17 5.78 4.42 2.99 13.1 12.5 3.88 5.29 3.38 2.36

16.0 17.8 3.83 6.77 4.18 2.63 15.2 13.1 4.66 5.95 3.26 2.20

Heating capacity Nominal Cooling capacity Nominal Heating PI Cooling PI COP EER Nominal Nominal Nominal Nominal

Notes

Condition 1: cooling Ta 35C - LWE 18C - heating Ta DB/WB 7C/6C - LWC 35C ( DT = 5C ) Condition 2: cooling Ta 35C - LWE 7C ( DT = 5C ) - heating Ta DB/WB 7C/6C - LWC 45C ( DT = 5C )

2-2
Casing

TECHNICAL SPECIFICATIONS
Colour Material Unit Height Width Depth Packing Height Width Depth mm mm mm mm mm mm kg kg

ERHQ011AA

ERHQ014AA

ERHQ016AA

Ivory white Painted galvanised steel plate 1,170 900 320 980 420 103 114 900 320 1,349 980 420 103 114 EPS Carton Wood PP (Straps) 980 420 103 114 900 320

Dimensions

Weight Packing

Unit Packed Unit Material

Weight Heat Exchanger Dimensions Length Nr of Rows Fin Pitch

kg mm mm

11 857 2 1.4 6 0.98 52

11 857 2 1.4 6 0.98 52 Hi-XSS(8) WF fin Anti-corrosion treatment (PE) Propeller

11 857 2 1.4 6 0.98 52

Nr of Passes Face Area m Nr of Stages Tube type Fin Fan Type Quantity Air Flow Rate Heating (nominal at 230V) Cooling High High m/min m/min Type Treatment

2 90 96

2 90 100

2 90 97

Altherma Outdoor units

Outdoor units ERHQ011-016AA

2
2-2
Fan

Specifications
TECHNICAL SPECIFICATIONS
Discharge direction Motor Quantity Model Steps Heating Cooling Output Drive rpm rpm W 2 8 760 800 70 1 Model Type Motor Output W
ERHQ011AA ERHQ014AA ERHQ016AA

Horizontal 2 Brushless DC motor 8 760 850 70 Direct drive 1 JT100G-VD Hermetically sealed scroll compressor 2,200 Inverter driven 33 -20 35 10 46 -20 43 64 49 64 50 42 45 33 -20 35 10 46 -20 43 64 51 66 52 42 45 R-410A kg 3.7 1 l 1.0 1 mm 1 mm 3 mm m 26 5 75 95 30 30 3.7 Expansion valve(electronic type) 1 Daphne FVC68D 1.0 1 Flare connection 9,52 1 Flare connection 15,9 3 Hole 26 5 75 95 30 See installation manual outdoor unit 4PW37976-1B 30 Both liquid and gas pipes 30 26 5 75 95 30 3 1 1.0 1 1 3.7 33 -20 35 10 46 -20 43 66 53 69 54 43 46 1 8 760 830 70 2

1
2

Motor

Speed (nominal) Motor Quantity Motor

Fan Compressor

Starting Method Crankcase W Heater Operation Range Heating Cooling Sanitary water Sound Level (nominal) Heating Min Max Min Max Min Max Sound Power Sound Pressure Cooling Sound Power Sound Pressure Sound Level (Night quiet) Heating Cooling Refrigerant Type Charge Control Nr of Circuits Refrigerant Oil Piping connections Type Charged Volume Liquid (OD) Quantity Type Diameter (OD) Gas Quantity Type Diameter (OD) Drain Quantity Type Diameter (OD) Piping Length Minimum Sound Pressure Sound Pressure CWB CWB CDB CDB CDB CDB dBA dBA dBA dBA dBA dBA

Maximum m Equivalent m Chargeless m Additional Refrigerant Charge kg/m Installation Maximum m height difference Heat Insulation

Altherma Outdoor units

Outdoor units ERHQ011-016AA

2
2-2

Specifications
TECHNICAL SPECIFICATIONS
ERHQ011AA ERHQ014AA ERHQ016AA

Defrost Method Defrost Control Capacity Control Method Safety Devices

Pressure equalising Sensor for outdoor heat exchanger temperature Inverter controlled Fan motor thermal protector Fuse High pressure switch

3 1
2

Standard Accessories

Item Quantity Item Quantity 1 2

Tie-wraps 2 Installation manual 1 1 The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing for more information. Down to 3m with recharging of the outdoor unit. Refer to the installation manual of the outdoor unit. 2

Notes

2-3

ELECTRICAL SPECIFICATIONS
Name Phase Frequency Voltage Voltage range Minimum Hz V V kVa A A Maximum V

ERHQ011AA

ERHQ014AA

ERHQ016AA

Power Supply

V3 1~ 50 230 50 230 -10% +10% Equipment complying with EN/IEC 61000-S-12 (1) 22.8 32 27.4 32 See installation manual outdoor unit 4PW37976-1B See installation manual outdoor unit 4PW37976-1B Outdoor unit only (1) European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A smaller than or equal to 75A per phase. 31.9 32 50 230

Current

Minimum Ssc value Maximum Cooling running Current Recomended fuses

Wiring connections

For Power Supply

Remark

For connection Remark with indoor Power Supply Intake Notes

Altherma Outdoor units

Outdoor units ERHQ011-016AA

3
3-1

Capacity tables
Cooling capacity tables
Tamb (C) LWE (C) 7 10 13 15 18 22 7 10 13 15 18 22 7 10 13 15 18 22 20 CC 11.7 12.9 14.1 14.9 16.2 18.0 14.5 16.0 17.6 18.6 20.2 22.5 15.3 16.9 18.5 19.6 21.0 23.3 PI 2.56 2.58 2.59 2.60 2.61 2.62 3.85 3.94 4.02 4.08 4.17 4.29 4.37 4.48 4.60 4.68 4.97 5.21 CC 11.2 12.3 13.4 14.2 15.5 17.2 13.9 15.3 16.8 17.8 19.3 21.5 14.7 16.2 17.7 18.7 20.0 22.2 25 PI 2.86 2.89 2.92 2.93 2.96 2.99 4.27 4.37 4.47 4.54 4.65 4.80 4.84 4.97 5.10 5.19 5.52 5.79 CC 10.6 11.6 12.8 13.5 14.7 16.4 13.2 14.6 15.9 16.9 18.4 20.4 13.9 15.3 16.7 17.7 18.9 21.0 30 PI 3.21 3.25 3.29 3.31 3.35 3.40 4.75 4.86 4.98 5.06 5.18 5.36 5.37 5.51 5.66 5.76 6.12 6.42 CC 10.0 11.0 12.1 12.8 13.9 15.5 12.5 13.7 15.0 15.9 17.3 19.3 13.1 14.4 15.7 16.6 17.8 19.7 35 PI 3.60 3.65 3.70 3.73 3.79 3.86 5.29 5.42 5.55 5.64 5.78 5.98 5.95 6.11 6.27 6.38 6.77 7.10 CC 9.39 10.3 11.3 12.0 13.1 14.7 11.7 12.9 14.1 14.9 16.2 17.0 12.2 13.3 14.6 15.4 16.4 17.0 40 PI 4.03 4.09 4.15 4.20 4.26 4.35 5.90 6.04 6.18 6.28 6.44 5.33 6.59 6.75 6.93 7.04 6.69 5.33 CC 8.75 9.65 10.6 11.3 12.3 13.3 11.1 11.2 11.9 12.2 12.9 13.3 11.1 11.2 11.9 12.2 12.9 13.3 45 PI 4.50 4.58 4.65 4.70 4.78 3.93 5.92 5.46 5.04 4.79 4.42 3.93 5.92 5.46 5.04 4.79 4.42 3.93

Maximum Cooling Capacity

1
3

ERHQ11

ERHQ14

ERHQ16

3TW57752-1B

Symbols
CC PI LWE Tamb : Cooling capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW) : Leaving Water Evaporator temperature (C) : Ambient temperature (C) RH=85% 1

Conditions
Cooling capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 38C Power input Power input is total of indoor and outdoor unit, except the circulation pump; according to Eurovent rating standard 6/C/003-2006. Pump power input to be added = 90 W (according EN14511).

Note
1 For the optional model with heatertape (V38) when ambient temperature becomes lower than 4C: add power input of 95W

Altherma Outdoor units

Outdoor units ERHQ011-016AA

3
3-2
Model

Capacity tables
Heating capacity tables
LWC Tamb -20 -15 -7 -2 2 7 12 15 20 -20 -15 -7 -2 2 7 12 15 20 -20 -15 -7 -2 2 7 12 15 20 LWC Tamb -20 -15 -7 -2 2 7 12 15 20 -20 -15 -7 -2 2 7 12 15 20 -20 -15 -7 -2 2 7 12 15 20 30 HC 5.66 6.48 8.04 9.18 10.2 11.6 13.1 14.1 15.9 7.24 8.19 10.1 11.5 12.7 14.4 16.3 17.6 19.9 8.35 9.38 11.5 13.0 14.4 16.3 18.5 20.0 22.5 30 HC 5.04 5.77 6.89 7.43 8.16 11.6 13.1 14.1 15.9 6.45 7.29 8.06 9.27 10.0 14.4 16.3 17.6 19.9 7.44 8.35 8.91 10.5 11.1 16.3 18.5 20.0 22.5 PI 2.17 2.21 2.24 2.11 2.16 2.21 2.18 2.15 2.10 2.72 2.78 2.84 2.70 2.78 2.88 2.86 2.85 2.82 3.25 3.33 3.34 3.26 3.15 3.50 3.51 3.51 3.50 HC 4.88 5.56 6.63 7.16 7.86 11.2 12.7 13.6 15.4 6.35 7.13 7.84 9.00 9.71 14.0 15.9 17.1 19.3 7.39 8.30 8.77 10.3 10.9 16.0 18.1 19.5 22.0 PI 2.17 2.21 2.24 2.24 2.23 2.21 2.18 2.15 2.10 2.72 2.78 2.84 2.87 2.87 2.88 2.86 2.85 2.82 3.25 3.33 3.42 3.46 3.48 3.50 3.51 3.51 3.50 HC 5.48 6.25 7.74 8.84 9.81 11.2 12.7 13.6 15.4 7.14 8.01 9.78 11.1 12.3 14.0 15.9 17.1 19.3 8.31 9.33 11.3 12.7 14.1 16.0 18.1 19.5 22.0 35 PI 2.37 2.42 2.46 2.33 2.39 2.46 2.43 2.41 2.36 2.97 3.04 3.11 2.96 3.05 3.17 3.16 3.15 3.13 3.54 3.63 3.64 3.56 3.45 3.83 3.85 3.86 3.85 HC 4.84 5.49 6.54 7.06 7.75 10.8 12.2 13.2 14.9 6.28 6.99 7.62 8.95 9.65 13.5 15.4 16.5 18.7 7.36 8.26 8.63 10.1 10.6 15.6 17.6 19.0 21.4 35 PI 2.37 2.42 2.46 2.47 2.47 2.46 2.43 2.41 2.36 2.97 3.04 3.11 3.14 3.16 3.17 3.16 3.15 3.13 3.54 3.63 3.73 3.78 3.81 3.83 3.85 3.86 3.85 HC 5.44 6.17 7.63 8.71 9.68 10.8 12.2 13.2 14.9 7.05 7.85 9.51 11.1 12.2 13.5 15.4 16.5 18.7 8.27 9.28 11.1 12.5 13.8 15.6 17.6 19.0 21.4 40 PI 2.61 2.67 2.72 2.58 2.65 2.74 2.72 2.70 2.65 3.26 3.34 3.43 3.26 3.37 3.50 3.50 3.50 3.48 3.86 3.98 4.00 3.91 3.79 4.22 4.24 4.25 4.25 HC 6.43 6.94 7.63 10.3 11.8 12.7 14.4 7.42 8.65 9.32 13.1 14.9 16.0 18.1 8.49 9.91 10.4 15.2 17.2 18.5 20.8 40 PI 2.61 2.67 2.72 2.74 2.74 2.74 2.72 2.70 2.65 3.26 3.34 3.43 3.47 3.48 3.50 3.50 3.50 3.48 3.89 3.98 4.10 4.15 4.19 4.22 4.24 4.25 4.25 HC 7.50 8.57 9.52 10.3 11.8 12.7 14.4 9.25 10.7 11.8 13.1 14.9 16.0 18.1 10.9 12.2 13.5 15.2 17.2 18.5 20.8 45 PI 3.02 2.87 2.96 3.06 3.04 3.03 2.99 3.79 3.52 3.64 3.88 3.89 3.89 3.87 4.41 4.31 4.18 4.66 4.69 4.69 4.70 HC 45 PI 3.02 3.05 3.06 3.06 3.04 3.03 2.99 3.79 3.74 3.76 3.88 3.89 3.89 3.87 4.52 4.58 4.62 4.66 4.69 4.69 4.70 HC 50 PI HC 55 PI

Maximum Heating Capacity (Peak values)

3 1
3.77 3.82 3.81 3.81 3.78

ERHQ11

8.18 9.10 9.94 11.3 12.2 13.8

3.36 3.38 3.42 3.41 3.40 3.37

8.72 9.53 10.9 11.7 13.3

ERHQ14

10.4 11.4 12.7 14.4 15.5 17.5

4.14 4.17 4.30 4.32 4.32 4.31

11.1 12.3 13.9 15.0 17.0

4.62 4.77 4.79 4.80 4.80

ERHQ16

12.0 13.1 14.8 16.7 18.0 20.3 50

5.06 5.11 5.15 5.18 5.20 5.21

11.9 13.4 15.1 16.6 18.7 55

5.35 5.40 5.44 5.75 5.77

Maximum Heating Capacity (integrated values*)

Model

PI

HC

PI

ERHQ11

6.63 7.29 9.94 11.3 12.2 13.8

3.17 3.26 3.42 3.41 3.40 3.37

6.99 9.53 10.9 11.7 13.3

3.64 3.82 3.81 3.81 3.78

ERHQ14

8.38 9.02 12.7 14.4 15.5 17.5

3.90 4.03 4.30 4.32 4.32 4.31

8.73 12.3 13.9 15.0 17.0

4.47 4.77 4.79 4.80 4.80

ERHQ16

9.71 10.2 14.8 16.7 18.0 20.3

4.77 4.62 5.15 5.18 5.20 5.21

9.19 13.4 15.1 16.6 18.7

4.84 5.40 5.44 5.75 5.77

3TW57752-1B

Symbols
HC PI LWC Tamb : Heating capacity at maximum operating frequency, measured acc. Eurovent 6/C/003-2006 (kW) : Power input (kW), measured acc. Eurovent 6/C/003-2006 (kW) : Leaving Water Condensor temperature (C) : Ambient temperature (C) RH=85% 1

Conditions
Heating capacity Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for chilled water range Dt = 38C Power input Power input is total of indoor and outdoor unit, except the circulation pump; according to Eurovent rating standard 6/C/003-2006. Pump power input to be added = 90 W (according EN14511).

Note
1 For the optional model with heatertape (V38) when ambient temperature becomes lower than 4C: add power input of 95W

Altherma Outdoor units

10

Outdoor units ERHQ011-016AA

4
4-1

Dimensional drawing & centre of gravity


Dimensional drawing

ERHQ011-016

1
4

Hole for anchor bolt 4-M12

1 2 3 4 5 6 7 8

Gas pipe connection 15.9 flare Liquid pipe connection 9.5 flare Service port (in the unit) Grounding terminal M5 (in switch box) Refrigerant piping intake Power supply wiring intake (knock out hole 34) control wiring intake (knock out hole 27) Drain outlet

3TW57764-1

11

Altherma Outdoor units

Outdoor units ERHQ011-016AA

4
4-2

Dimensional drawing & centre of gravity


Centre of gravity

ERHQ011-016

3 1
4

4TW57919-5

Altherma Outdoor units

12

Outdoor units ERHQ011-016AA

5
ERHQ

Piping diagram

1
5

Electronic expansion valve

Filter

Filter

Heat exchanger

4-Way-Valve

High Pressure Low Pressure Switch Sensor

EKHB 016 Field Piping 9.5 C 1220T-0 Compressor Field Piping 15.9 C 1220T-0 Accumulator Indoor Unit Stop Valve (With Service Port 5/16 Flare) Check Valve Flare Conn. Screw Conn. Flange Conn. Pinched Pipe Spinned Pipe Outdoor Unit Service Port 5/16

Heating Cooling

3TW57765-1

13

Altherma Outdoor units

Outdoor units ERHQ011-016AA

6
6-1

Wiring diagram
Wiring diagram

ERHQ011-016AAV3
Option EKBPHT16Y Only for *RHQ01*AAV3(7)

3
Indoor A1P A2P A3P A4P BS1BS4 C1C4 DS1 E1H E1HC F1U, F3U, F4U F6U H1P7P (A2P) HAP (A1P) K1R K4R K10R K11R L1R M1C M1F M2F PS Q1DI R1 R2 R1T R2T R3T R4T R5T R6T RC R10T S1NPH S1PH TC V1R V2R, V3R V1T X1M Y1E Y1S Z1CZ3C Z1FZ4F Optional Connector X1Y Printed circuit board (Main) Printed circuit board (INV) Printed circuit board (Noise filter) Printed circuit board Push button switch Capacitor DIP switch Electrical heatertape (fuse: 5A/250V) Crankcase heater Fuse (T 6.3A/250V) Fuse (T 5.0A/250V) Light emitting diode (service monitor green) Light emitting diode (service monitor green) Magnetic relay (Y1S) Magnetic relay (E1HC) Magnetic relay Magnetic relay Reactor Motor (Compressor) Motor (Fan) (upper) Motor (Fan) (lower) Switching power supply Field earth leakage breaker (300mA) Resistor Resistor Thermistor (Air) Thermistor (Discharge) Thermistor (Suction) Thermistor (Heat exchanger) Thermistor (heat exchanger middle) Thermistor (Liquid) Signal receiver circuit Thermistor (Fin) Pressure sensor Pressure switch (High) Signal transmission circuit Power module Diode module IGBT Terminal strip for power source Electronic expansion valve Solenoid valve (4 way valve) Noise filter (ferrity core) Noise filter Connector

Only for *RHQ01*AAV38

1
6

Outdoor

(Note 4)

HAP

Position of compressor terminal Wire entrance

El. comp. Assy (Position of elements)

Notes: 1 This wiring diagram only applies to the outdoor unit 2 L: Live N:Neutral g: Field wiring 3 D : Terminal strip F : Connector T : Connection R : Protective earth (screw) : Relay connector p : Noiseless earth G : Terminal 4 Refer to the option manual, for connecting wiring to x6A. 5 Refer to the Wiring diagram sticker (on back of front plate) on how to use BS1 BS4 and DS1 switch. 6 Do not operate the unit by short-circuiting protection device S1PH 7 Colors: BLK: black, RED: red, BLU: blue, WHT: white, YLW: yellow, ORG: orange, BRN: brown, GRN: green 8 Confirm the method of setting the selector switches by service. When the unit is shipped by factory all switches are set to be off. 9 Option Wiring dependent on model

(Back)

(Front)

2TW57986-1A

Altherma Outdoor units

14

Outdoor units ERHQ011-016AA

6
6-2

Wiring diagram
External connection diagram
ELECTRICAL CONNECTION DIAGRAM ALTHERMA (011/014/016 CLASS) Standard parts

1
6

Power supply OUTDOOR UNIT


unit power supply: 230V + earth backup heater power supply (3/6/9kW): 400V or 230V + earth 3 core X1M:L-N-earth

Optional power supply: backup heater power supply (3kW): 400V or 230V + earth

X1M:1-2-3 earth

Applicable for the following models: OUTDOOR UNIT: ERHQ011/014/016AAV3 INDOOR UNIT: EKHBH/X016AA3V3 EKHBH/X016AA6V3 EKHBH/X016AA6W1 EKHBH/X016AA6T1 EKHBH/X016AA9W1 EKHBH/X016AA9T1 For more details please check unit wiring diagram

<10m:4Gx1.5 >10m:4Gx1.5 4 core

3 or 4 core

Optional parts SANITARY TANK


2way valve Q3L-Q1T CLIXON THERMOSTAT 2-WAY VALVE

3 core

X1M:1-2-3 earth X1M:L1-L2-L3-earth X3M:L-N-earth

2 core 2x0.75 X5M 230V


ONLY FOR EKSWWU *V3

Field supply
X7M F2B

Power supply booster heater

4 core 230V 2 core 230V 2 or 3 core 230V

Room thermostat
A3P

X6M

5 core 5Gx2.5 230V or 400V

X4M:1-2 earth

X2M:1-2-3-4

2way valve
M25 (EKHBX units) for cooling mode

Q2L - Clixon booster heater

X2M:13-14

NO valve: X2M:6-7 NC valve: X2M:5-7 spring return: X2M:9-10 SPST: X2M: 8-9-10

R5T- Thermistor water temperature

2 core X9A (PCB A1P) signal Thermistor cable NOTE: min. distance to power cable = 3 cm

3way valve
M3S (When EKSWW is installed) selection sanitary-floorheating

INDOOR UNIT
user interface

3TW57746-7

EKHB-A
Standard parts Power supply Outdoor unit
Unit power supply: 230V + earth Backup heater power supply (3/6/9kW): 400V or 230V + earth 3 core X1M:L-N-Earth

For more details please check unit wiring diagram

Optional power supply Booster heater power supply (3kW): 400V or 230V + earth

X2M:1-2-3-Earth

4 core

3 or 4 core

3 core

Optional parts

Field supply
X1M:9-10-11-Earth

Sanitary tank Room thermostat


Power supply booster heater 4 core 5 core X1M:7-8-Earth A3P (optional)

Q2L - Clixon booster heater

230V or 400V

NO valve: NC valve:

2 core

2 way valve
M2S (EKHBX Units) for cooling mode

R5T - Thermistor water temperature

2 core Signal Thermistor cable Note: min. distance to power cable = 3cm

2 core

3 way valve
M3S (when EKSWW is installed) selection sanitary-floorheating

Indoor unit
User interface

3TW56719-6

15

Altherma Outdoor units

Outdoor units ERHQ011-016AA

7
7-1

Sound data
Sound pressure spectrum
ERHQ011AAV3 COOLING ERHQ014AAV3 COOLING ERHQ016AAV3 COOLING ERHQ011-016

3 1
7

Sound pressure level (dB)

Sound pressure level (dB)

Octave band center frequency (Hz)

Octave band center frequency (Hz)

Sound pressure level (dB)

Octave band center frequency (Hz) 3TW57767-1A

NOTES
1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room). dBA = A-Weighted sound pressure level. (A-scale according to IEC) Reference acoustic pressure 0dB = 20Pa. If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections.

Measuring location (Discharge side)

ERHQ011-016 ERHQ011AAV3 HEATING ERHQ014AAV3 HEATING ERHQ016AAV3 HEATING

Sound pressure level (dB)

Sound pressure level (dB)

Octave band center frequency (Hz)

Octave band center frequency (Hz)

Sound pressure level (dB)

Octave band center frequency (Hz) 3TW57767-2A

NOTES
1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room). dBA = A-Weighted sound pressure level. (A-scale according to IEC) Reference acoustic pressure 0dB = 20Pa. If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections.

Measuring location (Discharge side)

Altherma Outdoor units

16

Outdoor units ERHQ011-016AA

7
7-2

Sound data
Sound pressure spectrum quiet mode
ERHQ011AAV3 COOLING ERHQ014AAV3 COOLING ERHQ016AAV3 COOLING ERHQ011-016

1
7
Sound pressure level (dB) Sound pressure level (dB) Sound pressure level (dB) Octave band center frequency (Hz)

Octave band center frequency (Hz)

Octave band center frequency (Hz) 3TW57767-3

NOTES
1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room). dBA = A-Weighted sound pressure level. (A-scale according to IEC) Reference acoustic pressure 0dB = 20Pa. If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections.

Measuring location (Discharge side)

ERHQ011-016 ERHQ011AAV3 HEATING ERHQ014AAV3 HEATING ERHQ016AAV3 HEATING

Sound pressure level (dB)

Sound pressure level (dB)

Octave band center frequency (Hz)

Octave band center frequency (Hz)

Sound pressure level (dB)

Octave band center frequency (Hz) 3TW57767-4

NOTES
1 2 3 4 Data is valid at free field condition (measured in a semi-anachoic room). dBA = A-Weighted sound pressure level. (A-scale according to IEC) Reference acoustic pressure 0dB = 20Pa. If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections.

Measuring location (Discharge side)

17

Altherma Outdoor units

Outdoor units ERHQ011-016AA

8
8-1

Installation
Service space

ERHQ011-016 A. Non stacked installation


Legend Unit: mm
Suction side obstacle Discharge side obstacle Left side obstacle Right side obstacle Top side obstacle Obstacle is present

3 1
8

In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed.

In these cases, only 2 units can be installed.

This situation is not allowed. Figures between ( ) indicate the dimensions only for the 100-125-140 class models.

B. Stacked installation
1. Obstacles exist in front of the outlet side 2. Obstacles exist in front of the air inlet

Do not stack more than one unit. About 100mm is required as the dimension for laying the upper outdoor units drain pipe. Get the portion A sealed so that air from the outlet does not bypass.

C. Multiple-row installation
1. Installation of one unit per row
2. Installing multiple units (2 units or more) in lateral connection per row

Relation of dimensions of H, A, and L are shown in the table below.


LH H<L L 0 < L 1/2 H 1/2 H < L Installation impossible A 150 (250) 200 (300)

3TW26739-4

Altherma Outdoor units

18

Outdoor units ERHQ011-016AA

Operation range

ERHQ011-016AAV3
Outdoor temp. (CDB)

1
9
Cooling mode

Leaving evaporator Water temperature (C)

Outdoor temp. (CDB)

No heat pump operation, back up heater only


Heating mode

leaving condensor Water temperature (C)

Outdoor temp. (CDB)

Domestic hot water mode

Booster heater operation only

Water temperature domestic hot water tank (C)

4TW57753-1A

19

Altherma Outdoor units