You are on page 1of 4

1/31/2014

Installation Instructions - General

Installation Instructions - General


Operational Description - Centrifugal Separator As the air, gas, or steam flow enters the separator, it is forced through a centrifugal element. There the heavier moisture droplets and dry particles are centrifuged to the outer periphery of the flow and are impinged against the vessel's wall. The flow forms a helical pattern as its path extends to the drain side of the separator. The flow then reverses by way of a center vortex. This center return vortex is a danger point where re-entrainment is most likely. The exclusive Wright-Austin Vortex Containment Plate "VCP" combats reentrainment by providing a quiet zone where the entrainment is permitted to fall out of the flow. This arrangement effectively segregates the removed entrainment from the outlet flow. Maintenance and Spare Parts Wright-Austin separators have no moving parts. All components are either bolted or welded into place. Therefore parts lists are not available. The seprators are bolted, threaded, or welded into the lines. They are self-cleaning, and do not need lubrication or maintenance. For this reason, lubricating, operating and maintenance manuals are not available. Performance Wright-Austin separators, when properly sized, installed, and drained, will remove 99% of all liquid and solid entrainment where particle size exceeds 10 microns. Caution All threaded connections not being used must be plugged at time of installation. For Positive Drainage of Separator Install trap a minimum of 6" below separator drain. For every inch of horizontal piping to trap, add one inch to the vertical piping. Do not reduce separator drain size except at trap inlet. Never (with one exception) allow the top of the trap to extend above separator drain connection. Add 1/4" balance (vent) line where shown for air and other gas (not steam) installations.

Air and Gas (not steam) Service

http://swtnst.co.kr/produc/html/wa%20html/558.htm

1/4

1/31/2014

Installation Instructions - General

No. 90-AC 2" Type T cast iron separator 4" Type T cast iron separator removing removing moisture from a moisture and oil from a compressed air compressed air distribution line. line. No. 230-AC trap to drain. A sediment 3/4" No. 90-AC float type trap pocket, as shown, should be provided for installed below separator to drain. air and gas service (instead of a strainer). This is the only type air and gas drain trap installation that does not require a balance (vent) line.

Prime trap with water before turning air pressure on.

http://swtnst.co.kr/produc/html/wa%20html/558.htm

2/4

1/31/2014

Installation Instructions - General

3/4" No. 90-AC SISO (side inlet, side outlet) float trap installed on air receiving tank where floor clearance is at a minimum

Steam Service

Above: 2" Type T separator installed in 300 PSI steam line to turbine. 1-1/4" "Y" strainer and 3/4" No. 71 steam trap to drain. Below: 4" Type T separator removing moisture from a steam header at 125 PSI. One inch "Y" strainer and 510-C combination bucket and thermostatic trap to drain.

http://swtnst.co.kr/produc/html/wa%20html/558.htm

3/4

1/31/2014

Installation Instructions - General

http://swtnst.co.kr/produc/html/wa%20html/558.htm

4/4

You might also like