PetroChina International Jabung Ltd.

695-SWG/MCC-102A/B
No. Equipment No. Feeder

HV/MV SWGR / MCC SC Amps


PANEL NAME DWG No. Load Capacity CB/PF/MC CB

CALCULATION PROTECTIVE DEVICE COORDINATION STUDY

4.16 kV
Item No.

13.5 kA
SENSOR & RATIO SEPAM (ANSI CODE) I/U or OTHER SETTING RANGE TIME CURVE ANGLE INITIAL SETTING Value absolute Basic Calculation / Remarks Value relative Time UNIT TS REMARKS REV.

BCD3-000-46-CAL-4-110-00 Rev.1

1/2

217363058.xlsx.ms_office/695-SWG-102

PetroChina International Jabung Ltd.


695-SWG/MCC-102A/B
No. Equipment No. Feeder

HV/MV SWGR / MCC SC Amps


PANEL NAME DWG No. Load Capacity CB/PF/MC CB

CALCULATION PROTECTIVE DEVICE COORDINATION STUDY

4.16 kV
Item No.

13.5 kA
SENSOR & RATIO SEPAM (ANSI CODE) I/U or OTHER SEPAM 1000+ M41 50 51 50N 51N 67N 27 46 SETTING RANGE TIME CURVE ANGLE INITIAL SETTING Value absolute Basic Calculation / Remarks Value relative Time UNIT TS Modbus slave number 06 19200bps, None parity, Synchronization by network, Remote control mode: direct Not active 71x1.07/1.2=63.3, 63.3/75=0.844 Not active 1 Not active REMARKS REV.

695-MCC-102A

102A-42F03

615-KM-101

COMBUSTION AIR BLOWER A Z-20028-02-308-1-30 Starting Current Starting Time

373 500 71 451 6

kW HP A A S

PF 200A

CT:75/5A 5VA 5P10

1 1 1

0.1 to 24In 0.1 to 2.4In 20A rating : 2A to 300A 20A rating : 2A to 20A 20A rating : 2A to 300A 20A rating : 2A to 20A 5 to 100 % Un

0.05s to 300s 0.1 to 12.5 s at 10 Is 0.05s to 300s 0.1 to 12.5 s at 10 Iso 0.05s to 300s 0.1 to 12.5 s at 10 Iso 0.05s to 300s

DT SIT DT IDMT DT IDMT DT DT 0

63 30A Type 1 Direction: Line

0.844 30A 30A 80% Un 40%Ib 20%Ib 100% 110% 95%

12.5 0.15 0.15 3s 0.5s 15s 35 min 90 min -

----UNIT 1 UNIT 1 ----UNIT 1 ----UNIT 1 UNIT 1 UNIT 2

----TS002 TS005 ----TS035 ----TS019 TS012 TS013

30A 3.3kV

49

51L/R

66

0. 1 to 5 Ib 0.1 to 300 s 0. 1 to 5 Ib 0.1 to 300 s 0 to 300% of rated thermal Heat rise alarm set Es1: capacity Heat rise trip set Es2: 0 to 300% of rated thermal capacity Heat rise time T1: 1 to 600min Cooling time T2: 1 to 600min Initial heat rise (Eso) : 0 to 100 % accounting for negative sequence component: 0, 2.25, 4.5, 9 Heat rise alarm set Es1: 0 to 300% of rated thermal capacity Heat rise trip set Es2: 0 to 300% of rated thermal capacity Heat rise time T1: 1 to 600min Cooling time T2: 1 to 600min Initial heat rise (Eso) : 0 to 100 % accounting for negative sequence component: 0, 2.25, 4.5, 9 Change of operating rate by threshold Is: 0.2In to 2.6In excessive starting time ST: 50 % to 500 % of Ib 500 ms to 300 s Locked rotor time LT: 50 ms to 300 s Locked rotor time on start LTS: 50 ms to 300 s periode of time1 to 6 hour Total number of starts(Nt) allowed per period of time :(p) setting range :1 to 60 number of consecutive hot starts (Nh) setting range :1 to Nt number of consecutive cold starts (Nc) setting range :1 to Nt delay between stop/start : setting range : 0 to 90 min(0=no delay)

high threshold Low threshold For Rate 1 For Rate 1 For Rate 1 For Rate 1 For Rate 1

Ib = 67.6A

Trip Trip

1 1 1

Tripping Set point

TS010

1 1 1 1

For Rate 1 For Rate 2 For Rate 2 For Rate 2 For Rate 2 For Rate 2

9 100% 110% 95%

90 min 90 min Tripping Set point TS010

1 1 1 1 1 1

For Rate 2 180A -

9 2.4In 250%Ib 1hour

15s 8s 15s Excessive Start time Locked rotor Locked rotor on start TS16 TS14 TS15

250%Ib / 75A = 71A x 250% / 75A = 2.4In Allowed locked rotor time at Un (Hot) from motor data LT=(Locked rotor on start)/2 Allowed locked rotor time at Un (Hot) from motor data Start inhibit. Not trip 5 times at motor running condition during 6 HRs / 3 times at motor stopping condition during 6 HRs

1 1 1 1 1 1 1

Protection 66

TS32

2 10min

Restart inhibit while motor is rotating by inertia.

1 1

BCD3-000-46-CAL-4-110-00 Rev.1

2/2

217363058.xlsx.ms_office/695-SWG-102