Midea Commercial Air Conditioner

Malfunction Handbook
May 1, 2008

Customer Service Philosophy of Midea Air Conditioner

Service Target: 100% Customer Satisfaction Service Standard: 100% Earnestness Service Tenet: Customer First Forever

Contents I . E r r o r Indication o f M D V I n d o o r U n i t s 6 II. Error Indication of MDV Digital Scroll Central Air Conditioner8 1. Error Indication of Digital Scroll Unit D3 (D4)8 2. MDV-D540 (560, 580, 820, 840, 860) W/S-820.....................12 3. MDV-D280 (220) W/S-810....................15 III. Error Indica tion of Intellige nt Variable Frequency Ce ntral Air Co n di t i o ne r 1 8 1. Error Indication of V3 (V4, Vi) Intelligent Variable Frequency Unit18

2. MDV-J280W/S-810(811) 23 3. MDV-280W/BS................26 IV. Error Indication of MDV Home Central Air Conditioner32 1. MDV(H)-J140(120)W-510(511), MDV(H)-J160(180)W(/S)-720...32 2. MDV-D100 (120) (/S) ..35 3. Error Code List for Novel M-home Series Digital Indoor Unit. 38 4. Error Code List for Novel Home Digital Water Unit.41 5. MDVJ110 ~ MDVJ160 AC Inverter44 6. Home Central Air Conditioner with Water System Based on Frequency Conversion. .52

7. KFR-61T2W/BP or KFR-402W/BP-510T2.59 V. Error Indication of Unitary Central Air Conditioner...70 1. Error Code List of Ordinary One-to-One ...70 2. Error Code List of Novel Four-way cassette ...74

3. Error Code List of 10HP Air Cooled Cabinet Unit78 4. Error Indication of 20HP Medium Static Pressure Fan Coil Unit...79 VI. Error Indication of Digital Scroll Air Cooled Module ...92 1. Display List of Error and Protection for 60Kw Modular Air Cooled Heat Pump Unit..92 2. Display List of Error and Protection for 200KW Large Modular Air Cooled

Heat Pump Unit.96 3. Code List of Error and Protection for Wire Controller on Modular Unit.97 VII. Error Indication of Water Cooled Cabinet Unit.100 VIII. Error Indication of Screw Unit105 IX. Error Indication of Network Air Conditioner.113

I. Error Indication of MDV Indoor Units LED Flash RUN Indicator Flash, Slowly RUN Indicator Constantly On Pre-heating/Defrosting Indicator Constantly On Timing Indicator Constantly On RUN Indicator Flash, Quickly Definition of Error or Protection Standby Operation Anti-cooling or Defrosting Start up Timing Function Error in Any Temperature Sensor in Indoor Unit

Timing Indicator Flash, Quickly Pre-heating/Defrosting Indicator Flash, Quickly Alarm Indicator Flash, Quickly Alarm Indicator Flash, Slowly

Communication Error between Indoor Units and Outdoor Unit Mode Conflict Water Level Alarm Outdoor Unit Error

II. Error Indication of Midea Digital Scroll A/C 1. Error Indication of Digital Scroll Unit D3 (D4) Display Content E0 E1 E2 Definition of Error or Protection Communication Error between Outdoor Units Phase-sequence Protection Communication Error between Indoor Units and Outdoor Unit Remark Only Displayed on Principal Unit

E3 E4

T3 Tube Temperature Sensor Error T4 Ambient Temperature Sensor Error Digital Discharge Temperature Sensor Error Outdoor Address Error Mode Conflict Error (D3 R410a) Communication Error between Chips Reduction in the Number of Outdoors Only Displayed on

E5 E8 H0 H1 H2

Units H3 P1 P2 P3 Increase in the Number of Outdoor Units High-voltage Protection Low-voltage Protection Over-current Protection of Digital Scroll Compressor

Master Unit Only Displayed on Master Unit

10

P4

Over-high Discharge Temperature Protection of Compressor High Tube Temperature Protection of Outdoor Condenser Current Protection of NO.1 Fixed Compressor Current Protection of NO. 2 Fixed Compressor

P5

P7

P8

11

2. MDV-D540 (560, 580, 820, 840, 860) W/S-820 Error Indication of Outdoor Main Control Board DSP1 (Digital Tube) Display Content of Digital Tube Quantity of Indoor Unit Capability Demand of Indoor Units dF Normal Operation Defrosting Definition of Error or Protection Standby

12

P1 P2 P3 P4 P5

High-voltage Protection Low-voltage Protection Current Protection of Compressor Discharge Temperature Protection of Compressor High Temperature Protection of Outdoor Condenser Communication Error between Outdoor Units

E0

13

E1 E2 E3 E4 E5 E6 E7

Phase-sequence Error Communication Error between Indoor Units and Outdoor Unit Outdoor Tube Temperature Sensor Error Outdoor Ambient Temperature Sensor Error Discharge Temperature Sensor Error Water Level Alarm Error Inlet Temperature Sensor Error of Condenser for Master Unit

14

3. MDV-D280220W/S-810 Error Indication of Outdoor Main Control Board DSP1 (Digital Tube) Display Content of Digital Tube Capability Demand of Indoor Unit dF Definition of Error or Protection Standby Operation Defrosting

15

P1 P2 P3 P4 P5 E1

High-voltage Protection Low-voltage Protection Current Protection of Compressor Discharge Temperature Protection of Compressor High Temperature Protection of Outdoor Condenser Phase-sequence Error

16

E2 E3 E4 E5 E6

Communication Error between Indoor Units and Outdoor Unit Outdoor Tube Temperature Sensor Error Outdoor Ambient Temperature Sensor Error Discharge Temperature Sensor Error Water Level Alarm Error

17

IIIError Indication of Intelligent Variable Frequency Central Air Conditioner 1. Error Indication of V3 (V4) Intelligent Variable Frequency Unit Display Content E0 E1 E2 Definition of Error or Protection Communication Error between Outdoor Units Phase-sequence Error Communication Error between Indoor Remark Only Displayed on Master Unit

18

Units and Master Unit E3 or E4 E8 E9 H0 H1 Ambient Temperature or Tube Temperature Sensor Error Outdoor Unit Address Error

Voltage Error Communication Error between DSP and 780034 Communication Error between 9177

19

and 780034 H2 Reduction in the Number of Outdoor Units Increase in the Number of Outdoor Units Temperature Protection of Top Part of Inverter Compressor High-voltage Protection Only Displayed on Master Unit Only Displayed on Master Unit

H3

P0 P1

20

P2 P3

Low-voltage Protection Over Current Protection of Inverter Compressor Over-high DischargeTemperature Protection High Tube Temperature Protection Module Protection Current Protection of NO.1 Fixed

P4 P5 P6 P7

21

Compressor P8 Current Protection of NO.2 Fixed Compressor

22

2. MDV-J280W/S-810(811) Display Content Operating Frequency of Compressor dF P1 Definition of Error or Protection Standby Normal Operation Defrosting High-voltage Protection

23

P2 P3 P4 P5 P6 E1

Low-voltage Protection Current Protection of Compressor Discharge Temperature Protection of Compressor High Temperature Protection of Outdoor Condenser Module Protection Phase-sequence Error

24

E2 E3 E4 E5 E6

Communication Error between Indoor Units and Outdoor Unit Communication Error between outdoor PCB and Inverter Module Ambient Temperature Sensor Error Voltage Protection Water Level Alarm Error

25

3. MDV-280W/BS Spot Inspection Error Information Code 99 A0 A1 A2 18 Error Content Terminal Blocks of Wire Controller Loop of Outlet Temperature Sensor (TD1) Loop of Outlet Temperature Sensor (TD2) Loop of Inlet Temperature Sensor (TS) Loop of Outdoor Heat Exchanger Sensor (TE) Spot Inspection

26

AA B4 1C 22 E6 95 96 A6

Loop of High Pressure Sensor (Pd) Loop of Low Pressure Sensor (Ps) Interface Substrate Loop High Voltage Protection Action (Sensor Pd) Phase-sequence Error of Power Supply Communication Loop of Indoor and Outdoor Inconsistency Detection of Indoor and Outdoor Address Protection Action of Outlet Temperature (TD1)

27

bb AE A7 Ab 89

Protection Action of Outlet Temperature (TD2) Protection Action of Discharge Temperature (TD1) during Low Frequency Protection Action of Inlet Temperature Wiring Error of Pressure Sensor (Pd, Ps) The capability of indoor unit connected is transfinite.

28

0b 0c 11 12 93 94 95

Spot Inspection Error Information of Indoor Unit Drainage System of Suction Pump Loop of Room Temperature Sensor (TA) Motor Loop Loop of Indoor Substrate Loop of Indoor Heat Exchanger (Tc1) Loop of Indoor Heat Exchanger (Tc2) Outdoor Unit Communication Loop

29

97 98 9A b5 b6 b9

Communication Loop of Centralized Management Address Setting of Centralized Management Wiring Error of Indoor Equipment, Connection Error

External Chain Display Indoor Sensor Loop

30

Spot Inspection Error Information of Frequency Converter Plate Spot Inspection Information Over-current Protection of Frequency Converter Compressor System Loop Current Detection Loop High-voltage Switch Loop of Frequency Converter Side Current Transformer Loop

Error Content 14 1d 1F 21 17

31

IV. Error Indication of MDV Home Central Air Conditioner 1. MDV (H)-J140(120, 80)W-510(511) and Free Frequency Converter Error Indication of Outdoor Main Control Board DSP1 (Digital Tube) MDV(H)-J160 (180)W(/S)-720

32

LED Display E1 E2 E3 E4 E5 H0 P1 P2

Content Phase-sequence Error Communication Error between Indoor Unit and Outdoor Unit Communication Error between PCB and inverter module Outdoor Temperature Sensor Error Voltage Protection Error Mismatching Error of Indoor Units High-voltage Protection Low-voltage Protection

33

P3 P4 P5 P6

Current Protection of Compressor Discharge Temperature Protection High-temperature Protection of Condenser Module Protection

34

2. MDV (H) -D100 (120) (/S)-510 Error Code Display of Outdoor Unit LED Display Quantity of Indoor Units Capability Demand of Indoor Unit dF E1 Content Standby Normal Operation Period of Defrosting Phase-sequence Protection (only 5HP unit has)

35

E2 E3 E4 E5 H0 P1

Communication Error between Indoor Units and Outdoor Unit Outdoor Tube Temperature Error Outdoor Ambient Temperature Sensor Error Discharge Temperature Sensor Error of Compressor Mismatching Error of Indoor Units High-voltage Protection

36

P2 P3 P4 P5

Low-voltage Protection Current Protection of Compressor Discharge Temperature Protection High-temperature protection of Condenser

37

3. Error Code List of Novel M-home Series Digital Indoor Unit Display (LED) Timing Indicator LED2 Flash, Quickly RUN Indicator LED1 Flash, Quickly RUN Indicator LED1 Flash, Quickly RUN Indicator LED1 Flash, Display E1 Definition of Error Communication Error between Indoor Units and Outdoor Unit Room Temperrature Sensor Error

E2

E3 E4

Tube Temperature Sensor Error Tube Temperature Sensor Error

38

Quickly Alarm Indicator LED4 Flash, Quickly RUN Indicator LED1 Flash, Slowly Defrosting Indicator LED3 Flash, Quickly Alarm Indicator LED4 Flash, Slowly EE Water Level Alarm Error

E7

EEPROM Error

E0

Model Conflict Error

Ed

Outdoor Unit Error

39

Four LED Indicators Flash, Simultaneously

Ed

Mismatching Error of Indoor Units and Outdoor Unit

40

4. Error Code List of Novel Home Digital Water Chiller Display E0 E1 E2 E3 E4 E5 Definition of Error Detection Error of Water Flow Pahse-sequence Error Communication Error between Indoor Units and Outdoor Unit Backwater Temperature Sensor Error Outdoor Ambient Temperature Sensor Error Outlet Water Temperature Sensor Error

41

E6 E7 E8 E9 P0 P1 P2 P3

Tube Temperature Sensor Error of Condenser Temperature Sensor Error 1of Plate Exchanger Temperature Sensor Error 2 of Plate Exchanger Digital Compressor Discharge ( Dispaly E4 on Wire Controller) Current Protection of System High-voltage Protection Low-voltage Protection Discharge Temperature Protection

42

P4 P5 P6 Pb

Temperature Difference Protection of Inlet and Outlet Water High-temperature Protection of System Condenser Low-temperature Protection of Plate Exchanger Anti-Freezing Protection of System Temperature Difference Protection of Inlet and Outlet Water (3 times

P8

within one hour, power on anew) Dispaly P4 on Wire Controller

43

5. MDV-J110 ~MDV-J160 AC Inverter Error Indication of Outdoor Unit LED4 X LED3 X LED2 X LED1 X LED0 O Definition of Error or Protection Normal Status (Compressor is shut down) Normal Status (Compressor is operating) Module Error Temperature Protection of Top

O X X

O X X

X X O

X O X

44

part of Compressor X O X X Room Temperature or Inner Tube Temperature Sensor Error Outdoor Temperature Sensor Error Discharge Temperature Protection High-temperature Protection of Indoor Heat Exchanger

45

X O O

O X O

O O X

X X X

Over-voltage or Short-voltage Error Current Protection Low-temperature Protection of Indoor Heat Exchanger (Freezing Prevention Protection) Communication Error between Outdoor Plate and Frequency Converter Plate Communication Error between Indoor Plate and Outdoor Plate High-temperature Protection of Outdoor Heat Exchanger

O O X

O O X

X O X

O X X

46

O X

O X

O O

O O

Protection for the Disconnection of Temperature Fuse Over-low or Over-high Outdoor Ambient Temperature (Cancelled)

-O (On)/ -X(Off) / -(Flash)

47

Error Indication of Display Board for Indoor Unit Anti-cold fan Mode Conflict Room Temperature

Defrosting and Preheating Indicator Flash at 0.2Hz Timing Indicator and Defrosting Indicator Flash at 5Hz, Simultaneously Timing Indicator Flash at 5Hz

Sensor Error Evaporator Error Burnt out of Sensor

Automatic Indicator Flash at 5Hz RUN Indicator Flash at 5 Hz

48

Temperature Fuse Communication Error of Indoor Units

Defrosting Indicator Flash at 5Hz RUN Indicator LED1, Timing Indicator LED2, Automatic Indicator LED3 and Defrosting and Preheating Indicator LED4 Flash at 0.2 Hz, Simultaneously

Outdoor Error

49

Error Indication of Indoor One-Drivers-Two System

Unit

with

Variable-frequency

LED Display RUN Indicator Flash, Slowly RUN Indicator On RUN Indicator of Principal Unit Flash, Slowly Preheating/Defrosting Indicator On

Definition of Error or Protection Initial Power On Start up Single Unit

Start up Double Units

Period of Cold Air Prevention

50

Timing Indicator On

Timing Setting Room Temperature Sensor is Abnormal Evaporator Sensor is Abnormal Communication Error Outdoor Unit Error

Timing Indicator Flash

Automatic Indicator Flash Preheating/Defrosting Indicator Flash Four Indicators Flash, Simultaneously

51

6. Variable- Frequency Water System Home Central Air Conditioner What displayed on the integrated controller (KJR-07B) of Midea variable frequency water chiller is only simple code, but not the real error code. The real error code is shown on the signaling transfer board of outdoor unit. Error Codes of Wire Controller LED Display E0 E1 E2 Parameter Error Communication Error of Outdoor Unit Outlet Water Temperature Sensor Error Content

52

E3

Outdoor Fixed-frequency System Heat Exchanger Sensor Error Refrigerant Inlet Sensor Error of Plate-type Heat Exchanger Side by Variable Frequency System Refrigerant Inlet Sensor Error of Plate-type Heat Exchanger Side by Fixed Frequency System Outdoor Heat Exchanger Sensor or Temperature Sensor (T4) Error of Variable Frequency System Communication Error of Wire Controller

E4

E5

E6 E7

53

P0 P1 P2 P3 P4 P5 P6 P7

Temperature Protection of Top Part of Compressor Pump Mode (Prevent pump being frozen) Hydraulic Pressure Protection of Inlet Water Module Protection Current Protection Voltage Protection Freezing Prevention Protection of Fixed-frequency System High-temperature Protection of Fixed-frequency Compressor and Condenser

54

P8 P9 PA PB

Over-high Discharge Temperature Protection Freezing Prevention Protection of Variable-frequency System High-temperature Protection of Heat Exchanger (None) High-temperature Protection of Variable-frequency Compressor and Condenser

As for the variable frequency water chiller being produced after 2005, signaling transfer board is cancelled in outdoor unit, while LED digital tube is added. Error Codes for Integrated Controller of Variable Frequency Water Chiller or Digital Tube of Outdoor Unit:

55

LED Display P0 P1 P2 P3 P4 P5 P6

Content Current Protection Temperature Protection of Top Part of Compressor Discharge Temperature Protection of Compressor Module Protection Voltage Protection High-temperature Protection of Frequency Converter Tube High-temperature Protection of Fixed Frequency Tube

56

Pb E0 E1 E2

Freezing Prevention Protection Detection Error of Water Flow EEPROM Error Communication Error between Integrated Controller Outdoor Unit and

E3 E4 E5 E6

Communication Error of Outdoor Frequency Converter T4 or T3BP Error Temperature Sensor Error of Outlet Water T3DP Error

57

E7 E8 E9 H0 H1 H2

Temperature Sensor 1 Error of Plate Exchanger Temperature Sensor 2 Error of Plate Exchanger Error Codes of Integrated Controller EEPROM Error Error of Room Temperature T1 Communication Error between Integrated Controller and Outdoor Unit

H3

Model Conflicts between Integrated Controller and Principal Unit

58

7. KFR-61T2W/BP or KFR-402W/BP-510T2 LED Display Timing Indicator and Defrosting Indicator Off, RUN Indicator Flash Timing Indicator and Defrosting Indicator Flash, RUN Indicator Flash, Alternate Flash Timing Indicator, RUN Indicator and Defrosting Indicator Flash Content Indoor Tube Temperature Error

Communication Error between Indoor Units and Outdoor Unit Overloading Protection of Compressor (Temperature of top part

59

exceeds 120) Defrosting Indicator, RUN Indicator and Timing Indicator Flash Timing Indicator On, RUN Indicator and Defrosting Indicator Flash Defrosting Indicator On, RUN Indicator and Timing Indicator Flash Timing Indicator Off, Defrosting Indicator On, RUN Indicator Flash Module Protection

High/Low Voltage Alarm

Outdoor Temperature Sensor Error

Defrosting

60

at 1.5Hz Timing Indicator On, Defrosting Indicator Unknown, RUN Indicator Flash at 1.5Hz Plasma Dedusting Mark

61

Direct-Current Variable-Frequency One-to-Any Air Conditioner with One Group of Tube Display Content E0 E2 EEPROM Error Communication Error between Indoor Chips and Outdoor Chip E3 E4 Communication Error between Outdoor Chip and DSP Ambient Temperature Sensor Error Definition of Error or Protection

62

E5

Voltage Protection of Compressor

P0 P1 P2 P3 P4 P5 P6

Temperature Protection of Top Part High-voltage Protection Low-voltage Protection Current Protection of Compressor Discharge Temperature Protection High-temperature Protection of Outdoor Condenser Module Protection

63

DC Inverter "One-to-Two" or "One-to-Three" Air Conditioner with Several Groups of Tube Display Content E0 E1 E2 E3 E4 Definition of Error or Protection EEPROM Parameter Error Temperature Sensor Error of 1# Indoor Evaporator Outlet Temperature Sensor Error of 2# Indoor Evaporator Outlet Temperature Sensor Error of 3# Indoor Evaporator Outlet Ambient Temperature Sensor Error

64

E5 E6 E7 P0 P1 P2 P3 P4

Voltage Protection of Compressor Pre-reserved Communication Error of Outdoor Frequency Converter Temperature Protection of Top Part High-voltage Protection (Pre-reserved) Low-voltage Protection (Pre-reserved) Current Protection of Compressor Module Protection

65

P5 P6 P7

Ambient Low-Temperature Protection High-temperature Protection of Outdoor Condenser Pre-reserved

66

DC Variable-Frequency "One-to-Four" Air Conditioner with Several Groups of Tube Display Content E0 E1 E2 E3 Definition of Error or Protection EEPROM Parameter Error Temperature Sensor Error of 1# Indoor Evaporator Outlet Temperature Sensor Error of 2# Indoor Evaporator Outlet Temperature Sensor Error of 3# Indoor Evaporator Outlet

67

E4 E5 E6 E7 P0 P1 P2

Ambient Temperature and Tube Temperature Sensor Error Voltage Protection Temperature Sensor Error of 4# Indoor Evaporator Outlet Communication Error between DSP and 780034 Temperature Protection for Top of Inverter Compressor High-voltage Protection Low-voltage Protection

68

P3 P4 P5 P6 P7 P8

Current Protection of Frequency Converter Module Protection Ambient Low-Temperature Protection High-temperature Protection of Outdoor Condenser Pre-reserved Pre-reserved

69

V. Error Indication of Unitary Central Air Conditioner 1. Error Code List for Ordinary One-to-One Error Code Indication of Indoor Unit LED Flash All indicators flash at 5Hz Timing indicator flashes at 5Hz Definition of Error or Protection Neutral line has not been connected to the PRO port on indoor electric control panel, or optical coupler on circuit wafer has been damaged. Room Temperature Sensor Error

70

Run indicator flashes at 5Hz Defrosting indicator flashes at 5Hz Warning indicator flashes at 5Hz

Temperature Sensor Error of Evaporator

Temperature Sensor Error of Condenser

Detection Error of Water Level Switch

71

LED Error Indication of Outdoor Main Control Board

1) LED Error List for 3HP Detection Panel of Outdoor Phase-sequence Symptom LED1 Off On Off On On LED2 Off Off On On On LED3 On On On On On Normal Phase-sequence is reversed. Over Current Phase-loss Pressure Protection Definition of Error or Protection

72

2) LED Error List for 5HP Outdoor Main Control Panel Symptom LED1 Flash Flash Off Off Off Flash LED2 Off Flash Off Flash Flash Flash LED3 Off Off Flash Flash Off Flash Phase-loss, or Phase-sequence is reversed. High/Low Pressure Protection Over Current T3 Open Circuit or Short circuit Error T4 Open Circuit or Short circuit Error High Temperature Protection of Condenser Definition of Error or Protection

73

2. Error Code List for Novel Four-way Cassette Symptom Operating On Timing On Defrosting On Full-water On Error Code Definition of Error or Protection Room X X X E2 Temperature Sensor Error X X X E3 Temperature Sensor Error of

74

Evaporator Temperature X X X E4 Sensor Error of Condenser Temperature X X E5 Sensor Error of Water Pump E6 Outdoor Error Unit

75

X X

E7 E8

EEPROM Error Full-water Error

(X indicates that the indicator is Off, indicates that the indicator flashes at 5Hz.) (X indicates that the indicator is Off, indicates that the indicator flashes at 5Hz.)

76

3. Error Code List for 10HP Cabinet Unit Display Content Error Icon E1 On Error Icon E2 On Error Icon P1 On Error Icon P2 On Definition of Error or Protection T1 Open Circuit or Short Circuit Error T2 Open Circuit or Short Circuit Error T2 Low Temperature Protection under Cooling Model T2 High Temperature Protection under Heating Model

77

4. Error Indication of 20HP Medium Static-pressure (Outdoor Unit) Symptom Definition of Error or Protection LED1 Flash Flash Off Off LED2 Off Flash Off Flash LED3 Off Off Flash Flash Communication Error Low-pressure Protection Open Circuit or Short Circuit Error of Room Temperature High Temperature Protection of Condenser

78

Flash Off Flash

Flash Flash Off

Flash Off Flash

Phase-lacking or Phase-sequence is reversed. T3 Open Circuit or Short Circuit Error None

79

53/71 DC Inverter "One-toOne Air Conditioner Display Content E0 E2 E3 E4 Definition of Error or Protection EEPROM Error Communication Error between Indoor Chip and Outdoor Chip Communication Error between Outdoor Chip and DSP Ambient Temperature Sensor Error

80

E5 P0 P1 P2 P3 P4 P5 P6

Voltage Protection of Compressor Temperature Protection of Top Part High-voltage Protection Low-voltage Protection Current Protection of Compressor Discharge Temperature Protection High Temperature Protection for Outdoor Condenser Module Protection

81

90/105/140 Single-Phase Direct-Current Variable-Frequency "One-toOne Air Conditioner Display Content E0 E2 E3 Definition of Error or Protection EEPROM Error Communication Error between Indoor Chip and Outdoor Chip Communication Error between Outdoor Chip and DSP

82

E4 E5 E6 P0 P1 P2 P3 P4

Ambient Temperature Sensor Error Voltage Protection of Compressor PFC Module Protection Temperature Protection of Top Part High-voltage Protection Low-voltage Protection Current Protection of Compressor Discharge Temperature Protection

83

P5 P6

High Temperature Protection for Outdoor Condenser Module Protection

84

105/140/160 Three-Phase DC Inverter "One-toOne Air Conditioner Display Content E0 E2 E3 E4 E5 Definition of Error or Protection EEPROM Error Communication Error between Indoor Chip and Outdoor Chip Communication Error between Outdoor Chip and DSP Ambient Temperature Sensor Error Voltage Protection of Compressor

85

P0 P1 P2 P3 P4 P5 P6

Temperature Protection of Top Part High-voltage Protection Low-voltage Protection Current Protection of Compressor Discharge Temperature Protection High Temperature Protection for Outdoor Condenser Module Protection

86

87

Indication List for LED Display No. 1 LED1 LED2 LED3 Description Heating Mode (after the Startup of Compressor) Cooling Mode (after the Startup of Compressor) Defrosting Heating Mode, Indoor T2 High-temperature Protection, Shut down Fan as Required.

2 3 4

88

5 6 7 8 9 10 11

Standby Ambient Temperature Sensor Error Outdoor Tube Temperature Sensor Error Phase-sequence Protection T3 High Temperature Protection Low-voltage Protection 1 High-voltage Protection, Discharge Protection 1

89

12 13 14 15 16 17

Current Protection 1 Current Protection 2 Current Protection 3 Current Protection 4 Discharge Protection 2, 3 Discharge Protection 4

: On, : Off, : Flash Quickly, : Flash Slowly

90

DIP switch setting: J2: Double Fan / Single Fan (Connected / Unconnected) J1: Three-phase / Single-phase (Connected / Unconnected)
ON

1: ON with self-check 2: ON with fast-check

91

VI. Error Indication of Digital Scroll Air Cooling Module 1. Error Protection Display for 60KW Modular Air-Cooling Heat-Pump Unit E0 E1 E2 E3 E4 E5 Detection Error of Water Flow (Third Time) Phase-sequence Error of Power Supply Communication Error Temperature Sensor Error of Master Outlet Water (Principal Unit is in Effect) Temperature Sensor Error of Outlet Water for Plate Exchanger Tube Temperature Sensor Error of Condenser A

92

E6 E7 E8 E9 Eb EF EA

Tube Temperature Sensor Error of Condenser B Ambient Temperature Sensor Error Discharge Temperature Sensor Error of Digital Compressor for System A Detection Error of Water Flow (First and Second Time) Error of Plate Exchanger Low-temperature Freezing-prevention Protection Sensor T61 Error of Plate Exchanger Low-temperature Freezing-prevention Protection Sensor T62 Communication Protection of Subordinate Module (Display of Wire Controller)

93

P0 P1 P2 P3 P4 P5 P6 P7

High-voltage or Discharge Temperature Protection of System A Low-voltage Protection of System A High-voltage or Discharge Temperature Protection of System B Low-voltage Protection of System B Current Protection of System A Current Protection of System B High-temperature Protection of Condenser of System A High-temperature Protection of Condenser of System B

94

P8 Pb PE

Discharge Temperature Protection of Digital Compressor for System A System Freezing-prevention Protection Low-temperature Protection of Plate Exchanger

95

2. Error Protection Display for 200KW Large Modular Air-Cooling Heat-Pump Unit E0 E1 E2 E3 E4 E5 E7 E9 EA Eb P0 Detection Error of Water Flow (Third Time) Phase-sequence Error of Power Supply Communication Error Temperature Sensor Error of Master Outlet Water Temperature Sensor Error of System Inlet Water Tube Temperature Sensor Error of Condenser Ambient Temperature Sensor Error Detection Error of Water Flow (First Time) Communication Protection of Subordinate Module Error of Sensor T6 High-voltage or Discharge Temperature Protection

96

P1 P4 P6 Pb

Low-voltage Protection Current Protection of Compressor High-temperature Protection of Condenser of System System Freezing-prevention Protection

3. List of Display Code for Modular Wire Controller Error Protection E0 E1 E2 E3 E4 Detection Error of Water Flow (Third Time) Phase-sequence Error of Power Supply Communication Error Temperature Sensor Error of Master Outlet Water (Principal Unit is in Effect) Temperature Sensor Error of Outlet Water for Plate Exchanger

97

E5 E6 E7 E8 E9 EA Eb EC ED EE

Tube Temperature Sensor Error of Condenser A Tube Temperature Sensor Error of Condenser B Ambient Temperature Sensor Error Discharge Temperature Sensor Error of Digital Compressor for System A Detection Error of Water Flow (First and Second Time) Reduction in the Number of Subordinate Unit Detected by Principal Unit Freezing-prevention Temperature Sensor Error of Plate Exchanger A Online module unit could not be found on Wire Controller. Communication Data Error for Wire Controller and Module Communication Error between Wire Controller and Computer

98

EF P0 P1 P2 P3 P4 P5 P6 P7 P8 Pb

Freezing-prevention Temperature Sensor Error of Plate Exchanger High-voltage or Exhaust Temperature Protection of System A Low-voltage Protection of System A High-voltage or Exhaust Temperature Protection of System B Low-voltage Protection of System B Current Protection of System A Current Protection of System B High-temperature Protection of Condenser of System A High-temperature Protection of Condenser of System B Discharge Temperature Protection of Digital Compressor for System A System Freezing-prevention Protection

99

PC PE

Protection for Digital Discharge Temperature above 125 Low-temperature Protection of Plate Exchanger

VII Error Indication of Water Cooled Cabinet Unit Error Display Content Error Icon E0 On Error Icon E1 On Error Icon E2 and No. 1 On Definition of Error or Protection T1 Open Circuit or Short Circuit Error Phase-sequence Error T2 Open Circuit or Short Circuit Error of System 1 (T2A)

100

Error Icon E2 and No. 2 On Error Icon E2 and No. 3 On Error Icon E5 and No. 1 On Error Icon E5 and No. 2 On Error Icon E5 and No. 3

T2 Open Circuit or Short Circuit Error of System 2 (T2B) T2 Open Circuit or Short Circuit Error of System 3 (T2C) Three errors in System 1 within 30 minutes

Three errors in System 2 within 30 minutes Three errors in System 3 within 30 minutes

101

On Error Icon P0 and No. 1 On Error Icon P0 and No. 2 On Error Icon P0 and No. 3 On Error Icon P1 and No. 1 On T2 Low-temperature Protection of System 1 (T2A) T2 Low-temperature Protection of System 2 (T2B) T2 Low-temperature Protection of System 3 (T2C) Current Protection of Compressor 1

102

Error Icon P2 and No. 1 On Error Icon P3 and No. 2 On Error Icon P4 and No. 2 On Error Icon P5 and No. 3 On Error Icon P6 and No. 3

Current Protection of Compressor 2

Current Protection of Compressor 3 Current Protection of Compressor 4

Current Protection of Compressor 5

Current Protection of Compressor 6

103

On Error Icon P7 On Error Icon P9 and No. 1 On Error Icon P9 and No. 2 On Error Icon P9 and No. 3 On Protection of Indoor Blower Motor Discharge Temperature and High/Low Voltage Protection Discharget Temperature and High/Low Voltage Protection Discharge Temperature and High/Low Voltage Protection

104

VIII. Error Indication of Screw Unit Error Indication of Screw Unit with 100 (200) USRT LED2 Off On Off Flash LED3 Off Off Off On EP E1 Display N/A Standby Operation Voltage Protection and Phase-sequence Error Flash Inlet Sensor Protection of Chilled Water Error Content

LED1 On On Flash

105

Flash On Off Flash Flash Flash

Off Flash Flash On Flash Flash

On On On On Off Flash

E2 E3 E4 E5 E6 E7

Outlet Sensor Protection of Chilled Water Inlet Sensor Protection of Cooling Water Outlet Sensor Protection of Cooling Water Protection of Discharge Temperature Sensor Low-voltage Protection Communication Error

106

Flash On On Off Off Flash

Off Flash Off Flash On On

Flash Off Flash Flash Flash Off

P0 P1 P2 P3 P4 P5

Switch Protection of Chilled Water Flow Switch Protection of Cooling Water Flow High-voltage Protection Internal Compressor Protection Overload of Compressor Protection of Oil Pressure Difference

107

Off On

Flash On

Off Flash

P6 P7

Protection of Oil Level High Discharge Temperature Protection

108

Error Indication of Screw Unit with 400 USRT LED1 On On LED2 Off On LED3 Off Off Display N/A Error Content Standby Operation Voltage Protection Flash Off Off EP and Phase-sequence Error Inlet Sensor Flash Flash On E1 Protection of Chilled Water

109

Outlet Sensor Flash Off On E2 Protection of Chilled Water Inlet Sensor On Flash On E3 Protection of Cooling Water Outlet Sensor Off Flash On E4 Protection of Cooling Water Protection of Flash On On E5 Discharge Temperature Sensor

110

Flash Flash Flash On On Off

Flash Flash Off Flash Off Flash

Off Flash Flash Off Flash Flash

E6 E7 P0 P1 P2 P3

Low-voltage Protection Communication Error Switch Protection of Chilled Water Flow Switch Protection of Cooling Water Flow High-voltage Protection Internal Compressor Protection

111

Off Flash Off

On On Flash

Flash Off Off

P4 P5 P6

Overload of Compressor Protection of Oil Pressure Difference Protection of Oil Level Protection of

On

On

Flash

P7

Over-high Discharge Temperature

112

IX. Error Indication of Network Air Conditioner Error Code Error Content Protection Code Content of Protection

Error and Protection of Air Conditioner EF EE Other Error Error of Water Level Detection ED EC Protection of Outdoor Unit Error Fresh Error (Reserved) PC Reserved PD Reserved PF PE Other Protection Reserved

113

Protection of Variable EB Frequency Module (Reserved) EA Over Current of Compressor (Four Times) Communication Error of E9 Main Board and Display Board E8 Wind-speed detection is out of control (Reserved) P8 Over Current of Compressor P9 Reserved PA Reserved PB Reserved

114

E7

EEPROM Error (Reserved)

P7

Over/under Voltage Protection of Power Discharge Low-voltage Protection

E6

Zero-crossing Detection Error (Reserved) Sensor T3 or T4 Error or Error of Discharge

P6

E5

Temperature Sensor for Digital Compressor (Reserved)

P5

Discharge High-voltage Protection

115

E4

Sensor T2B Error

P4

E3

Sensor T2A Error

P3

E2

Sensor T1 Error Communication Error

P2

Temperature Protection of Vent Tube Temperature Protection of Compressor High Temperature Protection of Condenser Protection of Preventing Cold Air or Defrosting

E1

between Outdoor and Indoor Unit (Variable Frequency or Digital Unit)

P1

116

(Reserved) E0 Phase-sequence Error or Phase-loss (Reserved) Network Error Communication Error 03# between Centralized 01# Monitor and Computer (Gateway) Monitor and Network Interface Module Communication Error between Centralized P0 Temperature Protection of Evaporator

117

Communication Error 02# between Centralized 00# Monitor and Function Module

Communication Error between Network Interface Module and Main Control Board

118