sl no

Nom kV

No of Circuits

Type of Conductor

No of Conductor per phase

Budgetary Cost / km Including supply+erection & civil works

1 2 3 4 5

33 66 132 220 400

Single Circuit Double Circuit Single Circuit Double Circuit Single Circuit Double Circuit Single Circuit Double Circuit Single Circuit Double Circuit

ACSR - Dog ACSR - Dog ACSR - Dog ACSR - Dog ACSR - Panther ACSR - Panther ACSR - Zebra ACSR - Zebra ACSR - Moose ACSR - Moose

1 1 1 1 1 1 1 1 2 2 25 lakhs/km 8.5 lakhs / km

sl no 1 Broad Parameters Nom kV No of Circuits Type of Conductor (a) Current Capacity at standard reference conditions (b) Overall deration at 50deg C (c) Current Capacity at 50deg C condition (Amps) (d) A.C. Resistance at 85 deg C (ohm/km) No of Conductors / phase Power Capacity in MVA Power Loss (I 2 R) : kW / km 2 Clearances Phase - to - Phase Phase - to - Earth

33 Single Circuit ACSR - Dog 291 0.94 274 0.3924 1 16 29.36

33 Double Circuit ACSR - Dog 291 0.94 274 0.3924 1 31 58.72

Towers Type of Towers Wgt of tower in Tons

Insulators

Tension / Suspension Hardware

Earth Wire

sl no 1 Broad Parameters Nom kV No of Circuits Type of Conductor (a) Current Capacity at standard reference conditions (b) Overall deration at 50deg C (c) Current Capacity at 50deg C condition (Amps) (d) A.C. Resistance at 85 deg C (ohm/km) No of Conductors / phase Power Capacity in MVA Power Loss (I 2 R) : kW / km 2 Clearances Phase - to - Phase Phase - to - Earth

66 Single Circuit ACSR - Dog 291 0.94 274 0.3924 1 31 29.36

66 Double Circuit ACSR - Dog 291 0.94 274 0.3924 1 63 58.72

Towers Type of Towers

Insulators

Wgt of tower Tons

sl no 1 Broad Parameters Nom kV No of Circuits Type of Conductor (a) Ampacity at standard reference conditions (b) Overall deration at 50deg C (c) Ampacity at site condition (d) A.C.Resistance No of Conductors / phase Power Carrying Capacity in MVA Power Loss (I2R) / km 2 Clearances Phase - to - Phase Phase - to - Earth

132 Single Circuit ACSR - Panther 487 0.94 458 0.1706 1 105

132 Double Circuit ACSR - Panther 487 0.94 458 0.1706 1 209

Towers Type of Towers

Insulators

Wgt of tower Tons

sl no 1 Broad Parameters Nom kV No of Circuits Type of Conductor (a) Ampacity at standard reference conditions (b) Overall deration at 50deg C (c) Ampacity at site condition (d) A.C.Resistance No of Conductors / phase Power Carrying Capacity in MVA Power Loss (I2R) / km 2 Clearances Phase - to - Phase Phase - to - Earth

220 Single Circuit ACSR - Zebra 737 0.9 663 0.08699 1 253

220 Double Circuit ACSR - Zebra 737 0.9 663 0.08699 1 505

Towers Type of Towers

Insulators

Wgt of tower Tons

sl no 1 Broad Parameters Nom kV 400 400 No of Circuits Single Circuit Double Circuit Type of Conductor ACSR - Moose ACSR - Moose (a) Ampacity at reference conditions ( alpha: 0.5, E=0.5, S=0.985, 836 V=2200 mts/sec) 836 (b) Overall deration at 50deg C 0.9 0.9 (c) Ampacity at site condition 752 752 (d) A.C.Resistance 0.07111 0.07111 No of Conductors / phase 2 2 Power Carrying Capacity in MVA 1043 2085 Power Loss (I2R) / km 2 Clearances Phase - to - Phase Phase - to - Earth

Towers Type of Towers

Insulators

Wgt of tower Tons