www.hilti.com.ph Company: Specifier: Address: Phone I Fax: E-Mail: Page: Project: Sub-Project I Pos. No.

: Date:

Profis Anchor 2.4.6


1 VIRIDIAN CANOPY 3/5/2014

Specifier's comments: This anchor design calculation is subject to the comments and approval of the strucutral engineer of the project.

1 Input data
Anchor type and diameter: Effective embedment depth: Material: Evaluation Service Report: Issued I Valid: Proof: Stand-off installation: Anchor plate: Profile: Base material: Installation: Reinforcement: HIT-RE 500 + HIT-V (5.8) M16 hef,opti = 192 mm (hef,limit = 314 mm) 5.8 ETA 04/0027 6/26/2013 | 5/16/2018 design method ETAG BOND (EOTA TR 029) eb = 0 mm (no stand-off); t = 16 mm lx x ly x t = 270 mm x 250 mm x 16 mm; (Recommended plate thickness: not calculated) no profile uncracked concrete, C20/25, fcc = 25.00 N/mm2; h = 350 mm, Temp. short/long: 40/24 C hammer drilled hole, installation condition: dry no reinforcement or reinforcement spacing >= 150 mm (any ) or >= 100 mm ( <= 10 mm) no longitudinal edge reinforcement Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for agreement with the existing conditions and for plausibility! PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

www.hilti.com.ph Company: Specifier: Address: Phone I Fax: E-Mail: Page: Project: Sub-Project I Pos. No.: Date:

Profis Anchor 2.4.6


2 VIRIDIAN CANOPY 3/5/2014

2 Load case/Resulting anchor forces


Load case: Design loads Anchor reactions [kN] Tension force: (+Tension, -Compression) Tension force Shear force Shear force x Anchor 1 27.500 0.000 0.000 2 27.500 0.000 0.000 3 27.500 0.000 0.000 4 27.500 0.000 0.000 max. concrete compressive strain: - [] max. concrete compressive stress: - [N/mm2] resulting tension force in (x/y)=(0/0): 110.000 [kN] resulting compression force in (x/y)=(0/0): 0.000 [kN] 3 y 4

Shear force y 0.000 0.000 0.000 0.000

Tension

3 Tension load (EOTA TR 029, Section 5.2.2)


Steel Strength* Combined pullout-concrete cone failure** Concrete Breakout Strength** Splitting failure** * anchor having the highest loading 3.1 Steel Strength NRk,s [kN] 79.000 gM,s 1.500 NRd,s [kN] 52.667 NSd [kN] 27.500 Load [kN] 27.500 110.000 110.000 110.000 **anchor group (anchors in tension) Capacity [kN] 52.667 134.679 110.210 156.416 Utilization bN [%] 53 82 100 71 Status OK OK OK OK

3.2 Combined pullout-concrete cone failure Ap,N [mm2] 400117 yc 1.000 ec1,N [mm] 0 N0 Rk,p [kN] 144.765
2 A0 p,N [mm ] 204800 2 tRk,ucr [N/mm ] 15.00 2 tRk,ucr,25 [N/mm ] 15.00

scr,Np [mm] 453 yg,Np 1.000 yec2,Np 1.000 NRd,p [kN] 134.679
0

ccr,Np [mm] 226 yg,Np 1.000 ys,Np 1.000 NSd [kN] 110.000

cmin [mm]

k 3.200 ec2,N [mm] 0 gM,p 2.100

yec1,Np 1.000 NRk,p [kN] 282.826

yre,Np 1.000

3.3 Concrete Breakout Strength Ac,N [mm2] 571536 ec1,N [mm] 0 N0 Rk,c [kN] 134.352 3.4 Splitting failure Ac,N [mm2] 471145 ec1,N [mm] 0 N0 Rk,c [kN] 134.352
2 A0 c,N [mm ] 256441 2 A0 c,N [mm ] 331776

ccr,N [mm] 288 ec2,N [mm] 0 NRd,c [kN] 110.210

scr,N [mm] 576 yec2,N 1.000 NSd [kN] 110.000 ys,N 1.000 yre,N 1.000 k1 10.100

yec1,N 1.000 gM,c 2.100

ccr,sp [mm] 253 ec2,N [mm] 0 NRd,sp [kN] 156.416

scr,sp [mm] 506 yec2,N 1.000 NSd [kN] 110.000

yh,sp 1.331 ys,N 1.000 yre,N 1.000 k1 10.100

yec1,N 1.000 gM,sp 2.100

Input data and results must be checked for agreement with the existing conditions and for plausibility! PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

www.hilti.com.ph Company: Specifier: Address: Phone I Fax: E-Mail: Page: Project: Sub-Project I Pos. No.: Date:

Profis Anchor 2.4.6


3 VIRIDIAN CANOPY 3/5/2014

4 Shear load (EOTA TR 029, Section 5.2.3)


Steel Strength (without lever arm)* Steel failure (with lever arm)* Pryout Strength* Concrete edge failure in direction ** * anchor having the highest loading Load [kN] N/A N/A N/A N/A **anchor group (relevant anchors) Capacity [kN] N/A N/A N/A N/A Utilization bV [%] N/A N/A N/A N/A Status N/A N/A N/A N/A

5 Displacements (highest loaded anchor)


Short term loading: NSk VSk = = 20.370 [kN] 0.000 [kN] dN dV dNV Long term loading: NSk VSk = = 20.370 [kN] 0.000 [kN] dN dV dNV = = = 0.169 [mm] 0.000 [mm] 0.169 [mm] = = = 0.084 [mm] 0.000 [mm] 0.084 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements are valid without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not included in this calculation! The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

6 Warnings
To avoid failure of the anchor plate the required thickness can be calculated in PROFIS Anchor. Load re-distributions on the anchors due to elastic deformations of the anchor plate are not considered. The anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the loading! Checking the transfer of loads into the base material is required in accordance with EOTA TR 029, Section 7! The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 4.1 of EOTA TR029! For larger diameters of the clearance hole see Chapter 1.1. of EOTA TR029! The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to be followed to ensure a proper installation. Characteristic bond resistances depend on short- and long-term temperatures. Please contact Hilti to check feasibility of HIT-V rod supply. Edge reinforcement is not required to avoid splitting failure

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility! PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

www.hilti.com.ph Company: Specifier: Address: Phone I Fax: E-Mail: Page: Project: Sub-Project I Pos. No.: Date:

Profis Anchor 2.4.6


4 VIRIDIAN CANOPY 3/5/2014

7 Installation data
Anchor plate, steel: Anchor type and diameter: HIT-RE 500 + HIT-V (5.8), M16 Profile: no profile; 0 x 0 x 0 mm Installation torque: 0.080 kNm Hole diameter in the fixture: df = 18 mm Hole diameter in the base material: 18 mm Plate thickness (input): 16 mm Hole depth in the base material: 192 mm Recommended plate thickness: not calculated Minimum thickness of the base material: 228 mm Cleaning: Manual cleaning of the drilled hole according to instructions for use is required.

7.1 Required accessories Drilling Suitable Rotary Hammer Properly sized drill bit Cleaning Manual blow-out pump Proper diameter wire brush y Setting Dispenser including cassette and mixer Torque wrench

135

135

35 180 125

2 35

45

180

45

Coordinates Anchor [mm] Anchor 1 2 3 4 x -90 90 -90 90 y -90 -90 90 90 c-x c+x c-y c+y -

Input data and results must be checked for agreement with the existing conditions and for plausibility! PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

125

www.hilti.com.ph Company: Specifier: Address: Phone I Fax: E-Mail: Page: Project: Sub-Project I Pos. No.: Date:

Profis Anchor 2.4.6


5 VIRIDIAN CANOPY 3/5/2014

8 Remarks; Your Cooperation Duties


Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a specific application. You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility! PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan