STUDY OF HEAT EXCHANGERS

Submitted in partial fulfillment for the award of the degree Of BACHELOR OF TECHNOLOGY IN

MECHANICAL ENGINEERING
Submitted By

B KIRAN KUMAR P NIRESH KUMAR

11675A0316 11675A0321

Under the Guidance of D.V.S.RAJU Assoc.Professor

J B INSTITUTE OF ENGINEERING AND TECHNOLOGY (Affiliated to Jawaharlal Nehru Technological University Hyderabad) HYDERABAD
April-2014
1

Department of Mechanical Engineering

Batch Certificate
Project Report submitted to the Department of Mechanical Engineering in accordance with the partial fulfillment of academic requirement.

SUBMITTED BY
B KIRAN KUMAR P NIRESH KUMAR (11675A0316) (11675A0321)

This is to certify that the Project work entitled STUDY OF HEAT EXCHANGERS submitted by B KIRAN KUMAR and P NIRESH KUMAR of 3rd year 2nd semester in ME, J.B.Institute of Engineering & Technology, Yenkapally, Moinabad in accordance with the partial fulfillment of academic requirement, is a bonafied work carried out by them in the academic year 20132014 at BHARAT HEAVY ELECTRICALS under our LIMITED, guidance and RAMACHANDRAPURAM, other Institute. HYDERABAD-32

supervision. The project report has not been submitted to any other University or

INTERNAL GUIDE
D.V.S.RAJU Assoc.Professor

EXTERNAL GUIDE
Shri. B.SRINIVAS, A.G.M-Heat Exchangers, Engineering Dept. BHEL, HYD-32.

HEAD OF THE DEPARTMENT Dr.C.UDAYA KIRAN


2

Study of Heat Exchangers in Thermal Power Plant application.


A MINI PROJECT REPORT SUBMITTED IN PARTIAL FULFILLMENT OF THE ACADEMIC REQUIREMENT

SUBMITTED BY

B KIRAN KUMAR

J.B.Institute of Engineering & Technology 3rd YEAR

UNDER THE GUIDANCE OF

Shri. B.SRINIVAS A.G.M. Heat Exchangers (Engg.) BHEL, Hyderabad

ACKNOWLEDGEMENT

Success will be crowned to the people who made it a reality but the people whose constant guidance and encouragement made it possible will be crowned first on the eve of success. This acknowledgement transcends the reality of formality when we would like to express deep gratitude and respect to all those people behind the screen who guided, inspired and helped us for the completion of our project work We take it as a great privilege for having done this project under the guidance of our internal guide. We consider ourselves lucky enough to get such a good project. This project would add as an asset to our academic profile. We express our profound thanks to Dr.K.V.J.RAO, Principal, J.B.Institute of engineering and technology for their kind patronage We should thanks Mr.D.V.S.RAJU Assoc. professor, ME and Mr. UDAYA KIRAN Head of the department of mechanical engineering for scrupulous guidance and scholarly encouragement science the dawn of this project work they extended their sagacious and sapient advices. We also thank our external guide Shri B.SRINIVAS and Shri

M. VENKATESWARLU for guiding us at BHEL, R.C.Puram, Hyderabad for giving us valuable information and helping us in completing our project successively.

B KIRAN KUMAR P NIRESH KUMAR

ABSTRACT

A heat exchanger is a device that is used to transfer thermal energy (enthalpy) between two or more fluids, between a solid surface and a fluid, or between solid particulates and a fluid, at different temperatures and in thermal contact. In heat exchangers, there are usually no external heat and work interactions. Typical applications involve heating or cooling of a fluid stream of concern and evaporation or condensation of single- or multicomponent fluid streams. In other applications, the objective may be to recover or reject heat, or sterilize, pasteurize, fractionate, distill, concentrate, crystallize, or control a process fluid. In a few heat exchangers, the fluids exchanging heat are in direct contact. In most heat exchangers, heat transfer between fluids takes place through a separating wall or into and out of a wall in a transient manner. In many heat exchangers, the fluids are separated by a heat transfer surface, and ideally they do not mix or leak. Such exchangers are referred to as direct transfer type, or simply recuperators. In contrast, exchangers in which there is intermittent heat exchange between the hot and cold fluidsvia thermal energy storage and release through the exchanger surface or matrixare referred to as indirect transfer type, or simply regenerators. Such exchangers usually have fluid leakage from one fluid stream to the other, due to pressure differences and matrix rotation/valve switching. Common examples of heat exchangers are shell-and tube exchangers, automobile radiators, condensers, evaporators, air preheaters, and cooling towers.

TABLE OF CONTENTS
TOPIC Page

1. Introduction 2. Classification of heat exchangers: According to construction Indirect contact type a. direct transfer type Shell and tube Plate

07 07

08

b. storage type Direct contact type 3. Rankine cycle 4. Reheat cycle 5. Regenerative cycle 6. Condenser Steam Jet air Ejector Gland steam condenser 7. Feed water heaters 8. Deaerator Spray type deaerator Tray type deaerator Spray cum tray type deaerator 9. Conclusion

10

13 14 15 16 23 24 25 30 34 34 35 36

Introduction
A heat exchanger is a component that allows the transfer of heat from one fluid (liquid or gas) to another fluid. Reasons for heat transfer include the following: 1. To heat a cooler fluid by means of a hotter fluid 2. To reduce the temperature of a hot fluid by means of a cooler fluid 3. To boil a liquid by means of a hotter fluid 4. To condense a gaseous fluid by means of a cooler fluid 5. To boil a liquid while condensing a hotter gaseous fluid Regardless of the function the heat exchanger fulfills, in order to transfer heat the fluids involved must be at different temperatures and they must come into thermal contact. Heat can flow only from the hotter to the cooler fluid.

Classification of Heat Exchanger


Although heat exchangers come in every shape and size imaginable, the construction of most heat exchangers fall into one of two categories:

INDIRECT CONTACT 1. DIRECT TRANSFER TYPE Shell and Tube Plate


2. STORAGE TYPE

DIRECT CONTACT

Direct-Transfer Type Heat Exchangers


In this type, heat transfers continuously from the hot fluid to the cold fluid through a dividing wall. Although a simultaneous flow of two (or more) fluids is required in the exchanger, there is no direct mixing of the two (or more) fluids because each fluid flows in separate fluid passages. In general, there are no moving parts in most such heat exchangers. This type of exchanger is designated as a recuperative heat exchanger or simply as a recuperator. {Some examples of direct transfer type heat exchangers are tubular, plate-type, and extended surface exchangers. Note that the term recuperator is not commonly used in the process industry for shell-and-tube and plate heat exchangers, although they are also considered as recuperators. Recuperators are further sub classified as prime surface exchangers and extended-surface exchangers. Prime surface exchangers do not employ fins or extended surfaces on any fluid side. Plain tubular exchangers, shell-and-tube exchangers with plain tubes, and plate exchangers are good examples of prime surface exchangers. Recuperators constitute a vast majority of all heat exchangers.

Tube and Shell The most basic and the most common type of heat exchanger construction is the tube and shell, as shown in Figure 1. This type of heat exchanger consists of a set of tubes in a container called a shell. The fluid flowing inside the tubes is called the tube side fluid and the fluid flowing on the outside of the tubes is the shell side fluid. At the ends of the tubes, the tube side fluid is separated from the shell side fluid by the tube sheet(s). The tubes are rolled and press-fitted or welded into the tube sheet to provide a leak tight seal. In systems where the two fluids are at vastly different pressures, the higher pressure fluid is typically directed through the tubes and the lower pressure fluid is circulated on the shell side. This is due to economy, because the heat exchanger tubes can be made to withstand higher pressures than the shell of the heat exchanger for a much lower cost. The support plates shown on Figure 1 also act as baffles to direct the flow of fluid within the shell back and forth across the tubes.

Plate
A plate type heat exchanger, as illustrated in Figure below, consists of plates instead of tubes to separate the hot and cold fluids. The hot and cold fluids alternate between each of the plates. Baffles direct the flow of fluid between plates. Because each of the plates has a very large surface area, the plates provide each of the fluids with an extremely large heat transfer area. Therefore a plate type heat exchanger, as compared to a similarly sized tube and shell heat exchanger, is capable of transferring much more heat. This is due to the larger area the plates provide over tubes. Due to the high heat transfer efficiency of the plates, plate type heat exchangers are usually very small when compared to a tube and shell type heat exchanger with the same heat transfer capacity. Plate type heat exchangers are not widely used because of the inability to reliably seal the large gaskets between each of the plates. Because of this problem, plate type heat exchangers have only been used in small, low pressure applications such as on oil coolers for engines. However, new improvements in gasket design and overall heat exchanger design have allowed some large scale applications of the plate type heat exchanger. As older facilities are upgraded or newly designed facilities are built, large plate type heat exchangers are replacing tube and shell heat exchangers and becoming more common.
9

Fig: Plate Heat Exchanger

Storage Type Exchangers


In a storage type exchanger, both fluids flow alternatively through the same flow passages, and hence heat transfer is intermittent. The heat transfer surface (or flow passages) is generally cellular in structure and is referred to as a matrix or it is a permeable (porous) solid material, referred to as a packed bed. When hot gas flows over the heat transfer surface (through flow passages), the thermal energy from the hot gas is stored in the matrix wall, and thus the hot gas is being cooled during the matrix heating period. As cold gas flows through the same passages later (i.e., during the matrix cooling period), the matrix wall gives up thermal energy, which is absorbed by the cold fluid. Thus, heat is not transferred continuously through the wall as in a direct-transfer type exchanger (recuperator), but the corresponding thermal energy is alternately stored and released by the matrix wall. This storage type heat exchanger is also referred to as a regenerative heat exchanger, or simply as a regenerator.{ To operate continuously and within a desired temperature range, the gases, headers, or matrices are switched periodically (i.e., rotated), so that the same passage is occupied periodically by hot and cold gases.

Direct Contact Heat Exchangers


In a direct-contact exchanger, two fluid streams come into direct contact, exchange heat, and are then separated. Common applications of a direct-contact exchanger involve mass transfer in addition to heat transfer, such as in evaporative cooling and rectification; applications involving only sensible heat transfer are rare. The enthalpy of phase change in such an
10

exchanger generally represents a significant portion of the total energy transfer. The phase change generally enhances the heat transfer rate. Compared to indirect contact recuperators and regenerators, in direct-contact heat exchangers, (1) very high heat transfer rates are achievable, (2) the exchanger construction is relatively inexpensive, and (3) the fouling problem is generally nonexistent, due to the absence of a heat transfer surface (wall) between the two fluids. However, the applications are limited to those cases where a direct contact of two fluid streams is permissible.

Classification according to Flow arrangement


Because heat exchangers come in so many shapes, sizes, makes, and models, they are categorized according to common characteristics. One common characteristic that can be used to categorize them is the direction of flow the two fluids have relative to each other. The three categories are parallel flow, counter flow and cross flow. Parallel flow, as illustrated in Figure 3, exists when both the tube side fluid and the shell side fluid flow in the same direction. In this case, the two fluids enter the heat exchanger from the same end with a large temperature difference. As the fluids transfer heat, hotter to cooler, the temperatures of the two fluids approach each other. Note that the hottest cold-fluid temperature is always less than the coldest hot-fluid temperature.

11

Counter flow, as illustrated in Figure 4, exists when the two fluids flow in opposite directions. Each of the fluids enters the heat exchanger at opposite ends. Because the cooler fluid exits the counter flow heat exchanger at the end where the hot fluid enters the heat exchanger, the cooler fluid will approach the inlet temperature of the hot fluid. Counter flow heat exchangers are the most efficient of the three types. In contrast to the parallel flow heat exchanger, the counter flow heat exchanger can have the hottest cold- fluid temperature greater than the coldest hot-fluid temperature.

Cross flow, as illustrated in Figure 5, exists when one fluid flows perpendicular to the second fluid; that is, one fluid flows through tubes and the second fluid passes around the tubes at 90 angle. Cross flow heat exchangers are usually found in applications where one of the fluids changes state (2-phase flow). An example is a steam systems condenser, in which the steam exiting the turbine enters the condenser shell side, and the cool water flowing in the tubes absorbs the heat from the steam, condensing it into water. Large volumes of vapor may be condensed using this type of heat exchanger flow.

12

RANKINE CYCLE

The Rankine cycle used in modern power plants has many more components, but the four components are common to all power plants. In this cycle, water is heated in the steam generator to produce high temperature and pressure steam. This steam is then expanded in a turbine to produce electricity from a generator that is connected to the turbine.
13

The steam from the turbine is then condensed back into water in the condenser. The pump then returns the water to the steam generator.

REHEAT CYCLE

For modern turbines the admissible dryness fraction of exhaust steam (at the turbine exit) should be not less than x = 0.86 to 0.88. One of the ways to reduce the wetness of exhaust steam at the turbine exit is to superheat the steam in the boiler. Superheating leads to an increase in the thermal efficiency of the cycle realized, and at the same time, on the T-s diagram it shifts the point corresponding to the conditions of exhaust steam to the right, into the region of greater dryness fractions. We have also found that with the same superheat temperature the use of high pressures increases the cycle areas ratio and, consequently, the thermal efficiency of the cycle, but simultaneously a higher pressure diminishes the dryness fraction of the exhaust steam and the internal relative efficiency of the turbine.

14

REGENERATIVE CYCLE

As in gas-turbine plants, the thermal efficiency of a steam power plant is raised by means of heat regeneration. If a steam power plant is operated on a Rankine cycle without steam reheating and if complete regeneration of heat is accomplished, then the thermal efficiency of this Rankine cycle will be equal to the thermal efficiency of a Carnot cycle. In actual steam power cycles regeneration is effected with the aid of surface-type or direct-contact regenerative feed-water heaters, either of which is supplied with steam from intermediate turbine stages The steam condenses in the regenerative feed-water heaters FWH 1 and FWH 2 heating the feed water which is delivered to the boiler.

15

TS DIAGRAM SHOWING COMBINED CYCLE(REHEAT AND REGENERATIVE)

CONDENSER AS HEAT EXCHANGER IN THERMAL POWER PLANT

CONDENSER The main purposes of the condenser are to condense the exhaust steam from the turbine for reuse in the cycle and to maximize turbine efficiency by maintaining proper vacuum. As the operating pressure of the condenser is lowered (vacuum is increased), the enthalpy drop of the expanding steam in the turbine will also increase. This will increase the amount of available work from the turbine (electrical output). By lowering the condenser operating pressure, the following will occur: Increased turbine output Increased plant efficiency
16

Reduced steam flow (for a given plant output) It is therefore very advantageous to operate the condenser at the lowest possible pressure (highest vacuum). FUNCTION OF CONDENSER Function of the condenser is to create a vacuum by condensing steam, Removing dissolved non condensable gases from the condensate Conserving the condensate for re-use as the feed water supply to the steam generator Providing a leak-tight barrier between the high grade condensate contained within the shell and the untreated cooling water Providing a leak-tight barrier against air ingress, preventing excess back pressure on the turbine Serving as a drain receptacle, receiving vapor and condensate from various other plant heat exchangers, steam dumps, and turbine bleed-offs Receptacle for adding DM makeup

CONDENSER

17

CONDENSER OPERATION The main heat transfer mechanisms in a surface condenser are the condensing of saturated steam on the outside of the tubes and the heating of the circulating water inside the tubes. Thus for a given circulating water flow rate, the water inlet temperature to the condenser determines the operating pressure of the condenser. As this temperature is decreased, the condenser pressure will also decrease. As described above, this decrease in the pressure will increase the plant output and efficiency. The non-condensable gases consist of mostly air that has leaked into the cycle. These gases must be vented from the condenser.

REASON FOR REMOVING AIR/GAS The gases will increase the operating pressure of the condenser. This rise in pressure will decrease the turbine output and efficiency. The gases will blanket the outer surface of the tubes. This will severely decrease the heat transfer of the steam to the circulating water. Again, the pressure in the condenser will increase. The corrosiveness of the condensate in the condenser increases as the oxygen content increases. Oxygen causes corrosion, mostly in the steam generator. Thus, these gases must be removed in order to extend the life of cycle components.

CONDENSER TUBE MATERIALS Copper based alloy (ASTM B 111, B543) Stainless steel (ASTM A268, B268, A249, A213, A269) Titanium (ASTM B 338 Gr 1&2) Carbon steel (ASTM A179, A214)

18

CONDENSER IN POWER CYCLE

CONDENSER ASSOCIATED EQUIPMENTS 1 LP Turbine / condenser 2 Turbine / condenser expansion Actuated (manual) (electric joint: motor) (pneumatic) (rubber) (stainless steel) 3 Provisions for feed water 4 LP Turbine extraction: Continuous tube cleaning system Pipes: (Lagging) (Supports) (Expansion joints) Priming system 5 Air removal equipment: Air release valves (vacuum pumps) (steam jet air ejectors) (hybrid pump / ejector system) 6 Pressure relief device: expansion provisions: (rupture disc) (atmospheric relief (spring supported) (expansion valve) joint) (solid mounted) 7 Vacuum breaker valve 8 Instrumentation

19

9 Water box accessories: heaters located in transition Circulating water expansion joints section: (rubber arch type) (Supports) (Closing plates) Gauge glasses (Lagging) Cathodic protection

Effect of Air Ingress


For maximum thermal efficiency, corresponding to a minimum back pressure, a vacuum is maintained in the condenser. However, this vacuum encourages air in- leakage. Thus, to keep the concentration of non-condensable gases as low as possible, the condenser system must be leak tight, together with any part of the condensate system that is under vacuum. Failure to prevent or remove the non-condensable gases may cause serious corrosion in the system, lower heat transfer properties, and/or increase plant heat rate due to the back pressure rise associated with a high in leakage. The cost of excess back pressure in terms of additional fuel or increased heat rate. An adequate air-removal and monitoring system is essential.

SOURCES OF AIR LEAKAGE IN A CONDENSER Atmospheric relief valves or vacuum breakers Rupture disks Drains that pass through the condenser Turbine seals Turbine/condenser expansion joint Tube sheet to shell joints Air-removal suction components Instrumentation, sight glasses, etc. Low-pressure feedwater heaters, associated piping, Valve stems, piping flanges, orifice flanges Manhole Shell welds Condensate pump seals
20

CIRCULATING WATER IN LEAKAGE Circulating water in-leakage into the condenser has been the major source of impurities introduced into the condensate and, thus, has been a major factor in boiler corrosion. There are a number of possible causes of water in- leakage, including: Use of tube materials, such as admiralty brass, that are susceptible to erosion/corrosion Improperly rolled tube joints Poor condenser design leading to tube failures. Improperly supported tubes, which can lead to tube vibration failures Tube manufacturing defects. Water In-Leakage Detection Methods Smoke Thermography Ultrasonics Plastic wrap Foam Water Fill Leak Test Rubber Stoppers Individual Tube ressure/Vacuum Testing Tracer Gas Method HELIUM

Cycle Isolation Generating plants often suffer from power losses/heat rate due to leakages through valves to condenser. Check incoming drain lines, feedwater heater high level dumps, minimum flow valves, and steam traps for leakage or improper operation which could add unexpected heat load to the condenser.

21

To minimize leakages through valves to condenser , Select all control valves (e g emergency drain of heaters) to condenser with leakage class v and Select all isolating /drain valve to condenser with leakage class MSS SP 61.

CONDENSER DESIGN CRITERIA The steam condensing plant shall be designed, manufactured and tested as per HEI (latest edition). The condenser(s) shall be designed for heat load corresponding to unit operation for valves wide open (VWO) conditions, 3% make-up, design condenser pressure . The value of design condenser pressure to be measured at 300 mm above the top row of condenser tubes shall be guaranteed under VWO condition, 3% make-up, design CW inlet temperature and CW flow. The condenser vacuum shall be measured with a vacuum grid utilizing ASME basket tips. The condenser hot well shall be sized for three (3) minute storage capacity (between normal and low-low level). Maximum oxygen content of condensate leaving the condenser shall be 0.015 cc per litre over 50-100% load range.

CONDENSER ( 500 MW )

22

STANDARDS ASME PTC 12.2 -Steam surface condensers HEI - Standards for steam surface condensers TEMA.

STEAM JET AIR EJECTOR


An air ejector or steam ejector is a device which uses the motion of moving fluid (Motive Fluid) to transport another fluid (Suction fluid). It has a wide range of application in steam ejector in boiler condenser, fresh water generator and in priming the centrifugal pump.

It works on the principle of convergent /divergent nozzle as it provides the venturi effect at the point of diffusion as the tube gets narrows at the throat the velocity of the fluid increases and because of the venturi affect it pressure decreases, vacuum will occur in the diffuser throat where the suction line will be provided.

23

The operating medium of an air ejector can be either high-pressure gas or liquid. This is passed through a nozzle and the pressure energy is converted into velocity energy. The highvelocity fluid aspirates the air and the non-condensable gases and the mixture is projected into a diffuser which reconverts the velocity energy into pressure energy.

GLAND STEAM CONDENSER


The gland steam condenser is utilized as a low pressure noncontact feed water heater with the discharge drain flowing to the condenser via the condenser flash box. The gland condenser is fitted with a gland condenser extraction fan to remove any air that accumulates in the top of the gland stream condenser after the steam air mixture is separated. The gland steam condenser is cooled by the condensate extracted from the main condenser and so acting as a feed heater. The gland steam often shares its condenser with the air ejector reducing the cost of having two units A fan is fitted to induce a flow through the system without incurring a negative pressure in the final pocket as this would allow the ingress of air. This is ensured by the fitting on valves to the exhaust line from the glands so enabling the back pressure to be set.

24

FEEDWATER HEATERS IN THERMAL POWER PLANTS


FEED WATER HEATERS A feed water heater is a power plant component used to pre-heat water delivered to a steam generating boiler. In a steam power plant (usually modeled as a Rankine cycle), feed water heaters allow the feed water to be brought up to the saturation temperature very gradually. PURPOSE OF FEED WATER HEATERS Feed water heaters serve three purposes in the power plant. They provide efficiency gains in the steam cycle by increasing the initial water temperature to the boiler, so there is less sensible heat addition which must occur in the boiler, They provide efficiency gains by reducing the heat rejected in the condenser, and they minimize thermal effects in the boiler. Steam is extracted from selected stages in the turbine to shell and tube heat exchangers or to open feed water heaters where the steam and feed water are in direct contact.

FEED WATER HEATERS IN POWER CYCLES

25

FEED WATER HEATERS In shell and tube or closed type feed water heaters the feed water flows through the tubes and the extracted steam condenses on the shell side. The condensed steam from each feed water heater drains successively to the next lower pressure heater and is returned to the feed water through a heater drain pump or through the condenser.

PRESSURE CLASSIFICATION Low Pressure Heater: A heater located (with regard to feedwater flow) between the condensate pump and either the boiler feed pump. It normally extracts steam from the low pressure turbine.

26

High Pressure Heater: A heater located downstream of the boiler feed pump. Typically, the tube side design pressure is at least 100 KG/CM2, and the steam source is the high pressure turbine.

HEATERS TO POWER PLANT CYCLE The heating process by means of extraction steam is referred to as being regenerative. The feed water heaters are an integral portion of the power plant thermodynamic cycle. Normally, there are multiple stages of feed water heating. Each stage corresponds to a turbine extraction point. The presence of the heaters in the cycle enhances the thermal efficiency of the power plant. ORIENTATION Horizontal: Most heaters are of this configuration. These are the most stable in regard to level control, although they occupy more floor space. Disassembly is by means of either shell or bundle removal. Most are floor mounted, although some are mounted in the condenser exhaust neck. Vertical, Channel Down: Although these conserve floor space, the amount of control area available for liquid level fluctuation is less. Disassembly is by shell removal. Installation and removal may be more difficult than for horizontal heaters. Vertical, Channel Up: These are the least frequently used. Disassembly is by means of bundle removal. If a sub cooling zone is present, it must extend the full length of the bundle, since the water must enter the bottom and exit at the top end of the heater.

ZONES
Condensing Zone: All feed waters have this zone. All of the steam is condensed in this area, and any remaining non condensable gases must be removed. A large percentage of the energy added by the heater occurs here. Sub cooling Zone: The condensed steam enters this zone at the saturation temperature and is cooled by convective heat transfer from the incoming feed water.

27

Desuperheating Zone: The incoming steam enters this zone, giving up most of its superheat to the feed water exiting from the heater.

TUBE MATERIAL Both copper alloys & non-ferrous alloys are used for the LP Heaters & HP Heaters tubes. Copper alloys are used extensively in the LP Heaters tubes. These alloys have got excellent thermal conductivity but on the other hand these alloys have problems of copper carry over & ammonia attack, which may require a complex boiler cleaning after short intervals. To avoid all the above problems, the stainless steel tubes are invariably used for LP Heaters. Stainless steel is unaffected at all operating conditions, except that, it is susceptible to chloride induced stress corrosion. Most common materials used for HP Heaters are carbon steel, stainless steel & Monel metal. FEEDWATER HEATER EFFICIENCY Two variables are used to monitor a feed water heaters efficiency. The heater Terminal Temperature Difference or TTD is a measure of how close the outlet feed water temperature is to the feed water heater saturation temperature. The heater Drain Cooler Approach or DCA is a measure of how close the heater drain outlet temperature is to the feed water inlet temperature.
28

ITEMS AFFECT PERFORMANCE OF FEEDWATER HEATERS

Improper heater level can cause flashing in the drain cooler section and tube damage. Check operation of automatic controls and level instrumentation. Check for possible tube leaks in feed water heater. Vent valves may not be set up properly. Improper extraction line pressure drops. Possible problem with extraction line check valve.

Tube fouling due to corrosion affects the heat transfer in the heater. Clean tube bundles x Continuous vent orifice plugging. Channel pass partition/gasket leak.

Efficiency Improvement as an Emissions Control Strategy Feed water heaters are designed into the turbine cycle to improve efficiency (lower heat rate). As the heat rate decreases (heat rate improves), the amount of fuel for the same generation also goes down. Of course with less fuel burned, emissions are lowered. Safety Issue during Tube Leaks As per HEI (14), section 6.1.2 (b), a feed water heater shell-side safety valve shall be sized to pass the flow from a clean break in one tube resulting in the flow from two tubes. If a heater is not isolated promptly when a tube leak occurs, more tubes may be damaged resulting in a higher flow into the shell than the safety can relieve. Obviously as the heater becomes more susceptible to tube leaks, the risk of this scenario increases.

29

HEAT BALANCE SHEET

DEAERATOR
DEAERATOR PRINCIPLE The removal of dissolved gases from boiler feed water is an essential process in a steam system. The presence of dissolved oxygen in feed water causes rapid localized corrosion in boiler tubes. Carbon dioxide will dissolve in water, resulting in low pH levels and the production of corrosive carbonic acid. Low pH levels in feed water causes severe acid attack throughout the boiler system. While dissolved gases and low pH levels in the feed water can be controlled or removed by the addition of chemicals, it is more economical and thermally efficient to remove these gases mechanically. This mechanical process is known as deaeration and will increase the life of a steam system dramatically.
30

Deaeration is based on two scientific principles. The first principle can be described by Henry's Law. Henry's Law asserts that gas solubility in a solution decreases as the gas partial pressure above the solution decreases. The second scientific principle that governs deaeration is the relationship between gas solubility and temperature. Easily explained, gas solubility in a solution decreases as the temperature of the solution rises and approaches saturation temperature. A deaerator utilizes both of these natural processes to remove dissolved oxygen, carbon dioxide, and other non-condensable gases from boiler feed water. The feed water is sprayed in thin films into a steam atmosphere allowing it to become quickly heated to saturation. Spraying feed water in thin films increases the surface area of the liquid in contact with the steam, which, in turn, provides more rapid oxygen removal and lower gas concentrations. This process reduces the solubility of all dissolved gases and removes it from the feed water. The liberated gases are then vented from the deaerator.With these principles in mind, Sterling Deaerator Company employs a two-stage system of heating and deaerating feed water. This system reduces dissolved oxygen concentration to less than 0.005 cc/liter (7 ppb), and completely eliminates the carbon dioxide concentration.
31

Reason to Deaerate The most common source of corrosion in boiler systems is dissolved gas: oxygen, carbon dioxide and ammonia. Of these, oxygen is the most aggressive. The importance of eliminating oxygen as a source of pitting and iron deposition cannot be over-emphasized. Even small concentrations of this gas can cause serious corrosion problems. Makeup water introduces appreciable amounts of oxygen into the system. Oxygen can also enter the feed water system from the condensate return system. Possible return line sources are direct air-leakage on the suction side of pumps, systems under vacuum, the breathing action of closed condensate receiving tanks, open condensate receiving tanks and leakage of nondeaerated water used for condensate pump seal and/or quench water. With all of these sources, good housekeeping is an essential part of the preventive program. One of the most serious aspects of oxygen corrosion is that it occurs as pitting. This type of corrosion can produce failures even though only a relatively small amount of metal has been lost and the overall corrosion rate is relatively low. The degree of oxygen attack depends on the concentration of dissolved oxygen, the pH and the temperature of the water. The influence of temperature on the corrosivity of dissolved oxygen is particularly important in closed heaters and economizers where the water temperature increases rapidly. Elevated temperature in itself does not cause corrosion. Small concentrations of oxygen at elevated temperatures do cause severe problems. This temperature rise provides the driving force that accelerates the reaction so that even small quantities of dissolved oxygen can cause serious corrosion. Operation Mechanical deaeration is the first step in eliminating oxygen and other corrosive gases from the feed water. Free carbon dioxide is also removed by deaeration, while combined carbon dioxide is released with the steam in the boiler and subsequently dissolves in the condensate. This can cause additional corrosion problems. Because dissolved oxygen is a constant threat to boiler tube integrity, this discussion on the deaerator will be aimed at reducing the oxygen content of the feed water. The two major types of deaerators are the tray type and the spray type. In both cases, the major portion of gas removal is accomplished by spraying cold makeup water into a steam environment.
32

Tray-Type Deaerating Heaters

Tray-type deaerating heaters release dissolved gases in the incoming water by reducing it to a fine spray as it cascades over several rows of trays. The steam that makes intimate contact with the water droplets then scrubs the dissolved gases by its counter-current flow. The steam heats the water to within 3-5 F of the steam saturation temperature and it should remove all but the very last traces of oxygen. The deaerated water then falls to the storage space below, where a steam blanket protects it from recontamination. Nozzles and trays should be inspected regularly to insure that they are free of deposits and are in their proper position

Spray-Type Deaerating Heaters

Spray-type deaerating heaters work on the same general philosophy as the tray-type, but differ in their operation. Spring-loaded nozzles located in the top of the unit spray the water into a steam atmosphere that heats it. Simply stated, the steam heats the water, and at the elevated temperature the solubility of oxygen is extremely low and most of the dissolved gases are removed from the system by venting. The spray will reduce the dissolved oxygen content to 2050 ppb, while the scrubber or trays further reduce the oxygen content to approximately 7 ppb or less.

During normal operation, the vent valve must be open to maintain a continuous plume of vented vapors and steam at least 18 inches long. If this valve is throttled too much, air and
33

non-condensable gases will accumulate in the deaerator. This is known as air blanketing and can be remedied by increasing the vent rate. For optimum oxygen removal, the water in the storage section must be heated to within 5 F of the temperature of the steam at saturation conditions. From inlet to outlet, the water is deaerated in less than 10 seconds. The storage section is usually designed to hold enough water for 10 minutes of boiler operation at full load.

Spray Cum Tray type Deaerator

Deaeration is based on two scientific principles. The first principle can be described by Henry's Law. Henry's Law asserts that gas solubility in a solution decreases as the gas partial pressure above the solution decreases. The second scientific principle that governs deaeration is the relationship between gas solubility and temperature. Easily explained, gas solubility in a solution decreases to almost zero as the temperature of the solution rises and approaches saturation temperature. A deaerator utilizes both of these natural processes to remove dissolved oxygen, carbon dioxide, and other non-condensable gases from boiler feed water. The feed water is sprayed in thin films into a steam atmosphere allowing it to become quickly heated to saturation temperature. Spraying feed water in thin films increases the surface area of the liquid in contact with the steam, which, in turn, provides more rapid oxygen removal and lower gas concentrations. This process reduces the solubility of all dissolved gases and removes it from the feed water. The liberated gases are then vented from the deaerator.

34

It is of spray and trays type deaerator consist of a feed water storage tank and vapour tank with vent condenser.

Water is sprayed from the top of vapour tank through ten spray nozzles on set of multilevel perforated trays below it for easy and complete scrubbing with steam.

Steam is fed in storage tank through distribution header below the water level. Partial scrubbing of steam with water takes place by raising the water temperature (Since solubility of gases like oxygen carbon dioxide decreases with increase in water temperature).

35

CONCLUSION

Study was conducted at BHEL, Hyderabad on Heat Exchangers used in thermal power plant application and the modification done in the rankine cycle by regenerative and reheat process is studied for the better performance and to increase the efficiency and output of the power plant.