You are on page 1of 4

Product data sheet

3VL4731-1DC36-2SB1
CIRCUIT-BREAKER VL 400N STANDARD BREAKING CAPACITY ICU=55KA / 415 V AC 3 POLE, LINE PROTECTION OVERCURRENT RELEASE TM, LI IN=315A, RATED CURRENT IR=250-315A, OVERLOAD II=1575-3150A, SHORT CIRCUIT

Similar to image

General technical data:


Number of poles Design of the overcurrent release Acceptability for application Electrical operating cycles as operating time / typical Mechanical operating cycles as operating time / typical Active power loss / maximum Product component auxiliary switch Voltage trigger undervoltage release mechanism undervoltage release with leading contact Product function of the thermal overload release ground-fault protection for zero conductors / short-circuit and overload protection overload protection Operating cycles / maximum Protection class IP 1/s adjustable No No Yes 120 IP20 Yes No Yes No W 3 TM system protection 10,000 20,000 175

3VL4731-1DC36-2SB1 Page 1/ 4

11/13/2013

subject to modifications Copyright Siemens AG 2013

Protective function of the overcurrent release Impulse voltage resistance / rated value Ambient temperature during operating during storage C C kV

LI 8

0 70 -40 +80

Main circuit:
Insulation voltage / for AC / rated value Operating frequency 1 / rated value 2 / rated value Item designation according to DIN 40719 extendable after IEC 204-2 / according to IEC 750 according to DIN EN 61346-2 Operating voltage / for main circuit at 50 Hz / with AC maximum at 60 Hz / with AC maximum Operating voltage / for main current circuit / for DC maximum Operating current at 40 C / rated value at 50 C / rated value at 60 C / rated value at 70 C / rated value Continuous current / rated value Derating temperature / for the rated value of the continuous current A A A A A C 315 315 293 270.9 315 50 V 500 V 690 V 690 Q Hz Hz 50 60 V 800

Auxiliary circuit:
Number of NC contacts / for auxiliary contacts Number of NO contacts / for auxiliary contacts 1 1

Short-circuit:
Adjustable response current of the current-dependent overload release of the non-delayed short-circuit release Breaking capacity limit short-circuit current (lcu) / at 415 V / rated value A A kA 252 315 1,575 3,150 55

3VL4731-1DC36-2SB1 Page 2/ 4

11/13/2013

subject to modifications Copyright Siemens AG 2013

Installation/mounting/dimensions:
Type of mounting Height Width Depth mm mm mm fixed mounting 279.5 139 163.5

Connections:
Arrangement of electrical connectors / for main current circuit Design of the electrical connection / for main current circuit Type of the connectable conductor cross-section for main contacts solid stranded for auxiliary contacts solid finely stranded / with conductor end processing 0.75 ... 1.5 mm 0,75 ... 1.0 mm 50 ... 300 mm 50 ... 300 mm front side screw-type terminals

Certificates/approvals:
General Product Approval Declaration of Conformity KTL Test Certificates

Special Test Certificate

Shipping Approval

other Confirmation other Environmental Confirmations

Further information:
Information- and Downloadcenter (Catalogs, Brochures,) http://www.siemens.com/lowvoltage/catalogs Industry Mall (Online ordering system) http://www.siemens.com/lowvoltage/mall Service&Support (Manuals, Certificates, Characteristics, FAQs,...) http://support.automation.siemens.com/WW/view/en/3VL4731-1DC36-2SB1/all Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...) http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3VL4731-1DC36-2SB1 CAx-Online-Generator http://www.siemens.com/cax

3VL4731-1DC36-2SB1 Page 3/ 4

11/13/2013

subject to modifications Copyright Siemens AG 2013

Tender specifications Datanorm GAEB81 GAEB83 RTF TXT

last change:

Aug 12, 2013

3VL4731-1DC36-2SB1 Page 4/ 4

11/13/2013

subject to modifications Copyright Siemens AG 2013

You might also like