Professional Documents
Culture Documents
BG0426 Rev. A3
Every effort has been made to ensure that the material herein is complete and accurate. However, the manufacturer is not responsible for any mistakes in printing or faulty instructions contained in this book. Notification of any errors or misprints will be received with appreciation. For further information regarding a particular installation, operation or maintenance of equipment, contact the manufacturer or your local representative or distributor.
REVISION HISTORY
A1 A2 Nov 2007 Dec 2009 Release F/W versions 11.1.11 or higher. Added time triggers. F/W versions 11.2.1 or higher. Added 8 tariffs. F/W versions 11.3.1 or higher. Added event and data log setup and file transfer registers. A3 Jun 2010 F/W versions 11.3.3 or higher. Added kVAh import/export and 4-quadrant kvarh registers.
Table of Contents
1 GENERAL ..........................................................................................................7 2 ASCII PROTOCOL DESCRIPTION....................................................................8
2.1 ASCII Framing ................................................................................................. 8 2.1.1 ASCII Message Frame .........................................................................................8 2.2 Exception Responses........................................................................................ 9 2.3 Protocol Implementation ................................................................................. 9 2.3.1 ASCII Specific and Direct Requests .......................................................................9 2.3.2 Data Formats................................................................................................... 10 2.4 Direct Read/Write Request ............................................................................ 10 2.4.1 General .......................................................................................................... 10 2.4.2 Long-Size Direct Read/Write .............................................................................. 10 2.4.3 Variable-Size Direct Read/Write.......................................................................... 11 2.4.4 User Assignable Registers.................................................................................. 11 2.5 Password Protection ...................................................................................... 12 2.6 Data Recording and File Transfers ................................................................. 12 2.6.1 Log File Organization ........................................................................................ 12 Multi-section Files ............................................................................................... 12 Data Log Files .................................................................................................... 13 Profile Data Log File ............................................................................................ 13 Real-time Waveforms .......................................................................................... 13 2.6.2 File Transfers................................................................................................... 13 Common File Transfer ......................................................................................... 13 Reading a Daily Profile Log File ............................................................................. 14 Reading Real-time Waveforms .............................................................................. 14
4.2
Analog Registers, Binary Registers and Counters........................................... 21 Special Inputs .................................................................................................... 21 Digital Inputs DI1-DI4 (bitmap) ............................................................................ 21 Relay Outputs RO1-RO2 (bitmap).......................................................................... 21 Counters ........................................................................................................... 21 1-Cycle Phase Values .......................................................................................... 21 1-Cycle Total Values............................................................................................ 22 1-Cycle Auxiliary Values ...................................................................................... 22 Phasor .............................................................................................................. 23 1-Second Phase Values........................................................................................ 23 1-Second Total Values ......................................................................................... 24 1-Second Auxiliary Values .................................................................................... 24 Present Volt, Ampere and Power Demands ............................................................. 24 Total Energies E .................................................................................................. 25 Summary Energy Registers E ................................................................................ 26 Phase Energies E ................................................................................................. 26 V1/V12 Harmonic Distortion EH .............................................................................. 26 V2/V23 Harmonic Distortion EH .............................................................................. 26 V3/V31 Harmonic Distortion EH .............................................................................. 26 I1 Harmonic Distortion EH ..................................................................................... 26 I2 Harmonic Distortion EH ..................................................................................... 27 I3 Harmonic Distortion EH ..................................................................................... 27 Fundamental Phase Values EH ............................................................................... 27 Fundamental Total Values EH................................................................................. 27 Minimum 1-Cycle Phase Values ............................................................................. 27 Minimum 1-Cycle Total Values .............................................................................. 28 Minimum 1-Cycle Auxiliary Values ......................................................................... 28 Maximum 1-Cycle Phase Values ............................................................................ 28 Maximum 1-Cycle Total Values ............................................................................. 28 Maximum 1-Cycle Auxiliary Values ........................................................................ 28 Maximum Demands ............................................................................................ 28 TOU Parameters E ............................................................................................... 29 Scaled Analog Outputs......................................................................................... 29 TOU Energy Register #1 E .................................................................................... 29 TOU Energy Register #2 E .................................................................................... 29 TOU Energy Register #3 E .................................................................................... 29 TOU Energy Register #4 E .................................................................................... 29 Summary Energy Accumulated Demands E ............................................................. 29 Summary Energy Block Demands E........................................................................ 29 Summary Energy Sliding Window Demands E .......................................................... 30 Summary Energy Maximum Demands E.................................................................. 30 TOU Maximum Demand Register #1 E .................................................................... 30 TOU Maximum Demand Register #2 E .................................................................... 30 TOU Maximum Demand Register #3 E .................................................................... 30 TOU Maximum Demand Register #4 E .................................................................... 30 V1/V12 Harmonic Angles EH .................................................................................. 30 V2/V23 Harmonic Angles EH .................................................................................. 30 V1/V31 Harmonic Angles EH .................................................................................. 31 I1 Harmonic Angles EH ......................................................................................... 31 I2 Harmonic Angles EH ......................................................................................... 31 I3 Harmonic Angles EH ......................................................................................... 31 Setpoint Status SP1-SP16 (bitmap) ....................................................................... 31 4.3 Minimum/Maximum Log Registers ................................................................. 32 Minimum Phase Values ........................................................................................ 32 Minimum Total Values ......................................................................................... 32 Minimum Auxiliary Values .................................................................................... 32 Maximum Phase Values ....................................................................................... 32 Maximum Auxiliary Values ................................................................................... 33 Summary Energy Maximum Demands E.................................................................. 33
4.4
4.5
4.6
4.7
4.8
Maximum Demands ............................................................................................ 33 TOU Maximum Demand Register #1 E .................................................................... 34 TOU Maximum Demand Register #2 E .................................................................... 34 TOU Maximum Demand Register #3 E .................................................................... 34 TOU Maximum Demand Register #4 E .................................................................... 34 Device Control and Status Registers .............................................................. 36 Device Authorization Register ............................................................................... 36 Remote Relay Control.......................................................................................... 36 Device Reset/Clear Registers ................................................................................ 36 Device Status Registers ....................................................................................... 36 Alarm Notification Registers ................................................................................. 36 Device Setup Registers .................................................................................. 38 Device Identification............................................................................................ 38 Factory Device Settings ....................................................................................... 38 Communication Ports Setup ................................................................................. 38 Basic Setup........................................................................................................ 39 Device Options Setup .......................................................................................... 39 Digital Inputs Setup ............................................................................................ 39 Alarm/Event Setpoints Setup................................................................................ 40 Local Settings .................................................................................................... 40 TOU Daily Profile Setup E ..................................................................................... 41 TOU Calendar Setup E .......................................................................................... 41 Summary Energy/TOU Registers Setup E ................................................................ 42 Summary Energy/TOU Registers Source Setup E ...................................................... 42 Digital Inputs Setup ............................................................................................ 42 Relay Outputs Setup ........................................................................................... 43 Analog and Digital I/O Configuration ............................................................. 44 I/O Slots Configuration Info ................................................................................. 44 I/O Type Info ..................................................................................................... 44 File Transfer Registers E ................................................................................. 45 File Allocation Status Registers ............................................................................. 45 File Transfer Control/Status Registers .................................................................... 45 Data Log File Transfer Registers............................................................................ 46 Event Log File Transfer Registers .......................................................................... 46 Waveform Header Transfer Registers ..................................................................... 47 Waveform Series Transfer Block............................................................................ 47 Billing/TOU Daily Profile Data Log E ............................................................... 49
Counter Source ID .............................................................................................. 54 Relay Output Pulse Source ID ............................................................................... 54 AO Output Parameters ID .................................................................................... 54 Event Cause/Point ID .......................................................................................... 55 Event Effect ID ................................................................................................... 55 Data Point ID ..................................................................................................... 56 Device Diagnostics .............................................................................................. 56 Instrument Options ............................................................................................. 56 I/O Slot Types .................................................................................................... 57 Reset/Clear Function ........................................................................................... 57 Basic Setup Parameters ID ................................................................................... 57
1 General
This document specifies the SATEC ASCII serial communications protocol used to transfer data between a master computer station and the PM130. The document provides the complete information necessary to develop third-party communications software capable of communication with the Series PM130 instruments. For additional information concerning operating the device, configuring the communication parameters, and communication connections see the PM130 PLUS Installation and Operation Manual. The document is applicable to PM130A, PM130P, PM130E and PM130EH meters.
IMPORTANT
In 3-wire connection schemes, the unbalanced current and phase readings for power factor, active power, and reactive power will be zeros, because they have no meaning. Only the total three-phase power values are provided. Most of the advanced features are configured using multiple setup parameters that can be accessed in a number of contiguous registers. When writing the setup registers, it is recommended to write all the registers at once using a single request, or to clear (zero) the setup before writing into separate registers.
Designations used in the guide: E - available in the PM130E and PM130EH EH - available in the PM130EH
SYNC Synchronization character: one character '!' (ASCII 33), used for starting synchronization. Message length The length of the message including only number of bytes in fields #2, #3, #4 and #5. Contains three characters between '006' and '252'. Slave address Contains two characters from '00' to '99'. The instrument with address '00' responds to requests with any incoming address. For RS-422/RS-485 communications (multi-drop mode), this field must NEVER be zero. Message type Consists of one character representing the type of a host request. A list of the message types is shown in Tables 2-1 and 2-2. Note that they are case-sensitive. Message body Contains the message parameters in ASCII representation. All parameter fields have a fixed format. The data fields vary in length depending on the data type. Unless otherwise indicated, the parameters should be right justified and left-padded with zeros. Most parameters are represented in ASCII hexadecimal notation, and in some cases (to provide compatibility with old devices) a decimal representation is preserved. For data formats, see Section 3.2. Checksum Arithmetic sum, calculated in a 2-byte word over fields #2, #3, #4 and #5 to produce a onebyte check sum in the range of 0x22 to 0x7E (hexadecimal) as follows: [(each byte 0x22)] mod 0x5C + 0x22 Trailer The message termination consisting of two ASCII characters CR (ASCII 13) and LF (ASCII 10).
NOTE Fields #3 and #4 of the instrument response are always the same as those in the host request.
10
+0 +4 +0 +4
+0 +4 +0 +2
+0 +4 +6
+0 +4
11
- write 0x0C00 to point 0x8100 - write 0x1700 to point 0x8101 Reading from points 0x8000-0x8001 will return the voltage reading through point 0x8000, and the kWh reading through point 0x8001.
12
are associated with the same event. A multi-section file has also a single read position pointer for all sections. Data Log Files Data log files can store up to 9 measured parameters per a record. Any data measured by the device can be stored in the log file. The number of parameters that each record will hold and the list of parameters you want to be recorded in the file can be selected through the Data log setup registers for a particular file. Recording data to the data log files can be triggered through the setpoints, either on a time basis using the meter clock or periodic timers, or upon any event detected by setpoints. Profile Data Log File Data log file #16 can be configured for a daily profile log of the energy usage and maximum demand registers. A profile log file is organized as a multi-section file that has a separate section for each energy and maximum demand register. A file record stores the summary data (total of all tariffs) and all tariff data for each configured Summary/TOU register. See Section 4.8 for information on the file record structure. The number of sections is taken automatically from the Summary/TOU Registers setup. Since each Summary/TOU energy register has a shadow maximum demand register, the number of sections in the file can be twice the number of the allocated Summary/TOU registers. Always configure the Summary/TOU registers before you allocate memory for your profile log file. New records are added to the file automatically every day at midnight. You can review the list of parameters that are recorded to the file through the Data log #16 setup. It is preset automatically by the meter and shows the recorded data for the first file section, which represents the first configured energy usage register. Real-time Waveforms Real-time waveforms are read as a multi-section file that stores data for each recording channel in a separate section. A real-time waveform contains six AC channels - three voltage and three current waveforms, which are recorded in successive sections. A single waveform record for a channel contains 512 points of the sampled input signal. Refer to the line frequency field in the channel header record to correctly set up the time scale for the waveforms.
13
For the event log files, the file transfer block can contain up to 6 records that can be read at once: the file position automatically moves to the record following the last one you have just read in the file transfer block. The file transfer is completed after you have read the last record of the file. Before storing a file record to your database, always check bit 1 in the record status word, which contains the endof-file (EOF) flag. This bit set to 1 indicates that the file read pointer does not point to any record within the file, and you should not store any record that has this bit set. The EOF flag is set only after you have read the last record of the file, so that testing for end-of-file requires one extra read. If you wish to stop the transfer just after storing the last file record, check bit 0 in the record status word. Bit 0 is set to 1 only once when you read the last record of the file. The following gives a summary of steps you should do to read an ordinal log file: 1. If you want to begin reading a file from a particular record or from the first record, either set the file position to the desired record sequence number, or preset the file position to point to oldest record. 2. Read the record data through the corresponding file transfer block. The file pointer will be automatically moved to the next file record. 3. Repeat steps 1-2 until all the file records are read, i.e., until either bit 0 or bit 1 is set in the record status word. Reading a Daily Profile Log File Reading a multi-section profile log file does not differ from reading ordinal files with the only exception that each file section is accessed through a separate transfer block. If you want to know which registers are recorded to the file sections before reading them, check the daily profile log sections map through point 0xA0F4 (see Section 4.7, File Transfer Registers). This is a bitmap that contains one in a bit position if a designated register is recorded to the file, and contains zero if it is not. The following gives a summary of steps for a multi-section file: 1. If you want to begin reading a file section from a particular record or from the first record, either set the file section position to the desired record sequence number, or preset the file section position to point to oldest record. 2. Read the record data through the corresponding file section transfer block. The file pointer automatically moves to the next file record. 3. Repeat steps 1-2 until all the file section records are read, i.e., until either bit 0 or bit 1 is set in the record status word. Reading Real-time Waveforms Each waveform record consists of six channel records that are read in sequence always starting with channel V1. Each channels data is read in two stages. The channel header record is read first through a separate transfer block followed be reading the channel sample series. Each time you read the V1 channel header record, the meter captures new waveforms to the buffer so that you can then read all of them through the waveform transfer blocks. The following gives a summary of steps for reading real-time waveforms: 1. Read the V1 channel header data through the corresponding real-time waveform header transfer block. The captured waveforms data is moved to the ports communication buffer. 2. Read the V1 channel sample series through the waveform series transfer block. 3. Read the next channels header data through the corresponding waveform header transfer block. 4. Read the sample series for the selected channel through the waveform series transfer block. 5. Repeat steps 3, 4 until all channels records are read.
14
Range
Units
Type
R/W
Notes
+0 +4 +8 +12 +17 +22 +27 +33 +39 +45 +49 +53 +57 +63 +67 +73 +78 +82 +88 +94 +100 +106 +112 +118 +124 +130 +136 +142 +148 +153 +158 +163 +165
4 4 4 5 5 5 6 6 6 4 4 4 6 4 6 5 4 6 6 6 6 6 6 6 6 6 6 6 5 5 5 2 6
15
Offset +171 +177 +181 +185 +189 +193 +197 +201 +209 +215 +221 +225 +229 +233 NOTES:
Length 6 4 4 4 4 4 4 8 6 6 4 4 4 4
Description Maximum sliding window kVA demand 5 V1/V12 Voltage THD V2/V23 Voltage THD V3/V31 Voltage THD I1 Current THD I2 Current THD I3 Current THD kVAh total Present sliding window kW import demand Present sliding window kVA demand 5 PF (import) at maximum KVA demand I1 Current TDD I2 Current TDD I3 Current TDD
Range 0 to Pmax 0.0 to 999. 0.0 to 999. 0.0 to 999. 0.0 to 999. 0.0 to 999. 0.0 to 999. 0 to 99999.99 0 to Pmax 0 to Pmax 0 to 1.00 0.0 to 99.9 0.0 to 99.9 0.0 to 99.9
Units U3 % % % % % % MVAh U3 U3 % % %
Type
R/W
1 1
Notes 3-sec value 3-sec value 1 3-sec value 3-sec value 3-sec value 3-sec value
3
Energy and power demand readings are only available in PM130E and PM130EH meters. Total harmonics are only available in PM130EH meters.
1
Voltage and voltage harmonics readings: when the 4LN3, 3LN3 or 3BLN3 wiring mode is selected, the voltages will be line-to-neutral; for any other wiring mode, they will be line-to-line voltages. All analog registers except of harmonics are 1-second average values. For volts, amps and power scales and units, refer to Section 5 Data Scales and Units. When ASCII compatibility mode is disabled (see Section 5.5), voltages, currents and powers are transmitted with a decimal point in units defined in the table. When the value is greater than the field width, the right most digits of the fractional part are truncated. When ASCII compatibility mode is enabled, the meter provides a fully downward-compatible response using a lower resolution for voltages, currents and powers - the value is transmitted as a whole number until the field is filled up, and then it is converted to higher units and transmitted with a decimal point. If the value is greater than the field width, the right most digits of the fractional part are truncated. Voltages are transmitted in volts as whole numbers or in kilovolts with a decimal point, currents in amperes as whole numbers, and powers in kilowatts as whole numbers or in megawatts with a decimal point.
Energy readings are transmitted in MWh, Mvarh and MVAh units with a decimal point. If the energy value exceeds the field width, the right-most digits are truncated. If you use these request for energy readings, then, to avoid overflow, limit the energy roll value (see Device Options Setup) to 7 digits if you use kvarh net reading or to 8 digits if you do not use it. For negative power factor, the minus sign is transmitted before a decimal point as shown in the table.
+0 +1
16
Offset Length Warm Restart Message Type Request Body Response Body Firmware Version
Range
Units
Type
R/W
Notes
+0 +4 Device Status
Message Type Request Body Response Body 4 Firmware version number 2 Firmware build number Message Type Request Body Response Body Relay status (bitmap) Not used Digital (status) inputs (bitmap) Setpoints status (bitmap) Not used
Two higher decimal digits = major version number, two lower decimal digits = minor version number
+0 +4 +8 +12 +16
4 4 4 4 40
3 3 4 6
Message Type Request Body (decimal): +0 3 Parameter ID +3 4 Not used +7 6 Parameter value Response the same as request Read Analog Output Setup Message Type
17
Description Request Body +0 2 Analog channel number Response Body (hexadecimal) +0 2 Analog channel number +2 4 Output parameter point ID +6 8 Zero scale (0/4 mA) +14 8 Full scale (20/1 mA) Write Analog Output Setup Message Type Request Body (hexadecimal) +0 2 Analog channel number +2 4 Output parameter point ID +6 8 Zero scale (0/4 mA) +14 8 Full scale (20/1 mA) Response Body the same as request Read Pulse Counter Setup Message Type Request Body +0 2 Counter ID Response Body (hexadecimal) +0 2 Counter ID +2 2 Source ID +4 4 Multiplier Write Pulse Counter Setup Message Type Request Body (hexadecimal) +0 2 Counter ID +2 2 Source ID +4 4 Multiplier +2 4 Timer interval Response Body the same as request Read File Setup E Message Type Request Body (hexadecimal) +0 2 File ID Response Body (hexadecimal) +0 2 File ID +2 8 Allocated file size, bytes +10 4 Number of records in the file +14 4 File record size, bytes +18 2 The number of parameters per record +20 2 File attributes
Offset
Length
Range 0-1=channel AO1-AO2 0-1=channel AO1-AO2 F18 See Section 4.2 See Section 4.2 b 0-1=channel AO1-AO2 F18 See Section 4.2 See Section 4.2
Units
Type
R/W
Notes
J 0-3=counter #1-#4 0-3=counter #1-#4 0=not assigned, 1-4=DI1-DI4 1-9999 j 0-3=counter #1-#4 0=not assigned, 1-2=DI1-DI2 1-9999 1-9999, 0=timer disabled
K F8 F8 0-65535 0-16 F3
18
Description Message Type Request Body (hexadecimal) 2 File ID 4 Number of records in the file 2 The number of parameters per record 2 File attributes Response Body (hexadecimal) 2 File ID Message Type Request Body (hexadecimal) Data log ID Response Body (hexadecimal) Data log ID Number of parameters per record Data log parameter #1 point ID Data log parameter #2 point ID Data log parameter #3 point ID Data log parameter #4 point ID Data log parameter #5 point ID Data log parameter #6 point ID Data log parameter #7 point ID Data log parameter #8 point ID Data log parameter #9 point ID Message Type Request Body (hexadecimal) Data log ID Number of parameters per record Data log parameter #1 point ID Data log parameter #2 point ID Data log parameter #3 point ID Data log parameter #4 point ID Data log parameter #5 point ID Data log parameter #6 point ID Data log parameter #7 point ID Data log parameter #8 point ID Data log parameter #9 point ID Response Body (hexadecimal) Data log ID k
Range
Units
Type
R/W
Notes
F8 1-65535, 0=delete a file 0-9 F3 F8 L 0=Data log #1, 15=Data log #16 0=Data log #1, 15=Data log #16 1-9, 0=file does not exist See Section 4.2
+0
+0 2 +2 2 +4 4 +8 4 +12 4 +16 4 +20 4 +24 4 +28 4 +32 4 +36 4 Write Data Log Setup E
l 0=Data log #1, 15=Data log #16 1-9 See Section 4.2
2 2 4 4 4 4 4 4 4 4 4 2
19
Description Message Type Request Body Response Body (decimal) Second Minute Hour Day Month Year Day of week Message Type Request Body (decimal) Second Minute Hour Day Month Year Day of week Response Body the same as request S No
Range
Units
Type
R/W
Notes
2 2 2 2 2 2 2
0-59 0-59 0-23 1-31 1-12 0-99 1-7 (1=Sunday) T 0-59 0-59 0-23 1-31 1-12 0-99 1-7 (1=Sunday)
+0 +2 +4 +6 +8 +10 +12
2 2 2 2 2 2 2
20
Units
Type UINT16 UINT16 UINT16 UINT16 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32
Notes
21
Point ID 0x0C06 0x0C07 0x0C08 0x0C09 0x0C0A 0x0C0B 0x0C0C 0x0C0D 0x0C0E 0x0C0F 0x0C10 0x0C11 0x0C12 0x0C13 0x0C14 0x0C15 0x0C16 0x0C17 0x0C18 0x0C19 0x0C1A 0x0C1B 0x0C1C 0x0C1D 0x0C1E 0x0C1F 0x0C20 0x0F00 0x0F01 0x0F02 0x0F03 0x0F04 0x0F05 0x0F06 0x0F07 0x0F08 0x0F09 0x0F0A 0x0F0B 0x0F0C 0x1000
Description kW L1 kW L2 kW L3 kvar L1 kvar L2 kvar L3 kVA L1 kVA L2 kVA L3 Power factor L1 Power factor L2 Power factor L3 V1/V12 Voltage THD V2/V23 Voltage THD V3/V31 Voltage THD I1 Current THD I2 Current THD I3 Current THD I1 K-Factor I2 K-Factor I3 K-Factor I1 Current TDD I2 Current TDD I3 Current TDD V12 Voltage V23 Voltage V31 Voltage 1-Cycle Total Values Total kW Total kvar Total kVA Total PF Total PF lag Total PF lead Total kW import Total kW export Total kvar import Total kvar export 3-phase average L-N/L-L voltage 3-phase average L-L voltage 3-phase average current 1-Cycle Auxiliary Values Not used
Options/Range -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax 0-Pmax 0-Pmax 0-Pmax -1000-1000 -1000-1000 -1000-1000 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 10-9999 10-9999 10-9999 0-1000 0-1000 0-1000 0-Vmax 0-Vmax 0-Vmax -Pmax-Pmax -Pmax-Pmax 0-Pmax -1000-1000 0-1000 0-1000 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Vmax 0-Vmax 0-Imax
Units U3 U3 U3 U3 U3 U3 U3 U3 U3 0.001 0.001 0.001 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1 0.1 0.1 0.1% 0.1% 0.1% U1 U1 U1 U3 U3 U3 0.001 0.001 0.001 U3 U3 U3 U3 U1 U1 U2
Type INT32 INT32 INT32 INT32 INT32 INT32 UINT32 UINT32 UINT32 INT16 INT16 INT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 INT32 INT32 UINT32 INT16 UINT16 UINT16 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32
R/W R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R
Notes
2-cycle value 2-cycle value 1 2-cycle value 2-cycle value 2-cycle value 2-cycle value 2-cycle value 2-cycle value 2-cycle value 2-cycle value 2-cycle value 2-cycle value
1
22
Point ID 0x1001 0x1002 0x1003 0x1004 0x1080 0x1081 0x1082 0x1083 0x1084 0x1085 0x1086 0x1087 0x1088 0x1089 0x108A 0x108B 0x108C 0x108D 0x108E 0x108F 0x1100 0x1101 0x1102 0x1103 0x1104 0x1105 0x1106 0x1107 0x1108 0x1109 0x110A 0x110B 0x110C 0x110D 0x110E 0x110F 0x1110 0x1111 0x1112 0x1113 0x1114
Description In (neutral) Current Frequency Voltage unbalance Current unbalance Phasor V1/V12 Voltage magnitude V2/V23 Voltage magnitude V3/V31 Voltage magnitude Not used I1 Current magnitude I2 Current magnitude I3 Current magnitude Not used V1/V12 Voltage angle V2/V23 Voltage angle V3/V31 Voltage angle Not used I1 Current angle I2 Current angle I3 Current angle Not used 1-Second Phase Values V1/V12 Voltage V2/V23 Voltage V3/V31 Voltage I1 Current I2 Current I3 Current kW L1 kW L2 kW L3 kvar L1 kvar L2 kvar L3 kVA L1 kVA L2 kVA L3 Power factor L1 Power factor L2 Power factor L3 V1/V12 Voltage THD V2/V23 Voltage THD V3/V31 Voltage THD
Options/Range 0-Imax 0-Fmax 0-3000 0-3000 0-Vmax 0-Vmax 0-Vmax 0-Imax 0-Imax 0-Imax -1800-1800 -1800-1800 -1800-1800 -1800-1800 -1800-1800 -1800-1800
Units U2 0.01Hz 0.1% 0.1% U1 U1 U1 U2 U2 U2 0.1 0.1 0.1 0.1 0.1 0.1
Type UINT32 UINT16 UINT16 UINT16 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 INT16 INT16 INT16 INT16 INT16 INT16 INT16 INT16 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 INT32 INT32 INT32 INT32 INT32 INT32 UINT32 UINT32 UINT32 INT16 INT16 INT16 UINT16 UINT16 UINT16
R/W R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R
1 1 1
Notes
1 1 1
0-Vmax 0-Vmax 0-Vmax 0-Imax 0-Imax 0-Imax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax 0-Pmax 0-Pmax 0-Pmax -1000-1000 -1000-1000 -1000-1000 0-9999 0-9999 0-9999
1 1 1
23
Point ID 0x1115 0x1116 0x1117 0x1118 0x1119 0x111A 0x111B 0x111C 0x111D 0x111E 0x111F 0x1120 0x1400 0x1401 0x1402 0x1403 0x1404 0x1405 0x1406 0x1407 0x1408 0x1409 0x140A 0x140B 0x140C 0x1500 0x1501 0x1502 0x1503 0x1504 0x1600 0x1601 0x1602 0x1603 0x1604 0x1605 0x1606 0x1607 0x1608 0x1609
Description I1 Current THD I2 Current THD I3 Current THD I1 K-Factor I2 K-Factor I3 K-Factor I1 Current TDD I2 Current TDD I3 Current TDD V12 Voltage V23 Voltage V31 Voltage 1-Second Total Values Total kW Total kvar Total kVA Total PF Total PF lag Total PF lead Total kW import Total kW export Total kvar import Total kvar export 3-phase average L-N/L-L voltage 3-phase average L-L voltage 3-phase average current 1-Second Auxiliary Values Not used In (neutral) Current Frequency Voltage unbalance Current unbalance Present Volt, Ampere and Power Demands V1/V12 Volt demand V2/V23 Volt demand V3/V31 Volt demand I1 Ampere demand I2 Ampere demand I3 Ampere demand kW import block demand kvar import block demand kVA block demand kW import sliding window demand
Options/Range 0-9999 0-9999 0-9999 10-9999 10-9999 10-9999 0-1000 0-1000 0-1000 0-Vmax 0-Vmax 0-Vmax -Pmax-Pmax -Pmax-Pmax 0-Pmax -1000-1000 0-1000 0-1000 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Vmax 0-Vmax 0-Imax
Units 0.1% 0.1% 0.1% 0.1 0.1 0.1 0.1% 0.1% 0.1% U1 U1 U1 U3 U3 U3 0.001 0.001 0.001 U3 U3 U3 U3 U1 U1 U2
Type UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 INT32 INT32 UINT32 INT16 UINT16 UINT16 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT16 UINT16 UINT16 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32
R/W R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R
Notes 3-sec 3-sec 3-sec 3-sec 3-sec 3-sec 3-sec 3-sec 3-sec value value value value value value value value value
0-Imax 0-Fmax 0-3000 0-3000 0-Vmax 0-Vmax 0-Vmax 0-Imax 0-Imax 0-Imax 0-Pmax 0-Pmax 0-Pmax 0-Pmax
1 1 1
24
Point ID 0x160A 0x160B 0x160C 0x160D 0x160E 0x160F 0x1610 0x1611 0x1612 0x1613 0x1614 0x1615 0x1616 0x1617 0x1618 0x1619 0x161A 0x161B 0x161C 0x161D 0x161E 0x161F 0x1620 0x1621 0x1622 0x1700 0x1701 0x1702 0x1703 0x1704 0x1705 0x1706 0x1707 0x1708 0x1709 0x170A 0x170B 0x170C 0x170D 0x170E 0x170F 0x1710
Description kvar import sliding window demand kVA sliding window demand Not used Not used Not used kW import accumulated demand kvar import accumulated demand kVA accumulated demand kW import predicted sliding window demand kvar import predicted sliding window demand kVA predicted sliding window demand PF (import) at Max. kVA sliding window demand kW export block demand kvar export block demand kW export sliding window demand kvar export sliding window demand kW export accumulated demand kvar export accumulated demand kW export predicted sliding window demand kvar export predicted sliding window demand Not used Not used Not used Not used In Ampere demand Total Energies E kWh import kWh export Not used Not used kvarh import kvarh export Not used Not used kVAh total Not used Not used kVAh import kVAh export Not used Not used Not used Not used
Options/Range 0-Pmax 0-Pmax 0 0 0 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-1000 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0 0 0 0 0-Imax 0-999,999,999 0-999,999,999
Units U3 U3
U3 U3 U3 U3 U3 U3 0.001 U3 U3 U3 U3 U3 U3 U3 U3
U2 kWh kWh
Type UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT16 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 INT32 UINT32 UINT32 UINT32 INT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32
R/W R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R
Notes
0-999,999,999 0-999,999,999
kvarh kvarh
0-999,999,999
kVAh
0-999,999,999 0-999,999,999
kVAh kVAh
25
Point ID 0x1711 0x1712 0x1713 0x1714 0x1715 0x1780 0x1781 0x1782 0x1783 0x1800 0x1801 0x1802 0x1803 0x1804 0x1805 0x1806 0x1807 0x1808 0x1900 0x1901 0x1927 0x1A00 0x1A01 0x1A27 0x1B00 0x1B01 0x1B27 0x1C00 0x1C01 0x1C27
Description Not used kvarh Q1 kvarh Q2 kvarh Q3 kvarh Q4 Summary Energy Registers E Summary energy register #1 Summary energy register #2 Summary energy register #3 Summary energy register #4 Phase Energies E kWh import L1 kWh import L2 kWh import L3 kvarh import L1 kvarh import L2 kvarh import L3 kVAh total L1 kVAh total L2 kVAh total L3 V1/V12 Harmonic Distortion EH H01 Harmonic distortion H02 Harmonic distortion ... H40 Harmonic distortion V2/V23 Harmonic Distortion EH H01 Harmonic distortion H02 Harmonic distortion ... H40 Harmonic distortion V3/V31 Harmonic Distortion EH H01 Harmonic distortion H02 Harmonic distortion ... H40 Harmonic distortion I1 Harmonic Distortion EH H01 Harmonic distortion H02 Harmonic distortion ... H40 Harmonic distortion
Options/Range 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-10000 0-10000 0-10000 0-10000 0-10000 0-10000 0-10000 0-10000 0-10000 0-10000 0-10000 0-10000
Units kvarh kvarh kvarh kvarh kWh kWh kWh kWh kWh kWh kWh kvarh kvarh kvarh kVAh kVAh kVAh 0.01% 0.01% 0.01% 0.01% 0.01% 0.01% 0.01% 0.01% 0.01% 0.01% 0.01% 0.01%
Type UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16
R/W R R R R R R R R R R R R R R R R R R
1
Notes
R R R
1
R R R
1
R R R R R R
26
Point ID 0x1D00 0x1D01 0x1D27 0x1E00 0x1E01 0x1E27 0x2900 0x2901 0x2902 0x2903 0x2904 0x2905 0x2906 0x2907 0x2908 0x2909 0x290A 0x290B 0x290C 0x290D 0x290E 0x290F 0x2910 0x2911 0x2A00 0x2A01 0x2A02 0x2A03 0x2C00 0x2C01 0x2C02 0x2C03 0x2C04 0x2C05
Description I2 Harmonic Distortion EH H01 Harmonic distortion H02 Harmonic distortion ... H40 Harmonic distortion I3 Harmonic Distortion EH H01 Harmonic distortion H02 Harmonic distortion ... H40 Harmonic distortion Fundamental Phase Values EH V1/V12 Voltage V2/V23 Voltage V3/V31 Voltage I1 Current I2 Current I3 Current kW L1 kW L2 kW L3 kvar L1 kvar L2 kvar L3 kVA L1 kVA L2 kVA L3 Power factor L1 Power factor L2 Power factor L3 Fundamental Total Values EH Total fundamental kW Total fundamental kvar Total fundamental kVA Total fundamental PF Minimum 1-Cycle Phase Values V1/V12 Voltage V2/V23 Voltage V3/V31 Voltage I1 Current I2 Current I3 Current
Options/Range 0-10000 0-10000 0-10000 0-10000 0-10000 0-10000 0-Vmax 0-Vmax 0-Vmax 0-Imax 0-Imax 0-Imax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax 0-Pmax 0-Pmax 0-Pmax -1000-1000 -1000-1000 -1000-1000 -Pmax-Pmax -Pmax-Pmax 0-Pmax -1000-1000 0-Vmax 0-Vmax 0-Vmax 0-Imax 0-Imax 0-Imax
Units 0.01% 0.01% 0.01% 0.01% 0.01% 0.01% U1 U1 U1 U2 U2 U2 U3 U3 U3 U3 U3 U3 U3 U3 U3 0.001 0.001 0.001 U3 U3 U3 0.001 U1 U1 U1 U2 U2 U2
Type UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 INT32 INT32 INT32 INT32 INT32 INT32 UINT32 UINT32 UINT32 INT16 INT16 INT16 INT32 INT32 UINT32 INT16 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32
Notes
2-cycle values
27
Point ID 0x2D00 0x2D01 0x2D02 0x2D03 0x2E00 0x2E01 0x2E02 0x3400 0x3401 0x3402 0x3403 0x3404 0x3405 0x3500 0x3501 0x3502 0x3503 0x3600 0x3601 0x3602 0x3700 0x3701 0x3702 0x3703 0x3704 0x3705 0x3706 0x3707 0x3708 0x3709 0x370A 0x370B 0x3737 0x370D 0x370E 0x370F 0x3710
Description Minimum 1-Cycle Total Values Total kW Total kvar Total kVA Total PF Minimum 1-Cycle Auxiliary Values Not used In Current Frequency Maximum 1-Cycle Phase Values V1/V12 Voltage V2/V23 Voltage V3/V31 Voltage I1 Current I2 Current I3 Current Maximum 1-Cycle Total Values Total kW Total kvar Total kVA Total PF Maximum 1-Cycle Auxiliary Values Not used In Current Frequency Maximum Demands V1/V12 Maximum volt demand V2/V23 Maximum volt demand V3/V31 Maximum volt demand I1 Maximum ampere demand I2 Maximum ampere demand I3 Maximum ampere demand Not used Not used Not used Maximum kW import sliding window demand Maximum kvar import sliding window demand Maximum kVA sliding window demand Not used Not used Not used Maximum kW export sliding window demand Maximum kvar export sliding window demand
Units U3 U3 U3 0.001
Type INT32 INT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 INT32 INT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32
R/W R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R
1 1 1 1 1 1
Notes
Absolute value
0-Imax 0-Fmax 0-Vmax 0-Vmax 0-Vmax 0-Imax 0-Imax 0-Imax -Pmax-Pmax -Pmax-Pmax 0-Pmax 0-1000
U2 0.01Hz U1 U1 U1 U2 U2 U2 U3 U3 U3 0.001
Absolute value
U2 0.01Hz U1 U1 U1 U2 U2 U2
U3 U3 U3
0-Pmax 0-Pmax
U3 U3
28
Description Not used Not used Not used Not used In Maximum ampere demand TOU Parameters E 0x3C00 Active tariff 0x3C01 Active profile
Options/Range
Units
0-Imax 0-7 0-15: 0-3 = Season 1 Profile #1-4, 4-7 = Season 2 Profile #1-4, 8-11 = Season 3 Profile #1-4, 12-15 = Season 4 Profile #1-4 0-4095 0-4095 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax
U2
R/W R R R R R R R
Notes
Scaled Analog Outputs 0x3C80 Analog output AO1 0x3C81 Analog output AO2 TOU Energy Register #1 E 0x3D00 Tariff #1 register 0x3D01 Tariff #2 register 0x3D07 Tariff #8 register TOU Energy Register #2 E 0x3E00 Tariff #1 register 0x3E01 Tariff #2 register 0x3E07 Tariff #8 register TOU Energy Register #3 E 0x3F00 Tariff #1 register 0x3F01 Tariff #2 register 0x3F07 Tariff #8 register TOU Energy Register #4 E 0x4000 Tariff #1 register 0x4001 Tariff #2 register 0x4007 Tariff #8 register Summary Energy Accumulated Demands E 0x4500 Summary register #1 demand 0x4501 Summary register #2 demand 0x4502 Summary register #3 demand 0x4503 Summary register #4 demand Summary Energy Block Demands E 0x4580 Summary register #1 demand
UINT32 UINT32 kWh kWh kWh kWh kWh kWh kWh kWh kWh kWh kWh kWh U3 U3 U3 U3 U3 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32
R/W R/W R R R R R R R R R R R R R R R R R R R R R
29
Point ID Description 0x4581 Summary register #2 demand 0x4582 Summary register #3 demand 0x4583 Summary register #4 demand Summary Energy Sliding Window Demands E 0x4600 Summary register #1 demand 0x4601 Summary register #2 demand 0x4602 Summary register #3 demand 0x4603 Summary register #4 demand Summary Energy Maximum Demands E 0x4780 Summary register #1 maximum demand 0x4781 Summary register #2 maximum demand 0x4782 Summary register #3 maximum demand 0x4783 Summary register #4 maximum demand TOU Maximum Demand Register #1 E 0x4800 Tariff #1 maximum demand 0x4801 Tariff #2 maximum demand 0x4807 Tariff #8 maximum demand TOU Maximum Demand Register #2 E 0x4900 Tariff #1 maximum demand 0x4901 Tariff #2 maximum demand 0x4907 Tariff #8 maximum demand TOU Maximum Demand Register #3 E 0x4A00 Tariff #1 maximum demand 0x4A01 Tariff #2 maximum demand 0x4A07 Tariff #8 maximum demand TOU Maximum Demand Register #4 E 0x4880 Tariff #1 maximum demand 0x4881 Tariff #2 maximum demand 0x4887 Tariff #8 maximum demand V1/V12 Harmonic Angles EH 0x6400 H01 Harmonic angle 0x6400 H02 Harmonic angle ... 0x6427 H40 Harmonic angle V2/V23 Harmonic Angles EH 0x6500 H01 Harmonic angle
Options/Range 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax -1800-1800 -1800-1800 -1800-1800 -1800-1800
Type UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 INT16 INT16 INT16 INT16
R/W R R R R R R R R R R R R R R R R R R R R R R R R R R R
1, 3
Notes
R R R
1, 3
30
Point ID Description 0x6500 H02 Harmonic angle ... 0x6527 H40 Harmonic angle V1/V31 Harmonic Angles EH 0x6600 H01 Harmonic angle 0x6600 H02 Harmonic angle ... 0x6627 H40 Harmonic angle I1 Harmonic Angles EH 0x6700 H01 Harmonic angle 0x6700 H02 Harmonic angle ... 0x6727 H40 Harmonic angle I2 Harmonic Angles EH 0x6800 H01 Harmonic angle 0x6800 H02 Harmonic angle ... 0x6827 H40 Harmonic angle I3 Harmonic Angles EH 0x6900 H01 Harmonic angle 0x6900 H02 Harmonic angle ... 0x6927 H40 Harmonic angle 0x7C00 Setpoint Status SP1-SP16 (bitmap) NOTES:
Options/Range -1800-1800 -1800-1800 -1800-1800 -1800-1800 -1800-1800 -1800-1800 -1800-1800 -1800-1800 -1800-1800 -1800-1800 -1800-1800 -1800-1800 -1800-1800 -1800-1800 0x00000000-0x0000FFFF
Units 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1
Type INT16 INT16 INT16 INT16 INT16 INT16 INT16 INT16 INT16 INT16 INT16 INT16 INT16 INT16 UINT32
R/W R R
1, 3
Notes
R R R
3
R R R
3
R R R
3
R R R R
Energy and power demand readings are only available in PM130E and PM130EH meters. Harmonics are only available in PM130EH meters.
1
Voltage and voltage harmonics readings: when the 4LN3, 3LN3 or 3BLN3 wiring mode is selected, the voltages will be line-to-neutral; for any other wiring mode, they will be line-to-line voltages. For volts, amps, power and frequency scales and units, refer to Section 5 Data Scales and Units. Harmonic angles are referenced to the fundamental voltage harmonic H01 on phase L1.
2 3
31
Units U1 sec U1 sec U1 sec U2 sec U2 sec U2 sec U3 sec U3 sec U3 sec 0.001 sec
Type UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 INT32 UINT32 INT32 UINT32 UINT32 UINT32 INT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32
R/W R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R
1 1 1 1 1 1
Notes
0 0-Imax 0-Fmax U2 sec 0.01Hz sec U1 sec U1 sec U1 sec U2 sec U2 sec U2 sec
32
Point ID
Description Maximum Auxiliary Values 0xB300 Not used 0xB301 0xB302 Max. In Current 0xB303 Timestamp 0xB304 Max. Frequency 0xB305 Timestamp Summary Energy Maximum Demands E 0xB340 Summary register #1 Maximum Demand 0xB341 Timestamp 0xB342 Summary register #2 Maximum Demand 0xB343 Timestamp 0xB344 Summary register #3 Maximum Demand 0xB345 Timestamp 0xB346 Summary register #4 Maximum Demand 0xB347 Timestamp Maximum Demands 0xB380 V1/V12 Maximum volt demand 0xB381 Timestamp 0xB382 V2/V23 Maximum volt demand 0xB383 Timestamp 0xB384 V3/V31 Maximum volt demand 0xB385 Timestamp 0xB386 I1 Maximum ampere demand 0xB387 Timestamp 0xB388 I2 Maximum ampere demand 0xB389 Timestamp 0xB38A I3 Maximum ampere demand 0xB38B Timestamp 0xB38C Not used 0xB38D 0xB38E Not used 0xB38F 0xB390 Not used 0xB391 0xB392 Maximum kW import sliding window demand 0xB393 Timestamp 0xB394 Maximum kvar import sliding window demand 0xB395 Timestamp 0xB396 Maximum kVA sliding window demand 0xB397 Timestamp 0xB398 Not used 0xB399 0xB39A Not used
Units
Type UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32
R/W R R R R R R R R R R
1 1 1
Notes
UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32
R R R R R R R R R R R R R R R R R R R R R R R R R R R
33
Point ID 0xB39B 0xB39C 0xB39D 0xB39E 0xB39F 0xB3A0 0xB3A1 0xB3A2 0xB3A3 0xB3A4 0xB3A5 0xB3A6 0xB3A7 0xB3A8 0xB3A9 0xB3AA 0xB3AB 0xB480 0xB481 0xB482 0xB483 0xB48E 0xB48F 0xB500 0xB501 0xB502 0xB503 0xB50E 0xB50F 0xB580 0xB581 0xB582 0xB583 0xB58E 0xB58F 0xB4C0
Description Not used Maximum kW export sliding window demand Timestamp Maximum kvar export sliding window demand Timestamp Not used Not used Not used Not used In Maximum ampere demand Timestamp TOU Maximum Demand Register #1 E Tariff #1 maximum demand Timestamp Tariff #2 maximum demand Timestamp Tariff #8 maximum demand Timestamp TOU Maximum Demand Register #2 E Tariff #1 maximum demand Timestamp Tariff #2 maximum demand Timestamp Tariff #8 maximum demand Timestamp TOU Maximum Demand Register #3 E Tariff #1 maximum demand Timestamp Tariff #2 maximum demand Timestamp Tariff #8 maximum demand Timestamp TOU Maximum Demand Register #4 E Tariff #1 maximum demand 0
Options/Range/Format
Units
U3 sec U3 sec
U2 sec U3 sec U3 sec U3 sec U3 sec U3 sec U3 sec U3 sec U3 sec U3 sec U3
Type UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32
R/W R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R
Notes
0-Pmax 0-Pmax
0-Pmax
0-Pmax 0-Pmax
0-Pmax
0-Pmax 0-Pmax
0-Pmax
0-Pmax
34
Point ID Description 0xB4C1 Timestamp 0xB4C2 Tariff #2 maximum demand 0xB4C3 Timestamp 0xB4CE Tariff #8 maximum demand 0xB4CF Timestamp NOTES:
Options/Range/Format 0-Pmax
0-Pmax
R/W R R R R R R
Notes
Power demand readings are only available in the PM130E and PM130EH meters.
1 2
Voltage readings: when the 4LN3, 3LN3 or 3BLN3 wiring mode is selected, the voltages will be line-to-neutral; for any other wiring mode, they will be line-to-line voltages. For volts, amps, power and frequency scales and units, refer to Section 5 Data Scales and Units.
35
UINT16
UINT16 UINT16
W W
UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16
W W W W W W W R R R R R R/W When read: Bits set to 1 indicate that the designated setpoint have been operated at least once since the alarm bits were reset. When written: Bits preset to 0 clear corresponding alarms, Bits set to 1 have no Bits set to 1 indicate closed relay contacts. Bits set to 1 indicate closed input contacts. Bits set to 1 indicate operated (activated) setpoints.
36
Point ID
Description F23
Options/Range
Units
Type UINT16
R/W R/W
0x7E01 Self-check alarm status (device diagnostics). Nonvolatile register that keeps the status of the internal device diagnostics.
Notes effect. When read: Bits set to 1 indicate that the designated diagnostics failed at least once since the alarm bits were reset. When written: Bits preset to 0 clear corresponding alarms; bits set to 1 have no effect.
37
% A V
R R R
+1 Interface
+2 Device address
+3 Baud rate
COM1: 0=SATEC ASCII, 1=Modbus RTU, 2=DNP3.0, 4=DTE, COM2: 0=SATEC ASCII, 1=Modbus RTU, 2=DNP3.0, 5=Profibus DP COM1: 2=RS-485, COM2: 0=RS-232, 1=RS-422, 2=RS-485, 6=Ethernet, 7=Profibus, 8=GSM/GPRS SATEC ASCII: 0-99 Modbus RTU: 1-247 DNP3.0: 065532 Profibus DP: 0-126 1=300 bps, 2=600 bps, 3=1200 bps, 4=2400 bps, 5=4800 bps, 6=9600 bps, 7=19200 bps, 8=38400 bps, 9=57600 bps, 10=115200 bps 0=7 bits/even parity, 1=8 bits/no parity, 2=8 bits/even parity 0=no flow control 1=software (XON/XOFF) 2=hardware (CTS) 0=not used, 1=RTS is permanently asserted 2=RTS is asserted during the transmission 0=disabled, 1=enabled
UINT16
R/W
UINT16
R/W
UINT16
R/W
UINT16
R/W
R/W R/W R/W N/A for COM1 (read as 65535) N/A for COM1 (read as 65535)
UINT16
R/W
38
Options/Range
Units
Type UINT16
R/W R
Notes
0.1 A min
If the external synchronization is selected, the DI1 input is considered a pulse or KYZ input. The pulse edge restarts the power demand block accumulation interval. E Read as 65535
E
Volt/ampere demand period Reserved Number of blocks in a sliding window Reserved Nominal line frequency Maximum demand load current
sec
Read as 65535
+13-19 Reserved +20 PT ratio multiplication factor Device Options Setup 0x8700-0x870A +0 Power calculation mode +1 Energy roll value +2 +3-9 +10 +11 +12-13 +14
E
Read as 65535
Phase energy calculation mode E Reserved Energy LED test mode E Starting voltage, percent of FS voltage Reserved Device resolution (see Section 5 for details)
0=using reactive power: S=f(P,Q), 1=using non-active power: Q=f(S,P) 0=1104, 1=1105, 2=1106, 3=1107, 4=1108, 5=1x109 0=disabled, 1=enabled 0=disabled, 1=Wh test, 2=varh test 15-50 0.1% 0 = Low resolution, 1 = High resolution
Read as 65535 LED pulse rate is 10,000 pulses/kWh Default 1.5% Read as 65535 Default 0
Digital Inputs Setup 0x8900-0x8904 +0 +1 +2 +3 +4 Status inputs (bitmap) Pulse inputs (bitmap) Not used External demand synchronization input (bitmap) Time synchronization input (bitmap) 0x0003 0x0003 0 0x0001=DI1 0x0001=DI1, 0x0002=DI2, UINT16 UINT16 UINT16 UINT16 UINT16 R/W R/W R/W R/W R/W
Obsolete registers. Refer to Digital Inputs setup registers 0X9600-0X9607 Ignored when written Ignored when written Ignored when written
39
Address
Description
Units
Type
R/W
Notes
Alarm/Event Setpoints Setup 0x8200-0x825F +0 Trigger parameter ID +1 Action ID +2 Operate delay +3 Release delay +4,5 Operate limit +6,7 Release limit 0x8200-0x8205 Setpoint #1 0x8206-0x820B Setpoint #2 0x820C-0x8211 Setpoint #3 0x8212-0x8217 Setpoint #4 0x8218-0x821D Setpoint #5 0x821E-0x8223 Setpoint #6 0x8224-0x8229 Setpoint #7 0x822A-0x822F Setpoint #8 0x8230-0x8235 Setpoint #9 0x8236-0x820B Setpoint #10 0x823C-0x8241 Setpoint #11 0x8242-0x8247 Setpoint #12 0x8248-0x824D Setpoint #13 0x824E-0x8253 Setpoint #14 0x8254-0x8259 Setpoint #15 0x825A-0x825F Setpoint #16 Local Settings 0x8C00-0x8C0A +0 Daylight savings time (DST) option +1 DST start month +2 DST start week of the month +3 DST start weekday +4 DST end month +5 DST end week of the month +6 DST end weekday +7 Clock synchronization source +8 Country code +9 DST start hour +10 DST end hour
F12 F14 0-9999 0-9999 See Section 4.2 See Section 4.2
0 = DST disabled (standard time only), 1 = DST enabled 1-12 1-4 = 1st, 2nd, 3rd and 4th week, 5=the last week of the month 1-7 (1=Sun, 7=Sat) 1-12 1-4=1st, 2nd, 3rd and 4th week, 5=the last week of the month 1-7 (1=Sun, 7=Sat) 1-4 = DI1-DI4, 32767 = meter clock ITU calling number 1-6 1-6
UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16
R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W
A DI input is considered a pulse or KYZ input. The pulse edge adjusts the clock at the nearest whole minute.
40
Address Description TOU Daily Profile Setup E 0x9000-0x907F +0 1st tariff change +1 2nd tariff change +2 3rd tariff change +3 4th tariff change +4 5th tariff change +5 6th tariff change +6 7th tariff change +7 8th tariff change 0x9000-0x9007 Daily profile #1: Season 1, Day type 1 0x9008-0x900F Daily profile #2: Season 1, Day type 2 0x9010-0x9017 Daily profile #3: Season 1, Day type 3 0x9018-0x901F Daily profile #4: Season 1, Day type 4 0x9020-0x9027 Daily profile #5: Season 2, Day type 1 0x9028-0x902F Daily profile #6: Season 2, Day type 2 0x9030-0x9037 Daily profile #7: Season 2, Day type 3 0x9038-0x903F Daily profile #8: Season 2, Day type 4 0x9040-0x9047 Daily profile #9: Season 3, Day type 1 0x9048-0x904F Daily profile #10: Season 3, Day type 2 0x9050-0x9057 Daily profile #11: Season 3, Day type 3 0x9058-0x905F Daily profile #12: Season 3, Day type 4 0x9060-0x9067 Daily profile #13: Season 4, Day type 1 0x9068-0x906F Daily profile #14: Season 4, Day type 2 0x9070-0x9077 Daily profile #15: Season 4, Day type 3 0x9078-0x907F Daily profile #16: Season 4, Day type 4 TOU Calendar Setup E 0x9100-0x923F +0-9 Calendar entry record +0 Daily profile
Options/Range
Units
Type
R/W
Notes
+1 Week of month +2 +3 +4 +5 +6 +7 +8-9 Weekday Till Weekday Month Day of month Till Month Till Day of month Reserved
0-3 = Season 1, Day types 0-3 4-7 = Season 2, Day types 0-3 8-11 = Season 3, Day types 0-3 12-15 = Season 4, Day types 0-3 0=all, 1=1st, 2=2nd, 3=3rd, 4=4th, 5=last week of the month 0=all, 1-7 (Sun=1, Sat=7) 0=all, 1-7 (Sun=1, Sat=7) 0=all, 1-12=January - December 0=all, 1-31=day 1-31 0=all, 1-12=January - December 0=all, 1-31=day 1-31
UINT16
R/W R/W
41
Address Description 0x9100-0x9109 Calendar entry #1 0x910A-0x9113 Calendar entry #2 0x9114-0x911D Calendar entry #3 0x9236-0X923F Calendar entry #32 Summary Energy/TOU Registers Setup E 0X9400-0X941F +0 Not used +1 Units of measurement
Options/Range
Units
Type
R/W
Notes
+2 Flags (bitmap)
+3 Not used 0X9400-0X9403 Register #1 Setup 0X9404-0X9407 Register #2 Setup 0X9408-0X940B Register #3 Setup 0X940C-0X940F Register #4 Setup Summary Energy/TOU Registers Source Setup E 0X9500-0X9517 +0 Energy source ID +1 Target summary register number +2 Multiplier 0X9500-0X9502 Energy Source #1 0X9503-0X9505 Energy Source #2 0X9506-0X9508 Energy Source #3 0X9509-0X950B Energy Source #4 Digital Inputs Setup 0X9600-0X960F +0 Pulse mode +1 Polarity +2 De-bounce time, ms +3 0X9600-0X9603 0X9604-0X9607 0X9608-0X960B 0X960C-0X960F Reserved DI1 Setup DI2 Setup DI3 Setup DI4 Setup
0=none, 1=kWh, 2=kvarh, 3=kVAh, 4=m3, 5=CF (cubic feet), 6=CCF (hundred cubic feet) Bit 0=1 - TOU enabled Bit 1=1 - Use profile enabled Bit 2=1 - Max. Demand profile enabled Bit 3=1 - Summary (total) profile enabled 0
UINT16 UINT16
R/W R/W
UINT16
R/W
UINT16
R/W
0.001
42
Options/Range
Units
Type
R/W
Notes
+2 +3 +4 +5 0X9700-0X9705 0X9706-0X970B
Pulse width, ms Pulse source ID Units per pulse Reserved RO1 Setup RO2 Setup
0=latched, 1=unlatched, 2=pulse, 3=KYZ Bit 0 Polarity: 0=normal, 1=inverting, Bit 1 - Retentive mode: 0=disabled, 1=enabled 1-1000 F17 1-10000
UINT16 UINT16
R/W R/W
x0.1
43
R R R R
R R R R
44
Options/Range 59520 F6 0 F7
Units
R/W R R R R R
Notes
Bits set to 1 indicate that the memory is allocated to the designated files Bits set to 1 indicate that the corresponding sections are allocated in the Data log #8 file to the designated energy/maximum demand registers
File Transfer Control/Status Registers 0xA100-0xA3FF +0 File status (bitmap) +1 Number of records logged in the file +2 Number of the new records never read before +3 Sequence number of the last record in a file + 1 (modulo 65536) +4 Sequence number of the first (oldest) record in a file +5 Sequence number of the first new record in a file never read before +6 Sequence number of the current record to be read through the file read window. Can be overwritten to point to the desired record in a file +7 Command register (write-only)
F4 0 to 65535 0 to 65535 0 to 65535 (increments modulo 65536 with each new record) 0 to 65535 0 to 65535 0 to 65535 Write value: 0 = point to the first (oldest) record in a file 1 = point to the first new record never read before. If there are no new records, the file pointer will be set to the oldest record in a file
R R R R R R R/W R/W
If there is no a record in the file that matches the written sequence, the device will respond with the exception code 03 (invalid data) Read as 0
0xA100-0xA107 0xA108-0xA10F 0xA180-0xA187 0xA300-0xA307 0xA308-0xA30F 0xA310-0xA317 0xA318-0xA31F 0xA380-0xA387 0xA388-0xA38F 0xA390-0xA397
Event log file control Data log #1 file control Data log #16 file control Daily Profile Log, Energy/Usage Reg.#1 control Daily Profile Log, Energy/Usage Reg.#2 control Daily Profile Log, Energy/Usage Reg.#3 control Daily Profile Log, Energy/Usage Reg.#4 control Daily Profile Log, Max. Demand Reg.#1 control Daily Profile Log, Max. Demand Reg.#2 control Daily Profile Log, Max. Demand Reg.#3 control
UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16
R R R R R R R R R R
45
Address Description 0xA398-0xA39F Daily Profile Log, Max. Demand Reg.#4 control Data Log File Transfer Registers 0xC000-0xC77F Data Log Record Structure +0 Record status (bitmap) +1 Record sequence number Record time, sec Record time, fractional seconds, ms Trigger event ID Parameter #1 value Parameter #2 value Parameter #3 value Parameter #4 value Parameter #5 value Parameter #6 value Parameter #7 value Parameter #8 value Parameter #9 value Data Log Transfer Blocks 0xC000-0xC017 Data log #1 0xC468-0xC47F Data log #16 0xC480-0xC497 Daily Profile Log, Energy/Usage Reg.#1 section 0xC498-0xC4AF Daily Profile Log, Energy/Usage Reg.#2 section 0xC4B0-0xC4C7 Daily Profile Log, Energy/Usage Reg.#3 section 0xC4C8-0xC4DF Daily Profile Log, Energy/Usage Reg.#4 section 0xC600-0xC617 Daily Profile Log, Max. Demand Reg.#1 section 0xC618-0xC62F Daily Profile Log, Max. Demand Reg.#2 section 0xC630-0xC647 Daily Profile Log, Max. Demand Reg.#3 section 0xC648-0xC65F Daily Profile Log, Max. Demand Reg.#4 section Event Log File Transfer Registers 0xCD80-0xCDAF Event Record Structure +0 Record status (bitmap) +1 Record sequence number +2 +3 +4 +5 +6 +7 Record time, sec Record time, fractional seconds, ms Event point/cause ID Log value Event effect Reserved +2 +3 +4 +5 +6 +7 +8 +9 +10 +11 +12 +13
Options/Range
Units
Type UINT16
R/W R
Notes
UINT16 UINT16 sec ms UINT32 UINT16 UINT16 INT32 INT32 INT32 INT32 INT32 INT32 INT32 INT32 INT32
R R R R R R R R R R R R R R R R R R R R R R R R
R R R R R R R R
46
Address
Description Event Log Transfer Blocks 0xCD80-0xCD87 Event log record #1 0xCD88-0xCD8F Event log record #2 0xCD90-0xCD97 Event log record #3 0xCD98-0xCD9F Event log record #4 0xCDA0-0xCDA7 Event log record #5 0xCDA8-0xCDAF Event log record #6 Waveform Header Transfer Registers 0xCE00-0xCEFB Waveform Header Structure +0 Record status (bitmap) +1 Record sequence number in a file +2 Record time, sec +3 +4 +5 +6 +7 Record time, fractional seconds, ms Trigger event ID Waveform series (compound waveform) number Record sequence number in a waveform series Analog input full scale, engineering units (volts/amperes) (ANALOG_SCALE) +8 Digital full scale for the channel, sample code (DIGITAL_SCALE) +9 Zero offset, sample code (ZERO_OFFSET) +10 Line frequency +11 Trigger sample point offset in the waveform series +12,13 Reserved Waveform Header Transfer Blocks 0xCE00-0xCE0D Real-time waveform, channel V1/V12 0xCE0E-0xCE1B Real-time waveform, channel V2/V23 0xCE1C-0xCE29 Real-time waveform, channel V3/V31 0xCE2A-0xCE37 Real-time waveform, channel I1 0xCE38-0xCE45 Real-time waveform, channel I2 0xCE46-0xCE53 Real-time waveform, channel I3 Waveform Series Transfer Block 0xD000-0xD1FF Waveform Sample Series +0 Sample point 1 +1 Sample point 2 +2 Sample point 2
Options/Range
Units
Type
R/W R R R R R R
Notes
F5 0 to 65535 (increments modulo 65536) F1 0-999 0=real-time waveform 1 0 Vmax, Imax -4096 to 4095 0 0 to 6500 0-511 0
UINT16 UINT16 sec ms UINT32 UINT16 UINT16 UINT16 UINT16 UINT32 INT16 INT16 x 0.01Hz UINT16 UINT16 UINT16
R R R R R R R R R R R R R R R R R R R Corresponds to twice the analog input fullscale range. Corresponds to the center of the digital scale range The sampling frequency is equal to the line frequency multiplied by the sampling rate in samples per cycle Corresponds to the first record in the series Indicates the time for the last sample point in the record
1 1 1
R R R
47
Address
Units
Type INT16
R/W R
Notes
NOTE
1 2
When the 3OP2 or 3OP3 wiring mode is selected, the voltages will be line-to-line; for any other wiring mode, they will be line-to-neutral. To convert digital samples to their analog equivalents in input measurement units (volts, amps), the following scaling should be applied:
48
Description
Range
Units
Type
Notes
REG4 TRF1 TRF2 TRF3 TRF4 TRF5 TRF6 TRF7 TRF8 REG1 MD TRF1 MD TRF2 MD TRF3 MD TRF4 MD TRF5 MD TRF6 MD TRF7 MD TRF8 MD
0x1783 0x7000 0x7001 0x7002 0x7003 0x7004 0x7005 0x7006 0x7007 0x4780 0x7100 0x7101 0x7102 0x7103 0x7104 0x7105 0x7106 0x7107
Energy Register #1 Summary (total) energy reading Tariff #1 energy reading Tariff #2 energy reading Tariff #3 energy reading Tariff #4 energy reading Tariff #5 energy reading Tariff #6 energy reading Tariff #7 energy reading Tariff #8 energy reading Energy Register #4 Summary (total) energy reading Tariff #1 energy reading Tariff #2 energy reading Tariff #3 energy reading Tariff #4 energy reading Tariff #5 energy reading Tariff #6 energy reading Tariff #7 energy reading Tariff #8 energy reading Daily Maximum Demand Register #1 Summary (total) max. demand reading Tariff #1 max. demand reading Tariff #2 max. demand reading Tariff #3 max. demand reading Tariff #4 max. demand reading Tariff #5 max. demand reading Tariff #6 max. demand reading Tariff #7 max. demand reading Tariff #8 max. demand reading Daily Maximum Demand Register #4 Summary (total) max. demand reading Tariff #1 max. demand reading Tariff #2 max. demand reading Tariff #3 max. demand reading Tariff #4 max. demand reading
0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax
UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32
U3 U3 U3 U3 U3
49
Point Label
Point ID 0x7104 0x7105 0x7106 0x7107 Tariff Tariff Tariff Tariff #5 #6 #7 #8 max. max. max. max. demand demand demand demand
Description
Range
Units
Type
Notes
MD MD MD MD
U3 U3 U3 U3
An energy use profile section is allocated for registers for which a source input is selected in the Summary/TOU Register setup and for which energy use profile is enabled. A maximum demand profile section is allocated for registers for which maximum demand profile is enabled in the Summary/TOU Register setup. Not configured sections/channels are not available for download. Refer to the file channel mask in the file info for configured channels. The number of parameters in a section is automatically configured depending on the number of actually used tariffs selected in the TOU Daily Profiles. For power scale and units, refer to Section 5 Data Scales and Units.
2 3
50
Wiring 4LN3, 3LN3, 3BLN3 Wiring 4LL3, 3LL3, 3BLL3, 3OP2, 3OP3, 3DIR2 Fmax Nominal frequency 25, 50 or 60 Hz Nominal frequency 400Hz Data Units Low Resolution Option U1 U2 U3 Data Units High Resolution Option U1 PT Ratio = 1 PT Ratio > 1 U2 U3 PT Ratio = 1 PT Ratio > 1
See Device Options Setup for information on selecting the device resolution option.
1 CT Ratio = CT primary current/CT secondary current 2 The default Voltage scale is 144V (120V + 20%). You can change it via the Device Data Scale setup (see Section 4.1) or via
the Device Options setup in PAS. it via the Device Data Scale setup (see Section 4.1) or via the Device Options setup in PAS.
3 The default Current scale is 2 CT secondary current (2.0A with 1A secondaries, 10.A with 5A secondaries). You can change 4 Pmax is rounded to whole kilowatts. With PT=1.0, if Pmax is greater than 9,999,000 W, it is truncated to 9,999,000 W.
51
6 Data Formats
Format Code Timestamp F1 Wiring Mode F2 Value Description Local time in a UNIX-style format. Represents the number of seconds since midnight (00:00:00), January 1, 1970. The time is valid after January 1, 2000. 0 1 2 3 4 5 6 8 9 3OP2 - 3-wire open delta using 2 CTs (2 element) 4LN3 - 4-wire WYE using 3 PTs (3 element), line-toneutral voltage readings 3DIR2 - 3-wire direct connection using 2 CTs (2 element) 4LL3 - 4-wire WYE using 3 PTs (3 element), line-to-line voltage readings 3OP3 - 3-wire open delta using 3 CTs (2 1/2 element) 3LN3 - 4-wire WYE using 2 PTs (2 1/2 element), line-toneutral voltage readings 3LL3 - 4-wire WYE using 2 PTs (2 1/2 element), line-toline voltage readings 3BLN3 - 3-wire broken delta using 2 PTs (2 1/2 element), line-to-neutral voltage readings 3BLL3 - 3-wire broken delta using 2 PTs (2 1/2 element), line-to-line voltage readings Notes
File Attributes F3 Bit 0 = 0 Non-wrap (stop when filled) Bit 0 = 1 Wrap-around (circular file) Bit 5 = 1 TOU daily profile log File Status Word F4 Bit 0 = 0 Non-wrap (stop when filled) Bit 0 = 1 Wrap-around (circular file) Bit 5 = 1 Daily profile log file Bit 9 = 1 Reading after EOF File Record Status Word F5 Bit 0 = 1 The last record of the file is being read Bit 1 = 1 Reading after EOF Bit 8 = 1 File is empty Bit 9 = 1 Corrupted record (CRC error) Bit 15 = 1 Generic read error (with one of the bits 8-9) File Allocation Map F6 Bit 0 Event log file Bit 1 Data log #1 file Bit 2-15 Reserved Bit 16 Data log #16 file Bits 17-31 Reserved Profile Log Sections Map F7 Bit 0:3 = 1 Summary/TOU energy/usage registers #1-#4 Bit 16:19 = 1 Summary/TOU maximum demand registers #1-#4 File ID F8 0 Event log file 1 Data log #1 file 16 Data log #16 file Waveform Log Channel Mask F9 Bit 0 = 1 Channel V1/V12 Bit 1 = 1 Channel V2/V23 Bit 2 = 1 Channel V3/V31 Bit 3 = 1 N/A Bit 4 = 1 Channel I1 Bit 5 = 1 Channel I2 Bit 6 = 1 Channel I3 TOU Tariff Change Time F10 Bits 8:15 = 0-7 Tariff number #1-#8 Bits 2:7 = 0-23 Tariff start hour Bits 0:1 = 0-3 Tariff start quarter of an hour Summary/TOU Energy Register Source ID F11 0x0000 None 0x0700-0x0703 Pulse input DI1-DI4 0x1700 kWh import
52
Value 0x1701 0x1704 0x1705 0x1708 0x1709 0x170A 0x170B 0x170C 0x170D 0x170E Setpoint Trigger Parameters ID F12 0x0000 0x0600 0x0601 0x0602 0x0603 0x8600 0x8601 0x8602 0x8603 0x0701 0x0800 0x0801 0x8800 0x8801 0x8901 0x8902 0x0A00 0x0A01 0x0A02 0x0A03 0x0E00 0x8D00 0x0E01 0x8D01 0x0E07 0x0E08 0x0E09 0x0E0A 0x1002 0x9002 0x1003 0x1004 0x1103 0x1104 0x1105 0x9103 0x9104 0x9105 0x1300 0x9200 0x1301 0x9201 0x1406 0x1407 0x1408 0x1409 0x1402
Format Code
Description kWh export kvarh import kvarh export kVAh total kVAh import kVAh export kvarh Q1 kvarh Q2 kvarh Q3 kvarh Q4 None (condition is not active) Status Inputs Status input #1 ON Status input #2 ON Status input #3 ON Status input #4 ON Status input #1 OFF Status input #2 OFF Status input #3 OFF Status input #4 OFF Pulse input #2 Relays Relay #1 ON Relay #2 ON Relay #1 OFF Relay #2 OFF Phase Reversal Positive phase rotation reversal Negative phase rotation reversal Pulse Counters High pulse counter #1 High pulse counter #2 High pulse counter #3 High pulse counter #4 1-Cycle Values on any Phase High voltage Low voltage High current Low current High voltage THD EH High current THD EH High K-Factor EH High current TDD EH 1-Cycle Auxiliary Values High frequency Low frequency High voltage unbalance High current unbalance 1-Sec Phase Values High I1 current High I2 current High I3 current Low I1 current Low I2 current Low I3 current 1-Sec Values on any Phase High voltage Low voltage High current Low current 1-Sec Total Values High total kW import High total kW export High total kvar import High total kvar export High total kVA
Notes
53
Format Code 0x9404 0x9405 0x1501 0x1502 0x9502 0x1600 0x1601 0x1602 0x1603 0x1604 0x1605 0x1606 0x1608 0x1609 0x160B 0x160F 0x1611 0x1612 0x1614
Value
0x0B02 0x0B03 0x0B04 0x0B05 0x0B06 0x0B07 0x0B08 0x0B09 Setpoint Action ID F14 0x0000 0x3000 0x3001 0x3100 0x3101 0x4000 0x4001 0x4002 0x4003 0x4400 0x4401 0x4402 0x4403 0x5100 0x7100 Counter Source ID F16 0x0000 0x0001-0x0002 Relay Output Pulse Source ID F17 0x0000 0x0400 0x0401 0x0403 0x0404 0x0405 0x0406 AO Output Parameters ID F18 0x0000 0x0C00 0x0C01 0x0C02 0x0C03 0x0C04 0x0C05 0x0C1E
Description Low total PF Lag Low total PF Lead 1-Sec Auxiliary Values High neutral current High frequency Low frequency Present Demands High V1/V12 Volt demand High V2/V23 Volt demand High V3/V31 Volt demand High I1 Ampere demand High I2 Ampere demand High I3 Ampere demand High block kW import demand E High block kVA demand E High sliding window kW import demand High sliding window kVA demand E High accumulated kW import demand E High accumulated kVA demand E High predicted kW import demand E High predicted kVA demand E Time and Date Parameters Day of week Year Month Day of month Hour Minutes Seconds Minute interval No action Operate Relay #1 Operate Relay #2 Release latched Relay #1 Release latched Relay #2 Increment counter #1 Increment counter #2 Increment counter #3 Increment counter #4 Count operating time using Count operating time using Count operating time using Count operating time using Send event notification Data log #1 None Pulse input DI1-DI2 None kWh import pulse E kWh export pulse E kvarh import pulse E kvarh export pulse E kvarh total pulse E kVAh pulse E None (output disabled) 1-Cycle Phase Values V1/V12 Voltage V2/V23 Voltage V3/V31 Voltage I1 Current I2 Current I3 Current V12 Voltage
Notes
#1 #2 #3 #4
54
Format Code 0x0C1F 0x0C20 0x0F00 0x0F01 0x0F02 0x0F03 0x0F04 0x0F05 0x1001 0x1002 0x1100 0x1101 0x1102 0x1103 0x1104 0x1105 0x111E 0x111F 0x1120 0x1400 0x1401 0x1402 0x1403 0x1404 0x1405 0x1501 0x1502 0x160F 0x1610 0x1611 0x161A 0x161B Event Cause/Point ID
Value
Description V23 Voltage V31 Voltage 1-Cycle Total Values Total kW Total kvar Total kVA Total PF Total PF Lag Total PF Lead 1-Cycle Auxiliary Values In Current Frequency 1-Sec Phase Values V1/V12 Voltage V2/V23 Voltage V3/V31 Voltage I1 Current I2 Current I3 Current V12 Voltage V23 Voltage V31 Voltage 1-Sec Total Values Total kW Total kvar Total kVA Total PF Total PF Lag Total PF Lead 1-Sec Auxiliary Values In Current Frequency Present Demands E Accumulated kW import demand Accumulated kvar import demand Accumulated kVA demand Accumulated kW export demand Accumulated kvar export demand Communications Events Data point ID (low byte, see F21) Front Panel Operations Data point ID (low byte, see F21) Self-Check Diagnostics Events Data point ID (low byte, see F21) Hardware Diagnostics Events RAM/Data error Hardware watchdog reset DSP/Sampling fault CPU exception Reserved Software watchdog reset Low battery EEPROM fault External Events Power down Power up External reset Communications/Self-check/Front Panel Events None Total energy registers cleared All total maximum demands cleared Power maximum demands cleared Volt/Ampere/Harmonic maximum demands cleared Summary/TOU energy registers cleared Summary/TOU maximum demand registers cleared
Notes
0x5B00-0x5BFF 0x5C00-0x5CFF 0x5D00-0x5DFF 0x6202 0x6203 0x6204 0x6205 0x6206 0x6207 0x620D 0x620F 0x6300 0x6308 0x6309 Event Effect ID F20 0x0000 0x6000 0x6100 0x6101 0x6102 0x6200 0x6300
55
Format Code
Value 0x6400 0x6401-0x6403 0x6500 0x6600 0x6700, 0x670F 0x6710 0x6B06 0xF100-0xF10F 0xF200 0xF300 0xF400 0xF500
Description All counters cleared Counter cleared (low byte = counter ID) Min/Max log cleared Event log file cleared (low byte = File ID) Data log file cleared (low byte = File ID) All data logs cleared Communication counters cleared Setpoint cleared (low byte = setpoint ID) Setup/Data cleared Setup reset (set by default) Setup changed RTC set Data Locations Data memory Factory setup Access/Password setup Basic setup Communications setup Real-time clock Digital inputs setup Pulse counters setup AO setup Timers setup Event/alarm setpoints Pulsing setup User assignable register map Data log setup File/Memory setup TOU energy registers setup TOU daily profiles TOU calendar RO Setup User selectable options DNP 3.0 class 0 map DNP 3.0 options setup DNP 3.0 events setup DNP 3.0 event setpoints Calibration registers Date/Time Setup Net setup Reserved Reserved Reserved RAM/Data error CPU watchdog reset Sampling fault CPU exception Reserved Software watchdog reset Power down Device reset Configuration reset RTC fault Reserved Reserved Reserved EEPROM fault 120V Option 690V Option Reserved Analog output 0/4 or 4/20mA Analog output 0-1mA Analog output 1mA RO option
Notes
Data Point ID F21 0x03 0x04 0x05 0x06 0x07 0x08 0x09 0x0A 0x0B 0x0E 0x10 0x11 0x12 0x14 0x15 0x16 0x18 0x19 0x1B 0x1C 0x1F 0x20 0x21 0x22 0x23 0x24 0x25 0x2B-0x3F Device Diagnostics F23 Bit 0 Bit 1 Bit 2 = 1 Bit 3 = 1 Bit 4 = 1 Bit 5 = 1 Bit 6 Bit 7 = 1 Bit 8 = 1 Bit 9 = 1 Bit 10 = 1 Bit 11 = 1 Bit 12 Bit 13 Bit 14 Bit 15 = 1 Instrument Options F28 Bit 0=1 Bit 1=1 Bits 2-5 Bit 6=1 Bit 7=1 Bit 8=1 Bit 9=1
56
Format Code Bit 10=1 Bit 11=1 Bit 12=1 Bit 13=1 Bit 14=1 Bit 15 Bits 16-18 Bits 19-22 Bits 23-24 Bits 25-29 Bits 30-31
Value
Description DI option Reserved Setup is secured by a password (authorization required) Reserved Reserved Reserved Number of RO - 1 Number of DI 1 Number of AO - 1 Reserved Reserved 00000000B 00100000B 01010000B 01010001B 01010010B 01010011B 01100000B 01100001B 01100010B 01100011B 11111111B
Notes
I/O Slot Types F29 DI DRY RO AI 1 mA AI 0-20 mA AI 4-20 mA AI 0-1 mA AO 1 mA AO 0-20 mA AO 4-20 mA AO 0-1 mA Empty slot Reset/Clear Function F30 Function Target 1 0 2 0=all maximum demands 1=power demands E 2=volt, ampere demands 3 0 4 0 5 0=all counters 1-4=counter #1-#4 6 0 Basic Setup Parameters ID F31 W40 U14 I17 D11 F47 C12 Q51 Q52 Q60 NOTES:
1
Clear TOU energy registers E Clear TOU demand registers E Clear pulse counters Clear Min/Max log Wiring mode PT ratio CT primary current Power block demand period E The number of blocks in a sliding window Volt/ampere demand period Nominal frequency Maximum demand load current PT ratio multiplication factor
Analog Outputs
1) For bi-directional analog output (1 mA), the zero scale setup corresponds to the center (0 mA) of the scale range, and the direction of the current matches the sign of the output parameter. Unsigned parameters are output within the current range 0 to +1 mA and can be scaled as in the case of single-ended analog output (0-1 mA). For signed values, such as powers and signed power factor, the scale is always symmetrical with regard to 0 mA, and the full scale corresponds to +1 mA output for positive readings and to -1 mA output for negative readings. The zero scale (0 mA output) is permanently set in the instrument to zero for all parameters except the signed power factor for which it is set to 1.000 (see Note 2). In write requests, the zero scale is ignored. 2) Except for the signed power factor, the setup scale is continuous within the entire value range. For signed power factor, the setup scale is broken at +1.000 in order to provide continuous output current when the power factor changes close to 1.000. The setup scale is symmetrical in the range of -0 to +0 with a center at 1.000 (-1.000 is assumed to be equal to +1.000). Negative power factor is output as -1.000 minus measured value, and non-negative power factor is output as +1.000 minus measured value. To set the entire range for power factor from-0 to +0, the scales would be specified as -0 to 0. Because of the fact that negative zero may not be transmitted through communications, the value of -0.001 is used to specify the scale of -0, and both +0.001 and 0.000 are used to specify the scale of +0.
57
The setpoint is operated when the actual phase sequence does not match the designated phase rotation order.
58