Daikin8ZoneMultiSplitSystem

RESIDENTIAL | LIGHT COMMERCIAL | COMMERCIAL

KeyPointsoftheInstallationProcess

2012 Daikin AC

Topics
InstallationConsiderations OutdoorUnit IndoorUnits&Controls BranchProviderUnits 8ZoneSelectionTool RefrigerantPiping REFNETFittings InstallationExamples StartUpChecklist

Slide2

2012DaikinAC

InstallationConsiderations

2012 Daikin AC

Tools&Support

DaikineQuipApp

8ZoneSelectionTool

Manuals

ProductCatalog
Slide4 2012DaikinAC

DaikinToolsforInstall

Slide5

2012DaikinAC

AdditionalToolsforInstall
Metrictools(hexkeysetandsocketset)arerequiredwhen installingorservicingDaikinRLCunits Nitrogenregulatorcapableofmeasuringupto700plusPSIis necessaryforinstallingDaikinRLCunits

MetricHexKeySet

750 1000PSI

MetricSocketSet

Slide6

2012DaikinAC

PolyVinylEtherOil(PVE)

CompatiblewithallHFCRefrigerants Excellentantiwearproperties Bettersolubilitywithprocessfluids SuperiorResistancetoCaptubeblockage Betterlubricity Optimalfornondriersystems VeryHygroscopic butwithnohydrolysis Moistureeasilyremoved

PVEw/drier

PVEw/odrier

Slide7

2012DaikinAC

MultiSplitInstallation
LabeltheindoorunitsA,B,C,D,etc.asappropriate Daikindoesnothavepreferenceregardinginstallorder Importantforwiringandpiping Pipingandwiringmustmatch IfthesystemispipedA,B,&CthenitMUSTbewiredAtoA,BtoB,andC
toC,etc.

Slide8

2012DaikinAC

SystemLayout

Slide9

2012DaikinAC

OutdoorUnit
RMXS48LVJU

2012 Daikin AC

RMXSFeatures
Designflexibilitywiththeabilityto
connectfrom2zonesto8Zonesona singlesystem

Abilitytoconnectupto50%to130%of
indoorunitcapacity

Longpipinglengthsforindoor
installationflexibility

Slimdesignforaspacesavingand
unobtrusivelooktothehomeexterior

Slide11

2012DaikinAC

RMXSFeatures
MaxCoolingCapacity 48,000Btu/h
(Heating54,000Btu/h)

Upto18.8SEER(HSPF11.3) ConnectstoCTXS,FTXS,FDXS,CDXS,
andFFQindoorunits

130%ConnectionRatio 440feettotalpipelength SoundLevels 57to58dBA OperatingRange Cooling23 to115 F Heating5 to75 F

Slide12

2012DaikinAC

RMXSDimensions

53
4

Min.4clearance oninletside,to wall.

35 7/16

Unitshouldbeplacedwherethereispropersupportfortheweightofthecondenser Raiseunitupforsnowanddrainageofwaterduringdefrostwhereconditionsrequire Securelyfastenunittowithstandhighwindsandearthquake Unitmustbeinstalledlevel Areamusthaveadequateventilation Areamusthaveadequateclearancefortheunit

Refrigerantpipingcan berunthroughfront, bottom,sideorrearof cabinet

Slide13

2012DaikinAC

RMXSClearances

Slide14

2012DaikinAC

IndoorUnits&Controls
CTXS,FTXS,CDXS,FDXS,&FFQ DaikinENVi (DACATS11),NavigationRemoteController (BRC1E72),WirelessRemoteController(ARC452),&Wired RemoteController(BRC944B)

2012 Daikin AC

WallMount

AvailableModels FTXS CTXS CTXS07LVJU CTXS09HVJU CTXS12HVJU FTXS15LVJU FTXS18LVJU FTXS24LVJU

Autoswingmechanismensuresefficientairdistributionvialouversthat
automaticallyclosewhentheunitisturnedoff Wideairdischargeoutletdistributesacomfortableairflowthroughouttheentire space Horizontallouversandfrontpanelcanbeeasilyremovedforcleaning Undisturbedcomfortwithindooroperatingsoundlevelsaslowas22dB(A)
Slide16 2012DaikinAC

ConcealedSlimDuct

FDXS_LVJU/CDXS_LVJU
AvailableModels FDXS CDXS FDXS09LVJU FDXS12LVJU CDXS15LVJU CDXS18LVJU CDXS24LVJU

Slimlowprofiledesign,only77/8 inheight Rearorbottomreturn Moldproofwashableresinfilterincluded WirelessReceiverwith60 cable

10ft.(DACAARCW901P10)&25ft.(DACAARCW901P25) receivercableextensionaccessoryoptionsavailable NOTE: When used on RXS09&12 DAVJU units, SEER rating is 13
Slide17 2012DaikinAC

FFQ_LVJU2x2CeilingCassette

FFQ_LVJU AvailableModels FFQ FFQ09LVJU FFQ12LVJU FFQ15LVJU FFQ18LVJU

Enhancedcomfortwithuniformairflowandtemperaturedistribution Draughtfreeprotectionwithhorizontalairdischarge Simpleinstallationwithaneasytofitdecorationpanelthatblendswithanyinterior


design

Easymaintenancewithaneasytocleangrilleandwashablelonglifefilter

Slide18

2012DaikinAC

CondensateDrainInstallation FFQ_LVJU2x2

Raisingsectionmust berunwith condensatepipe

Slide19

2012DaikinAC

IndoorUnitPipingConnections
CTXS07 Liquid (O.D.) Inches Gas (O.D.) Inches 3/8 3/8 FDXS09 3/8 FDXS12 1/4 CTXS09 CTXS12 1/4 FTXS15 FTXS18 FTXS24

CTXS/ FTXS

1/2 CDXS15

1/2 CDXS18

5/8 CDXS24

Piping CDXS/ Connections FDXS (Flared)

Liquid (O.D.) Inches Gas (O.D.) Inches Liquid (O.D.) Inches Gas (O.D.) Inches 3/8 FFQ09 3/8 FFQ12

1/2 FFQ15 1/4

1/2 FFQ18

5/8

FFQ

3/8

3/8

1/2

1/2

Slide20

2012DaikinAC

IndividualZoneControl
Daikins8ZoneMultiSplitsystemoffers consistenttemperaturethroughoutthehome withtheabilitytoindependentlycontrolupto eightindividualroomsonasinglesystem. UsingthefollowingRemoteControllers*: DaikinENVi (DACATS11) NavigationRemoteController(BRC1E72) WirelessRemoteController(ARC452) WiredRemoteController(BRC944B) WirelessRemoteControllerKit(BRC7E830) *RCselectionisdependentonindoorunit installed. ARC452 Wireless

DACATS11 DaikinENViOption NotavailableforFFQ

BRC944 WiredOption NotavailableforFFQ

BRC1E72 NavigationRemote FFQOnly BRC7E830 WirelessKit FFQOnly


Slide21 2012DaikinAC

DaikinENVi(DACATS11)
CompatiblewithCTXS/FTXSandCDXS/FDXS KeyFeaturesandFunctions: Cool,Heat,andAutomodeswithdualsetpoints Weeklyschedulingforresidentialuse Setbackcontrol Optimumstart Hold,Quicksave,andVacationsettings FanOn/Auto,Fanspeed,andLouverdirection Errorcodewithplaintextexplanation WiFienabled accessiblethroughPCweb,Smart phone/Tablet DealerWebPortal AlertEmailandTrendGraph Display Roomtemperature/relativehumiditydisplay Outdoortemperatureandweatherforecast Other Backlit Fahrenheit/Celsiusselectable Currentoperationstatus Roomtemperaturesensor RelayforAUXheaterconnection(manuallyswitchover fromHPtoAUXisrequiredbyuser)
Slide22 2012DaikinAC

NavigationRemoteController (BRC1E72)
KeyFeaturesandFunctions: Configurabledisplay Standard,Detailed,andSimple DualorsingleCoolandHeatsetpointsforoccupiedperiods Setbacksetpointsforunoccupiedperiods Unwantedbuttons/operationmodescanbedisabled Poweroffeliminatessetpointandmodeadjustment configurable Setpointrangelimitation Individualbuttonprohibits AutomaticadjustmentforDaylightSavingsTime(DST) Schedule Weeklyschedule 7day,weekdayplusSaturdayand Sunday(5+1+1),weekdayplusweekend(5+2)and Everyday(1) Allowsprogrammingupto5eventsperdaywithCooland Heatorsinglesetpoints SetbackconfigurationwithCoolandHeatsetpoints Display Detaileddisplaymode Standarddisplaymode Simpledisplaymode(new) Facedecaloptiontoeliminateunnecessarybuttons

withoptionalface plate

AvailableforFFQOnly,mustbepurchasedseparately
Slide23 2012DaikinAC

WirelessRemoteController(ARC452)
CompatiblewithCDXS/FDXSandCTXS/FTXS

KeyFeaturesandFunctions: SwingFunction ModeSelection(Auto,Dry,Cool,Heat,Fan) PowerfulFunction IntelligentEye(wallmountunitsonly) QuietOperation On/OffTimer SelfDiagnosiswithDigitalDisplay NightSetMode

Slide24

2012DaikinAC

WiredRemoteController(BRC944B)
CompatiblewithallindoorunitsexceptFFQ KeyFeaturesandFunctions:

Builtinonetimeordailytimerfunctionality
withupto2timeractionsperday

LCDletsyoudisplaysetpointtemperaturein
1For1Cunits

Selectableauto/cool/heat/dry/fan
operationmodeswithadjustabletemperature andairflowrates

Approximatelytwohourbatterybackup Controllercanbeusedinconjunctionwiththe
factorysuppliedstandardwirelessremote controller
Slide25 2012DaikinAC

BRC7E830Option
HandheldWirelessRemoteController
WirelessRemoteControllersare
providedaskits

Temperatureissetpointdisplay WirelessControllersonly
communicatewiththefancoil whentheyarepointedatthe receiverandabuttonispressed

ListenforaBeeporBeepBeep
forconfirmation

AvailableforFFQOnly,mustbepurchasedseparately
Slide26 2012DaikinAC

BranchProviderUnits(BP)

2012 Daikin AC

BPUnitExplodedView

Gas Line Connection

Liquid Line Connection


Slide28 2012DaikinAC

AllowforServiceClearance
RemovingtheBPunitcoverisnecessary forservicingtheunit.DonotinstallBP unitflushagainstaceilingorother obstruction. InstallusingAllthreadorsimilar suspensionmethod. Toservice: Removethe4screwsonthebottom oftheunit Removethe4screwsthatsecurethe electricalwiringboxcover Removethe4screwsthatsecurethe electricalwiringboxtotheBPunit LifttheBPboxunit Liftthetophalfofthethermal insulationmolding

Allowatleast8of clearanceaboveBP unittoallowfor service.


Slide29 2012DaikinAC

InternalPipingDiagram
TheinletpipingtotheBPMKSUnitisencapsulatedinthermalinsulationmolding.Thelines enteringtheBPunitareseparateGasandLiquidLinesasindicatedinthefollowinginternal pipingdiagram.

Slide30

2012DaikinAC

Specifications
Flarenutconnections Choiceof2zoneor3zone BPunitstomatchthesystem selectiontoindividual requirements
Model Name Power Supply Power Consumption Minimum Circuit Amps (MCA) Running Current Sound Pressure - (Cooling/Heating) Number of Connectable Indoor Units Min. Connection Combination Max. Connection Combination Piping Outdoor Unit Side Liquid Connections Indoor Unit Side (O.D.) Outdoor Unit Side Gas Indoor Unit Side Drain Reducer in. in. in. in. in. pc. pc. pc. Dimensions (H x W x D) Net Weight in. lbs. 5/8 x 2 Not required 1 ( 3/8 1/4) 4 ( 5/8 1/2) 3 ( 5/8 3/8) 7-1/16 x 11-9/16 x 13-3/4 18.0 20.0 1/4 x 2 5/8 x 1 5/8 x 3 W A A dB(A) BPMKS048A2U 10.0 15.0 0.05 32/32 1 to 2 7,000 48,000 3/8 x 1 1/4 x 3 BPMKS049A3U 10.0 15.0 0.05 32/32 1 to 3 7,000 62,000 Single phase 60Hz 208/230V

Slide31

2012DaikinAC

Installation
TheBPunitisforindooruseandshouldbeinstalledaboveaceilingor behindawallinaccordancewiththefollowingconditions. Theunitmustbe:

Fullysupportedinalocationwithlittleornovibration Easilyaccessiblewithadequatespaceforservicingorrepairs Placedwithindistanceofallowablepipelength Locatedawayfromitemsproducingheatorsteam(gas) Locatedinawellventilatedarea;notinstalledinalocationthatishot


orhumidforlongperiodsoftime(DBtempof140 orabove)

Notinstallednearbedroomsduetopossibleaudiblesoundsof
refrigerantflowthroughthepiping

Slide32

2012DaikinAC

InstallationRestrictions&Clearances

AccessPanel Provideanaccesspanelfor servicingandmaintenance.

Unit:inch(mm)

Slide33

2012DaikinAC

CeilingSuspendedInstallation
1. Fixthefurnished(B) washerretainingflange withtwo(C)screws.(4 locationsintotal) Unitmustbesuspended usinganallthreadbolt andhexnutandwashers. Insurethattheunitis level,tightenthehexnut.

2.

3.

TheBPUnitmustbeinstalled Level.Allowatleast8ofservice clearanceabovetheBPunit.


Slide34 2012DaikinAC

WallMountedInstallation

CAUTION Besuretoinstalltheunitwith thetopsurfaceup. Donotinstallnearbedrooms. Thesoundofrefrigerant flowingthroughthepiping maysometimesbeaudible.

TheBPUnitmustbeinstalledLevel. Allowatleast8ofserviceclearanceabovetheBPunit.
Slide35 2012DaikinAC

ElectricalBoxLocation
ThemountinglocationfortheElectricalBoxcanbemodifiedtobetterreflectthe needsoftheinstallation.

ElectricalBoxasShipped

ElectricalBoxwhenRelocated

Slide36

2012DaikinAC

RelocatingElectricalBox
ProceduresforChangingLocationofEBox
1. Removescrewsandpulloffelectrical wiringboxcover.

2.

Remove4screwsshowninthe figure,removetheprintedcircuit board.

Slide37

2012DaikinAC

RelocatingElectricalBox
3. Removethebindingband(A) whichholdsthewires.

4.

Removetheprintedcircuitboard, andreattachasshowninthe figure.

Slide38

2012DaikinAC

RelocatingElectricalBox
5. Reattachthebindingbandto position(B).

6.

Attachprintedcircuitboardand electricalwiringboxcoverto othersideandsecurewith screws.

Slide39

2012DaikinAC

BlankingOffPorts
TheBranchProviderUnitsareshipped witheachportblankedoff. Toaccessaportforuse: Removetheflarenut Removetheblank Anyportthatwillnotbeinuseshould remainblankedoff. Note:Aminimumoftwoindoorunits mustbeinstalledper8Zonesystem. Theindoorunitscaneachbeconnectedto separateBranchProviderunitstoallowfor futureexpansionofthesystem.

Slide40

2012DaikinAC

8ZoneSelectionTool

2012 Daikin AC

8ZoneSelectionTool

Slide42

2012DaikinAC

SelectionFlowChart

Slide43

2012DaikinAC

SelectionToolReport

Slide44

2012DaikinAC

ElectricalWiring

2012 Daikin AC

ElectricalWiring
Theoutdoorunitandbranchprovider(BP)unitsoperatefromseparate208/230V singlephasepowersupplies,eliminatingtheneedofpowersupplybetweenthem. Therefore,wiringsizefromtheoutdoorunittothebranchprovider(BP)unitscanbe reducedandeaseinstallation.
DIIInettransmissionline 4wiretransmissionandpowersupply PowerSupply

MaxWiringLengthbetweenunits 656ft. TotalSystemWiringLength 984ft. AWG1816


Alwaysfollowlocalcodes
Slide46 2012DaikinAC

DetailedViewofBPWiring

3ZoneBPunitshown

Alwaysfollowlocalcodes
Slide47 2012DaikinAC

DetailedViewofBPUnitPCB

Interunitwiring toZoneA(1,2,3& Grd) Interunitwiring toZoneB(1,2,3 &Grd) 33ft.useAWG1614 >33ft.useAWG14

F1&F2 Transmission wiretootherBP unitorOutdoor Unit(Sheathed 2strandAWG 1816) L1,L2,&GRD From 208/230V Electrical Supply(AWG 1614)

2ZoneBPunitshown

Alwaysfollowlocalcodes
Slide48 2012DaikinAC

BPUnitInstallation Electrical Conduit

L1&L2From208/230VElectricalSupply(AWG1614) MOCP=15

Alwaysfollowlocalcodes
Slide49 2012DaikinAC

ElectricalWiringConnections
ConnectionExampleofTotalSystemWiring
Dedicated circuit not required for individual BP units

Alwaysfollowlocalcodes
Slide50 2012DaikinAC

RefrigerantPiping

2012 Daikin AC

InstallGuidelines
Whenconnectingapipetotheunitbodyor removingit,besuretouseabackupwrench andtorquewrench. Fortheworkdimensionandthetightening torqueoftheflaresection,seethistable. Whenconnectingaflarenut,applyoiltothe flaresection(onlytheOUTERsurface),and screwthenutthreeorfourtimesinitiallyby hand. Besuretousetheflarenutsincludedwith thecondenserorfancoil.
PipeSize 1/4" 3/8" 1/2" 5/8" 3/4" TighteningTorque 10.412.7ftlbf 24.129.4ftlbf 36.544.5ftlbf 45.655.6ftlbf 71.787.5ftlbf
Piping union Torque Wrench Back up Wrench Flare Nut

Slide52

2012DaikinAC

InstallationProcedures
Keeprefrigerantpipingcleanandsealedduring
installation UseNitrogenpurgeduringbrazingprocess Refrigerantpipingmustbeproperlyinsulated Recommendedwallinsulation LiquidandGaspipesmustbeindividuallyinsulated AllFlarenutconnectionsmustbeinsulated Refrigerantpipingmustbeproperlysupported Followlocalcoderequirementsforpipingsupport locations Supportpipingwithin12ofBPBoxandFanCoilunit Keeptrackofeachrefrigerantcircuitduringinstallation Totalrefrigerantpipinglengthcannotexceed440ft (135m) Measureliquidlinesastheyareinstalled Avoidcrossingrefrigerantlinesduringinstallation

Slide53

2012DaikinAC

InsulationRequirements
TheLiquidandGaspipingmustbe
completelyinsulated Recommendedwallthickness 3/4 Allflareconnectionsmustbeinsulated

Indoor Unit Installation Kit

Slide54

2012DaikinAC

PipingRule#1
TotalpipinglengthbetweenoutdoorunitandBPunits180ft

a +b +c +d +e 180
a b c

Slide55

2012DaikinAC

PipingRule#2
TotalpipinglengthbetweenBPunitsandindoorunits262ft

f +g +h +i +j +k +l 262

f g

i j

Slide56

2012DaikinAC

PipingRule#3
TotalpipinglengthbetweenaBPunitandconnectedindoorunit49ft

f,g,h,i,j,k,l 49

h g

Slide57

2012DaikinAC

PipingRule#4
Totalallowableheightbetweenoutdoorandindoorunits98ft

H198

H1

Slide58

2012DaikinAC

PipingRule#5
TotalallowableheightbetweenoutdoorunitandBPunits98ft

H298

H2

Slide59

2012DaikinAC

PipingRule#6
TotalallowableheightbetweenBPunits49ft

H349

H3

Slide60

2012DaikinAC

PipingRule#7
Totalallowableheightbetweenindoorunits49ft

H449

H4

Slide61

2012DaikinAC

PipingRule#8
Minimumallowablepipinglengthbetweenoutdoorunitandfirst REFNET16.4ft

m16.4
m

Slide62

2012DaikinAC

PipingRule#9
MaximumpipinglengthfromfirstREFNETtofurthestindoorunit131ft

n131

REFNETkitsarerecommendedtobesetasnearas possibletotheBPunits.Thisrunisrecommendedto beasshortaspossible.


Slide63 2012DaikinAC

SystemExample

8ZoneMultiPlusSystemExample FromSelectionTool
Slide64 2012DaikinAC

PipeSizeSelection
Gas Liquid BetweenoutdoorunitandfirstREFNET Between1stREFNETand2ndREFNET BetweenREFNETandBPunit(TotalConnectedindoorunitcapacity17,000Btu/h) BetweenREFNETandBPunit(TotalConnectedindoorunitcapacity17,000Btu/h) 3/4" 3/8" 5/8" 3/8" 1/2" 1/4" 5/8" 3/8"

Slide65

2012DaikinAC

CalculateAdditionalRefrigerant
R = Total Length(ft)of liquidpipingsizeat 3/8in.OD x 0.036 lb/ft X Totallength(ft)of liquidpipingsizeat in. OD X 0.015lb/ft

ExampleforrefrigerantbranchusingREFNETjoint(unit:ODinchxft) R=[(a+b+d+e)x0.036]+[(c+f+g+h+i+j+k=L)]x0.015=[128x0.036]+[234x0.15]=8.118lbor8.1lb

a:3/8x32 b:3/8x32 c:3/8x32

d:3/8x32 e:3/8x32 f:1/4x32

g:1/4x32 h:1/4x32 i:1/4x32

j:1/4x32 k:1/4x32 L:1/4x32

Slide66

2012DaikinAC

REFNETFittings

2012 Daikin AC

REFNETComponents

REFNET Y Branch Gas & Liquid Kit KHRP26A22T

Slide68

2012DaikinAC

REFNETYJointInstallation

REFNET Y Joints to be installed: straight up - straight down level (+/- 30) Each REFNET included in the branch kit is labeled to identify circuit: Liquid Gas
Slide69 2012DaikinAC

REFNETY Positionvs.Flow Demonstration

Slide70

2012DaikinAC

RefrigerantFlowDemonstration

Slide71

2012DaikinAC

PipeFlaring

Properdeburringiscriticalforasuccessfulflarefitting
Slide72 2012DaikinAC

PipingFlaring
Bdepthforpipe Go/NoGo Flaring Block B

A
DACAFSG1 Bdepthforallothersizes DimensionArequirement PipeSize 1/4 3/8 1/2 5/8 3/4 Dimension 9.1mm 13.2mm 16.6mm 19.7mm 24.0mm DimensionBRequirement PipeSize 1/4 3/8 1/2 5/8 3/4 Dimension 1mm 2mm 2mm 2mm

2mm
Slide73 2012DaikinAC

Brazing
DryNitrogenMUST beusedduringallbrazing (Pressureregulatedto1.5to3PSIG)toprevent oxidationformation

TapeinSchraderFitting SetNitrogenregulatorto 1.5 3PSIG Leaveotherendofpipe open

Slide74

2012DaikinAC

InstallationExamples

2012 Daikin AC

OutdoorUnitInstalled
Properinstallation OutdoorUnitisinstalledlevel Shippingbracketshavebeen removed Allrefrigerantpipingisinstalled Pressuretestedto550psifor24 hours Tripleevacuationofrefrigerant system,finalevacuationto500 micronsorbelowandheldfor1 hour Additionalchargecalculatedby liquidlinesizesandlength UnitchargedwithR410Ainliquid state

Slide76

2012DaikinAC

BranchProviderUnitInstalled
Properinstallation BPUnitisinstalledleveland withproperclearance Highandlowvoltagewiring properlyterminated Refrigerantpipingproperly insulated Note:flarenutsinsulatedafter photo

Slide77

2012DaikinAC

REFNETInstalledLevel
Properinstallation REFNETfittingsareinstalledlevel Allrefrigerantpipingisinsulated

Slide78

2012DaikinAC

RefrigerantPipingInstalled
Properinstallation Refrigerantpipingisinsulated Bracketsareinstalledoutsideof insulationallowingfor expansionoflineset BPunitpowerdisconnect installed

Slide79

2012DaikinAC

WhatNOTtodo

Improper Installation BPunitinstalledflushwithceiling.BPunitsmustbeinstalledwithadequateservice clearance.Allowatleast8ofclearanceabovetheBPunit.


Slide80 2012DaikinAC

WhatNOTtodo

Improper Installation BPunitinstalledat30+degreeangle(BPunitsmustbeinstalledlevel).


Slide81 2012DaikinAC

StartUpChecklist

2012 Daikin AC

StartUpChecklist
Compressorshippingbracketsremoved StopValvessecurelyclosed&fieldrefrigerantpipingpressuretestedto550psifor24 hoursmin. Tripleevacuateto500micronsorless Allliquidlinesaremeasured,AdditionalRefrigerantChargeiscalculatedand weighedintothesystem,breakingthefinalvacuum StopValvesopened AllcontrolwiringisinstalledandproperlyconnectedateachterminalblocktoBP units Allcondensatedrainpipingisconnected,includingfancoiltiein,andinsulatedas required RefrigerantlinesarecompletelyinsulatedincludingflarenutconnectionsatIndoor UnitsandBPunits

Slide83

2012DaikinAC

StartUpChecklist
Allapplicableductworkisconnectedandairfiltersinstalled LineVoltageischeckedandverifiedtobewithinspecifiedrangeforallsystem components PowerupBPunits Powerupoutdoorunittoenergizecrankcaseheaters(minimum6hrs)Initialization sequencestartsandthesystemaddressesareset SetupNavigationRemote Controllers(forFFQ) Systemrefrigerantcharge AdditionalRefrigerantChargemode TestOperation RemainingSystemFieldSettings VerifysystemoperationinCool&Heatmodeasoutsideambienttemperature conditionsallow(heatmodeisprohibitedabove75.2Foutsideairtemperature)

Slide84

2012DaikinAC

OperatingTest
FollowtheOperatingTestasdescribedintheinstallationmanualoftheoutdoorunit.IfBP unitdoesnotoperatenormallyduringthetestrun,theerrorcanbecheckedontheremote controllerdisplayfortheindoorunit.
ErrorCodesdisplayedontheremotecontroller

Code A9 E2 J0 U4 U9

Nonconformity duringinstallation Electricexpansionvalve connectornot connected(BPunit) Printedcircuit boardfaulty(BPunit) Liquid andgasthermistorfaulty(BP unit) TransmissionerrorbetweenBPunitand indoorunit Transmissionerror betweenoutdoor unitandBPunit

Remedialaction Pleasecontactyourdealer

Correctlyconnecttheinterconnections betweenBPunitandindoorunit Correctlyconnecttheinterconnections betweenoutdoorunitandBPunit

*DONOTperformanyotherproceduresduringOperatingTest *OperatingTestCANNOTbeperformedduring:initialization,additionalcharge,orrecovering mode SimplediagnosiscanbedoneusingtheLEDsontheBPunitscircuitboard. Fordetails,seethelabelontheinsideoftheBPunitselectricalwiringunitcover.


Slide85 2012DaikinAC

OperatingTest
PowerOn CheckOperation Insureallthermisters andtransducersareinplace PowerONoutdoorunitfor6hours(crankcaseheater) PowerONbranchportunits OpenServiceValves Performcheckoperation Press/HoldBS4(Test)buttonfor5seconds

Slide86

2012DaikinAC

OperatingTest
TemperatureControl CheckOperation Makessuretheindoorandoutdoorunitsareoperatingnormally Runeachindoorunitoneatatimeandmakesuretheoutdoorunitisalso running Checktoseeifcold(orhot)airiscomingoutoftheindoorunit Pressthefandirectionandfanstrengthbuttonsontheindoorunittosee iftheyoperateproperly

Slide87

2012DaikinAC

TopicsRecap
OutdoorUnit IndoorUnits&Controls BranchProviderUnits 8ZoneSelectionTool RefrigerantPiping REFNETFittings InstallationExamples StartUpChecklist

Slide88

2012DaikinAC

Thank You

PTRLC1207PP001A
2012 Daikin AC