GUJARAT TRANSFORMERS PVT. LTD.

Reg., Office & Works : Maneja-BARODA-390013 Phone : (O) 0265 2642422, 0265- 3122233, Fax : 0265 2642567. Manufacturers of GUJFORMER Brand Power & Distribution Transformers upto 8000 KVA at 66KV

TECHNICAL PARTICULARS OF TRANSFORMER


Customer : M/s. GUJARAT PANEL BOARD PVT LTD. Our Reference No.: G1829/1/11
Make Reference Standards 1. TYPE OF TRANSFORMER

Date: 21/01/2012

GUJARAT TRANSFORMERS IS 1180 : 1982, IS : 2026 : 1977, IS: 11171 Outdoor, Double Copper Wound, Core Type Air Cooled Dry Type Resin Coated (Dip) Transformer Distribution Load

2. 3. a) b) 4. a) b) 5. 6. 7. a) b) 8. 9. a) b) 10. a) b) 11. a) b) c)

APPLICATION OF TRANSFORMER KVA RATING CONTINIOUS HV Winding LV Winding RATED VOLTAGE Primary Winding Secondary Winding RATED FREQUENCY NUMBER OF PHASES RATED CURRENT PRIMARY SIDE SECONDARY SIDE MATERIAL OF WINDING CONNECTIONS Primary Winding Secondary Winding VECTOR GROUP HV-LV Direction of Flow From TAPPING Range Number of Steps For high voltage variation % Amps Amps KVA KVA Volts Volts Hz

200 200 415 415 50 3

278.24 278.24 Double Copper Wound

Delta Star

Dy11 HV to LV Primary to Secandary

NIL

12. IN CASE OFF CIRCUIT VOLTAGE VARIATION, STATE (a) OR (b) a) Off Circuit Tap Switch b) Off Circuit Links

(b) 47.5 Hz to 52.5 Hz +2% to -5% +/-5%

13. Transformer suitability for Frequency Variation Between a) Voltage Variation b) Frequency Variation

1/4

Customer : M/s. GUJARAT PANEL BOARD PVT LTD. Our Reference No.: G1829/1/11
14. REFERENCE AMBIENT AIR TEMPERATURE 15. HOT SPOT TEMPERATURE 16. TYPE OF COOLING 17. TEMPERATURE RISE a) Top in Air b) Windings C C 50 C 150 C Max ONAN 120 C 140 C C.R.G.O. Low Loss Imported Materials 41 (Prime) material mm mm 0.27 mm 0.005 mm E.C. Grade Copper with 99.9% Purity from Birla Copper/Sterlite India 3880 Watts

Date: 21/01/2012

C C

18. CORE a) Core Laminations b) c) d) Grade Thickness of Core Lamination

Thickness of Insulation of Core Lamination 19. COPPER 20. TOTAL LOSS AT RATED VOLTAGE, AT PRINCIPLE TAPPING AND RATED FREQUENCY a) No Load Loss at rated voltage and Rated Frequency b) Load Loss at rated Current on Principle tapping at 75 C c) Tolerance On Losses 21. NO LOAD CURRENT AT RATED VOLTAGE AND RATED FREQUENCY a) When excited from LV at 100 % Rated Voltage b) When excited from LV at 110 % Rated Voltage 22. EFFICIENCY AT 75 C a) At full load b) At full load c) At full load 23. REGULATION AT FULL LOAD & AT 75 C a) At Unity Power Factor b) At 0.8 Power Factor (Lagging) c) Load of Maximum Efficiency d) Maximum Efficiency 24. FLUX DENSITY 25. CURRENT DENSITY USED FOR a) HV Winding b) LV Winding

Watts Watts Watts +10% of Total Losses 1200 + IS TOLL 2750 + IS TOLL

< 2% < 3% AT % % % Unity PF 98.06 98.20 98.14

% % % % Tesla

1.77% 3.55 66.05% 98.81% 1.65 MAX

Amp\mm 2 Amp\mm 2

1.6 1.7

26. IMPEDANCE VOLTAGE AT RATED CURRENT FOR THE PRINCIPLE TAPPING HV-LV % 27. REACTANCE AT RATED CURRENT & RATED FREQUENCY HV-LV

3.62

2/4

Customer : M/s. GUJARAT PANEL BOARD PVT LTD. Our Reference No.: G1829/1/11
28. SHORT CIRCUIT WITHSTAND Sec a) INJURY FOR 3 PHASE SHORT CIRCUIT AT TERMINAL 29. TOLERANCE ON IMPEDANCE VOLTAGE AT RATED CURRENT 30. OVERLOAD CAPACITY OF TRANSFORMER BOTH UNDER HOT & COLD CONDITION

Date: 21/01/2012

40 KA for 3 sec 5 SEC +/- 10%

31. HV PHASE SEQUENCE 32. CLEARANCES IN AIR WITH COVER (Minimum) a) b) c) d) e) HV Terminal To HV Terminal HV Terminal To Earth LV Phase To Phase LV Phase To Earth HV Winding To Earth mm 33. INSULATION LEVEL a ) SEPRATE SOURCE POWER FREQUENCY VOLTAGE WITHSTAND FOR 60 SECONDS i) HV Winding KV ii) LV Winding KV mm mm mm mm

As Per IS : 6600 : 1972 1U,1V,1W 120 120 75 25 25

3 3

b) INDUCED OVER VOLTAGE WITHSTAND FOR 60 SECONDS ii) LV Winding Volts c) i) ii) d) FULL WAVE LIGHTNING IMPULSE WITHSTAND VOLTAGE HV Winding LV Winding CLASS OF INSULATION

830 AT 143 HZ

KVP

NA NA A

34. TERMINAL ARRANGEMENT a) b) c) d) 35. a) b) c) d) 36. a) b) c) d) Primary Side Delta Secondary Side Star Neutral Neutral CT APPROXIMATE MASSES Core & Winding Tank, Fittings & Accessories Oil Total mass APPROXIMATE OVERALL DIMENSIONS OF TRANSFORMER Length Breadth Height Un tanking height Kg. Kg. Kg. Kg. 880 625 ----1625 Three weather Proof bare Bushing type Terminal in Cable Box. Three weather Proof bare Bushing type Terminal in Cable Box. In Cable Box N.A.

mm. mm. mm. mm

As per your Enclosure As per your Enclosure As per your Enclosure As per your Enclosure

3/4

Customer : M/s. GUJARAT PANEL BOARD PVT LTD. Our Reference No.: G1829/1/11
37. a) b) c) d) 38. 39. a) b) OIL DATA Quantity Oil Data for first filling Grade of Oil used Makers Name BDV at the time of filling BREATHER TYPE WITH CAPACITY OF SILICA GEL FILLED IN GRAM DETAIL OF BUSHINGS Type Make KV -------------------------------------------------------------------------------------------HV BUSHING 1.1 KV, 630 Amps Sampat Ceramics IS 3347 : 1987 IS : 2099 :1973 NA 2 2 2 Electrically welded M.S. Plates IP-55 --------------------------------------------------------------------Fiber glass sheet Nomex Double Paper covering of Bellerpur Nomex Double Paper covering of Bellerpur Fiber glass cylinder Fiber glass cylinder As Per IS 2026 : 1977 30% to 40% of non linear Load Light Grey 632 as per IS-5

Date: 21/01/2012

Litre

LV BUSHING 1.1 KV, 630 Amps Baroda Bushing / Sampat Cermics IS 3347 : 1987 IS : 2099 :1973

c) IS Reference d) Fault level withstand capacity at HV side 40. THICKNESS OF PLATE USED IN TANK a) Bottom mm b) Side mm c) Top mm 41. TYPE OF TANK a) Enclosure class of Transformer 42. AIR PRESSURE TEST FOR TANK LEAKAGE 43. VACCUM WITHSTAND CAPABILITY 44. 45. 46. a) b) c) d) 47. 48. 49. NOISE LEVEL THICKNESS OF RADIATOR INSULATION MATERIALS HV Conductor LV Conductor Core to LV Winding LV to HV Winding EXTERNAL SHORT CIRCUIT WITHSTANDING CAPACITY TRANSFORMER SUITABILITY FOR COLOR SHADE IN FINAL PAINTING

The weight & dimensions are Approximate & we do not give guarantee for that as it does not covered under IS : 2026.

FOR GUJARAT TRANSFORMERS PVT. LTD.