SUBSTATION STEEL STRUCTURES

Pacific Steel Structures, LLC 19814 E Pheasant Dr., Greenacres, WA 99016 Phone: (509) 921-5835 Fax: (509)921-5857

www.pacificsteelstructures.com

01 02 03 04 05 06 07 08 09 10 11 12 13 14 15

115 or 230kV A-Frame Dead-End 230kV Intercept Structure 230kV Bus & Airbrake Switch Support 230kV Single Phase Current Transformer Stand 13.8kV 3-Phase Switch Support 13.8kV 1200A Switch support 13.8kV 5000A Switch Support -A 13.8kV 5000A Switch Support-B 13.8kV Grounding Transformer Support 13.8kV 3-Phase Single Leg Bus Support 13.8kV 3-Phase Two Leg Bus Support 13.8kV Bus or Insulator Support 13.8kV 3-Phase Vertical Bus Suspension Support 13.8kV 3-Phase Bus Support with PT Mount 13.8kV 3-Phase Bus Jumper Structure

Pacific Steel Structures, LLC 19814 E Pheasant Dr., Greenacres, WA 99016 Phone: (509) 921-5835 Fax: (509)921-5857

www.pacificsteelstructures.com

115 or 230kV A-Frame DeadEnd


Custom Engineered Substation Structures Custom designed to meet your dimensional requirements. PE certified drawing & calculation package provided. Galvanized to ASTM A123.
Materials: Tubes: ASTM A500 Gr. B Shapes / Plates: ASTM A36 / ASTM A572 Gr. 50 Wide Flanges: ASTM A992 Base Plates: ASTM A572 Gr. 50 Erection Bolts: ASTM A325X

Design Codes and Specifications: Industry: NESC, IEEE Std 605, and ASCE Manual 113 Short Circuit Force: USDA/RUS Bulletin 1724E-300 (June 2001), Section 4.11 Rigid Bus Design. Wind: Per 2009 IBC & ASCE/SEI 705. Seismic: Per 2006 IBC Section 1613, ASCE 7-05 Sections 15.1.3 & 12.8. Welding: ANSI/AWS D1.1-06. Steel: AISC "Steel Construction Manual", Edition. [Type 13th text]

Pacific Steel Structures, LLC 19814 E Pheasant Dr., Greenacres, WA 99016 Phone: (509) 921-5835 Fax: (509)921-5857

www.pacificsteelstructures.com

230kV Intercept Structure


Custom designed to meet your dimensional requirements. PE certified drawing & calculation package provided. Galvanized to ASTM A123. Custom Engineered Substation Structures
Materials: Tubes: ASTM A500 Gr. B Shapes / Plates: ASTM A36 / ASTM A572 Gr. 50 Wide Flanges: ASTM A992 Base Plates: ASTM A572 Gr. 50 Erection Bolts: ASTM A325X

Design Codes and Specifications: Industry: NESC, IEEE Std 605, and ASCE Manual 113 Short Circuit Force: USDA/RUS Bulletin 1724E-300 (June 2001), Section 4.11 Rigid Bus Design. Wind: Per 2009 IBC & ASCE/SEI 7-05. Seismic: Per 2006 IBC Section 1613, ASCE 7-05 Sections 15.1.3 & 12.8. Welding: ANSI/AWS D1.1-06. Steel: AISC "Steel Construction Manual", 13th Edition.

Pacific Steel Structures, LLC 19814 E Pheasant Dr., Greenacres, WA 99016 Phone: (509) 921-5835 Fax: (509)921-5857

www.pacificsteelstructures.com

230 kV Bus and Airbreak Switch Support Structure


Custom Engineered Substation Structures Custom designed to meet your dimensional requirements. PE certified drawing & calculation package provided. Galvanized to ASTM A123.
Materials: Tubes: ASTM A500 Gr. B Shapes / Plates: ASTM A36 / ASTM A572 Gr. 50 Wide Flanges: ASTM A992 Base Plates: ASTM A572 Gr. 50 Erection Bolts: ASTM A325X

Design Codes and Specifications: Industry: NESC, IEEE Std 605, and ASCE Manual 113 Short Circuit Force: USDA/RUS Bulletin 1724E-300 (June 2001), Section 4.11 Rigid Bus Design. Wind: Per 2009 IBC & ASCE/SEI 7-05. Seismic: Per 2006 IBC Section 1613, ASCE 7-05 Sections 15.1.3 & 12.8. Welding: ANSI/AWS D1.1-06. Steel: AISC "Steel Construction Manual", 13th Edition.

Pacific Steel Structures, LLC 19814 E Pheasant Dr., Greenacres, WA 99016 Phone: (509) 921-5835 Fax: (509)921-5857

www.pacificsteelstructures.com

230 kV Single Phase Current Transformer Stand


Custom designed to meet your dimensional requirements. PE certified drawing & calculation package provided. Galvanized to ASTM A123. Custom Engineered Substation Structures
Materials: Tubes: ASTM A500 Gr. B Shapes / Plates: ASTM A36 / ASTM A572 Gr. 50 Wide Flanges: ASTM A992 Base Plates: ASTM A572 Gr. 50 Erection Bolts: ASTM A325X

Design Codes and Specifications: Industry: NESC, IEEE Std 605, and ASCE Manual 113 Short Circuit Force: USDA/RUS Bulletin 1724E-300 (June 2001), Section 4.11 Rigid Bus Design. Wind: Per 2009 IBC & ASCE/SEI 7-05. Seismic: Per 2006 IBC Section 1613, ASCE 7-05 Sections 15.1.3 & 12.8. Welding: ANSI/AWS D1.1-06. Steel: AISC "Steel Construction Manual", 13th Edition.

Pacific Steel Structures, LLC 19814 E Pheasant Dr., Greenacres, WA 99016 Phone: (509) 921-5835 Fax: (509)921-5857

www.pacificsteelstructures.com

13.8 kV 3-Phase Switch Support


Custom designed to meet your dimensional requirements. High or Low Configuration PE certified drawing & calculation package provided. Galvanized to ASTM A123.
Materials: Tubes: ASTM A500 Gr. B Shapes / Plates: ASTM A36 / ASTM A572 Gr. 50 Wide Flanges: ASTM A992 Base Plates: ASTM A572 Gr. 50 Erection Bolts: ASTM A325X

Custom Engineered Substation Structures

Design Codes and Specifications: Industry: NESC, IEEE Std 605, and ASCE Manual 113 Short Circuit Force: USDA/RUS Bulletin 1724E-300 (June 2001), Section 4.11 Rigid Bus Design. Wind: Per 2009 IBC & ASCE/SEI 7-05. Seismic: Per 2006 IBC Section 1613, ASCE 7-05 Sections 15.1.3 & 12.8. Welding: ANSI/AWS D1.1-06. Steel: AISC "Steel Construction Manual", 13th Edition.

Pacific Steel Structures, LLC 19814 E Pheasant Dr., Greenacres, WA 99016 Phone: (509) 921-5835 Fax: (509)921-5857

www.pacificsteelstructures.com

13.8kV 1,200Amp Switch Support


Custom designed to meet your dimensional requirements. PE certified drawing & calculation package provided. Galvanized to ASTM A123. Custom Engineered Substation Structures
Materials: Tubes: ASTM A500 Gr. B Shapes / Plates: ASTM A36 / ASTM A572 Gr. 50 Wide Flanges: ASTM A992 Base Plates: ASTM A572 Gr. 50 Erection Bolts: ASTM A325X

Design Codes and Specifications: Industry: NESC, IEEE Std 605, and ASCE Manual 113 Short Circuit Force: USDA/RUS Bulletin 1724E-300 (June 2001), Section 4.11 Rigid Bus Design. Wind: Per 2009 IBC & ASCE/SEI 7-05. Seismic: Per 2006 IBC Section 1613, ASCE 7-05 Sections 15.1.3 & 12.8. Welding: ANSI/AWS D1.1-06. Steel: AISC "Steel Construction Manual", 13th Edition.

Pacific Steel Structures, LLC 19814 E Pheasant Dr., Greenacres, WA 99016 Phone: (509) 921-5835 Fax: (509)921-5857

www.pacificsteelstructures.com

13.8 kV 5,000Amp Switch Support


Custom designed to meet your dimensional requirements. PE certified drawing & calculation package provided. Galvanized to ASTM A123. Custom Engineered Substation Structures
Materials: Tubes: ASTM A500 Gr. B Shapes / Plates: ASTM A36 / ASTM A572 Gr. 50 Wide Flanges: ASTM A992 Base Plates: ASTM A572 Gr. 50 Erection Bolts: ASTM A325X

Design Codes and Specifications: Industry: NESC, IEEE Std 605, and ASCE Manual 113 Short Circuit Force: USDA/RUS Bulletin 1724E-300 (June 2001), Section 4.11 Rigid Bus Design. Wind: Per 2009 IBC & ASCE/SEI 7-05. Seismic: Per 2006 IBC Section 1613, ASCE 7-05 Sections 15.1.3 & 12.8. Welding: ANSI/AWS D1.1-06. Steel: AISC "Steel Construction Manual", 13th Edition.

Pacific Steel Structures, LLC 19814 E Pheasant Dr., Greenacres, WA 99016 Phone: (509) 921-5835 Fax: (509)921-5857

www.pacificsteelstructures.com

13.8kV 5,000Amp Switch Support


Custom designed to meet your dimensional requirements. PE certified drawing & calculation package provided. Galvanized to ASTM A123. Custom Engineered Substation Structures
Materials: Tubes: ASTM A500 Gr. B Shapes / Plates: ASTM A36 / ASTM A572 Gr. 50 Wide Flanges: ASTM A992 Base Plates: ASTM A572 Gr. 50 Erection Bolts: ASTM A325X

Design Codes and Specifications: Industry: NESC, IEEE Std 605, and ASCE Manual 113 Short Circuit Force: USDA/RUS Bulletin 1724E-300 (June 2001), Section 4.11 Rigid Bus Design. Wind: Per 2009 IBC & ASCE/SEI 7-05. Seismic: Per 2006 IBC Section 1613, ASCE 7-05 Sections 15.1.3 & 12.8. Welding: ANSI/AWS D1.1-06. Steel: AISC "Steel Construction Manual", 13th Edition.

Pacific Steel Structures, LLC 19814 E Pheasant Dr., Greenacres, WA 99016 Phone: (509) 921-5835 Fax: (509)921-5857

www.pacificsteelstructures.com

13.8 kV Grounding Transformer Support


Custom Engineered Substation Structures Custom designed to meet your dimensional requirements. PE certified drawing & calculation package provided. Galvanized to ASTM A123.
Materials: Tubes: ASTM A500 Gr. B Shapes / Plates: ASTM A36 / ASTM A572 Gr. 50 Wide Flanges: ASTM A992 Base Plates: ASTM A572 Gr. 50 Erection Bolts: ASTM A325X

Design Codes and Specifications: Industry: NESC, IEEE Std 605, and ASCE Manual 113 Short Circuit Force: USDA/RUS Bulletin 1724E-300 (June 2001), Section 4.11 Rigid Bus Design. Wind: Per 2009 IBC & ASCE/SEI 7-05. Seismic: Per 2006 IBC Section 1613, ASCE 7-05 Sections 15.1.3 & 12.8. Welding: ANSI/AWS D1.1-06. Steel: AISC "Steel Construction Manual", 13th Edition.

Pacific Steel Structures, LLC 19814 E Pheasant Dr., Greenacres, WA 99016 Phone: (509) 921-5835 Fax: (509)921-5857

www.pacificsteelstructures.com

13.8 kV 3-Phase Single Leg Bus Support


Custom Engineered Substation Structures Custom designed to meet your dimensional requirements. PE certified drawing & calculation package provided. Galvanized to ASTM A123.
Materials: Tubes: ASTM A500 Gr. B Shapes / Plates: ASTM A36 / ASTM A572 Gr. 50 Wide Flanges: ASTM A992 Base Plates: ASTM A572 Gr. 50 Erection Bolts: ASTM A325X

Design Codes and Specifications: Industry: NESC, IEEE Std 605, and ASCE Manual 113 Short Circuit Force: USDA/RUS Bulletin 1724E-300 (June 2001), Section 4.11 Rigid Bus Design. Wind: Per 2009 IBC & ASCE/SEI 7-05. Seismic: Per 2006 IBC Section 1613, ASCE 7-05 Sections 15.1.3 & 12.8. Welding: ANSI/AWS D1.1-06. Steel: AISC "Steel Construction Manual", 13th Edition.

Pacific Steel Structures, LLC 19814 E Pheasant Dr., Greenacres, WA 99016 Phone: (509) 921-5835 Fax: (509)921-5857

www.pacificsteelstructures.com

10

13.8kV 3-Phase Two Leg Bus Support


Custom Engineered Substation Structures Custom designed to meet your dimensional requirements. High or Low Buss PE certified drawing & calculation package provided. Galvanized to ASTM A123.
Materials: Tubes: ASTM A500 Gr. B Shapes / Plates: ASTM A36 / ASTM A572 Gr. 50 Wide Flanges: ASTM A992 Base Plates: ASTM A572 Gr. 50 Erection Bolts: ASTM A325X

Design Codes and Specifications: Industry: NESC, IEEE Std 605, and ASCE Manual 113 Short Circuit Force: USDA/RUS Bulletin 1724E-300 (June 2001), Section 4.11 Rigid Bus Design. Wind: Per 2009 IBC & ASCE/SEI 7-05. Seismic: Per 2006 IBC Section 1613, ASCE 7-05 Sections 15.1.3 & 12.8. Welding: ANSI/AWS D1.1-06. Steel: AISC "Steel Construction Manual", 13th Edition.

Pacific Steel Structures, LLC 19814 E Pheasant Dr., Greenacres, WA 99016 Phone: (509) 921-5835 Fax: (509)921-5857

www.pacificsteelstructures.com

11

13.8kV Bus Support or Insulator Support


Custom Engineered Substation Structures Custom designed to meet your dimensional requirements. High or Low Buss PE certified drawing & calculation package provided. Galvanized to ASTM A123.
Materials: Tubes: ASTM A500 Gr. B Shapes / Plates: ASTM A36 / ASTM A572 Gr. 50 Wide Flanges: ASTM A992 Base Plates: ASTM A572 Gr. 50 Erection Bolts: ASTM A325X

Design Codes and Specifications: Industry: NESC, IEEE Std 605, and ASCE Manual 113 Short Circuit Force: USDA/RUS Bulletin 1724E-300 (June 2001), Section 4.11 Rigid Bus Design. Wind: Per 2009 IBC & ASCE/SEI 7-05. Seismic: Per 2006 IBC Section 1613, ASCE 7-05 Sections 15.1.3 & 12.8. Welding: ANSI/AWS D1.1-06. Steel: AISC "Steel Construction Manual", 13th Edition.

Pacific Steel Structures, LLC 19814 E Pheasant Dr., Greenacres, WA 99016 Phone: (509) 921-5835 Fax: (509)921-5857

www.pacificsteelstructures.com

12

13.8 kV 3-Phase Vertical Bus Suspension Support


Custom designed to meet your dimensional requirements. PE certified drawing & calculation package provided. Galvanized to ASTM A123.
Design Codes and Specifications: Industry: NESC, IEEE Std 605, and ASCE Manual 113 Short Circuit Force: USDA/RUS Bulletin 1724E-300 (June 2001), Section 4.11 Rigid Bus Design. Wind: Per 2009 IBC & ASCE/SEI 7-05. Seismic: Per 2006 IBC Section 1613, ASCE 7-05 Sections 15.1.3 & 12.8. Welding: ANSI/AWS D1.1-06. Steel: AISC "Steel Construction Manual", 13th Edition.

Custom Engineered Substation Structures


Materials: Tubes: ASTM A500 Gr. B Shapes / Plates: ASTM A36 / ASTM A572 Gr. 50 Wide Flanges: ASTM A992 Base Plates: ASTM A572 Gr. 50 Erection Bolts: ASTM A325X

Pacific Steel Structures, LLC 19814 E Pheasant Dr., Greenacres, WA 99016 Phone: (509) 921-5835 Fax: (509)921-5857

www.pacificsteelstructures.com

13

13.8 kV 3-Phase Bus Support with PT Mount


Custom Engineered Substation Structures Custom designed to meet your dimensional requirements. PE certified drawing & calculation package provided. Galvanized to ASTM A123.
Materials: Tubes: ASTM A500 Gr. B Shapes / Plates: ASTM A36 / ASTM A572 Gr. 50 Wide Flanges: ASTM A992 Base Plates: ASTM A572 Gr. 50 Erection Bolts: ASTM A325X

Design Codes and Specifications: Industry: NESC, IEEE Std 605, and ASCE Manual 113 Short Circuit Force: USDA/RUS Bulletin 1724E-300 (June 2001), Section 4.11 Rigid Bus Design. Wind: Per 2009 IBC & ASCE/SEI 7-05. Seismic: Per 2006 IBC Section 1613, ASCE 7-05 Sections 15.1.3 & 12.8. Welding: ANSI/AWS D1.1-06. Steel: AISC "Steel Construction Manual", 13th Edition.

Pacific Steel Structures, LLC 19814 E Pheasant Dr., Greenacres, WA 99016 Phone: (509) 921-5835 Fax: (509)921-5857

www.pacificsteelstructures.com

14

13.8kV 3-Phase Bus Jumper Structure


Custom Engineered Substation Structures Custom designed to meet your dimensional requirements. High or Low Buss PE certified drawing & calculation package provided. Galvanized to ASTM A123.
Materials: Tubes: ASTM A500 Gr. B Shapes / Plates: ASTM A36 / ASTM A572 Gr. 50 Wide Flanges: ASTM A992 Base Plates: ASTM A572 Gr. 50 Erection Bolts: ASTM A325X

Design Codes and Specifications: Industry: NESC, IEEE Std 605, and ASCE Manual 113 Short Circuit Force: USDA/RUS Bulletin 1724E-300 (June 2001), Section 4.11 Rigid Bus Design. Wind: Per 2009 IBC & ASCE/SEI 7-05. Seismic: Per 2006 IBC Section 1613, ASCE 7-05 Sections 15.1.3 & 12.8. Welding: ANSI/AWS D1.1-06. Steel: AISC "Steel Construction Manual", 13th Edition.

Pacific Steel Structures, LLC 19814 E Pheasant Dr., Greenacres, WA 99016 Phone: (509) 921-5835 Fax: (509)921-5857

www.pacificsteelstructures.com