SECTION l6780

SECURITY SYSTEM
1. PART 1 - GENERAL
1.01 SECTION INCLUDES
A.

This Section includes furnishing and installation of


a complete security system composed of different
systems for
the
protection
of
the
project
as shown
on the
drawings
and as specified in this section.

B.

Security systems shall be centralized and the related


controls shall be located in locations indicated on
Drawings. The security system shall be powered by UPS
with 3 hours autonomy batteries. Security system shall
include:

C.

D.

1.

CCTV system with black and white cameras for all


areas, access and site over view as shown in
drawings.

2.

Walkthrough Metal Detector System.

3.

Access Control Systems for access gate, entrances


& some
restricted
areas
as
indicated
in
drawings
using
the
following systems:
a.

Keypad Access Control System.

b.

Card Reader Access Control System.

c.

Video Doorphone Access Control System

4.

Detention audio/visual system.

5.

Photo ID Database.

Security system Accessories:


1.

Security door position indictor.

2.

Tamper protector.

3.

Lighting fixture sound monitor.

4.

Security door buzzer activated indictor.

Specifications
included
in
this
section
are
indicative and considered as a minimum, equipment &
software that shall be delivered at the
time
of implementing the
Security System

16780-1

Security System

project shall be the latest versions available in


the market.
1.02 REFERENCES
A.

B.

C.

D.

NFPA - National Fire Protection Association


NFPA 70

National Electrical Code

Art. 800

Communication Circuits

Art. 810

Radio and Television Equipment

Art. 820

Community
Antenna
Distribution System

Television

and

Radio

UL - Underwriter's Laboratories Inc.


UL 813

Commercial Audio Equipment

UL 983

Surveillance Cameras

UL 1410

Television Receivers and Video Products

ANSI - American National Standards Institute


ANSI 208

Measurement of Resolution of Camera System

ANSI 287

Precision Coaxial Connectors

Other references shall include


Electronic Industries Association - EIA International
Electro technical Commission - IEC Institute of
Electrical & Electronic Engineers - IEEE
International Organization for standardization - ISO
International Radio consultative Committee - CCIR

E.

All equipment shall


certified companies.

be

manufactured

by

ISO

9000

F.

Material and Systems with equal quality to ANSI,


NEMA, NEC, and UL but made to SASO, IEC or ISO are
acceptable and can be quoted for.

1.03 ENVIRONMENTAL REQUIREMENTS

16780-2

Security System

A.

All
equipment
installed
shall
not
require
readjustments of
controls,
realignment,
software
reloading
or
reconfiguring
when
operating
under
the following
conditions:
1.

The control areas indicated


air-conditioned.

2.

Equipment

on drawing shall be

installed outside shall


to operate at
their
performances
under
environmental conditions:

be capable
nominal
the
following

Maximum ambient temperature: 50C

Minimum ambient temperature: 5C

Average maximum temperature: 43C

Average minimum temperature: 15C

Temperature due to direct sun exposure: 85C

Maximum relative humidity : 100%

Maximum winspeed:60km/H

Maximum rainfall:100mm

1.04 SUBMITTALS
A.

Product Data: Submit manufacturer's


items of security system.

B.

Shop
Drawings:
Submit
systems of security.

C.

Wiring
Diagrams:
Submit
systems of
security
power
connections
components.

D.

Complete
Manual.

Installation,

for

all

for

all

wiring diagrams
for
and
electrical
to
equipment

all

layout

Operation

data

drawings

and

and

maintenance

1.05 QUALITY ASSURANCE


A.

The following association and organization shall be


referred to with respect to standards as they apply to
the materials
and equipment
provided under this
Section.
-

Electronics
Industries
Association
Publications and Engineering Publications.

(EIA):

Security System

16780-3

Security System

Underwriter's Laboratories (UL).

B.

Single
Source
Responsibility:
Components
and
accessories shall be product of single manufacturer to
the maximum extent.

C.

One week training program must be provided for the


selected
personnel
by
supplier/manufacturer
representative so that they can manage and maintain the
system efficiently.

1.06 WARRANTY
A.

Submit

written guarantee
signed
by
the
contractor, manufacturer for the period of 5
years from the date of substantial completion. The
guarantee shall cover the repair
and replacement
of
defective
materials
and workmanship
as directed by the Engineer.

2. PART 2 - PRODUCTS
2.01 CCTV SYSTEM
2.01.01 CCTV SYSTEM (Option 1)
A.

Fixed Black and White Cameras


1.

Cameras shall be installed at fixed positions as


shown in drawings. The location shall be chosen to
avoid
any
dead
angle
and
shall
take
into
account the height differences of fence.

2.

Cameras
will
have
characteristics:

at

least

the

following

Standard : EIA

Sensor : CCD 1:3" 440 000 pixels, B & W

Resolution : 580 lines

Light sensitivity:

Lens connection : C-CS mount

Automatic black light compensation

Automatic black level adjustment

0.8
0.4

lux for good picture


lux for exploitable
picture

16780-4
Security System

B.

Automatic with the level adjustment

Power supply 220V/60Hz

External
cameras

cameras

shall

3.

Cameras shall be approved.

4.

Lenses

be infrared

sensitive

Focal length: to
be
determined
by
the
contractor, depending of the field to cover

Auto Iris

C/CS mount

Lenses shall be approved.

5.

Housing and Bracket: For outdoor use, housings will


be anodized aluminum with reinforced thermoplastic
end cap, weatherproof standard IP66, fitted out
with thermostatically controlled heater. For indoor
use, no housing is required. Bracket shall make the
assembly insensitive to wind. The housing shall be
also
protected
from
sunlight by a
second
metal covering painted in
a
light
color.
Shall be approved.

6.

All perimeter cameras shall be installed on 4m high


poles
installed all along with the
fence,
or as shown in drawings. In order to prevent
excessive heat
release,
the
power
supplies of
the cameras shall be grouped
in sealed boxes. Picture shall be available
at
the control location
indicated
on
Drawings.

Monitors:
Monitors
characteristics:

will

have

EIA standard

Screen size: 17"

B/W monitors

19" rack housing

Resolution: 500 lines (at center)

the

following

16780-5
Security System

C.

D.

high immunity to external electrical and magnetic


interference

Power: 220V 60Hz

Controls
shall
include
brightness,
vertical and horizontal hold.

Video
Tape Recorder
specifications:

(VTR):

Shall

have

contrast,
following

Front loading

VHS compatible

7 days programmable timer

Time of alarm memory and recall

Electronic security lockout

Fast forward/rewind,
stop, record, audio dib,
time
select,
still
frame,
reverse/play
filed
advance and auto rewind at the end of video tape.

Audio and video channels shall have automatic gain


control

Power: 220V 60Hz

Sequential Switches
1.

The following two types will be used:


- Sequential and spot operation.
- Sequential operation.

E.

CCTV Concentration Systems: The whole CCTV system shall


be managed
from
the
controllocations
indicated on Drawings. Each access shall
also
include control terminals for the
access
zone controlling the mobile cameras of the access
concerned. The cameras shall be connected to the
central system on point to point link by means of
cables.

F.

Particular specifications
1.

Priority for video keyboard


control room should be done.

between

camera

and

16780-6
Security System

2.

One specific b/w video printer should be provided.

3.

VTR
-

The VTR should always record on low speed. The


speed should be defined by the procedure.

The VTR should shift to normal


picture/s) in case of alarm.

speed

(30

2.01.02 CCTV SYSTEM (Option 2)


The following CCTV System Version shall be
quoted as an Option-2.
Very Low Light Camera Featuring:

1/3 interline transfer CCD


470 TVL
0.5 Lux colour / 0.01 lux monochrome
>50 dB S/N ratio
On screen display (OSD) with easy to use menus
Auto tracing with balance (ATW)
Digital Signal Processing (DSP)
Internal and line lock synchronization
C/CS lens mount
Supports video iris and DD iris and manual iris
lenses
Auto iris (AI) / Auto electronic shutter (AES)
6 adjustable BLC windows
8 adjustable shutter steps
RS 485 control (on low voltage version),
230Vac or 24Vac @ 4.5W options

Vari Focal Lens Featuring:

Superior coating and polishing techniques


Exceptional light gathering ability
Precision crafted optics
Distortion-free laser-sharp Images
1/3 format
CS mount
Varifocal & fixed focal length options
Durable aluminum threads
Long iris control cable versions for side and
rear mount camera designs
Focal length 2.9mm-8mm.
Iris range F0.95-T360

Outdoor Housing Featuring:

16780-7
Security System

Weatherproof housings for external applications


Made from extruded aluminum with a polycarbonate
Scratch resistant window
IP 66 standard

16-Channel Digital Recorded Featuring:

16-Video Input
Simplex and duplex recording with capture
rate up to 60 ips
Storage capacity 320GB
Multiple recording modes-time laps, event
only
(with
configurable
pre-post
alarm
recording), or time and event
PTZ dome control
Remote access through PSTN, LAN/WAN (internal
NIC), DSL and ISDN (remote access software
should be included).
CD-writer
built
in
One main output monitor & one spot output
monitor
Built-in motion detector, that increase of
alarm will display the alarm in full screen
spot monitor.
16-alarm
Input
with
common
output
programmable
Instant search and retrieval modes-calendar,
event, time/date, first or last recorded
images.

21-inch Color Monitor Featuring:

High screen resolution 450 TVL


On screen display
Minimum 2 input & output

2.02 Walkthrough Metal Detector System: Metal detector shall be


installed in required locations. The system shall meets
NILECJ
standard
0601.00
level
1-5
and
F.A.A.
Microprocessor computer controlled circuitry with 12 digit
membrane keypad entry
control,
provided
with
the
following
main requirements:
A.

Uniform detection
through area

sensitivity

over

the

entire

B.

Detection of any metal object regardless of


orientation in the gate

C.

Adjustable sensitivity

D.

Low false alarm rate

walk

16780-8
Security System

E.

Compliance with
0601, IEC348

international

F.

Self testing

G.

Visual and audio alarms

H.

Indication of the relative size of a metal object

I.

Comprehensive display of adjustments:


tone, and volume sensitivity

J.

Size of clearance: H=2210mm, W=890mm, D=610 mm

K.

Standard
feature:
Digital
Single
Processing
DSP
circuitry eliminates spikes, noise, and two way radio
interference.

L.

Detection circuitry continuously active.

M.

Bright and large


alarm status.

N.

LCD display indicates settings, diagnostic functions


and operational menus. Diagnostics shall be built in
and circuits are constantly monitored for faults.

O.

Standard programs (capacity


ferrous metal detection.

P.

Sensitive range settings are calibrated 1 to 99 for


target detection.

Q.

Remote alarm relay and data output connector.

R.

Synchronization for adjacent


audio tone selection.

S.

System to be approved.

squared

safety

indictors

99),

limits:

NILECJ-

program,

for

ferrous

mode,

power

and

and

non-

unit operation with (4)

2.03 ACCESS CONTROL SYSTEMS


A.

General: Access control system


The

functions of the access


control
system
is
to monitor and record personnel entry to
and exit from the required areas and also to restrict
staff entry in some areas. Microcomputer based access
control system shall be
provided
featuring
expandable modular design, networking
capability,
user
definable access and
reporting
functions.
The
system
shall
provide
16780-9
Security System

uninterrupted growth as user requirements


grow. B.
1.

2.
C.

Keypad Access Control System

Keypad access control system shall be capable to


offer for the users to enter only their personal
numerical
code
to
gain
access
and
have
capability for cut down user errors by reducing the
number of attempts required
for
a
successful
number
and system
shall
be
provided
with
the
following
main
requirements:
-

Vandal and impact resistant

Weather, dust and water proof

No exposed moving parts

Heavy duty construction

LED power indicator

Intrinsically
environment

System to be approved.

safe to allow use in explosive

The
system
shall
be
centralized
controlled
through the control location indicated on Drawings.

Card Reader Access Control System.


1.

Card reader shall be capable of reading both swipe


and insert card formats and have bi-directional
reading capability for convenience of installation
and operation and cut down user errors by reducing
the
number
of
attempts
required
for
a
successful read
and the system
shall
be
provided with
the
following
main
requirements:
-

Vandal and impact resistant

Weather, dust and water proof

No exposed moving parts

Heavy duty construction

LED power indicator

Intrinsically
environment

safe to allow use in explosive

Security System

16780-10

Security System

2.

3.
D.

System to be approved.

Card reader shall contain and check the following


information:
-

Facility code and card number.

Check character to
card information.

Electric door strikes shall be provided on the


door through with
the access
is to be
controlled and these shall be supplied complete
with rectifier and transformer as necessary.

ensure

validity

of

the

The
system
shall
be
centralized
controlled
through the control location indicated on drawings.

Video Doorphone Access Control System


1.

Video
doorphone
system shall be
drawings and shall
access
personal
with the following

2.

Camera unit: Shall have following characteristics:

3.

access
control
audio
visual
fixed in locations shown in
be capable
to offer
only
for
the authorized
and system shall be provided
main requirements:

CCD door camera station

Wide-angle minimum 70 deg. Vertical and 90 deg.


Horizontal at 50cm distance

Infrared illuminators with minimum illumination


1 lux at 50cm.

No exposed moving parts

Heavy duty construction

LED power indicator

Intrinsically
environment

safe to allow use in explosive

Monitor unit: Shall have following characteristics:


-

4 inch direct flat CRT monitor

Monitor scanning line 525 lines

16780-11
Security System

the unit shall be provided with handset

No exposed moving parts

Heavy duty construction

LED power indicator

Intrinsically
environment.

safe to allow use in explosive

2.04 Detention Audio/Visual


System: Detention audio/visual
system shall be standard product of an approved specialist
manufacturer and shall be provided in locations shown in
drawings. System shall consist of, but not limited to the
following:
A.

Microphone (sound monitor), ceiling mounted, shall be


located in lighting fixtures of detention areas as
shown on Drawings.

B.

Head set loud speaker.

C.

Pre-amplifier.

D.

Switching console for 15 microphones.

E.

audio/video camera.

F.

Video Cassette Tape recorder.

G.

14" Monitor.

H.

Detention area sound system Rack (DSR).

2.05 Photo
ID Database System:
Provide
photo
identification (ID)
database
system
for
the
automatic
production
and storage of
criminal
files. The system shall consist of photograph
I.D
camera,
computer
unit,
system
software programs
including
all
cable
connections, necessary fittings,
supports
and
fixings as required for a fully operational database
system. System shall be located on locations shown on
drawings. System shall consist of, but not limited to the
following:
A.

Photograph
I.D
camera:
Shall
be
heavy
duty
professional type with all features required for the
intended use.

B.

Computer unit: Shall be from high-end models available


at the time of purchase and Shall be complete unite
with full components and accessories.
16780-12
Security System

C.

System

software programs:
System
software
programs shall
be supplied
and
operated
through
an
approved
specialist
manufacturer with full required features and shall be
compatible with the other security database systems.

2.06 SECURITY SYSTEM ACCESSORIES:


A.

Security Door Position Indictor:


Where indicated on Drawings, security doors shall be
provided with opening position indictor, the indictors
shall
be
controlled
through
panel
board
to
be
located in the control location indicated on Drawings.

B.

Tamper Protector:
Where indicated on drawings, Detention area elements
shall
be
provided
with
tamper
protectors,
the
sensors of the tamper protectors shall be controlled
(audible and visual) through panel board to be located
in the control location indicated on drawings.

C.

Lighting Fixture Sound Monitor:


Where indicated
on
drawings,
detention area
lighting
fixtures
shall
be provided with sound monitor, the
sound monitors shall be controlled through the control
location indicated on drawings.

D.

Security Door Buzzer Activated Indictor:


Where indicated on drawings, detention area security
roll up shutter doors shall be provided with buzzer
activated indictors to indicate opening position, the
indictors shall be controlled through panel board to be
located in the control location indicated on drawings.

2.07 CONTROL (ORERATION)ROOM EQUIPMENT


A.

free standing assembly


system
console
shall
be installed
in the control location
indicated on drawings to
support all keyboards,
monitors,
etc.
of
all security systems.
The console shall be modular designed suitable
for
the
area
and
location
subject
to
acceptance of the authorities.

2.08 UNINTERRUPTIBLE POWER SUPPLY


A.

A UPS shall be provided. It consists of a constant


voltage
rectifier/charger,
rechargeable
storage

Security System

16780-13

Security System

batteries, static inverter, transfer switch, by pass


transformer, regulator, manual by-pass switch and
associated accessories.
B.

C.

Main specifications
1.

UPS power shall be suitable


for the
total
load connected
to it, and for
4
hours
of
mains power outage.

Output power: 220V +/-1% at power factor 1 and full


load

2. The UPS shall have overloading


for
30 mm & 500% for 1/4 cycle.

ratings

of

115%

3.

The UPS shall be modular in design, it shall house


rectifier/charger, inverter, transfer switch and
auxiliaries.

4.

The batteries shall be heavy duty life time:


years, maintenance free, sealed type.

5.

Battery racks shall be


structural steel frames.

6.

Inverter shall be a static type, with the input


voltage
compatible
with
the
battery rectifier/charger output

7.

Output voltage regulation shall be within 2% and


frequency within +/- 0.5 Hz.

8.

Static transfer switch shall be provided and shall


be mounted
integrally
within the UPS
system enclosure. The transfer
switch
shall
operate
automatically
upon
detection of UPS system trouble within 5
milliseconds.
It shall operate
in
conjunction with
a synchronization
circuit
to ensure a smooth load transfer.

9.

A manually operated bypass switch shall be provided


to isolate the UPS from the load for maintenance
purposes. A bypass isolation transformer shall be
provided with a greater rating than the UPS, it
will be housed in a separate enclosure from the
UPS.

constructed

of

welded

10. The UPS enclosure shall be equipped with all


metering (voltage, current, etc.) and alarms.
Indicating lights shall be provided in the front of
the UPS
cabinet:
loss of
input AC,
ground

Security System

16780-14

Security System

detection,

static
switch
low
output voltage,
discharging,
loss
abnormal output voltage, inverter non
the bypass line.

on bypass,
battery
of cooling,
in sync with

11. Isolation breakers are to be provided at battery


outlet, inverter inlet and outlet, rectifier outlet
etc.
2.09 WIRE, CABLES AND HARDWARE
A.

CCTV System and Data


1.

Coaxial cable shielded copper cables comply with


the following requirements:
-

Produce color composite signals.

C.

Ambient temperatures- 10 Deg. C to + 50 Deg

Pick up element ccd.

Contain automatic light compensation.

The
phase.
2.
B.

voltage

220

V,

60

Hz,

The load impedance 75 ohms.

Twisted and shielded three pair cable

Video signal transmission


1.

C.

input

Coaxial cable shielded copper cables comply with


the following requirements:
-

Produce color composite signals.

C.

Ambient temperatures- 10 Deg. C to + 50 Deg

Pick up element ccd.

Contain automatic light compensation.

The input voltage 220 V, 60 Hz, 1 phase.

The load impedance 75 ohms.

Data Signal Transmission


1.

Unshielded Twisted Pair Cable, category 6.

2.10 RACEWAYS
Security System

16780-15

Security System

A.

Raceways shall be as mentioned in Section 16050 - BASIC


MATERIALS AND METHODS.

3. PART 3 - EXECUTION
3.01 INSTALLATION
A.

The entire security system shall be installed


by
specialized sub-contractor approved by the Engineer.
Installation
of
the
system
shall
conform
to
the equipment manufacturer's written
instructions, National Electric Code and approved
drawings.

B.

Other
electrical
workrequirements
shall be
as
specified in Section 16050 - BASIC MATERIALS AND
METHODS. Coaxial cable and power cable for each camera
shall be run in separate conduits.

C.

Testing: The completed installation shall be tested


in accordance
with
the equipment
manufacturer's written recommendation.
Testing
shall be conducted
by
manufacturer's
authorized representative. The Engineer shall
be
notified
in advance
to witness the test.
Certified copies of test procedure and results shall be
forwarded to the Engineer.
END OF SECTION