OBJECTIVE
The purpose of this document is to find the maximum Fault Level attained during a 3 phase Symmetrical fault, on different Buses. In order to arrive
at a more correct value, contribution of the Motors towards the fault ratings will also be considered.

REFERENCE DOCUMENT
Documents

Doc. No.

a) Overall Plant Electrical Key Single Line Diagram ( 33kV System)


b) Electrical Key Single Line Diagram

c) Electrical Design Basis

DH0008-ENG-E-DB-0001

d) Load List

DH0008-ENG-E-DC-0001

e) Specification for Transformer (Including Calculations)

DH0008-BE-E-SP-0006

NOTES
a) Base Voltage is 6.6kV and Base MVA is 100MVA throughout the system.
b) The impedance of busbars , circuit breakers , current transformers etc. which are negligibly small are not considered in this calculation.
c) Sub-transient reactance of high voltage Induction motor is considered to be 17%.
d) The short circuit current at the primary terminals (33kV) of the Transformers is 5.25KA as per 33KV fault current rating document .

BASIC DESIGN DATA

a.

System Data :

b.

c.

Source Voltage (Vs)

33

kV

Source Fault Current (IFS)

5.25

kA

Source Transformer (T1) Data(911-TR-001) :


Primary Voltage

33

kV

Secondary Voltage

6.6

kV

Transformer capacity

7.5

MVA

Transformer Impedance

Cable data for Transformer


Cable between (911-TR-001) Transformer and 6.6KV Switchboard (911-SW2-001) Located in LPS-301.
2

Cable Size & type

1CX400 mm ,Cu,XLPE Insulated

No. of Cable Runs

Voltage

6.6

KV

Cable length

22

Meters

Cable Resistance

0.05

/Km, at 90C

Cable Reactance

0.097

/Km, at 90C

d.

Cable Data for HT Motors (PP-301-01 ) :

Cable Between 6.6kV Switch Board to HV Motor

3C x 95 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

6.6

kV

Cable length

292

Meters

Cable Resistance

0.194

/Km, at 90C

Cable Reactance

0.092

/Km, at 90C

Cable Data for HT Motors (PP-301-02 ) :


Cable Between 6.6kV Switch Board to HV Motor
3C x 95 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

6.6

kV

Cable length

292

Meters

Cable Resistance

0.194

/Km, at 90C

Cable Reactance

0.092

/Km, at 90C

Sheet 1 of 97

Cable Data for HT Motors (PP-301-03 ) :


Cable Between 6.6kV Switch Board to HV Motor

3C x 95 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

6.6

kV

Cable length

292

Meters

Cable Resistance

0.194

/Km, at 90C

Cable Reactance

0.092

/Km, at 90C

Cable Data for HT Motors (PP-301-04 ) :


Cable Between 6.6kV Switch Board to HV Motor

3C x 95 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

6.6

kV

Cable length

274

Meters

Cable Resistance

0.194

/Km, at 90C

Cable Reactance

0.092

/Km, at 90C

Cable Data for HT Motors (PP-301-05 ) :


Cable Between 6.6kV Switch Board to HV Motor

3C x 95 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

6.6

kV

Cable length

268

Meters

Cable Resistance

0.194

/Km, at 90C

Cable Reactance

0.092

/Km, at 90C

Cable Data for HT Motors (PP-301-06 ) :


Cable Between 6.6kV Switch Board to HV Motor

3C x 95 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

6.6

kV

Cable length

262

Meters

Cable Resistance

0.194

/Km, at 90C

Cable Reactance

0.092

/Km, at 90C

Cable Data for HT Motors (PP-301-07 ) : FUTURE


Cable Between 6.6kV Switch Board to HV Motor

3C x 95 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

6.6

kV

Cable length

262

Meters

Cable Resistance

0.194

/Km, at 90C

Cable Reactance

0.092

/Km, at 90C

Cable Data for HT Motors (PP-301-08 ) : FUTURE


Cable Between 6.6kV Switch Board to HV Motor
3C x 95 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

6.6

kV

Cable length

262

Meters

Sheet 2 of 97

Cable Resistance

0.194

/Km, at 90C

Cable Reactance

0.092

/Km, at 90C

Cable Data for HT Motors (PP-301-09 ) : FUTURE


Cable Between 6.6kV Switch Board to HV Motor
3C x 95 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

6.6

kV

Cable length

262

Meters

Cable Resistance

0.194

/Km, at 90C

Cable Reactance

0.092

/Km, at 90C

CALCULATION

A.

GENERAL

a)

Basic equation for short circuit calculation is =

Short Circuit MVA

IS

&

Where

Base MVA

100
6.6

Is

MVA
kV
Fault impedance per unit
Symmetrical short circuit current (kA)

VS X IFS X 1.732

Machine Impedances are converted to 100MVA base per unit using the following equation :

Base MVA x p.u. impedanceat MachineMVA SystemkV


x

Machine MVA
Base kV

Per unit impedance =

B.

Fault (F1) at 6.6kV Switchboard : 911-SW2-001

a)

Source :
Fault MVA of source =
Source Impedance Zs =
XS=

b)

3 x Base kV

Fault MVA of source

b)

Short circuit MVA

Base Voltage =
Zpu

Base MVA
Z p.u.

300
0.333

MVA

(= VS X IFS X 1.732)

PU

(= Base MVA /Fault MVA)

0.333

, 90

7.5

MVA

Transformer:
Transformer rating

Transformer secondary No-load voltage =

6.6

KV

Impedance of Transformer T1 , at 6.9kV (Trafo No-load Voltage) =

0.06

p.u

Now, trafo impedance at Base MVA & 6.6 kV Bus Voltage =


= [ p.u. Trafo Impedance x [ (Trafo No-load Voltage/ Bus Voltage) ] x [ (Base MVA / Trafo MVA) ]
= 0.06 x (6.6/6.6) x (100 /7.5)
XTR=

0.800

c)

HV Motors

i)

780KW rated Motor (PP-303-01 TO 06)(3Nos FUTURE)


Motor rating =780KW =

876

, 90

KVA

Sub-transient reactance of HV motor = 17 %


XM1 = XM2 = XM3= XM4= XM5= XM6= XM7= XM8= XM9=Xd"(p.u.) x (Base MVA x 1000/ Motor kVA) x [ (Trafo No-load Voltage/ Bus Voltage) ]
=
XM=

0.17 x (100*1000/876) x (6.6/6.6)


j

d)

Cable

6.6kVCable to 911-SW2-001 SWITCHBOARD

19.397

, 90

Sheet 3 of 97

Size : 1Cx 400 mm

ZC1=

R = ( 0.05 x 22) / (2 x 1000)

0.001

X = ( 0.097 x 22) / (2 x 1000)

0.002

Rpu = R x (Base MVA/(Base kV) )

0.003

Xpu = X x (Base MVA/(Base kV) )


0.003 +
j 0.005

0.005

0.006

62.73

6.6kVCable to PP-301-01
Size : 3Cx 95 mm
R = ( 0.194 x 292) / (1 x 1000)
X = ( 0.092 x 292) / (1 x 1000)

ZC2=

=
=

0.057
0.027

Rpu = R x (Base MVA/(Base kV) )

0.130

Xpu = X x (Base MVA/(Base kV) )


0.130 +
j 0.062

0.062

0.144

25.37

6.6kVCable to PP-301-02
Size : 3Cx 95 mm
R = ( 0.194 x 292) / (1 x 1000)
X = ( 0.092 x 292) / (1 x 1000)

ZC3=

=
=

0.057
0.027

Rpu = R x (Base MVA/(Base kV) )

0.130

Xpu = X x (Base MVA/(Base kV) )


0.130 +
j 0.062

0.062

0.144

25.37

6.6kVCable to PP-301-03
Size : 3Cx 95 mm
R = ( 0.194 x 292) / (1 x 1000)
X = ( 0.092 x 292) / (1 x 1000)

ZC4=

=
=

0.057
0.027

Rpu = R x (Base MVA/(Base kV) )

0.130

Xpu = X x (Base MVA/(Base kV) )


0.130 +
j 0.062

0.062

0.144

25.37

6.6kVCable to PP-301-04
Size : 3Cx 95 mm
R = ( 0.194 x 274) / (1 x 1000)
X = ( 0.092 x 274) / (1 x 1000)

ZC5=

=
=

0.053
0.025

Rpu = R x (Base MVA/(Base kV) )

0.122

Xpu = X x (Base MVA/(Base kV) )


0.122 +
j 0.058

0.058

0.135

25.37

6.6kVCable to PP-301-05
Size : 3Cx 95 mm
R = ( 0.194 x 268) / (1 x 1000)
X = ( 0.092 x 268) / (1 x 1000)

0.052
0.025

Rpu = R x (Base MVA/(Base kV) )

0.119

Xpu = X x (Base MVA/(Base kV) )

0.057

0.119 +
j 0.057

ZC6=

=
=

0.132

25.37

6.6kVCable to PP-301-06
Size : 3Cx 95 mm
R = ( 0.194 x 262) / (1 x 1000)
X = ( 0.092 x 262) / (1 x 1000)

ZC7=

=
=

0.051
0.024

Rpu = R x (Base MVA/(Base kV) )

0.117

Xpu = X x (Base MVA/(Base kV) )


0.117 +
j 0.055

0.055

0.129

6.6kVCable to PP-301-07:FUTURE
Size : 3Cx 95 mm
R = ( 0.194 x 262) / (1 x 1000)

0.051
Sheet 4 of 97

25.37

X = ( 0.092 x 262) / (1 x 1000)

ZC8=

0.024

Rpu = R x (Base MVA/(Base kV) )

0.117

Xpu = X x (Base MVA/(Base kV) )


0.117 +
j 0.055

0.055

0.129

25.37

6.6kVCable to PP-301-08:FUTURE
Size : 3Cx 95 mm
R = ( 0.194 x 262) / (1 x 1000)
X = ( 0.092 x 262) / (1 x 1000)

ZC9=

10

0.051

0.024

Rpu = R x (Base MVA/(Base kV) )

0.117

Xpu = X x (Base MVA/(Base kV) )


0.117 +
j 0.055

0.055

0.129

25.37

6.6kVCable to PP-301-09:FUTURE
Size : 3Cx 95 mm
R = ( 0.194 x 262) / (1 x 1000)
X = ( 0.092 x 262) / (1 x 1000)

ZC10=

0.051

0.024

Rpu = R x (Base MVA/(Base kV) )

0.117

Xpu = X x (Base MVA/(Base kV) )


0.117 +
j 0.055

0.055

Z1=ZS+ZTR+ZC1
ZS=
ZTR=
ZC1=
Z1=ZS+ZTR+ZC1=
Z1MAG=
1/Z1MAG=
1/Z1REAL=
1/Z1REAC=

j
j
0.003
j
0.003
j

1.138
0.879
0.002
-0.879

1/Z1=

0.129

0.333
0.8
+
0.005
1.138
89.87
-89.87

0.002
j -0.879

Z2=ZC2+ZM
ZC2=
ZM=
Z2=ZC2+ZM=

0.130
j
j
0.130
j

Z2MAG= 19.460
1/Z2MAG= 0.051
1/Z2REAL= 0.0003
1/Z2REAC= -0.0514
1/Z2=

+
0.062
19.397
19.459
89.62
-89.62

0.0003
j -0.051

Z3=ZC2+ZM
ZC3=
ZM=
Z3=ZC2+ZM=

0.130
j
j
0.130
j

Z3MAG= 19.4595
1/Z3MAG= 0.0514

+
0.062
19.397
19.459
89.62
-89.62

1/Z3REAL= 0.0003
1/Z3REAC= -0.0514
1/Z3=

0.0003
j -0.051

Z4=ZC2+ZM
ZC4=
ZM=
Z4=ZC2+ZM=
Z4MAG= 19.460
1/Z4MAG= 0.0514
1/Z4REAL= 0.0003
1/Z4REAC= -0.0514
1/Z4=

0.130
j
j
0.130
j

+
0.062
19.397
19.459
89.62
-89.62

0.0003
j -0.051

Sheet 5 of 97

25.37

Z5=ZC2+ZM
ZC5=
ZM=
Z5=ZC2+ZM=

0.122
j
j
0.122
j

Z5MAG= 19.456
1/Z5MAG= 0.0514

+
0.058
19.397
19.455
89.64
-89.64

1/Z5REAL= 0.0003
1/Z5REAC= -0.051
1/Z5=

0.0003
j -0.051

Z6=ZC2+ZM
ZC6=
ZM=
Z6=ZC2+ZM=

0.119
j
j
0.119
j

Z6MAG= 19.454
1/Z6MAG= 0.051
1/Z6REAL= 0.0003
1/Z6REAC= -0.051
1/Z6=

+
0.057
19.397
19.454
89.65
-89.65

0.0003
j -0.051

Z7=ZC2+ZM
ZC7=
ZM=
Z7=ZC2+ZM=

0.117
j
j
0.117
j

Z7MAG= 19.453
1/Z7MAG= 0.0514
1/Z7REAL= 0.0003
1/Z7REAC= -0.0514
1/Z7=

+
0.055
19.397
19.453
89.66
-89.66

0.0003
j -0.0514

Z8=ZC2+ZM
ZC8=
ZM=
Z8=ZC2+ZM=

0.117
j
j
0.117
j

Z8MAG= 19.453
1/Z8MAG= 0.0514

+
0.055
19.397
19.453
89.66
-89.66

1/Z8REAL= 0.0003
1/Z8REAC= -0.051
1/Z8=

0.0003
j -0.051

Z9=ZC2+ZM
ZC9=
ZM=
Z9=ZC2+ZM=

0.117
j
j
0.117
j

Z9MAG= 19.453
1/Z9MAG= 0.051
1/Z9REAL= 0.0003
1/Z9REAC= -0.051
1/Z9=

+
0.055
19.397
19.453
89.66
-89.66

0.0003
j -0.051

Z10=ZC2+ZM
ZC10=
ZM=
Z10=ZC2+ZM=
Z10MAG= 19.453
1/Z10MAG= 0.051
1/Z10REAL= 0.0003
1/Z10REAC= -0.051

0.117
j
j
0.117
j

+
0.055
19.397
19.453
89.66
-89.66

1/Z10=

0.0003
j -0.051

1/ZEQ=

0.005
j -1.341

1/ZEQMAG= 1.341
ZEQMAG= 0.746

Sheet 6 of 97

Therefore, Maximum Fault level at F1

Maximum Fault level at F1 in KA

Base MVA
Zeq

134.1

=
=

MVA

134.1
6.6x1.732
11.73

KA

Sheet 7 of 97

OBJECTIVE
The purpose of this document is to find the maximum Fault Level attained during a 3 phase Symmetrical fault, on different Buses. In order to arrive
at a more correct value, contribution of the Motors towards the fault ratings will also be considered.

REFERENCE DOCUMENT
Documents

Doc. No.

a) Overall Plant Electrical Key Single Line Diagram ( 33kV System)


b) Electrical Key Single Line Diagram

c) Electrical Design Basis

DH0008-ENG-E-DB-0001

d) Load List

DH0008-ENG-E-DC-0001

e) Specification for Transformer (Including Calculations)

DH0008-BE-E-SP-0006

NOTES
a) Base Voltage is 6.6kV and Base MVA is 100MVA throughout the system.
b) The impedance of busbars , circuit breakers , current transformers etc. which are negligibly small are not considered in this calculation.
c) Sub-transient reactance of high voltage Induction motor is considered to be 17%.
d) The short circuit current at the primary terminals (33kV) of the Transformers is 5.25KA for 3 sec as per 33KV fault current rating document.

BASIC DESIGN DATA

a.

System Data :

b.

c.

Source Voltage (Vs)

33

kV

Source Fault Current (IFS)

5.25

kA

Source Transformer (T1) Data(912-TR-001) :


Primary Voltage

33

kV

Secondary Voltage

6.6

kV

Transformer capacity

7.5

MVA

Transformer Impedance

Cable data for Transformer


Cable between (912-TR-001) Transformer and 6.6KV Switchboard (912-SW2-001) Located in LPS-302.
2

Cable Size & type

1CX400 mm ,Cu,XLPE Insulated

No. of Cable Runs

Voltage

6.6

KV

Cable length

22

Meters

Cable Resistance

0.05

/Km, at 90C

Cable Reactance

0.097

/Km, at 90C

d.

Cable Data for HT Motors (PP-302-01 ) :

Cable Between 6.6kV Switch Board to HV Motor

3C x 95 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

6.6

kV

Cable length

292

Meters

Cable Resistance

0.194

/Km, at 90C

Cable Reactance

0.092

/Km, at 90C

Cable Data for HT Motors (PP-302-02 ) :


Cable Between 6.6kV Switch Board to HV Motor
3C x 95 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

6.6

kV

Cable length

286

Meters

Cable Resistance

0.194

/Km, at 90C

Cable Reactance

0.092

/Km, at 90C

Sheet 8 of 97

Cable Data for HT Motors (PP-302-03 ) :


Cable Between 6.6kV Switch Board to HV Motor

3C x 95 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

6.6

kV

Cable length

280

Meters

Cable Resistance

0.194

/Km, at 90C

Cable Reactance

0.092

/Km, at 90C

Cable Data for HT Motors (PP-302-04 ) :


Cable Between 6.6kV Switch Board to HV Motor

3C x 95 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

6.6

kV

Cable length

274

Meters

Cable Resistance

0.194

/Km, at 90C

Cable Reactance

0.092

/Km, at 90C

Cable Data for HT Motors (PP-302-05 ) :


Cable Between 6.6kV Switch Board to HV Motor

3C x 95 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

6.6

kV

Cable length

268

Meters

Cable Resistance

0.194

/Km, at 90C

Cable Reactance

0.092

/Km, at 90C

Cable Data for HT Motors (PP-302-06 ) :


Cable Between 6.6kV Switch Board to HV Motor

3C x 95 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

6.6

kV

Cable length

262

Meters

Cable Resistance

0.194

/Km, at 90C

Cable Reactance

0.092

/Km, at 90C

Cable Data for HT Motors (PP-302-07 ) :(FUTURE)


Cable Between 6.6kV Switch Board to HV Motor

3C x 95 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

6.6

kV

Cable length

262

Meters

Cable Resistance

0.194

/Km, at 90C

Cable Reactance

0.092

/Km, at 90C

Cable Data for HT Motors (PP-302-08 ) :(FUTURE)


Cable Between 6.6kV Switch Board to HV Motor
3C x 95 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

6.6

kV

Cable length

262

Meters

Sheet 9 of 97

Cable Resistance

0.194

/Km, at 90C

Cable Reactance

0.092

/Km, at 90C

Cable Data for HT Motors (PP-302-09 ) :(FUTURE)


Cable Between 6.6kV Switch Board to HV Motor
3C x 95 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

6.6

kV

Cable length

262

Meters

Cable Resistance

0.194

/Km, at 90C

Cable Reactance

0.092

/Km, at 90C

CALCULATION

A.

GENERAL

a)

Basic equation for short circuit calculation is =

Short Circuit MVA

IS

&

Where

Base MVA

100

Base Voltage =

6.6

Is

Fault MVA of source

b)

3 x Base kV
MVA
kV
Fault impedance per unit
Symmetrical short circuit current (kA)

VS X IFS X 1.732

Machine Impedances are converted to 25MVA base per unit using the following equation :

Base MVA x p.u. impedanceat MachineMVA SystemkV


x

Machine MVA
Base kV

Per unit impedance =

B.

Fault (F1) at 6.6kV Switchboard : 912-SW2-001

a)

Source :
300
0.333

Fault MVA of source =


Source Impedance Zs =
XS=
b)

Short circuit MVA

Zpu

Base MVA
Z p.u.

MVA

(= VS X IFS X 1.732)
(= Base MVA /Fault MVA)

PU
0.333

7.5

MVA

, 90

Transformer:
Transformer rating

Transformer secondary No-load voltage =

6.6

KV

Impedance of Transformer T1 , at 6.9kV (Trafo No-load Voltage) =

0.06

p.u

Now, trafo impedance at Base MVA & 6.6 kV Bus Voltage =


= [ p.u. Trafo Impedance x [ (Trafo No-load Voltage/ Bus Voltage) ] x [ (Base MVA / Trafo MVA) ]

c)

= 0.08 x (6.6/6.6) x (100 /7.5)


XTR=
HV Motors

i)

780KW rated Motor (PP-303-01 TO 06)(3Nos FUTURE)


Motor rating =780KW =

876

0.80

, 90

KVA

Sub-transient reactance of HV motor = 17 %


XM1 = XM2 = XM3 = XM4= XM5= XM6= XM7= XM8= XM9=Xd"(p.u.) x (Base MVA x 1000/ Motor kVA) x [ (Trafo No-load Voltage/ Bus Voltage) ]
=
XM=

0.17 x (100*1000/876) x (6.6/6.6)


j

d)

Cable

6.6kVCable to 912-SW2-001 SWITCHBOARD

19.397

, 90

Size : 1Cx 400 mm

Sheet 10 of 97

ZC1=

R = ( 0.05 x 22) / (2 x 1000)

0.001

X = ( 0.097 x 22) / (2 x 1000)

0.002

Rpu = R x (Base MVA/(Base kV) )

0.003

Xpu = X x (Base MVA/(Base kV) )


0.003 +
j 0.005

0.005

0.006

62.73

6.6kVCable to PP-302-01
Size : 3Cx 95 mm
R = ( 0.194 x 292) / (1 x 1000)
X = ( 0.092 x 292) / (1 x 1000)

0.057
0.027

Rpu = R x (Base MVA/(Base kV) )

0.130

Xpu = X x (Base MVA/(Base kV) )

0.062

0.130 +
j 0.062

ZC2=

=
=

0.144

25.37

6.6kVCable to PP-302-02
Size : 3Cx 95 mm
R = ( 0.194 x 292) / (1 x 1000)
X = ( 0.092 x 292) / (1 x 1000)

0.055
0.026

Rpu = R x (Base MVA/(Base kV) )

0.127

Xpu = X x (Base MVA/(Base kV) )

0.060

0.127 +
j 0.060

ZC3=

=
=

0.141

25.37

6.6kVCable to PP-302-03
Size : 3Cx 95 mm
R = ( 0.194 x 292) / (1 x 1000)
X = ( 0.092 x 292) / (1 x 1000)

ZC4=

=
=

0.054
0.026

Rpu = R x (Base MVA/(Base kV) )

0.125

Xpu = X x (Base MVA/(Base kV) )


0.125 +
j 0.059

0.059

0.138

25.37

6.6kVCable to PP-302-04
Size : 3Cx 95 mm
R = ( 0.194 x 274) / (1 x 1000)
X = ( 0.092 x 274) / (1 x 1000)

ZC5=

=
=

0.053
0.025

Rpu = R x (Base MVA/(Base kV) )

0.122

Xpu = X x (Base MVA/(Base kV) )


0.122 +
j 0.058

0.058

0.135

25.37

6.6kVCable to PP-302-05
Size : 3Cx 95 mm
R = ( 0.194 x 268) / (1 x 1000)
X = ( 0.092 x 268) / (1 x 1000)

0.052
0.025

Rpu = R x (Base MVA/(Base kV) )

0.119

Xpu = X x (Base MVA/(Base kV) )

0.057

0.119 +
j 0.057

ZC6=

=
=

0.132

25.37

6.6kVCable to PP-302-06
Size : 3Cx 95 mm
R = ( 0.194 x 262) / (1 x 1000)
X = ( 0.092 x 262) / (1 x 1000)

ZC7=

=
=

0.051
0.024

Rpu = R x (Base MVA/(Base kV) )

0.117

Xpu = X x (Base MVA/(Base kV) )


0.117 +
j 0.055

0.055

0.129

25.37

6.6kVCable to PP-302-07 (FUTURE)


Size : 3Cx 95 mm
R = ( 0.194 x 262) / (1 x 1000)

0.051

Sheet 11 of 97

X = ( 0.092 x 262) / (1 x 1000)

ZC8=

0.024

Rpu = R x (Base MVA/(Base kV) )

0.117

Xpu = X x (Base MVA/(Base kV) )


0.117 +
j 0.055

0.055

0.129

25.37

6.6kVCable to PP-302-08 (FUTURE)


Size : 3Cx 95 mm
R = ( 0.194 x 262) / (1 x 1000)
X = ( 0.092 x 262) / (1 x 1000)

ZC9=

10

0.051

0.024

Rpu = R x (Base MVA/(Base kV) )

0.117

Xpu = X x (Base MVA/(Base kV) )


0.117 +
j 0.055

0.055

0.129

25.37

6.6kVCable to PP-302-09 (FUTURE)


Size : 3Cx 95 mm
R = ( 0.194 x 262) / (1 x 1000)
X = ( 0.092 x 262) / (1 x 1000)

ZC10=

0.051

0.024

Rpu = R x (Base MVA/(Base kV) )

0.117

Xpu = X x (Base MVA/(Base kV) )


0.117 +
j 0.055

0.055

Z1=ZS+ZTR+ZC1
ZS=
ZTR=
ZC1=
Z1=ZS+ZTR+ZC1=
Z1MAG=
1/Z1MAG=
1/Z1REAL=
1/Z1REAC=

j
j
0.003
j
0.003
j

1.1382
0.8786
0.0019
-0.8786

1/Z1=

0.129

25.37

0.333
0.800
+
0.005
1.138
89.87
-89.87

0.002
j -0.879

Z2=ZC2+ZM
ZC2=
ZM=
Z2=ZC2+ZM=

0.130
j
j
0.130
j

Z2MAG= 19.460
1/Z2MAG= 0.051
1/Z2REAL= 0.0003
1/Z2REAC= -0.051
1/Z2=

+
0.062
19.397
19.459
89.62
-89.62

0.0003
j -0.051

Z3=ZC2+ZM
ZC2=
ZM=
Z3=ZC2+ZM=

0.127
j
j
0.127
j

Z3MAG= 19.458
1/Z3MAG= 0.051

+
0.060
19.397
19.458
89.62
-89.62

1/Z3REAL= 0.0003
1/Z3REAC= -0.051
1/Z3=

0.0003
j -0.051

Z4=ZC2+ZM
ZC2=
ZM=
Z4=ZC2+ZM=
Z4MAG= 19.457
1/Z4MAG= 0.051
1/Z4REAL= 0.0003
1/Z4REAC= -0.051
1/Z4=

0.125
j
j
0.125
j

+
0.059
19.397
19.457
89.63
-89.63

0.0003
j -0.051

Sheet 12 of 97

Z5=ZC2+ZM
ZC2=
ZM=
Z5=ZC2+ZM=

0.122
j
j
0.122
j

Z5MAG= 19.456
1/Z5MAG= 0.051

+
0.058
19.397
19.455
89.64
-89.64

1/Z5REAL= 0.0003
1/Z5REAC= -0.051
1/Z5=

0.0003
j -0.051

Z6=ZC2+ZM
ZC2=
ZM=
Z6=ZC2+ZM=

0.119
j
j
0.119
j

Z6MAG= 19.454
1/Z6MAG= 0.0514
1/Z6REAL= 0.0003
1/Z6REAC= -0.051
1/Z6=

+
0.057
19.397
19.454
89.65
-89.65

0.0003
j -0.051

Z7=ZC2+ZM
ZC2=
ZM=
Z7=ZC2+ZM=

0.117
j
j
0.117
j

Z7MAG= 19.453
1/Z7MAG= 0.0514
1/Z7REAL= 0.0003
1/Z7REAC= -0.051
1/Z7=

+
0.055
19.397
19.453
89.66
-89.66

0.0003
j -0.051

Z8=ZC2+ZM
ZC8=
ZM=
Z8=ZC2+ZM=

0.117
j
j
0.117
j

Z8MAG= 19.453
1/Z8MAG= 0.051

+
0.055
19.397
19.453
89.66
-89.66

1/Z8REAL= 0.0003
1/Z8REAC= -0.051
1/Z8=

0.0003
j -0.051

Z9=ZC2+ZM
ZC9=
ZM=
Z9=ZC2+ZM=

0.117
j
j
0.117
j

Z9MAG= 19.453
1/Z9MAG= 0.051
1/Z9REAL= 0.0003
1/Z9REAC= -0.051
1/Z9=

+
0.055
19.397
19.453
89.66
-89.66

0.0003
j -0.051

Z10=ZC2+ZM
ZC10=
ZM=
Z10=ZC2+ZM=

0.117
j
j
0.117
j

Z10MAG= 19.453
1/Z10MAG= 0.051
1/Z10REAL= 0.0003
1/Z10REAC= -0.051

+
0.055
19.397
19.453
89.66
-89.66

1/Z10=

0.0003
j -0.0514

1/ZEQ=

0.0048
j -1.341

1/ZEQMAG=
ZEQMAG=

1.341
0.746

Sheet 13 of 97

Therefore, Maximum Fault level at F1

Maximum Fault level at F1 in KA

Base MVA
Zeq

134.1

134.1

6.6x1.732
11.73

MVA

KA

Sheet 14 of 97

OBJECTIVE
The purpose of this document is to find the maximum Fault Level attained during a 3 phase Symmetrical fault, on different Buses. In order to arrive
at a more correct value, contribution of the Motors towards the fault ratings will also be considered.

REFERENCE DOCUMENT
Documents

Doc. No.

a) Overall Plant Electrical Key Single Line Diagram ( 33kV System)


b) Electrical Key Single Line Diagram

c) Electrical Design Basis

DH0008-ENG-E-DB-0001

d) Load List

DH0008-ENG-E-DC-0001

e) Specification for Transformer (Including Calculations)

DH0008-BE-E-SP-0006

NOTES
a) Base Voltage is 6.6kV and Base MVA is 100MVA throughout the system.
b) The impedance of busbars , circuit breakers , current transformers etc. which are negligibly small are not considered in this calculation.
c) Sub-transient reactance of high voltage Induction motor is considered to be 17%.
d) The short circuit current at the primary terminals (33kV) of the Transformers is 5.25KA for 3 sec as per 33KV fault current rating document.

BASIC DESIGN DATA

a.

System Data :

b.

c.

Source Voltage (Vs)

33

kV

Source Fault Current (IFS)

5.25

kA

Source Transformer (T1) Data(913-TR-001) :


Primary Voltage

33

kV

Secondary Voltage

6.6

kV

Transformer capacity

10.5

MVA

Transformer Impedance

Cable data for Transformer


Cable between (913-TR-001) Transformer and 6.6KV Switchboard (913-SW2-001) Located in LPS-303.
2

Cable Size & type

1CX400 mm ,Cu,XLPE Insulated

No. of Cable Runs

Voltage

6.6

KV

Cable length

22

Meters

Cable Resistance

0.05

/Km, at 90C

Cable Reactance

0.097

/Km, at 90C

d.

Cable Data for HT Motors (PP-303-01 ) :

Cable Between 6.6kV Switch Board to HV Motor

3C x 95 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

6.6

kV

Cable length

264

Meters

Cable Resistance

0.194

/Km, at 90C

Cable Reactance

0.092

/Km, at 90C

Cable Data for HT Motors (PP-303-02 ) :


Cable Between 6.6kV Switch Board to HV Motor
3C x 95 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

6.6

kV

Cable length

286

Meters

Cable Resistance

0.194

/Km, at 90C

Cable Reactance

0.092

/Km, at 90C

Sheet 15 of 97

Cable Data for HT Motors (PP-303-03 ) :


Cable Between 6.6kV Switch Board to HV Motor

3C x 95 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

6.6

kV

Cable length

280

Meters

Cable Resistance

0.194

/Km, at 90C

Cable Reactance

0.092

/Km, at 90C

Cable Data for HT Motors (PP-303-04 ):(FUTURE)


Cable Between 6.6kV Switch Board to HV Motor

3C x 95 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

6.6

kV

Cable length

280

Meters

Cable Resistance

0.194

/Km, at 90C

Cable Reactance

0.092

/Km, at 90C

Cable Data for HT Motors (PP-303-05):(FUTURE)


Cable Between 6.6kV Switch Board to HV Motor

3C x 95 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

6.6

kV

Cable length

280

Meters

Cable Resistance

0.194

/Km, at 90C

Cable Reactance

0.092

/Km, at 90C

Cable Data for HT Motors (PP-303-06):(FUTURE)


Cable Between 6.6kV Switch Board to HV Motor

3C x 95 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

6.6

kV

Cable length

280

Meters

Cable Resistance

0.194

/Km, at 90C

Cable Reactance

0.092

/Km, at 90C

Cable Data for HT Motors (PP-303-07):(FUTURE)


Cable Between 6.6kV Switch Board to HV Motor
3C x 95 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

6.6

kV

Cable length

280

Meters

Cable Resistance

0.194

/Km, at 90C

Cable Reactance

0.092

/Km, at 90C

CALCULATION

A.

GENERAL

a)

Basic equation for short circuit calculation is =

Short Circuit MVA


&

IS

Sheet 16 of 97

Base MVA
Z p.u.

Short circuit MVA


3 x Base kV

IS
Where

Base MVA

100

Base Voltage =

6.6

Zpu

Is

Fault MVA of source

b)

3 x Base kV
MVA
kV
Fault impedance per unit
Symmetrical short circuit current (kA)

VS X IFS X 1.732

Machine Impedances are converted to 25MVA base per unit using the following equation :

Base MVA x p.u. impedanceat MachineMVA SystemkV


x

Machine MVA
Base kV

Per unit impedance =

B.

Fault (F1) at 6.6kV Switchboard : 913-SW2-001

a)

Source :
300
0.333

Fault MVA of source =


Source Impedance Zs =

MVA

(= VS X IFS X 1.732)
(= Base MVA /Fault MVA)

PU
0.333

10.5

MVA

XS=
b)

Short circuit MVA

, 90

Transformer:
Transformer rating

Transformer secondary No-load voltage =

6.6

KV
0.08

Impedance of Transformer T1 , at 6.9kV (Trafo No-load Voltage) =

p.u

Now, trafo impedance at Base MVA & 6.6 kV Bus Voltage =


= [ p.u. Trafo Impedance x [ (Trafo No-load Voltage/ Bus Voltage) ] x [ (Base MVA / Trafo MVA) ]

c)

= 0.08 x (6.6/6.6) x (100 /10.5)


XTR=
HV Motors

i)

1800KW rated Motor (PP-303-01 TO 03) (4nos FUTURE)


Motor rating =1800KW =

0.8

2000

, 90

KVA

Sub-transient reactance of HV motor = 17 %


XM1 = XM2 = XM3= XM4= XM5= XM6= XM7 =Xd"(p.u.) x (Base MVA x 1000/ Motor kVA) x [ (Trafo No-load Voltage/ Bus Voltage) ]
=

0.17 x (100*1000/2000) x (6.6/6.6)

XM=
d)
1

8.5

, 90

Cable
6.6kVCable to 913-SW2-001 SWITCHBOARD
Size : 1Cx 400 mm

ZC1=

R = ( 0.05 x 22) / (2 x 1000)

0.001

X = ( 0.097 x 22) / (2 x 1000)

0.001

Rpu = R x (Base MVA/(Base kV) )

0.001

Xpu = X x (Base MVA/(Base kV) )


0.001 +
j 0.002

0.002

0.0028

62.73

6.6kVCable to PP-303-01
Size : 3Cx 95 mm
R = ( 0.194 x 264) / (1 x 1000)
X = ( 0.092 x 264) / (1 x 1000)

ZC2=

=
=

0.051
0.024

Rpu = R x (Base MVA/(Base kV) )

0.118

Xpu = X x (Base MVA/(Base kV) )


0.118 +
j 0.056

0.056

0.130

25.37

6.6kVCable to PP-303-02
Size : 3Cx 95 mm
R = ( 0.194 x 286) / (1 x 1000)
X = ( 0.092 x 286) / (1 x 1000)

ZC3=

=
=

0.055
0.026

Rpu = R x (Base MVA/(Base kV) )

0.127

Xpu = X x (Base MVA/(Base kV) )


0.127 +

0.060

0.141

25.37

Sheet 17 of 97

ZC3=

0.141

j 0.060

25.37

6.6kVCable to PP-303-03
Size : 3Cx 95 mm
R = ( 0.194 x 280) / (1 x 1000)
X = ( 0.092 x 280) / (1 x 1000)

ZC4=

0.054

0.026

Rpu = R x (Base MVA/(Base kV) )

0.125

Xpu = X x (Base MVA/(Base kV) )


0.125 +
j 0.059

0.059

0.138

25.37

6.6kVCable to PP-303-04 (FUTURE)


Size : 3Cx 95 mm
R = ( 0.194 x 280) / (1 x 1000)
X = ( 0.092 x 280) / (1 x 1000)

ZC5=

0.054

0.026

Rpu = R x (Base MVA/(Base kV) )

0.125

Xpu = X x (Base MVA/(Base kV) )


0.125 +
j 0.059

0.059

0.138

25.37

6.6kVCable to PP-303-05 (FUTURE)


Size : 3Cx 95 mm
R = ( 0.194 x 280) / (1 x 1000)
X = ( 0.092 x 280) / (1 x 1000)

ZC6=

0.054

0.026

Rpu = R x (Base MVA/(Base kV) )

0.125

Xpu = X x (Base MVA/(Base kV) )


0.125 +
j 0.059

0.059

0.138

25.37

6.6kVCable to PP-303-06 (FUTURE)


Size : 3Cx 95 mm
R = ( 0.194 x 280) / (1 x 1000)
X = ( 0.092 x 280) / (1 x 1000)

ZC7=

0.054

0.026

Rpu = R x (Base MVA/(Base kV) )

0.125

Xpu = X x (Base MVA/(Base kV) )


0.125 +
j 0.059

0.059

0.138

25.37

6.6kVCable to PP-303-07 (FUTURE)


Size : 3Cx 95 mm
R = ( 0.194 x 280) / (1 x 1000)
X = ( 0.092 x 280) / (1 x 1000)

ZC8=

0.054

0.026

Rpu = R x (Base MVA/(Base kV) )

0.125

Xpu = X x (Base MVA/(Base kV) )


0.125 +
j 0.059

0.059

Z1=ZS+ZTR+ZC1
ZS=
j
ZTR=
j
0.0013
ZC1=
j
0.0013
Z1=ZS+ZTR+ZC1=
j
Z1MAG= 1.0976
1/Z1MAG= 0.9111
1/Z1REAL= 0.0010
1/Z1REAC= -0.9111
0.0010
1/Z1=
j

0.138

25.37

0.333
0.762
+
0.0024
1.0976
89.93
-89.93

-0.9111

Z2=ZC2+ZM
ZC2=
ZM=
Z2=ZC2+ZM=
Z2MAG= 8.557
1/Z2MAG= 0.117
1/Z2REAL= 0.002
1/Z2REAC= -0.117

0.118
j
j
0.118
j

+
0.056
8.50
8.556
89.21
-89.21

Sheet 18 of 97

1/Z2=

0.002
j -0.117

Z3=ZC2+ZM
ZC3=
ZM=
Z3=ZC2+ZM=

0.127
j
j
0.127
j

Z3MAG= 8.561
1/Z3MAG= 0.117
1/Z3REAL= 0.002
1/Z3REAC= -0.117
1/Z3=

+
0.0604
8.50
8.560
89.15
-89.15

0.002
j -0.117

Z4=ZC2+ZM
ZC4=
ZM=
Z4=ZC2+ZM=

0.125
j
j
0.125
j

Z4MAG= 8.56
1/Z4MAG= 0.117

+
0.059
8.50
8.559
89.17
-89.17

1/Z4REAL= 0.002
1/Z4REAC= -0.117
1/Z4=

0.0017
j -0.117

Z5=ZC2+ZM
ZC5=
ZM=
Z5=ZC2+ZM=

0.125
j
j
0.125
j

Z5MAG= 8.560
1/Z5MAG= 0.117
1/Z5REAL= 0.002
1/Z5REAC= -0.1168
1/Z5=

+
0.059
8.50
8.559
89.17
-89.17

0.002
j -0.117

Z6=ZC2+ZM
ZC6=
ZM=
Z6=ZC2+ZM=

0.125
j
j
0.125
j

Z6MAG= 8.560
1/Z6MAG= 0.117
1/Z6REAL= 0.002
1/Z6REAC= -0.117
1/Z6=

+
0.059
8.50
8.559
89.17
-89.17

0.002
j -0.117

Z7=ZC2+ZM
ZC7=
ZM=
Z7=ZC2+ZM=

0.125
j
j
0.125
j

Z7MAG= 8.560
1/Z7MAG= 0.117
1/Z7REAL= 0.002
1/Z7REAC= -0.117
1/Z7=

+
0.059
8.50
8.559
89.17
-89.17

0.002
j -0.117

Z8=ZC2+ZM
ZC8=
ZM=
Z8=ZC2+ZM=
Z8MAG= 8.560
1/Z8MAG= 0.117
1/Z8REAL= 0.002
1/Z8REAC= -0.117

0.125
j
j
0.125
j

+
0.059
8.50
8.559
89.17
-89.17

1/Z8=

0.002
j -0.117

1/ZEQ=

0.013
j -1.729

Sheet 19 of 97

1.729
0.578

1/ZEQMAG=
ZEQMAG=
Therefore, Maximum Fault level at F1

=
=

Maximum Fault level at F1 in KA

=
=

Base MVA
Zeq
172.9

MVA

172.9
6.6x1.732
15.12

KA

Sheet 20 of 97

OBJECTIVE
The purpose of this document is to find the maximum Fault Level attained during a 3 phase Symmetrical fault, on different Buses. In order to arrive
at a more correct value, contribution of the Motors towards the fault ratings will also be considered.

REFERENCE DOCUMENT
Documents

Doc. No.

a) Overall Plant Electrical Key Single Line Diagram ( 33kV System)


b) Electrical Key Single Line Diagram

c) Electrical Design Basis

DH0008-ENG-E-DB-0001

d) Load List

DH0008-ENG-E-DC-0001

e) Specification for Transformer (Including Calculations)

DH0008-BE-E-SP-0006

NOTES
a) Base Voltage is 6.6kV and Base MVA is 100MVA throughout the system.
b) The impedance of busbars , circuit breakers , current transformers etc. which are negligibly small are not considered in this calculation.
c) Sub-transient reactance of high voltage Induction motor is considered to be 17%.
d) The short circuit current at the primary terminals (33kV) of the Transformers is 5.25KA for 3 sec as per 33KV fault current rating document.

BASIC DESIGN DATA

a.

System Data :

b.

c.

Source Voltage (Vs)

33

kV

Source Fault Current (IFS)

5.25

kA

Source Transformer (T1) Data(913-TR-001) :


Primary Voltage

33

kV

Secondary Voltage

6.6

kV

Transformer capacity

12.5

MVA

Transformer Impedance

Cable data for Transformer


Cable between (913-TR-001) Transformer and 6.6KV Switchboard (913-SW2-001) Located in LPS-303.
2

Cable Size & type

1CX400 mm ,Cu,XLPE Insulated

No. of Cable Runs

Voltage

6.6

KV

Cable length

22

Meters

Cable Resistance

0.05

/Km, at 90C

Cable Reactance

0.097

/Km, at 90C

d.

Cable Data for HT Motors (PP-303-01 ) :

Cable Between 6.6kV Switch Board to HV Motor

3C x 95 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

6.6

kV

Cable length

264

Meters

Cable Resistance

0.194

/Km, at 90C

Cable Reactance

0.092

/Km, at 90C

Cable Data for HT Motors (PP-303-02 ) :


Cable Between 6.6kV Switch Board to HV Motor
3C x 95 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

6.6

kV

Cable length

286

Meters

Cable Resistance

0.194

/Km, at 90C

Cable Reactance

0.092

/Km, at 90C

Sheet 21 of 97

Cable Data for HT Motors (PP-303-03 ) :


Cable Between 6.6kV Switch Board to HV Motor

3C x 95 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

6.6

kV

Cable length

280

Meters

Cable Resistance

0.194

/Km, at 90C

Cable Reactance

0.092

/Km, at 90C

Cable Data for HT Motors (PP-303-04 ):(FUTURE)


Cable Between 6.6kV Switch Board to HV Motor

3C x 95 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

6.6

kV

Cable length

280

Meters

Cable Resistance

0.194

/Km, at 90C

Cable Reactance

0.092

/Km, at 90C

Cable Data for HT Motors (PP-303-05):(FUTURE)


Cable Between 6.6kV Switch Board to HV Motor

3C x 95 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

6.6

kV

Cable length

280

Meters

Cable Resistance

0.194

/Km, at 90C

Cable Reactance

0.092

/Km, at 90C

Cable Data for HT Motors (PP-303-06):(FUTURE)


Cable Between 6.6kV Switch Board to HV Motor

3C x 95 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

6.6

kV

Cable length

280

Meters

Cable Resistance

0.194

/Km, at 90C

Cable Reactance

0.092

/Km, at 90C

Cable Data for HT Motors (PP-303-07):(FUTURE)


Cable Between 6.6kV Switch Board to HV Motor
3C x 95 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

6.6

kV

Cable length

280

Meters

Cable Resistance

0.194

/Km, at 90C

Cable Reactance

0.092

/Km, at 90C

CALCULATION

A.

GENERAL

a)

Basic equation for short circuit calculation is =

Short Circuit MVA


&

IS

Sheet 22 of 97

Base MVA
Z p.u.

Short circuit MVA


3 x Base kV

IS
Where

Base MVA

100

Base Voltage =

6.6

Zpu

Is

Fault MVA of source

b)

3 x Base kV
MVA
kV
Fault impedance per unit
Symmetrical short circuit current (kA)

VS X IFS X 1.732

Machine Impedances are converted to 25MVA base per unit using the following equation :

Base MVA x p.u. impedanceat MachineMVA SystemkV


x

Machine MVA
Base kV

Per unit impedance =

B.

Fault (F1) at 6.6kV Switchboard : 913-SW2-001

a)

Source :
300
0.333

Fault MVA of source =


Source Impedance Zs =

MVA

(= VS X IFS X 1.732)
(= Base MVA /Fault MVA)

PU
0.333

12.5

MVA

XS=
b)

Short circuit MVA

, 90

Transformer:
Transformer rating

Transformer secondary No-load voltage =

6.6

KV
0.08

Impedance of Transformer T1 , at 6.9kV (Trafo No-load Voltage) =

p.u

Now, trafo impedance at Base MVA & 6.6 kV Bus Voltage =


= [ p.u. Trafo Impedance x [ (Trafo No-load Voltage/ Bus Voltage) ] x [ (Base MVA / Trafo MVA) ]

c)

= 0.08 x (6.6/6.6) x (100 /10.5)


XTR=
HV Motors

i)

1800KW rated Motor (PP-303-01 TO 03) (4nos FUTURE)


Motor rating =1800KW =

0.6

2000

, 90

KVA

Sub-transient reactance of HV motor = 17 %


XM1 = XM2 = XM3= XM4= XM5= XM6= XM7 =Xd"(p.u.) x (Base MVA x 1000/ Motor kVA) x [ (Trafo No-load Voltage/ Bus Voltage) ]
=

0.17 x (100*1000/2000) x (6.6/6.6)

XM=
d)
1

8.5

, 90

Cable
6.6kVCable to 913-SW2-001 SWITCHBOARD
Size : 1Cx 400 mm

ZC1=

R = ( 0.05 x 22) / (2 x 1000)

0.001

X = ( 0.097 x 22) / (2 x 1000)

0.001

Rpu = R x (Base MVA/(Base kV) )

0.001

Xpu = X x (Base MVA/(Base kV) )


0.001 +
j 0.002

0.002

0.0028

62.73

6.6kVCable to PP-303-01
Size : 3Cx 95 mm
R = ( 0.194 x 264) / (1 x 1000)
X = ( 0.092 x 264) / (1 x 1000)

ZC2=

=
=

0.051
0.024

Rpu = R x (Base MVA/(Base kV) )

0.118

Xpu = X x (Base MVA/(Base kV) )


0.118 +
j 0.056

0.056

0.130

25.37

6.6kVCable to PP-303-02
Size : 3Cx 95 mm
R = ( 0.194 x 286) / (1 x 1000)
X = ( 0.092 x 286) / (1 x 1000)

ZC3=

=
=

0.055
0.026

Rpu = R x (Base MVA/(Base kV) )

0.127

Xpu = X x (Base MVA/(Base kV) )


0.127 +

0.060

0.141

25.37

Sheet 23 of 97

ZC3=

0.141

j 0.060

25.37

6.6kVCable to PP-303-03
Size : 3Cx 95 mm
R = ( 0.194 x 280) / (1 x 1000)
X = ( 0.092 x 280) / (1 x 1000)

ZC4=

0.054

0.026

Rpu = R x (Base MVA/(Base kV) )

0.125

Xpu = X x (Base MVA/(Base kV) )


0.125 +
j 0.059

0.059

0.138

25.37

6.6kVCable to PP-303-04 (FUTURE)


Size : 3Cx 95 mm
R = ( 0.194 x 280) / (1 x 1000)
X = ( 0.092 x 280) / (1 x 1000)

ZC5=

0.054

0.026

Rpu = R x (Base MVA/(Base kV) )

0.125

Xpu = X x (Base MVA/(Base kV) )


0.125 +
j 0.059

0.059

0.138

25.37

6.6kVCable to PP-303-05 (FUTURE)


Size : 3Cx 95 mm
R = ( 0.194 x 280) / (1 x 1000)
X = ( 0.092 x 280) / (1 x 1000)

ZC6=

0.054

0.026

Rpu = R x (Base MVA/(Base kV) )

0.125

Xpu = X x (Base MVA/(Base kV) )


0.125 +
j 0.059

0.059

0.138

25.37

6.6kVCable to PP-303-06 (FUTURE)


Size : 3Cx 95 mm
R = ( 0.194 x 280) / (1 x 1000)
X = ( 0.092 x 280) / (1 x 1000)

ZC7=

0.054

0.026

Rpu = R x (Base MVA/(Base kV) )

0.125

Xpu = X x (Base MVA/(Base kV) )


0.125 +
j 0.059

0.059

0.138

25.37

6.6kVCable to PP-303-07 (FUTURE)


Size : 3Cx 95 mm
R = ( 0.194 x 280) / (1 x 1000)
X = ( 0.092 x 280) / (1 x 1000)

ZC8=

0.054

0.026

Rpu = R x (Base MVA/(Base kV) )

0.125

Xpu = X x (Base MVA/(Base kV) )


0.125 +
j 0.059

0.059

Z1=ZS+ZTR+ZC1
ZS=
j
ZTR=
j
0.0013
ZC1=
j
0.0013
Z1=ZS+ZTR+ZC1=
j
Z1MAG= 0.9757
1/Z1MAG= 1.0249
1/Z1REAL= 0.0013
1/Z1REAC= -1.0249
0.0013
1/Z1=
j

0.138

25.37

0.333
0.640
+
0.0024
0.9757
89.93
-89.93

-1.0249

Z2=ZC2+ZM
ZC2=
ZM=
Z2=ZC2+ZM=
Z2MAG= 8.557
1/Z2MAG= 0.117
1/Z2REAL= 0.002
1/Z2REAC= -0.117

0.118
j
j
0.118
j

+
0.056
8.50
8.556
89.21
-89.21

Sheet 24 of 97

1/Z2=

0.002
j -0.117

Z3=ZC2+ZM
ZC3=
ZM=
Z3=ZC2+ZM=

0.127
j
j
0.127
j

Z3MAG= 8.561
1/Z3MAG= 0.117
1/Z3REAL= 0.002
1/Z3REAC= -0.117
1/Z3=

+
0.0604
8.50
8.560
89.15
-89.15

0.002
j -0.117

Z4=ZC2+ZM
ZC4=
ZM=
Z4=ZC2+ZM=

0.125
j
j
0.125
j

Z4MAG= 8.56
1/Z4MAG= 0.117

+
0.059
8.50
8.559
89.17
-89.17

1/Z4REAL= 0.002
1/Z4REAC= -0.117
1/Z4=

0.0017
j -0.117

Z5=ZC2+ZM
ZC5=
ZM=
Z5=ZC2+ZM=

0.125
j
j
0.125
j

Z5MAG= 8.560
1/Z5MAG= 0.117
1/Z5REAL= 0.002
1/Z5REAC= -0.1168
1/Z5=

+
0.059
8.50
8.559
89.17
-89.17

0.002
j -0.117

Z6=ZC2+ZM
ZC6=
ZM=
Z6=ZC2+ZM=

0.125
j
j
0.125
j

Z6MAG= 8.560
1/Z6MAG= 0.117
1/Z6REAL= 0.002
1/Z6REAC= -0.117
1/Z6=

+
0.059
8.50
8.559
89.17
-89.17

0.002
j -0.117

Z7=ZC2+ZM
ZC7=
ZM=
Z7=ZC2+ZM=

0.125
j
j
0.125
j

Z7MAG= 8.560
1/Z7MAG= 0.117
1/Z7REAL= 0.002
1/Z7REAC= -0.117
1/Z7=

+
0.059
8.50
8.559
89.17
-89.17

0.002
j -0.117

Z8=ZC2+ZM
ZC8=
ZM=
Z8=ZC2+ZM=
Z8MAG= 8.560
1/Z8MAG= 0.117
1/Z8REAL= 0.002
1/Z8REAC= -0.117

0.125
j
j
0.125
j

+
0.059
8.50
8.559
89.17
-89.17

1/Z8=

0.002
j -0.117

1/ZEQ=

0.013
j -1.843

Sheet 25 of 97

1.843
0.543

1/ZEQMAG=
ZEQMAG=
Therefore, Maximum Fault level at F1

Maximum Fault level at F1 in KA

Base MVA
Zeq

184.3

184.3

6.6x1.732
16.12

MVA

KA

Sheet 26 of 97

OBJECTIVE
The purpose of this document is to find the maximum Fault Level attained during a 3 phase Symmetrical fault, on different Buses. In order
to arrive at a more correct value, contribution of the Motors towards the fault ratings will also be considered.

REFERENCE DOCUMENT
Documents

Doc. No.

a) Overall Plant Electrical Key Single Line Diagram ( 33kV System)


b) Electrical Key Single Line Diagram

c) Electrical Design Basis

DH0008-ENG-E-DB-0001

d) Load List

DH0008-ENG-E-DC-0001

e) Specification for Transformer (Including Calculations)

DH0008-BE-E-SP-0006

NOTES
a) Base Voltage is 0.433kV and Base MVA is 100MVA throughout the system.
b) The impedance of busbars , circuit breakers , current transformers etc. which are negligibly small are not considered in this calculation.
c) Sub-transient reactance of low voltage Induction motor is considered to be 17%.
d) The short circuit current at the primary terminals (33kV) of the Transformers is 5.25KA as per 33KV fault current document.

BASIC DESIGN DATA

a.

System Data:

b.

c.

Source Voltage (Vs)

33

kV

Source Fault Current (IFS)

5.25

kA

Source Transformer (T1) Data ( 910-TR-001):


Primary Voltage

33

kV

Secondary Voltage

0.433

kV

Transformer capacity

MVA

Transformer Impedance

Cable data for Transformer


Cable between (910-TR-001) Transformer and 0.433KV Switchboard (910-SW3-001) Located in Main Consumer Substation.
1CX630 mm2,Cu,XLPE Insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

22

Cable Resistance

0.035

/Km, at 90C

Cable Reactance

0.084

/Km, at 90C

KV
Meters

d.

Cable Data for DB :

Cable Between 910-SW3-001 Board and 910-JP-DB-001(FIRE JOCKEY PUMP) DB

4C x 120 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

605

Cable Resistance

0.156

/Km, at 90C

Cable Reactance

0.072

/Km, at 90C

kV
Meters

Cable Between 910-SW3-001 Board and FS-DB-001(FIRE STATION) DB


4C x 35 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

372

Cable Resistance

0.525

/Km, at 90C

Cable Reactance

0.079

/Km, at 90C

kV
Meters

Cable Between 910-SW3-001 Board and WS-DB-001(WORKSHOP) DB


Cable Size & type

No. of Cable Runs

4C x70 mm2, XLPE insulated


1

Sheet 27 of 97

Voltage

0.433

Cable length

372

kV

Cable Resistance

0.269

/Km, at 90C

Cable Reactance

0.074

/Km, at 90C

Meters

Cable Between 910-SW3-001 Board and ADM-SSB-001(ADMN BLDG &CONTROL ROOM) DB


4C x150 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

341

Cable Resistance

0.128

/Km, at 90C

Cable Reactance

0.072

/Km, at 90C

kV
Meters

Cable Between 910-SW3-001 Board and RC-DB-001(REFUSE CHAMBER) DB


2

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

372

Cable Resistance

0.727

/Km, at 90C

Cable Reactance

0.081

/Km, at 90C

4C x25 mm , XLPE insulated

kV
Meters

Cable Between 910-SW3-001 Board and PS-DB-001(PUMP SHED) DB


4C x35 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

540

Cable Resistance

0.525

/Km, at 90C

Cable Reactance

0.079

/Km, at 90C

kV
Meters

Cable Between 910-SW3-001 Board and LAB-DB-002 DB


4C x35 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

372

Cable Resistance

0.525

/Km, at 90C

Cable Reactance

0.079

/Km, at 90C

kV
Meters

Cable Between 910-SW3-001 Board and FS-DB-002 (FIRE STATION) DB


4C x35 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

372

Cable Resistance

0.525

/Km, at 90C

Cable Reactance

0.079

/Km, at 90C

kV
Meters

Cable Between 910-SW3-001 Board and ADM-ESSB-001(ADMN BLDG & CONTROL ROOM) DB
4C x50 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

372

Cable Resistance

0.388

/Km, at 90C

Cable Reactance

0.075

/Km, at 90C

kV
Meters

Sheet 28 of 97

10

11

12

13

14

15

16

Cable Between 910-SW3-001 Board and 114-FP-01-SL(OUTDOOR LIGHTING) DB


4C x50 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

500

Cable Resistance

0.388

/Km, at 90C

Cable Reactance

0.075

/Km, at 90C

kV
Meters

Cable Between 910-SW3-001 Board and LCP-940-02A/B(SERVICE WATER PUMP) DB


4C x50 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

708

Cable Resistance

0.388

/Km, at 90C

Cable Reactance

0.075

/Km, at 90C

kV
Meters

Cable Between 910-SW3-001 Board and LCP-941-01A/B(FRESHWATER PUMP) DB


2

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

708

Cable Resistance

0.388

/Km, at 90C

Cable Reactance

0.075

/Km, at 90C

4C x50 mm , XLPE insulated

kV
Meters

Cable Between 910-SW3-001 Board and 910-DB-001(33KV CONSUMER SS) DB


4C x35 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

54

Cable Resistance

0.525

/Km, at 90C

Cable Reactance

0.079

/Km, at 90C

kV
Meters

Cable Between 910-SW3-001 Board and LAB-DB-001(LABORATORY/SAMPLE ROOM) DB


4C x35 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

372

Cable Resistance

0.525

/Km, at 90C

Cable Reactance

0.079

/Km, at 90C

kV
Meters

Cable Between 910-SW3-001 Board and AC-CS-SR-01(AIR COND PANEL ) DB


2

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

20

Cable Resistance

0.525

/Km, at 90C

Cable Reactance

0.079

/Km, at 90C

4C x35 mm , XLPE insulated

kV
Meters

Cable Between 910-SW3-001 Board and AC-CS-SGR-01(AIR COND PANEL ) DB


4C x25 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

24

kV
Meters

Sheet 29 of 97

17

18

19

20

21

22

23

Cable Resistance

0.727

/Km, at 90C

Cable Reactance

0.081

/Km, at 90C

Cable Between 910-SW3-001 Board and 910-UPS-001(AC UPS ) DB


4C x25 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

54

Cable Resistance

0.727

/Km, at 90C

Cable Reactance

0.081

/Km, at 90C

kV
Meters

Cable Between 910-SW3-001 Board and 910-UPS-001(AC UPS BYPASS ) DB


4C x25 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

54

Cable Resistance

0.727

/Km, at 90C

Cable Reactance

0.081

/Km, at 90C

kV
Meters

Cable Between 910-SW3-001 Board and 910-UPS-002(DC UPS ) DB


2

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

54

Cable Resistance

1.15

/Km, at 90C

Cable Reactance

0.081

/Km, at 90C

4C x16 mm , XLPE insulated

kV
Meters

Cable Between 910-SW3-001 Board and 910-UPS-003(DC UPS ) DB


2

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

54

Cable Resistance

1.15

/Km, at 90C

Cable Reactance

0.081

/Km, at 90C

4C x16 mm , XLPE insulated

kV
Meters

Cable Between 910-SW3-001 Board and ADM-UPS-001(AC UPS) DB


2

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

372

Cable Resistance

0.525

/Km, at 90C

Cable Reactance

0.079

/Km, at 90C

4C x35 mm , XLPE insulated

kV
Meters

Cable Between 910-SW3-001 Board and ADM-UPS-001(AC UPS BYPASS) DB


2

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

372

Cable Resistance

0.525

/Km, at 90C

Cable Reactance

0.079

/Km, at 90C

4C x35 mm , XLPE insulated

kV
Meters

Cable Between 910-SW3-001 Board and 910-DB-002(33KV CONSUMER SS) DB


Cable Size & type

4C x25 mm2, XLPE insulated

Sheet 30 of 97

24

25

26

27

No. of Cable Runs

Voltage

0.433

Cable length

54

Cable Resistance

0.727

/Km, at 90C

Cable Reactance

0.081

/Km, at 90C

kV
Meters

Cable Between 910-SW3-001 Board and LAB-DB-003(LABORATORY/SAMPLE ROOM) DB


4C x35 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

372

Cable Resistance

0.525

/Km, at 90C

Cable Reactance

0.079

/Km, at 90C

kV
Meters

Cable Between 910-SW3-001 Board and 910-FP-01-SL(OUTDOOR LIGHTING) DB


4C x25 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

96

Cable Resistance

0.727

/Km, at 90C

Cable Reactance

0.081

/Km, at 90C

kV
Meters

Cable Between 910-SW3-001 Board and TNB-DB-001L(TNB SUBSTATION) DB


4C x50 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

144

Cable Resistance

0.388

/Km, at 90C

Cable Reactance

0.075

/Km, at 90C

kV
Meters

Cable Between 910-SW3-001 Board and WH-DB-001(WARE HOUSE) DB


4C x50 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

368

Cable Resistance

0.388

/Km, at 90C

Cable Reactance

0.075

/Km, at 90C

CALCULATION

A.

GENERAL

a)

Basic equation for short circuit calculation is =

kV
Meters

Short Circuit MVA


&

Where
6.6kV Switchboard :

Base MVA

IS
=

Base Voltage =

Base MVA
Z p.u.

Short circuit MVA

100
0.433

3MVA
x Base kV
kV
Fault impedance per unit

Zpu

Is

Symmetrical short circuit current (kA)

VS X IFS X 1.732

Fault MVA of source

Sheet 31 of 97

b)

Machine Impedances are converted to 100MVA base per unit using the following equation :

Per unit impedance =

Base MVA x p.u. impedanceat MachineMVA SystemkV


x

Machine MVA
Base kV

B.

Fault at 0.433 KV DB : 910-SW3-001

a)

Source :
Fault MVA of source =
Source Impedance (Zs) =

300
0.333

MVA

(= VS X IFS X 1.732)

PU

(= Base MVA /Fault MVA)

0.333

, 90

MVA

XS=
b)

Transformer:
Transformer rating

Transformer secondary No-load voltage =

0.433

KV

Impedance of Transformer T1 , at 0.433kV (Trafo No-load Voltage) =

0.05

p.u

Now, trafo impedance at Base MVA & 0.415 kV Bus Voltage =


= [ p.u. Trafo Impedance x [ (Trafo No-load Voltage/ Bus Voltage) ] x [ (Base MVA / Trafo MVA) ]
= 0.05 x (0.433/0.415) x (100 /1)
j
XTR=
d)
1

, 90

5.443

Cable
0.433kVCable to 910-SW3-001 SWITCHBOARD
Size : 1Cx 630 mm
R = ( 0.035 x 22) / (2 x 1000)
X = ( 0.084 x 22) / (2 x 1000)

ZC1=

=
=

0.0004
0.0009

Rpu = R x (Base MVA/(Base kV) )

0.205

Xpu = X x (Base MVA/(Base kV) )


0.205 +
j 0.493

0.493

0.534

67.38

0.433kV Cable to 910-JP-DB-001


Size : 4Cx 120 mm
R = ( 0.156 x 605) / (1 x 1000)
X = ( 0.072 x605) / (1 x 1000)

ZC2=

0.094
0.044

Rpu = R x (Base MVA/(Base kV) )

50.339

Xpu = X x (Base MVA/(Base kV) )


50.339 +
j 23.233

23.233

55.442

24.78

0.433kV Cable to FS-DB-001 (FIRE STATION)


Size : 4Cx 35mm
R = ( 0.525 x 372) / (1 x 1000)
X = ( 0.079 x372) / (1 x 1000)

ZC2=

=
=

=
=

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
104.166 +
j 15.675

0.195
0.029
=

104.166

15.675

105.339

8.56

0.433kV Cable to WS-DB-001 (WORK SHOP)


Size : 4Cx 70mm
R = ( 0.269 x 372) / (1 x 1000)
X = ( 0.074 x372) / (1 x 1000)

ZC2=

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
53.373 +
j 14.682

0.100
0.028
=
=

53.373
14.682

55.355

15.38

0.433kV Cable to ADM-SSB-001 (ADMN BLDG & CONTROL ROOM)


Size : 4Cx 150mm
R = ( 0.128 x 341) / (2 x 1000)
X = ( 0.072 x341) / (2 x 1000)

ZC2=

=
=

=
=

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
11.640 +
j 6.548

0.022
0.012
=
=

11.640
6.548

13.355

Sheet 32 of 97

29.36

0.433kV Cable to RC-DB-001 (REFUSE CHAMBER)


Size : 4Cx 25mm
R = ( 0.727 x 372) / (1 x 1000)
X = ( 0.081 x372) / (1 x 1000)

ZC2=

=
=

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
144.245 +
j 16.071

X = ( 0.079 x540) / (1 x 1000)

144.245

16.071

145.138

6.36

0.433kV Cable to PS-DB-001 (PUMP SHED)


Size : 4Cx 35mm
R = ( 0.525 x 540) / (1 x 1000)

ZC2=

0.270
0.030

=
=

0.284
0.043

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
151.209 +
j 22.753

151.209

22.753

152.911

8.56

0.433kV Cable to LAB-DB-002 (LABORATORY/SAMPLE ROOM)


Size : 4Cx 35mm
R = ( 0.525 x 372) / (1 x 1000)
X = ( 0.079 x372) / (1 x 1000)

=
=

Rpu = R x (Base MVA/(Base kV) )

ZC2=

ZC2=

10

Xpu = X x (Base MVA/(Base kV) )


104.166 +
j 15.675

0.195
0.029
=
=

104.166
15.675

105.339

8.56

0.433kV Cable to FS-DB-002(FIRE STATION)


Size : 4Cx 35mm
R = ( 0.669 x 372) / (1 x 1000)

0.195

X = ( 0.0743 x372) / (1 x 1000)

0.029

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
104.166 +

104.166

15.675

105.339

8.56

j 15.675

0.433kV Cable to ADM-ESSB-001(ADM BLDG & CONTROL ROOM)


Size : 4Cx 50mm
R = ( 0.388 x 372) / (1 x 1000)
X = ( 0.075 x372) / (1 x 1000)

ZC2=

11

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
76.984 +

12

13

=
=

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
103.473 +
j 20.001

76.984
14.881

78.409

10.94

0.194
0.038
=
=

103.473
20.001

105.388

10.94

0.433kV Cable to LCP-940-02A/B(SERVICE WATER PUMP)


=
=

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
146.517 +
j 28.322

0.275
0.053
=
=

146.517
28.322

149.230

10.94

0.433kV Cable to LCP-941-01A/B(FRESH WATER PUMP)


Size : 4Cx 50mm
R = ( 0.388 x 708) / (1 x 1000)
X = ( 0.075 x708) / (1 x 1000)

=
=

Rpu = R x (Base MVA/(Base kV) )

ZC2=

=
=

0.433kV Cable to 114-FP-01-SL(OUTDOOR LIGHTING)

Size : 4Cx 50mm


R = ( 0.388 x 708) / (1 x 1000)
X = ( 0.075 x708) / (1 x 1000)

ZC2=

0.144
0.028

j 14.881

Size : 4Cx 50mm


R = ( 0.388 x 500) / (1 x 1000)
X = ( 0.075 x500) / (1 x 1000)

ZC2=

=
=

Xpu = X x (Base MVA/(Base kV) )


146.517 +

0.275
0.053
=
=

146.517
28.322

149.230
Sheet 33 of 97

10.94

ZC2=

14

149.230

15

0.433kV Cable to 910-DB-001(33KV CONSUMER SS)


Size : 4Cx35mm
R = ( 0.525 x 54) / (1 x 1000)
X = ( 0.079 x54) / (1 x 1000)

ZC2=

10.94

j 28.322

=
=

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
15.121 +
j 2.275

0.028
0.004
=
=

15.121
2.275

15.291

8.56

0.433kV Cable to LAB-DB-001(LABORATORY/SAMPLE ROOM)


Size : 4Cx 35mm
R = ( 0.525 x 372) / (1 x 1000)
X = ( 0.079 x372) / (1 x 1000)

ZC2=

16

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
104.166 +
j 15.675

17

0.195
0.029
=
=

104.166
15.675

105.339

8.56

8.56

0.433kV Cable to AC-CS-SR-01(AIR COND PANEL)


Size : 4Cx 35mm
R = ( 0.525 x 20) / (1 x 1000)
X = ( 0.079 x20) / (1 x 1000)

ZC2=

=
=

=
=

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
5.600 +
j 0.843

0.011
0.002
=

5.600

0.843

5.663

0.433kV Cable to AC-CS-SGR-01(AIR COND PANEL)


Size : 4Cx 25mm
R = ( 0.727 x 24) / (1 x 1000)
X = ( 0.081 x24) / (1 x 1000)

ZC2=

18

=
=

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
20.939 +
j 2.333

=
=

Rpu = R x (Base MVA/(Base kV) )

19

Xpu = X x (Base MVA/(Base kV) )


20.939 +
j 2.333

X = ( 0.081 x54) / (1 x 1000)

20

21

=
=

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
20.939 +
j 2.333

21.068

6.36

0.039
0.004
=
=

20.939
2.333

21.068

6.36

0.039
0.004
=
=

20.939
2.333

21.068

6.36

0.433kV Cable to 910-UPS-002(DC UPS )


Size : 4Cx 16mm
R = ( 1.15 x 54) / (1 x 1000)
X = ( 0.081 x54) / (1 x 1000)

ZC2=

20.939
2.333

0.433kV Cable to 910-UPS-001(AC UPS BYPASS)


Size : 4Cx 25mm
R = ( 0.727 x 54) / (1 x 1000)

ZC2=

=
=

0.433kV Cable to 910-UPS-001(AC UPS)


Size : 4Cx 25mm
R = ( 0.727 x 54) / (1 x 1000)
X = ( 0.081 x54) / (1 x 1000)

ZC2=

0.039
0.004

=
=

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
33.122 +

0.062
0.029
=
=

33.122
15.675

36.644

25.33

j 15.675
0.433kV Cable to 910-UPS-003(DC UPS )
Size : 4Cx 16mm
R = ( 1.15 x 54) / (1 x 1000)
X = ( 0.081 x54) / (1 x 1000)

=
=

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )

0.062
0.004
=
=

33.122
2.333

Sheet 34 of 97

33.122 +
j 2.333

ZC2=

22

33.204

X = ( 0.079 x372) / (1 x 1000)

0.195

0.029
=
=

Rpu = R x (Base MVA/(Base kV) )

23

Xpu = X x (Base MVA/(Base kV) )


104.166 +
j 15.675

X = ( 0.079 x372) / (1 x 1000)

105.339

=
=
105.339

=
=

Xpu = X x (Base MVA/(Base kV) )


20.939 +
j 2.333

21.068

6.36

0.195

0.029

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
104.166 +
j 15.675

104.166

15.675

105.339

8.56

0.433kV Cable to 910-FP-01-SL(OUTDOOR LIGHTING)


Size : 4Cx25mm
R = ( 0.727 x 96) / (1 x 1000)
X = ( 0.081 x96) / (1 x 1000)

27

20.939
2.333

0.433kV Cable to LAB-DB-003(LABORATORY/SAMPLE ROOM)

X = ( 0.079 x372) / (1 x 1000)

ZC2=

0.004

Size : 4Cx35mm
R = ( 0.525 x 372) / (1 x 1000)

26

8.56

0.039

Rpu = R x (Base MVA/(Base kV) )

ZC2=

104.166
15.675

0.433kV Cable to 910-DB-002(33KV CONSUMER SS)

X = ( 0.081 x54) / (1 x 1000)

25

0.029

Xpu = X x (Base MVA/(Base kV) )


104.166 +
j 15.675

Size : 4Cx 25mm


R = ( 0.727 x 54) / (1 x 1000)

ZC2=

8.56

0.195

Rpu = R x (Base MVA/(Base kV) )

24

104.166
15.675

0.433kV Cable to ADM-UPS-001(AC UPS BYPASS)


Size : 4Cx 35mm
R = ( 0.525 x 372) / (1 x 1000)

ZC2=

0.433kV Cable to ADM-UPS-001(AC UPS)


Size : 4Cx 35mm
R = ( 0.525 x 372) / (1 x 1000)

ZC2=

4.03

0.070
0.018

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
37.225 +

37.225

9.578

38.437

14.43

j 9.578

0.433kV Cable to TNB-DB-001(TNB SUBSTATION)


Size : 4Cx50mm
R = ( 0.388 x 144) / (1 x 1000)
X = ( 0.075 x144) / (1 x 1000)

ZC2=

28

0.056
0.011

=
=

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
29.800 +
j 5.760

30.352

10.94

0.433kV Cable to WH-DB-001(WARE HOUSE)


Size : 4Cx50mm
R = ( 0.388 x 368) / (1 x 1000)
X = ( 0.075 x368) / (1 x 1000)

=
=

0.143
0.028
=
=

Rpu = R x (Base MVA/(Base kV) )

ZC2=

29.800
5.760

Xpu = X x (Base MVA/(Base kV) )


76.156 +
j 14.721
Z1=ZS+ZTR+ZC1
ZS=
j
ZTR=
j
0.2053
ZC1=
j
0.2053
Z1=ZS+ZTR+ZC1=
j

76.156
14.721

77.566

0.333
5.443
+
0.4928
6.2692

Sheet 35 of 97

10.94

Z1MAG=
1/Z1MAG=
1/Z1REAL=
1/Z1REAC=

6.2726
0.1594
0.0052
-0.1593

88.12
-88.12

0.0052
j -0.1593

1/Z1=

Z2
50.34 +
j 23.23
Z2MAG= 55.4419
24.78
1/Z2MAG= 0.0180
-24.78
ZC2=

1/Z2REAL= 0.0164
1/Z2REAC= -0.0076
0.0164
j -0.0076

1/Z2=

Z3
104.17 +
j 15.67
Z3MAG= 105.34
8.56
1/Z3MAG= 0.0095
-8.56
ZC3=

1/Z3REAL= 0.0094
1/Z3REAC= -0.0014
0.0094
j -0.0014

1/Z3=

Z4
ZC4=
Z4MAG= 55.36
1/Z4MAG= 0.0181
1/Z4REAL= 0.0174

53.37 +
j 14.68
15.38
-15.38

1/Z4REAC= -0.0048
0.0174
j -0.0048

1/Z4=

Z5
ZC5=
Z5MAG= 13.36
1/Z5MAG= 0.0749

11.64 +
j 6.55
29.36
-29.36

1/Z5REAL= 0.0653
1/Z5REAC= -0.0367
0.0653

1/Z5=

j -0.0367
Z6
144.25 +

ZC6=
Z6MAG= 145.14
1/Z6MAG= 0.0069
1/Z6REAL= 0.0068

j 16.07
6.36
-6.36

1/Z6REAC= -0.0008
0.0068

1/Z6=

j -0.0008
Z7
151.21 +

ZC7=
Z7MAG= 152.91
1/Z7MAG= 0.0065
1/Z7REAL= 0.0065

j 22.75
8.56
-8.56

1/Z7REAC= -0.0010
0.0065
j -0.0010

1/Z7=

Z8
104.17 +
j 15.67
Z8MAG= 105.34
8.56
1/Z8MAG= 0.0095
-8.56
1/Z8REAL= 0.0094
1/Z8REAC= -0.0014
ZC8=

0.0094
j -0.0014

1/Z8=

Z9
ZC9=

104.17 +
j 15.67

Sheet 36 of 97

Z9MAG= 105.34
1/Z9MAG= 0.0095
1/Z9REAL= 0.0094
1/Z9REAC= -0.0014

8.56
-8.56

0.0094
j -0.0014

1/Z9=

Z10
ZC10=
Z10MAG= 78.41
1/Z10MAG= 0.0128

76.98 +
j 14.88
10.94
-10.94

1/Z10REAL= 0.0125
1/Z10REAC= -0.0024
0.0125
j -0.0024

1/Z10=

Z11
103.47 +

ZC11=
Z11MAG= 105.39
1/Z11MAG= 0.0095

j 20.00
10.94
-10.94

1/Z11REAL= 0.0093
1/Z11REAC= -0.0018
0.0093
j -0.0018

1/Z11=

Z12
146.52 +

ZC12=
Z12MAG= 149.23
1/Z12MAG= 0.0067

j 28.32
10.94
-10.94

1/Z12REAL= 0.0066
1/Z12REAC= -0.0013
0.0066

1/Z12=

j -0.0013
Z13
146.52 +

ZC13=
Z13MAG= 149.23
1/Z13MAG= 0.0067

j 28.32
10.94
-10.94

1/Z13REAL= 0.0066
1/Z13REAC= -0.0013
0.0066
j -0.0013

1/Z13=

Z14
15.12 +
j 2.28

ZC14=
Z14MAG= 15.29
1/Z14MAG= 0.0654
1/Z14REAL= 0.0647
1/Z14REAC= -0.0097

8.56
-8.56

0.0647
j -0.0097

1/Z14=

Z15
104.17 +
j 15.67

ZC15=
Z15MAG= 105.34
1/Z15MAG= 0.0095

8.56
-8.56

1/Z15REAL= 0.0094
1/Z15REAC= -0.0014
0.0094
j -0.0014

1/Z15=

Z16
5.6 +

ZC16=
Z16MAG= 5.6634
1/Z16MAG= 0.1766
1/Z16REAL= 0.1746
1/Z16REAC= -0.0263

j 0.84
8.56
-8.56

0.1746
j -0.0263

1/Z16=

Z17
ZC17=

20.94 +

Sheet 37 of 97

ZC17=
Z17MAG= 21.07
1/Z17MAG= 0.0475
1/Z17REAL= 0.0472

j 2.33
6.36
-6.36

1/Z17REAC= -0.0053
0.0472
j -0.0053

1/Z17=

Z18
ZC18=
Z18MAG= 21.07
1/Z18MAG= 0.0475
1/Z18REAL= 0.0472

20.94 +
j 2.33
6.36
-6.36

1/Z18REAC= -0.0053
0.0472
j -0.0053

1/Z18=

Z19
ZC19=
Z19MAG= 21.07
1/Z19MAG= 0.0475

20.94 +
j 2.33
6.36
-6.36

1/Z19REAL= 0.0472
1/Z19REAC= -0.0053
0.0472
j -0.0053

1/Z19=

Z20
ZC20=
Z20MAG= 36.64
1/Z20MAG= 0.0273
1/Z20REAL= 0.0247

33.12 +
j 15.67
25.33
-25.33

1/Z20REAC= -0.0117
0.0247
j -0.0117

1/Z20=

Z21
ZC21=
Z21MAG= 33.20
1/Z21MAG= 0.0301
1/Z21REAL= 0.0300
1/Z21REAC= -0.0021

33.12 +
j 2.33
4.03
-4.03

0.0300

1/Z21=

j -0.0021
Z22
104.17 +

ZC22=
Z22MAG= 105.34
1/Z22MAG= 0.0095
1/Z22REAL= 0.0094
1/Z22REAC= -0.0014

j 15.67
8.56
-8.56

0.0094
j -0.0014

1/Z22=

Z23
104.17 +

ZC23=
Z23MAG= 105.34
1/Z23MAG= 0.0095

j 15.67
8.56
-8.56

1/Z23REAL= 0.0094
1/Z23REAC= -0.0014
0.0094
j -0.0014

1/Z23=

Z24
ZC24=
Z24MAG= 21.07
1/Z24MAG= 0.0475
1/Z24REAL= 0.0472
1/Z24REAC= -0.0053

20.94 +
j 2.33
6.36
-6.36

0.0472

1/Z24=

j -0.0053
Z25

Sheet 38 of 97

104.17 +
j 15.67
Z25MAG= 105.34
8.56
1/Z25MAG= 0.0095
-8.56
ZC25=

1/Z25REAL= 0.0094
1/Z25REAC= -0.0014
0.0094

1/Z25=

j -0.0014
Z26
37.22 +
j 9.58

ZC26=
Z26MAG= 38.44
1/Z26MAG= 0.0260

14.43
-14.43

1/Z26REAL= 0.0252
1/Z26REAC= -0.0065
0.0252

1/Z26=

j -0.0065
Z27
29.80 +
j 5.76

ZC27=
Z27MAG= 30.35
1/Z27MAG= 0.0329

10.94
-10.94

1/Z27REAL= 0.0323
1/Z27REAC= -0.0063
0.0323
j -0.0063

1/Z27=

Z28
76.16 +
j 14.72

ZC28=
Z28MAG= 77.57
1/Z28MAG= 0.0129

10.94
-10.94

1/Z28REAL= 0.0127
1/Z28REAC= -0.0024
0.0127

1/Z28=

j -0.0024
0.7712

1/ZEQ=

j -0.3128

1/ZEQ MAG =

0.8322

ZEQ MAG =

1.2016

Therefore, Maximum Fault level at F1

Maximum Fault level at F1 in KA

Base MVA
Zeq

83.2

MVA

115.78

KA

Sheet 39 of 97

OBJECTIVE
The purpose of this document is to find the maximum Fault Level attained during a 3 phase Symmetrical fault, on different Buses. In order
to arrive at a more correct value, contribution of the Motors towards the fault ratings will also be considered.

REFERENCE DOCUMENT
Documents

Doc. No.

a) Overall Plant Electrical Key Single Line Diagram ( 33kV System)


b) Electrical Key Single Line Diagram

c) Electrical Design Basis

DH0008-ENG-E-DB-0001

d) Load List

DH0008-ENG-E-DC-0001

e) Specification for Transformer (Including Calculations)

DH0008-BE-E-SP-0006

NOTES
a) Base Voltage is 0.433kV and Base MVA is 100MVA throughout the system.
b) The impedance of busbars , circuit breakers , current transformers etc. which are negligibly small are not considered in this calculation.
c) Sub-transient reactance of low voltage Induction motor is considered to be 17%.
d) The short circuit current at the primary terminals (33kV) of the Transformers is 5.25KA as per 33KV fault current document.

BASIC DESIGN DATA

a.

System Data:

b.

Source Voltage (Vs)

33

kV

Source Fault Current (IFS)

5.25

kA

Source Transformer (T1) Data ( 910-TR-001):


Primary Voltage

33

kV

Secondary Voltage

0.433

kV

Transformer capacity

MVA

Transformer Impedance

c.

Cable data for Transformer

Cable between (910-TR-001) Transformer and 0.433KV Switchboard (910-SW3-001) Located in Main Consumer Substation.
1CX630 mm2,Cu,XLPE Insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

22

Cable Resistance

0.035

/Km, at 90C

Cable Reactance

0.084

/Km, at 90C

KV
Meters

d.

Cable Data for DB :

Cable Between 910-SW3-001 Board and 910-JP-DB-001(FIRE JOCKEY PUMP) DB

4C x 120 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

605

Cable Resistance

0.156

/Km, at 90C

Cable Reactance

0.072

/Km, at 90C

kV
Meters

Cable Between 910-SW3-001 Board and FS-DB-001(FIRE STATION) DB


4C x 35 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

372

Cable Resistance

0.525

/Km, at 90C

Cable Reactance

0.079

/Km, at 90C

kV
Meters

Cable Between 910-SW3-001 Board and WS-DB-001(WORKSHOP) DB


Cable Size & type

No. of Cable Runs

4C x70 mm2, XLPE insulated


1

Sheet 40 of 97

Voltage

0.415

Cable length

372

kV

Cable Resistance

0.269

/Km, at 90C

Cable Reactance

0.074

/Km, at 90C

Meters

Cable Between 910-SW3-001 Board and ADM-SSB-001(ADMN BLDG &CONTROL ROOM) DB


4C x150 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

341

Cable Resistance

0.128

/Km, at 90C

Cable Reactance

0.072

/Km, at 90C

kV
Meters

Cable Between 910-SW3-001 Board and RC-DB-001(REFUSE CHAMBER) DB


2

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

372

Cable Resistance

0.727

/Km, at 90C

Cable Reactance

0.081

/Km, at 90C

4C x25 mm , XLPE insulated

kV
Meters

Cable Between 910-SW3-001 Board and PS-DB-001(PUMP SHED) DB


4C x35 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

540

Cable Resistance

0.525

/Km, at 90C

Cable Reactance

0.079

/Km, at 90C

kV
Meters

Cable Between 910-SW3-001 Board and LAB-DB-002 DB


4C x35 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

372

Cable Resistance

0.525

/Km, at 90C

Cable Reactance

0.079

/Km, at 90C

kV
Meters

Cable Between 910-SW3-001 Board and FS-DB-002 (FIRE STATION) DB


4C x35 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

372

Cable Resistance

0.525

/Km, at 90C

Cable Reactance

0.079

/Km, at 90C

kV
Meters

Cable Between 910-SW3-001 Board and ADM-ESSB-001(ADMN BLDG & CONTROL ROOM) DB
4C x50 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

372

Cable Resistance

0.388

/Km, at 90C

Cable Reactance

0.075

/Km, at 90C

kV
Meters

Sheet 41 of 97

10

11

12

13

14

15

16

Cable Between 910-SW3-001 Board and LCP-940-02A/B(SERVICE WATER PUMP) DB


4C x50 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

708

Cable Resistance

0.388

/Km, at 90C

Cable Reactance

0.075

/Km, at 90C

kV
Meters

Cable Between 910-SW3-001 Board and LCP-941-01A/B(FRESHWATER PUMP) DB


4C x50 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

708

Cable Resistance

0.388

/Km, at 90C

Cable Reactance

0.075

/Km, at 90C

kV
Meters

Cable Between 910-SW3-001 Board and 910-DB-001(33KV CONSUMER SS) DB


2

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

54

Cable Resistance

0.525

/Km, at 90C

Cable Reactance

0.079

/Km, at 90C

4C x35 mm , XLPE insulated

kV
Meters

Cable Between 910-SW3-001 Board and LAB-DB-001(LABORATORY/SAMPLE ROOM) DB


4C x35 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

372

Cable Resistance

0.525

/Km, at 90C

Cable Reactance

0.079

/Km, at 90C

kV
Meters

Cable Between 910-SW3-001 Board and AC-CS-SR-01(AIR COND PANEL ) DB


4C x35 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

20

Cable Resistance

0.525

/Km, at 90C

Cable Reactance

0.079

/Km, at 90C

kV
Meters

Cable Between 910-SW3-001 Board and AC-CS-SGR-01(AIR COND PANEL ) DB


2

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

24

Cable Resistance

0.727

/Km, at 90C

Cable Reactance

0.081

/Km, at 90C

4C x25 mm , XLPE insulated

kV
Meters

Cable Between 910-SW3-001 Board and 910-DB-002(33KV CONSUMER SS) DB


4C x25 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

54

kV
Meters

Sheet 42 of 97

17

18

19

Cable Resistance

0.727

/Km, at 90C

Cable Reactance

0.081

/Km, at 90C

Cable Between 910-SW3-001 Board and LAB-DB-003(LABORATORY/SAMPLE ROOM) DB


4C x35 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

372

Cable Resistance

0.525

/Km, at 90C

Cable Reactance

0.079

/Km, at 90C

kV
Meters

Cable Between 910-SW3-001 Board and TNB-DB-001(TNB SUBSTATION) DB


2

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

144

Cable Resistance

0.388

/Km, at 90C

Cable Reactance

0.075

/Km, at 90C

4C x50 mm , XLPE insulated

kV
Meters

Cable Between 910-SW3-001 Board and WH-DB-001(WARE HOUSE) DB


4C x50 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

368

Cable Resistance

0.388

/Km, at 90C

Cable Reactance

0.075

/Km, at 90C

CALCULATION

A.

GENERAL

a)

Basic equation for short circuit calculation is =

kV
Meters

Short Circuit MVA


&

Where
6.6kV Switchboard :

Base MVA

IS
=

Base Voltage =

Base MVA
Z p.u.

Short circuit MVA

100
0.433

3MVA
x Base kV
kV
Fault impedance per unit

Zpu

Is

Symmetrical short circuit current (kA)

VS X IFS X 1.732

Fault MVA of source

Sheet 43 of 97

b)

Machine Impedances are converted to 100MVA base per unit using the following equation :

Per unit impedance =

Base MVA x p.u. impedanceat MachineMVA SystemkV


x

Machine MVA
Base kV

B.

Fault at 0.433 KV DB : 910-SW3-001

a)

Source :
Fault MVA of source =
Source Impedance (Zs) =

300
0.333

MVA

(= VS X IFS X 1.732)

PU

(= Base MVA /Fault MVA)

0.333

, 90

MVA

XS=
b)

Transformer:
Transformer rating

Transformer secondary No-load voltage =

0.433

KV

Impedance of Transformer T1 , at 0.433kV (Trafo No-load Voltage) =

0.05

p.u

Now, trafo impedance at Base MVA & 0.415 kV Bus Voltage =


= [ p.u. Trafo Impedance x [ (Trafo No-load Voltage/ Bus Voltage) ] x [ (Base MVA / Trafo MVA) ]
= 0.05 x (0.433/0.415) x (100 /1)
j
XTR=
d)
1

, 90

5.443

Cable
0.433kVCable to 910-SW3-001 SWITCHBOARD
Size : 1Cx 630 mm
R = ( 0.035 x 22) / (2 x 1000)
X = ( 0.084 x 22) / (2 x 1000)

ZC1=

=
=

0.0004
0.0009

Rpu = R x (Base MVA/(Base kV) )

0.205

Xpu = X x (Base MVA/(Base kV) )


0.205 +
j 0.493

0.493

0.534

67.38

0.433kV Cable to 910-JP-DB-001


Size : 4Cx 120 mm
R = ( 0.156 x 605) / (1 x 1000)
X = ( 0.072 x605) / (1 x 1000)

ZC2=

0.094
0.044

Rpu = R x (Base MVA/(Base kV) )

50.339

Xpu = X x (Base MVA/(Base kV) )


50.339 +
j 23.233

23.233

55.442

24.78

0.433kV Cable to FS-DB-001 (FIRE STATION)


Size : 4Cx 35mm
R = ( 0.525 x 372) / (1 x 1000)
X = ( 0.079 x372) / (1 x 1000)

ZC2=

=
=

=
=

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
104.166 +
j 15.675

0.195
0.029
=

104.166

15.675

105.339

8.56

0.433kV Cable to WS-DB-001 (WORK SHOP)


Size : 4Cx 70mm
R = ( 0.269 x 372) / (1 x 1000)
X = ( 0.074 x372) / (1 x 1000)

ZC2=

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
53.373 +

0.100
0.028
=
=

53.373
14.682

55.355

15.38

j 14.682

0.433kV Cable to ADM-SSB-001 (ADMN BLDG & CONTROL ROOM)


Size : 4Cx 150mm
R = ( 0.128 x 341) / (2 x 1000)
X = ( 0.072 x341) / (2 x 1000)

ZC2=

=
=

=
=

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
11.640 +
j 6.548

0.022
0.012
=
=

11.640
6.548

13.355

Sheet 44 of 97

29.36

0.433kV Cable to RC-DB-001 (REFUSE CHAMBER)


Size : 4Cx 25mm
R = ( 0.727 x 372) / (1 x 1000)

X = ( 0.081 x372) / (1 x 1000)

0.030

Rpu = R x (Base MVA/(Base kV) )

ZC2=

Xpu = X x (Base MVA/(Base kV) )


144.245 +
j 16.071

=
=

Rpu = R x (Base MVA/(Base kV) )

Xpu = X x (Base MVA/(Base kV) )


151.209 +
j 22.753

X = ( 0.079 x372) / (1 x 1000)

Xpu = X x (Base MVA/(Base kV) )


104.166 +

0.284
0.043
=
=

151.209
22.753

152.911

8.56

0.195

=
=

104.166
15.675

105.339

8.56

0.433kV Cable to FS-DB-002(FIRE STATION)


=
=

Rpu = R x (Base MVA/(Base kV) )

10

6.36

j 15.675

Size : 4Cx 35mm


R = ( 0.669 x 372) / (1 x 1000)
X = ( 0.0743 x372) / (1 x 1000)

ZC2=

145.138

0.029

Rpu = R x (Base MVA/(Base kV) )

144.245
16.071

0.433kV Cable to LAB-DB-002 (LABORATORY/SAMPLE ROOM)


Size : 4Cx 35mm
R = ( 0.525 x 372) / (1 x 1000)

ZC2=

=
=

0.433kV Cable to PS-DB-001 (PUMP SHED)


Size : 4Cx 35mm
R = ( 0.525 x 540) / (1 x 1000)
X = ( 0.079 x540) / (1 x 1000)

ZC2=

0.270

Xpu = X x (Base MVA/(Base kV) )


104.166 +
j 15.675

0.195
0.029
=
=

104.166
15.675

105.339

8.56

0.433kV Cable to ADM-ESSB-001(ADM BLDG & CONTROL ROOM)


Size : 4Cx 50mm
R = ( 0.388 x 372) / (1 x 1000)
X = ( 0.075 x372) / (1 x 1000)

ZC2=

11

=
=

0.144
0.028

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
76.984 +
j 14.881

76.984

14.881

78.409

10.94

0.433kV Cable to LCP-940-02A/B(SERVICE WATER PUMP)


Size : 4Cx 50mm
R = ( 0.388 x 708) / (1 x 1000)
X = ( 0.075 x708) / (1 x 1000)

ZC2=

12

=
=

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
146.517 +
j 28.322

0.275
0.053
=
=

146.517
28.322

149.230

10.94

0.433kV Cable to LCP-941-01A/B(FRESH WATER PUMP)


Size : 4Cx 50mm
R = ( 0.388 x 708) / (1 x 1000)
X = ( 0.075 x708) / (1 x 1000)

ZC2=

13

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
146.517 +
j 28.322

0.275
0.053
=
=

146.517
28.322

149.230

10.94

0.433kV Cable to 910-DB-001(33KV CONSUMER SS)


Size : 4Cx35mm
R = ( 0.525 x 54) / (1 x 1000)
X = ( 0.079 x54) / (1 x 1000)

ZC2=

=
=

=
=

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
15.121 +
j 2.275

0.028
0.004
=

15.121

2.275

15.291

Sheet 45 of 97

8.56

14

0.433kV Cable to LAB-DB-001(LABORATORY/SAMPLE ROOM)


Size : 4Cx 35mm
R = ( 0.525 x 372) / (1 x 1000)
X = ( 0.079 x372) / (1 x 1000)

ZC2=

15

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
104.166 +
j 15.675

X = ( 0.079 x20) / (1 x 1000)

16

104.166

15.675

105.339

8.56

8.56

6.36

0.433kV Cable to AC-CS-SR-01(AIR COND PANEL)


Size : 4Cx 35mm
R = ( 0.525 x 20) / (1 x 1000)

ZC2=

0.195
0.029

0.011

0.002

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
5.600 +
j 0.843

5.600

0.843

5.663

0.433kV Cable to AC-CS-SGR-01(AIR COND PANEL)


Size : 4Cx 25mm
R = ( 0.727 x 24) / (1 x 1000)
X = ( 0.081 x24) / (1 x 1000)

0.017
0.002

=
=

Rpu = R x (Base MVA/(Base kV) )

ZC2=

17

Xpu = X x (Base MVA/(Base kV) )


9.306 +
j 1.037

X = ( 0.081 x54) / (1 x 1000)

18

9.364

0.433kV Cable to 910-DB-002(33KV CONSUMER SS)


Size : 4Cx 25mm
R = ( 0.727 x 54) / (1 x 1000)

ZC2=

9.306
1.037

0.039

0.004

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
20.939 +

20.939

2.333

21.068

6.36

j 2.333

0.433kV Cable to LAB-DB-003(LABORATORY/SAMPLE ROOM)


Size : 4Cx35mm
R = ( 0.525 x 372) / (1 x 1000)
X = ( 0.079 x372) / (1 x 1000)

ZC2=

19

20

=
=

104.166
15.675

105.339

8.56

j 15.675

0.433kV Cable to TNB-DB-001(TNB SUBSTATION)


=

0.056
0.011

=
=

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
29.800 +
j 5.760

29.800
5.760

30.352

10.94

0.433kV Cable to WH-DB-001(WARE HOUSE)


Size : 4Cx50mm
R = ( 0.388 x 368) / (1 x 1000)
X = ( 0.075 x368) / (1 x 1000)

ZC2=

0.195
0.029

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
104.166 +

Size : 4Cx50mm
R = ( 0.388 x 144) / (1 x 1000)
X = ( 0.075 x144) / (1 x 1000)

ZC2=

=
=

=
=

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
76.156 +
j 14.721
Z1=ZS+ZTR+ZC1
ZS=
j
ZTR=
j
0.2053
ZC1=
j
0.2053
Z1=ZS+ZTR+ZC1=
j
Z1MAG= 6.2726
1/Z1MAG= 0.1594

0.143
0.028
=
=

76.156
14.721

77.566

0.333
5.443
+
0.4928
6.2692
88.12
-88.12

Sheet 46 of 97

10.94

1/Z1REAL= 0.0052
1/Z1REAC= -0.1593
0.0052
j -0.1593

1/Z1=

Z2
50.34 +
j 23.23

ZC2=
Z2MAG= 55.4419
1/Z2MAG= 0.0180

24.78
-24.78

1/Z2REAL= 0.0164
1/Z2REAC= -0.0076
0.0164

1/Z2=

j -0.0076
Z3

104.17 +
j 15.67
Z3MAG= 105.34
8.56
1/Z3MAG= 0.0095
-8.56
ZC3=

1/Z3REAL= 0.0094
1/Z3REAC= -0.0014
0.0094

1/Z3=

j -0.0014
Z4
53.37 +

ZC4=
Z4MAG= 55.36
1/Z4MAG= 0.0181

j 14.68
15.38
-15.38

1/Z4REAL= 0.0174
1/Z4REAC= -0.0048
0.0174

1/Z4=

j -0.0048
Z5
11.64 +
j 6.55

ZC5=
Z5MAG= 13.36
1/Z5MAG= 0.0749
1/Z5REAL= 0.0653

29.36
-29.36

1/Z5REAC= -0.0367
0.0653

1/Z5=

j -0.0367
Z6
144.25 +
j 16.07

ZC6=
Z6MAG= 145.14
1/Z6MAG= 0.0069

6.36
-6.36

1/Z6REAL= 0.0068
1/Z6REAC= -0.0008
0.0068
j -0.0008

1/Z6=

Z7
151.21 +
j 22.75
Z7MAG= 152.91
8.56
1/Z7MAG= 0.0065
-8.56
ZC7=

1/Z7REAL= 0.0065
1/Z7REAC= -0.0010
0.0065
j -0.0010

1/Z7=

Z8
104.17 +

ZC8=
Z8MAG= 105.34
1/Z8MAG= 0.0095
1/Z8REAL= 0.0094
1/Z8REAC= -0.0014

j 15.67
8.56
-8.56

0.0094
j -0.0014

1/Z8=

Z9
104.17 +
j 15.67
Z9MAG= 105.34
8.56
ZC9=

Sheet 47 of 97

1/Z9MAG= 0.0095
1/Z9REAL= 0.0094
1/Z9REAC= -0.0014

-8.56

0.0094

1/Z9=

j -0.0014
Z10

ZC10=
Z10MAG= 78.41
1/Z10MAG= 0.0128
1/Z10REAL= 0.0125

76.98 +
j 14.88
10.94
-10.94

1/Z10REAC= -0.0024
0.0125

1/Z10=

j -0.0024
Z11
146.52 +
j 28.32

ZC11=
Z11MAG= 149.23
1/Z11MAG= 0.0067
1/Z11REAL= 0.0066

10.94
-10.94

1/Z11REAC= -0.0013
0.0066

1/Z11=

j -0.0013
Z12
146.52 +
j 28.32

ZC12=
Z12MAG= 149.23
1/Z12MAG= 0.0067
1/Z12REAL= 0.0066

10.94
-10.94

1/Z12REAC= -0.0013
0.0066
j -0.0013

1/Z12=

Z13
15.12 +
j 2.28

ZC13=
Z13MAG= 15.29
1/Z13MAG= 0.0654
1/Z13REAL= 0.0647

8.56
-8.56

1/Z13REAC= -0.0097
0.0647

1/Z13=

j -0.0097
Z14

104.17 +
j 15.67
Z14MAG= 105.34
8.56
1/Z14MAG= 0.0095
-8.56
ZC14=

1/Z14REAL= 0.0094
1/Z14REAC= -0.0014
0.0094

1/Z14=

j -0.0014
Z15

ZC15=
Z15MAG= 5.6634
1/Z15MAG= 0.1766
1/Z15REAL= 0.1746

5.6 +
j 0.84
8.56
-8.56

1/Z15REAC= -0.0263
0.1746
j -0.0263

1/Z15=

Z16
9.31 +
j 1.04

ZC16=
Z16MAG= 9.36
1/Z16MAG= 0.1068
1/Z16REAL= 0.1061
1/Z16REAC= -0.0118

6.36
-6.36

0.1061
j -0.0118

1/Z16=

Z17
ZC17=

20.94 +
j 2.33

Sheet 48 of 97

Z17MAG= 21.07
1/Z17MAG= 0.0475
1/Z17REAL= 0.0472
1/Z17REAC= -0.0053

6.36
-6.36

0.0472
j -0.0053

1/Z17=

Z18
104.17 +
j 15.67
Z18MAG= 105.34
8.56
1/Z18MAG= 0.0095
-8.56
ZC18=

1/Z18REAL= 0.0094
1/Z18REAC= -0.0014
0.0094
j -0.0014

1/Z18=

Z19
29.80 +

ZC19=
Z19MAG= 30.35
1/Z19MAG= 0.0329

j 5.76
10.94
-10.94

1/Z19REAL= 0.0323
1/Z19REAC= -0.0063
0.0323
j -0.0063

1/Z19=

Z20
76.16 +

ZC20=
Z20MAG= 77.57
1/Z20MAG= 0.0129

j 14.72
10.94
-10.94

1/Z20REAL= 0.0127
1/Z20REAC= -0.0024
0.0127

1/Z20=

j -0.0024
0.6278

1/ZEQ=

j -0.2839

0.6890

1/ZEQ MAG =

1.4513

ZEQ MAG =
Therefore, Maximum Fault level at F1

Maximum Fault level at F1 in KA

Base MVA
Zeq

68.9

MVA

95.86

KA

Sheet 49 of 97

OBJECTIVE
The purpose of this document is to find the maximum Fault Level attained during a 3 phase Symmetrical fault, on different Buses. In order to
arrive at a more correct value, contribution of the Motors towards the fault ratings will also be considered.

REFERENCE DOCUMENT
Documents

Doc. No.

a) Overall Plant Electrical Key Single Line Diagram ( 33kV System)


b) Electrical Key Single Line Diagram

c) Electrical Design Basis

DH0008-ENG-E-DB-0001

d) Load List

DH0008-ENG-E-DC-0001

e) Specification for Transformer (Including Calculations)

DH0008-BE-E-SP-0006

NOTES
a) Base Voltage is 0.433kV and Base MVA is 100MVA throughout the system.
b) The impedance of busbars , circuit breakers , current transformers etc. which are negligibly small are not considered in this calculation.
c) Sub-transient reactance of low voltage Induction motor is considered to be 17%.
d) The short circuit current at the primary terminals (33kV) of the Transformers is 5.25KA for 3 sec as per 33KV fault current document.

BASIC DESIGN DATA

a.

System Data:

b.

Source Voltage (Vs)

33

kV

Source Fault Current (IFS)

5.25

kA

Source Transformer (T1) Data ( 911-TR-002):


Primary Voltage

33

kV

Secondary Voltage

0.433

kV

Transformer capacity

2.5

Transformer Impedance

MVA
%

c.

Cable data for Transformer

Cable between (911-TR-002) Transformer and 0.433KV Switchboard (911-SW3-001) Located in LPS301.
1CX630 mm 2,Cu,XLPE Insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

22

Cable Resistance

0.035

/Km, at 90C

Cable Reactance

0.084

/Km, at 90C

KV
Meters

d.

Cable Data for DB :

Cable Between 911-SW3-001 Board and 415V LCS 301 (911-DB-001) DB

4C x 16 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

54

Cable Resistance

1.15

/Km, at 90C

Cable Reactance

0.081

/Km, at 90C

kV
Meters

Cable Between 911-SW3-001 Board and (301-DB-001-MOV) DB


4C x 50 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

180

Cable Resistance

0.388

/Km, at 90C

Cable Reactance

0.075

/Km, at 90C

kV
Meters

Cable Between 911-SW3-001 Board and (301-DB-002-MOV) DB


4C x 50 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

228

Cable Resistance

0.388

/Km, at 90C

Cable Reactance

0.075

/Km, at 90C

kV
Meters

Cable Between 911-SW3-001 Board and (301-DB-003-MOV) DB


4C x 50 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

252

Cable Resistance

0.388

kV
Meters
/Km, at 90C

Sheet 50 of 97

Cable Reactance

10

11

12

/Km, at 90C

0.075

Cable Between 911-SW3-001 Board and (301-DB-004-MOV) DB


4C x 50 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

276

Cable Resistance

0.388

/Km, at 90C

Cable Reactance

0.075

/Km, at 90C

kV
Meters

Cable Between 911-SW3-001 Board and (301-DB-005-MOV) DB


4C x 50 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

294

Cable Resistance

0.388

/Km, at 90C

Cable Reactance

0.075

/Km, at 90C

kV
Meters

Cable Between 911-SW3-001 Board and (301-DB-006-MOV) DB


2

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

96

Cable Resistance

0.388

/Km, at 90C

Cable Reactance

0.075

/Km, at 90C

4C x 50 mm , XLPE insulated

kV
Meters

Cable Between 911-SW3-001 Board and (301-DB-007-MOV) DB


4C x 50 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

120

Cable Resistance

0.388

/Km, at 90C

Cable Reactance

0.075

/Km, at 90C

kV
Meters

Cable Between 911-SW3-001 Board and (301-DB-008-MOV) DB


4C x 50 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

168

Cable Resistance

0.388

/Km, at 90C

Cable Reactance

0.075

/Km, at 90C

kV
Meters

Cable Between 911-SW3-001 Board and (301-DB-009-MOV) DB


4C x 50 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

168

Cable Resistance

0.388

/Km, at 90C

Cable Reactance

0.075

/Km, at 90C

kV
Meters

Cable Between 911-SW3-001 Board and (301-DB-010-MOV) DB


4C x 50 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

168

Cable Resistance

0.388

/Km, at 90C

Cable Reactance

0.075

/Km, at 90C

kV
Meters

Sheet 51 of 97

13

14

15

16

17

18

19

20

21

Cable Between 911-SW3-001 Board and 101-MCC-003-MIX(MIXER) DB


2

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

440

Cable Resistance

0.066

/Km, at 90C

Cable Reactance

0.07

/Km, at 90C

4C x 300 mm , XLPE insulated

kV
Meters

Cable Between 911-SW3-001 Board and 101-MCC-007-MIX(MIXER) DB


4C x 150 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

440

Cable Resistance

0.128

/Km, at 90C

Cable Reactance

0.072

/Km, at 90C

kV
Meters

Cable Between 911-SW3-001 Board and 103-MCC-003-MIX(MIXER) DB


4C x 300 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

275

Cable Resistance

0.066

/Km, at 90C

Cable Reactance

0.07

/Km, at 90C

kV
Meters

Cable Between 911-SW3-001 Board and 103-MCC-007-MIX(MIXER) DB


2

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

300

Cable Resistance

0.269

/Km, at 90C

Cable Reactance

0.074

/Km, at 90C

4C x 70 mm , XLPE insulated

kV
Meters

Cable Between 911-SW3-001 Board and ADDITIVE TRANSFER PUMP (P-920-01A) DB


3C x 25 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

252

Cable Resistance

0.728

/Km, at 90C

Cable Reactance

0.081

/Km, at 90C

kV
Meters

Cable Between 911-SW3-001 Board and ADDITIVE TRANSFER PUMP (P-920-01B) DB


2

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

252

Cable Resistance

0.728

/Km, at 90C

Cable Reactance

0.081

/Km, at 90C

3C x 25 mm , XLPE insulated

kV
Meters

Cable Between 911-SW3-001 Board and 101-MCC-005-AUX (OILY WATER PUMP) DB


4C x 35 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

440

Cable Resistance

0.525

/Km, at 90C

Cable Reactance

0.079

/Km, at 90C

kV
Meters

Cable Between 911-SW3-001 Board and 103-MCC-005-AUX (OILY WATER PUMP) DB


4C x 35 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

306

Cable Resistance

0.525

/Km, at 90C

Cable Reactance

0.079

/Km, at 90C

kV
Meters

Cable Between 911-SW3-001 Board and P-301-10A (SUMP PUMP)


Cable Size & type

No. of Cable Runs

3C x 25 mm 2, XLPE insulated
1

Sheet 52 of 97

22

23

24

25

26

27

28

29

Voltage

0.415

Cable length

308

kV

Cable Resistance

0.728

/Km, at 90C

Cable Reactance

0.081

/Km, at 90C

Meters

Cable Between 911-SW3-001 Board and P-301-10B (SUMP PUMP)


3C x 25 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

308

Cable Resistance

0.728

/Km, at 90C

Cable Reactance

0.081

/Km, at 90C

kV
Meters

Cable Between 911-SW3-001 Board and P-301-11 (SLOP PUMP)


3C x10 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

308

Meters

Cable Resistance

1.83

/Km, at 90C

Cable Reactance

0.085

/Km, at 90C

kV

Cable Between 911-SW3-001 Board and 912-SW3-001 DB


4C x 400 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

253

Cable Resistance

0.054

/Km, at 90C

Cable Reactance

0.07

/Km, at 90C

kV
Meters

Cable Between 912-SW3-001 Board and 415V LCS 302 DB(912-DB-001) DB


2

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

54

Cable Resistance

1.15

/Km, at 90C

Cable Reactance

0.081

/Km, at 90C

4C x 16 mm , XLPE insulated

kV
Meters

Cable Between 912-SW3-001 Board and ADDITIVE INJ 3&4(302-LCP-011-AI) DB


2

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

252

Cable Resistance

0.727

/Km, at 90C

Cable Reactance

0.081

/Km, at 90C

4C x 25mm , XLPE insulated

kV
Meters

Cable Between 912-SW3-001 Board and MOV(302-DB-001-MOV) DB


4C x50mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

228

Cable Resistance

0.388

/Km, at 90C

Cable Reactance

0.075

/Km, at 90C

kV
Meters

Cable Between 912-SW3-001 Board and MOV(302-DB-002-MOV) DB


4C x50mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

252

Cable Resistance

0.388

/Km, at 90C

Cable Reactance

0.075

/Km, at 90C

kV
Meters

Cable Between 912-SW3-001 Board and MOV(302-DB-003-MOV) DB


4C x50mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

276

Cable Resistance

0.388

/Km, at 90C

Cable Reactance

0.075

/Km, at 90C

kV
Meters

Sheet 53 of 97

30

31

32

33

34

35

36

37

38

Cable Between 912-SW3-001 Board and MOV(302-DB-004-MOV) DB


2

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

300

Cable Resistance

0.388

/Km, at 90C

Cable Reactance

0.075

/Km, at 90C

4C x50mm , XLPE insulated

kV
Meters

Cable Between 912-SW3-001 Board and MOV(302-DB-005-MOV) DB


4C x50mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

324

Cable Resistance

0.388

/Km, at 90C

Cable Reactance

0.075

/Km, at 90C

kV
Meters

Cable Between 912-SW3-001 Board and MOV(302-DB-006-MOV) DB


4C x50mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

96

Cable Resistance

0.388

/Km, at 90C

Cable Reactance

0.075

/Km, at 90C

kV
Meters

Cable Between 912-SW3-001 Board and MOV(302-DB-007-MOV) DB


2

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

120

Cable Resistance

0.388

/Km, at 90C

Cable Reactance

0.075

/Km, at 90C

4C x50mm , XLPE insulated

kV
Meters

Cable Between 912-SW3-001 Board and MOV(302-DB-008-MOV) DB


4C x50mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

144

Cable Resistance

0.388

/Km, at 90C

Cable Reactance

0.075

/Km, at 90C

kV
Meters

Cable Between 912-SW3-001 Board and MOV(302-DB-009-MOV) DB


2

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

168

Cable Resistance

0.388

/Km, at 90C

Cable Reactance

0.075

/Km, at 90C

4C x50mm , XLPE insulated

kV
Meters

Cable Between 912-SW3-001 Board and MOV(302-DB-010-MOV) DB


4C x50mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

192

Cable Resistance

0.388

/Km, at 90C

Cable Reactance

0.075

/Km, at 90C

kV
Meters

Cable Between 912-SW3-001 Board and MIXER (102-MCC-003-MIX) DB


4C x 185 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

473

Cable Resistance

0.102

/Km, at 90C

Cable Reactance

0.072

/Km, at 90C

kV
Meters

Cable Between 912-SW3-001 Board and MIXER (102-MCC-007-MIX) DB


Cable Size & type

No. of Cable Runs

4C x 120 mm 2, XLPE insulated


2

Sheet 54 of 97

39

40

41

Voltage

0.415

Cable length

473

kV

Cable Resistance

0.156

/Km, at 90C

Cable Reactance

0.072

/Km, at 90C

Meters

Cable Between 912-SW3-001 Board and MIXER (104-MCC-003-MIX) DB


4C x 300mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

275

Cable Resistance

0.066

/Km, at 90C

Cable Reactance

0.07

/Km, at 90C

kV
Meters

Cable Between 912-SW3-001 Board and MIXER (104-MCC-007-MIX) DB


4C x 185mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

300

Cable Resistance

0.102

/Km, at 90C

Cable Reactance

0.072

/Km, at 90C

kV
Meters

Cable Between 911-SW3-001 Board and 912-SW3-002 DB

Sheet 55 of 97

42

43

44

45

4C x 400 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

253

Cable Resistance

0.054

/Km, at 90C

Cable Reactance

0.07

/Km, at 90C

kV
Meters

Cable Between 912-SW3-002 Board and 415V LCS 302 DB(912-DB-002) DB


2

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

54

Cable Resistance

1.83

/Km, at 90C

Cable Reactance

0.085

/Km, at 90C

4C x 10mm , XLPE insulated

kV
Meters

Cable Between 912-SW3-001 Board and SUMP PUMP (P-302-10A) DB


3C x 25mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

336

Cable Resistance

0.728

/Km, at 90C

Cable Reactance

0.081

/Km, at 90C

kV
Meters

Cable Between 912-SW3-002 Board and SUMP PUMP (P-302-10B) DB


3C x 25mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

336

Cable Resistance

0.728

/Km, at 90C

Cable Reactance

0.081

/Km, at 90C

kV
Meters

Cable Between 912-SW3-002 Board and SLOP PUMP(P-302-11) DB


2

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

336

Meters

Cable Resistance

1.83

/Km, at 90C

Cable Reactance

0.085

/Km, at 90C

3C x 10mm , XLPE insulated

CALCULATION

A.

GENERAL

a)

Basic equation for short circuit calculation is =

kV

Short Circuit MVA

IS

Short circuit MVA


3 x Base kV

&
Where

Base MVA

100

Base Voltage =
Zpu

Is

Fault MVA of source


b)

0.433

MVA
kV
Fault impedance per unit
Symmetrical short circuit current (kA)

VS X IFS X 1.732

Machine Impedances are converted to 100MVA base per unit using the following equation :

Base MVA x p.u. impedanceat MachineMVA SystemkV


x

Machine MVA
Base kV

Per unit impedance =

B.

Fault at 0.415 KV DB : 911-SW3-001

a)

Source :
Fault MVA of source =
Source Impedance (Zs) =

300

MVA

(= VS X IFS X 1.732)

PU

(= Base MVA /Fault MVA)

0.333

, 90

2.5

MVA

0.333

XS=
b)

Base MVA
Z p.u.

Transformer:
Transformer rating

Transformer secondary No-load voltage =

0.433

KV

Impedance of Transformer T1 , at 0.433kV (Trafo No-load Voltage) =

0.06

p.u

Now, trafo impedance at Base MVA & 0.415 kV Bus Voltage =


= [ p.u. Trafo Impedance x [ (Trafo No-load Voltage/ Bus Voltage) ] x [ (Base MVA / Trafo MVA) ]
= 0.06 x (0.433/0.415) x (100/2.5)
Sheet 56 of 97

XTR=

d)

, 90

2.613

Cable for Transformer


1

0.415kVCable to 911-SW3-001 SWITCHBOARD


Size : 1Cx 630 mm
R = ( 0.038 x 22) / (5 x 1000)
X = ( 0.075 x 22) / (5 x 1000)

=
=

0.0002
0.0004

Rpu = R x (Base MVA/(Base kV) )

0.082

Xpu = X x (Base MVA/(Base kV) )

0.197

0.082 +

ZC1=

0.214

67.38

j 0.197

0.415kV Cable to 911-DB-001


Size : 4Cx 16mm
R = ( 0.388 x 228) / (1 x 1000)
X = ( 0.075 x228) / (1 x 1000)

=
=

0.062
0.004

Rpu = R x (Base MVA/(Base kV) )

33.122

Xpu = X x (Base MVA/(Base kV) )

2.333

33.122 +

ZC2=

4.03

10.94

33.204

j 2.333

0.415kV Cable to 301-DB-001-MOV


Size : 4Cx 50mm
R = ( 0.388 x 180) / (1 x 1000)
X = ( 0.075 x180) / (1 x 1000)

=
=

0.07
0.014

Rpu = R x (Base MVA/(Base kV) )

37.25

Xpu = X x (Base MVA/(Base kV) )

7.2

37.250 +

ZC3=

37.940

j 7.200

0.415kV Cable to 301-DB-002-MOV


Size : 4Cx 50mm
R = ( 0.388 x 228) / (1 x 1000)
X = ( 0.075 x228) / (1 x 1000)

=
=

0.088
0.017

Rpu = R x (Base MVA/(Base kV) )

47.184

Xpu = X x (Base MVA/(Base kV) )

9.121

47.184 +

ZC4=

48.057

10.94

j 9.121

0.415kV Cable to 301-DB-003-MOV


Size : 4Cx 50mm
R = ( 0.388 x 252) / (1 x 1000)
X = ( 0.075 x252) / (1 x 1000)

=
=

0.098
0.019

Rpu = R x (Base MVA/(Base kV) )

52.150

Xpu = X x (Base MVA/(Base kV) )

10.081

52.150 +

ZC5=

53.116

10.94

j 10.081

0.415kV Cable to 301-DB-004-MOV


Size : 4Cx 50mm
R = ( 0.388 x276) / (1 x 1000)
X = ( 0.075x276) / (1 x 1000)

=
=

0.107
0.021

Rpu = R x (Base MVA/(Base kV) )

57.117

Xpu = X x (Base MVA/(Base kV) )

11.041

57.117 +

ZC6=

58.174

10.94

j 11.041

0.415kV Cable to 301-DB-005-MOV


Size : 4Cx 50mm
R = (0.388 x 294) / (1 x 1000)
X = ( 0.075x294) / (1 x 1000)

=
=

Rpu = R x (Base MVA/(Base kV) )

0.114
0.022
=

60.842

Sheet 57 of 97

Xpu = X x (Base MVA/(Base kV) )

60.842 +

ZC7=

11.761

61.968

10.94

j 11.761

0.415kV Cable to 301-DB-006-MOV


Size : 4Cx 50mm
R = (0.388 x 96) / (1 x 1000)
X = ( 0.075x96) / (1 x 1000)

=
=

0.037
0.007

Rpu = R x (Base MVA/(Base kV) )

19.867

Xpu = X x (Base MVA/(Base kV) )

3.840

19.867 +

ZC8=

20.235

10.94

j 3.840

0.415kV Cable to 301-DB-007-MOV


Size : 4Cx 50mm
R = (0.388 x 120) / (1 x 1000)
X = ( 0.075x120) / (1 x 1000)

=
=

0.047
0.009

Rpu = R x (Base MVA/(Base kV) )

24.833

Xpu = X x (Base MVA/(Base kV) )

4.800

24.833 +

ZC9=

25.293

10.94

j 4.800

10

0.415kV Cable to 301-DB-008-MOV


Size : 4Cx 50mm
R = (0.388 x 168) / (1 x 1000)
X = ( 0.075x168) / (1 x 1000)

=
=

0.065
0.013

Rpu = R x (Base MVA/(Base kV) )

34.767

Xpu = X x (Base MVA/(Base kV) )

6.720

34.767 +

ZC10=

35.410

10.94

j 6.720

11

0.415kV Cable to 301-DB-009-MOV


Size : 4Cx 50mm
R = (0.388 x 168) / (1 x 1000)
X = ( 0.075x168) / (1 x 1000)

=
=

0.065
0.013

Rpu = R x (Base MVA/(Base kV) )

34.767

Xpu = X x (Base MVA/(Base kV) )

6.720

34.767 +

ZC11=

35.410

10.94

j 6.720

12

0.415kV Cable to 301-DB-010-MOV


Size : 4Cx 50mm
R = ( 0.388 x168) / (1 x 1000)
X = ( 0.075 x168) / (1 x 1000)

=
=

0.065
0.013

Rpu = R x (Base MVA/(Base kV) )

34.767

Xpu = X x (Base MVA/(Base kV) )

6.720

34.767 +

ZC12=

35.410

10.94

j 6.720

13

0.415kV Cable to 101-MCC-003-MIX


Size : 4Cx 300mm
R = ( 0.066 x440) / (2 x 1000)
X = ( 0.07 x440) / (2 x 1000)

=
=

0.015
0.015

Rpu = R x (Base MVA/(Base kV) )

7.744

Xpu = X x (Base MVA/(Base kV) )

8.214

7.744 +

ZC13=

11.289

j 8.214

14

0.415kV Cable to 101-MCC-007-MIX


Size : 4Cx 150mm
R = ( 0.128 x440) / (2 x 1000)

0.028

Sheet 58 of 97

46.68

X = ( 0.072 x440) / (2 x 1000)

0.016

Rpu = R x (Base MVA/(Base kV) )

15.020

Xpu = X x (Base MVA/(Base kV) )

8.448

15.020 +

ZC14=

17.233

29.36

j 8.448

15

0.415kV Cable to 103-MCC-003-MIX


Size : 4Cx 300mm
R = ( 0.066 x275) / (2 x 1000)
X = ( 0.07 x275) / (2 x 1000)

=
=

0.009
0.010

Rpu = R x (Base MVA/(Base kV) )

4.840

Xpu = X x (Base MVA/(Base kV) )

5.134

4.840 +

ZC15=

7.056

46.68

j 5.134

16

0.415kV Cable to 103-MCC-007-MIX


Size : 4Cx 70mm
R = ( 0.269 x300) / (2 x 1000)
X = ( 0.074 x300) / (2 x 1000)

=
=

0.040
0.011

Rpu = R x (Base MVA/(Base kV) )

21.521

Xpu = X x (Base MVA/(Base kV) )

5.920

21.521 +

ZC16=

22.321

15.38

j 5.920

17 0.415kV Cable to P-920-01A


Size : 3Cx 25mm
R = ( 0.728 x252) / (2 x 1000)
X = ( 0.081 x252) / (2 x 1000)

=
=

0.183
0.020

Rpu = R x (Base MVA/(Base kV) )

97.849

Xpu = X x (Base MVA/(Base kV) )

10.887

97.849 +

ZC17=

98.453

6.35

j 10.887

18 0.415kV Cable to P-920-01B


Size : 3Cx 25mm
R = ( 0.728 x252) / (2 x 1000)
X = ( 0.081 x252) / (2 x 1000)

=
=

0.183
0.020

Rpu = R x (Base MVA/(Base kV) )

97.849

Xpu = X x (Base MVA/(Base kV) )

10.887

97.849 +

ZC18=

98.453

6.35

j 10.887

19

0.415kV Cable to 101-MCC-005-AUX


Size : 4Cx 35mm
R = ( 0.525 x440) / (2 x 1000)
X = ( 0.079 x440) / (2 x 1000)

=
=

0.231
0.035

Rpu = R x (Base MVA/(Base kV) )

123.207

Xpu = X x (Base MVA/(Base kV) )

18.540

123.207 +

ZC19=

124.594

8.56

j 18.540

20

0.415kV Cable to 103-MCC-005-AUX


Size : 4Cx 35mm
R = ( 0.525 x306) / (2 x 1000)
X = ( 0.079 x306) / (2 x 1000)

ZC20=

=
=

0.161
0.024

Rpu = R x (Base MVA/(Base kV) )

85.685

Xpu = X x (Base MVA/(Base kV) )

12.894

85.685 +

86.650

j 12.894

21

0.415kV Cable to P-301-10A

Sheet 59 of 97

8.56

Size : 3Cx 25mm


R = ( 0.728 x308) / (1 x 1000)

X = ( 0.081 x308) / (1 x 1000)

0.224
0.025

Rpu = R x (Base MVA/(Base kV) )

119.593

Xpu = X x (Base MVA/(Base kV) )

13.306

119.593 +

ZC21=

120.331

6.35

j 13.306

22

0.415kV Cable to P-301-10B


Size : 3Cx 25mm
R = ( 0.525 x308) / (1 x 1000)

X = ( 0.079 x308) / (1 x 1000)

0.224
0.025

Rpu = R x (Base MVA/(Base kV) )

119.593

Xpu = X x (Base MVA/(Base kV) )

13.306

119.593 +

ZC22=

120.331

6.35

j 13.306

23

0.415kV Cable to P-301-11


Size : 3Cx 10mm
R = ( 1.83 x308) / (1 x 1000)

0.564

X = ( 0.085 x308) / (1 x 1000)

0.026

Rpu = R x (Base MVA/(Base kV) )

300.626

Xpu = X x (Base MVA/(Base kV) )

13.963

300.626 +

ZC23=

2.66

52.35

300.950

j 13.963

24

0.415kV Cable to 912-SW3-001


Size : 4Cx 400mm
R = ( 0.054 x253) / (4 x 1000)
X = ( 0.07 x253) / (4 x 1000)

=
=

0.003
0.004

Rpu = R x (Base MVA/(Base kV) )

1.822

Xpu = X x (Base MVA/(Base kV) )

2.361

1.822 +

ZC24=

2.982

j 2.361

25

0.415kV Cable to 912-DB-001


Size : 4Cx 16mm
R = ( 1.15 x54) / (1 x 1000)

0.062

X = ( 0.081 x54) / (1 x 1000)

0.004

Rpu = R x (Base MVA/(Base kV) )

33.122

Xpu = X x (Base MVA/(Base kV) )

2.333

33.122 +

ZC25=

33.204

4.03

j 2.333

26

0.415kV Cable to 302-LCP-011-AI


Size : 4Cx 25mm
R = (0.727 x252) / (1 x 1000)

0.183

X = ( 0.081 x252) / (1 x 1000)

0.020

Rpu = R x (Base MVA/(Base kV) )

97.715

Xpu = X x (Base MVA/(Base kV) )

10.887

97.715 +

ZC26=

98.319

6.36

j 10.887

27

0.415kV Cable to 302-DB-001-MOV


Size : 4Cx 50mm

ZC27=

R = (0.388 x228) / (1 x 1000)

0.088

X = ( 0.075 x228) / (1 x 1000)

0.017

Rpu = R x (Base MVA/(Base kV) )

47.184

Xpu = X x (Base MVA/(Base kV) )

9.121

47.184 +

48.057

j 9.121

Sheet 60 of 97

10.94

28

0.415kV Cable to 302-DB-002-MOV


Size : 4Cx 50mm
R = (0.388 x252) / (1 x 1000)

0.098

X = ( 0.075 x252) / (1 x 1000)

0.019

Rpu = R x (Base MVA/(Base kV) )

52.150

Xpu = X x (Base MVA/(Base kV) )

10.081

52.150 +

ZC28=

53.116

10.94

j 10.081

29

0.415kV Cable to 302-DB-003-MOV


Size : 4Cx 50mm
R = (0.388 x276) / (1 x 1000)

0.107

X = ( 0.075 x276) / (1 x 1000)

0.021

Rpu = R x (Base MVA/(Base kV) )

57.117

Xpu = X x (Base MVA/(Base kV) )

11.041

57.117 +

ZC29=

58.174

10.94

j 11.041

30

0.415kV Cable to 302-DB-004-MOV


Size : 4Cx 50mm
R = (0.388 x300) / (1 x 1000)

0.116

X = ( 0.075 x300) / (1 x 1000)

0.023

Rpu = R x (Base MVA/(Base kV) )

62.084

Xpu = X x (Base MVA/(Base kV) )

12.001

62.084 +

ZC30=

63.233

10.94

j 12.001

31

0.415kV Cable to 302-DB-005-MOV


Size : 4Cx 50mm
R = (0.388 x324) / (1 x 1000)

0.126

X = ( 0.075 x324) / (1 x 1000)

0.024

Rpu = R x (Base MVA/(Base kV) )

67.050

Xpu = X x (Base MVA/(Base kV) )

12.961

67.050 +

ZC31=

68.291

10.94

j 12.961

32

0.415kV Cable to 302-DB-006-MOV


Size : 4Cx 50mm
R = (0.388 x96) / (1 x 1000)

0.037

X = ( 0.075 x96) / (1 x 1000)

0.007

Rpu = R x (Base MVA/(Base kV) )

19.867

Xpu = X x (Base MVA/(Base kV) )

3.840

19.867 +

ZC32=

20.235

10.94

j 3.840

33

0.415kV Cable to 302-DB-007-MOV


Size : 4Cx 50mm
R = (0.388 x120) / (1 x 1000)

0.047

X = ( 0.075 x120) / (1 x 1000)

0.009

Rpu = R x (Base MVA/(Base kV) )

24.833

Xpu = X x (Base MVA/(Base kV) )

4.800

24.833 +

ZC33=

25.293

10.94

j 4.800

34

0.415kV Cable to 302-DB-008-MOV


Size : 4Cx 50mm
R = (0.388 x144) / (1 x 1000)

0.056

X = ( 0.075 x144) / (1 x 1000)

0.011

Rpu = R x (Base MVA/(Base kV) )

29.8

Xpu = X x (Base MVA/(Base kV) )

5.760

Sheet 61 of 97

29.800 +

ZC34=

30.352

10.94

j 5.760

35

0.415kV Cable to 302-DB-009-MOV


Size : 4Cx 50mm
R = (0.388 x168) / (1 x 1000)

0.065

X = ( 0.075 x168) / (1 x 1000)

0.013

Rpu = R x (Base MVA/(Base kV) )

34.767

Xpu = X x (Base MVA/(Base kV) )

6.720

34.767 +

ZC35=

35.410

10.94

j 6.720

36

0.415kV Cable to 302-DB-010-MOV


Size : 4Cx 50mm
R = (0.388 x192) / (1 x 1000)

0.074

X = ( 0.075 x192) / (1 x 1000)

0.014

Rpu = R x (Base MVA/(Base kV) )

39.734

Xpu = X x (Base MVA/(Base kV) )

7.680

39.734 +

ZC36=

40.469

10.94

j 7.680

37

0.415kV Cable to 102-MCC-003-MIX


Size : 4Cx 185mm
R = (0.102 x473) / (2 x 1000)

0.024

X = ( 0.072 x473) / (2 x 1000)

0.017

Rpu = R x (Base MVA/(Base kV) )

12.866

Xpu = X x (Base MVA/(Base kV) )

9.082

12.866 +

ZC37=

15.749

35.22

j 9.082

38

0.415kV Cable to 102-MCC-007-MIX


Size : 4Cx 120mm
R = (0.156 x473) / (2 x 1000)

0.037

X = ( 0.072 x473) / (2 x 1000)

0.017

Rpu = R x (Base MVA/(Base kV) )

19.678

Xpu = X x (Base MVA/(Base kV) )

9.082

19.678 +

ZC38=

21.673

24.78

j 9.082

39

0.415kV Cable to 104-MCC-003-MIX


Size : 4Cx 300mm
R = (0.066x275) / (2 x 1000)
X = ( 0.07 x275) / (2 x 1000)

=
=

0.009
0.010

Rpu = R x (Base MVA/(Base kV) )

4.840

Xpu = X x (Base MVA/(Base kV) )

5.134

4.840 +

ZC39=

7.056

46.68

j 5.134

40

0.415kV Cable to 104-MCC-007-MIX


Size : 4Cx 185mm
R = (0.102x300) / (1 x 1000)

0.031

X = ( 0.072 x300) / (1 x 1000)

0.022

Rpu = R x (Base MVA/(Base kV) )

16.321

Xpu = X x (Base MVA/(Base kV) )

11.521

16.321 +

ZC40=

19.977

35.22

j 11.521

41

0.415kV Cable to 912-SW3-002


Size : 4Cx 120mm
R = ( 0.156 x276) / (1 x 1000)
X = ( 0.072 x276) / (1 x 1000)

=
=

Rpu = R x (Base MVA/(Base kV) )

0.003
0.004
=

1.822

Sheet 62 of 97

Xpu = X x (Base MVA/(Base kV) )

1.822 +

ZC41=

2.361

2.982

52.35

j 2.361

42

0.415kV Cable to 415V LCS 302 DB (912-DB-002)


Size : 4Cx 10mm
R = ( 1.83 x54) / (1 x 1000)

0.099

X = ( 0.085 x54) / (1 x 1000)

0.005

Rpu = R x (Base MVA/(Base kV) )

52.707

Xpu = X x (Base MVA/(Base kV) )

2.448

52.707 +

ZC42=

52.764

2.66

j 2.448

43

0.415kV Cable to P-302-10A


Size : 3Cx 25mm
R = ( 0.728 x336) / (1 x 1000)
X = ( 0.081 x336) / (1 x 1000)

0.245

0.027

Rpu = R x (Base MVA/(Base kV) )

130.47

Xpu = X x (Base MVA/(Base kV) )

14.516

130.465 +

ZC43=

131.270

6.35

j 14.516

44

0.415kV Cable to P-302-10B


Size : 3Cx 25mm
R = ( 0.728 x336) / (1 x 1000)
X = ( 0.081 x336) / (1 x 1000)

0.245

0.027

Rpu = R x (Base MVA/(Base kV) )

130.47

Xpu = X x (Base MVA/(Base kV) )

14.516

130.465 +

ZC44=

131.270

6.35

j 14.516

45

0.415kV Cable to P-302-11


Size : 3Cx 10mm

ZC45=

R = ( 1.83 x308) / (1 x 1000)

0.615

X = ( 0.085 x308) / (1 x 1000)

0.029

Rpu = R x (Base MVA/(Base kV) )

327.955

Xpu = X x (Base MVA/(Base kV) )

15.233

327.955 +

328.309

j 15.233

Z1=ZS+ZTR+ZC1
ZS=
ZTR=
ZC1= 0.082
Z1=ZS+ZTR+ZC1=
Z1MAG= 3.144
1/Z1MAG= 0.318
1/Z1REAL= 0.008
1/Z1REAC= -0.318

Z2
33.122

Z2MAG= 33.204
1/Z2MAG= 0.030
1/Z2REAL= 0.030
1/Z2REAC= -0.002

j 2.333
4.03
-4.03

0.030
j -0.002

1/Z2=

Z3
Z3= 37.25
Z3MAG= 37.94
1/Z3MAG= 0.026
1/Z3REAL= 0.026
1/Z3REAC= -0.005

j 7.2
10.94
-10.94

0.026
j -0.005

1/Z3=

Z4=

0.082
j 3.143
88.50
-88.50

0.008
j -0.318

1/Z1=

Z2=

j 0.333
j 2.613
+
j 0.197

Z4
47.184

Sheet 63 of 97

2.66

Z4=
Z4MAG= 48.057
1/Z4MAG= 0.021
1/Z4REAL= 0.020
1/Z4REAC= -0.004

j 9.121
10.94
-10.94

0.020
j -0.004

1/Z4=

Z5
Z5= 52.150
Z5MAG= 53.116
1/Z5MAG= 0.019
1/Z5REAL= 0.018
1/Z5REAC= -0.004

-10.94

0.018
j -0.004

1/Z5=

Z6=

j 10.081
10.94

Z6
57.117

Z6MAG= 58.174
1/Z6MAG= 0.017
1/Z6REAL= 0.017
1/Z6REAC= -0.003

j 11.041
10.94
-10.94

0.017
j -0.003

1/Z6=

Z7
Z7= 60.842

11.761

Z7MAG= 61.968
1/Z7MAG= 0.016
1/Z7REAL= 0.016
1/Z7REAC= -0.003

10.94
-10.94

0.0158
j -0.0031

1/Z7=

Z8
Z8= 19.867

10.94
-10.94

0.0485
j -0.0094

1/Z8=

Z9=

Z9
24.833
10.94
-10.94

0.039
j -0.008

1/Z9=

Z10
34.767
10.94
-10.94

0.028
j -0.005

1/Z10=

Z11
34.767
10.94
-10.94

0.028
j -0.005

1/Z11=

Z12
Z12= 34.767

6.720

Z12MAG= 35.410
1/Z12MAG= 0.028
1/Z12REAL= 0.028
1/Z12REAC= -0.005

10.94
-10.94

0.028
j -0.005

1/Z12=

Z13
7.744

1/Z13=

Z14
Z14= 15.020

8.214

Z13MAG= 11.289
1/Z13MAG= 0.089
1/Z13REAL= 0.061
1/Z13REAC= -0.064

46.68
-46.68

0.061
j -0.064

8.448

Z14MAG= 17.233
1/Z14MAG= 0.058
1/Z14REAL= 0.051
1/Z14REAC= -0.028
1/Z14=

6.720

Z11MAG= 35.410
1/Z11MAG= 0.028
1/Z11REAL= 0.028
1/Z11REAC= -0.005

Z13=

6.72

Z10MAG= 35.410
1/Z10MAG= 0.028
1/Z10REAL= 0.028
1/Z10REAC= -0.005

Z11=

4.80

Z9MAG= 25.293
1/Z9MAG= 0.040
1/Z9REAL= 0.039
1/Z9REAC= -0.008

Z10=

3.840

Z8MAG= 20.235
1/Z8MAG= 0.049
1/Z8REAL= 0.049
1/Z8REAC= -0.009

29.36
-29.36

0.051

Sheet 64 of 97

1/Z14=

j -0.028
Z15

Z15= 4.84

46.68
-46.68

0.0972
j -0.1031

1/Z15=

Z16
Z16= 21.521

5.920

Z16MAG= 22.321
1/Z16MAG= 0.045
1/Z16REAL= 0.043
1/Z16REAC= -0.012

15.38
-15.38

0.043
j -0.012

1/Z16=

Z17=

5.134

Z15MAG= 7.056
1/Z15MAG= 0.142
1/Z15REAL= 0.097
1/Z15REAC= -0.103

Z17
97.849
10.887

Z17MAG= 98.453
1/Z17MAG= 0.010
1/Z17REAL= 0.010
1/Z17REAC= -0.001

6.35
-6.35

0.010
j -0.001

1/Z17=

Z18
Z18= 97.849

6.35
-6.35

0.010
j -0.001

1/Z18=

Z19=

Z19
123.207
18.540

Z19MAG= 124.594
1/Z19MAG= 0.008
1/Z19REAL= 0.008
1/Z19REAC= -0.001

8.56
-8.56

0.008
j -0.001

1/Z19=

Z20=

10.887

Z18MAG= 98.453
1/Z18MAG= 0.010
1/Z18REAL= 0.010
1/Z18REAC= -0.001

Z20
85.685
12.894

Z20MAG= 86.650
1/Z20MAG= 0.012
1/Z20REAL= 0.011
1/Z20REAC= -0.002

8.56
-8.56

0.011
j -0.002

1/Z20=

Z21
Z21= 119.593

1/Z21=

Z22
Z22= 119.593

6.35
-6.35

0.008
j -0.001

Z23
Z23= 300.626

6.35
-6.35

0.008
j -0.001

Z24
Z24= 1.822

2.66
-2.66

0.003
j 0.000

Z25
Z25= 33.122
Z25MAG= 33.204

2.361

Z24MAG= 2.982
1/Z24MAG= 0.335
1/Z24REAL= 0.205
1/Z24REAC= -0.265
1/Z24=

13.963

Z23MAG= 300.950
1/Z23MAG= 0.003
1/Z23REAL= 0.003
1/Z23REAC= 0.000
1/Z23=

13.306

Z22MAG= 120.331
1/Z22MAG= 0.008
1/Z22REAL= 0.008
1/Z22REAC= -0.001
1/Z22=

13.306

Z21MAG= 120.331
1/Z21MAG= 0.008
1/Z21REAL= 0.008
1/Z21REAC= -0.001

52.35
-52.35

0.205
j -0.265

2.333

j
4.03

Sheet 65 of 97

1/Z25MAG= 0.030
1/Z25REAL= 0.030
1/Z25REAC= -0.002

-4.03

0.030
j -0.002

1/Z25=

Z26
Z26= 97.715

10.887

Z26MAG= 98.319
1/Z26MAG= 0.010
1/Z26REAL= 0.010
1/Z26REAC= -0.001

6.36
-6.36

0.010
j -0.001

1/Z26=

Z27
Z27= 47.184

9.121

Z27MAG= 48.057
1/Z27MAG= 0.021
1/Z27REAL= 0.020
1/Z27REAC= -0.004

10.94
-10.94

0.020
j -0.004

1/Z27=

Z28
Z28= 52.150

10.081

Z28MAG= 53.116
1/Z28MAG= 0.019
1/Z28REAL= 0.018
1/Z28REAC= -0.004

10.94
-10.94

0.018
j -0.004

1/Z28=

Z29
Z29= 57.117

11.041

Z29MAG= 58.174
1/Z29MAG= 0.017
1/Z29REAL= 0.017
1/Z29REAC= -0.003

10.94
-10.94

0.017
j -0.003

1/Z29=

Z30
Z30= 62.084

12.001

Z30MAG= 63.233
1/Z30MAG= 0.016
1/Z30REAL= 0.016
1/Z30REAC= -0.003

10.94
-10.94

0.016
j -0.003

1/Z30=

Z31
Z31=

67.050
12.961

Z31MAG= 68.291
1/Z31MAG= 0.015
1/Z31REAL= 0.014
1/Z31REAC= -0.003

10.94
-10.94

0.014
j -0.003

1/Z31=

Z32
Z32=

19.867
10.94
-10.94

0.049
j -0.009

1/Z32=

Z33
Z33= 24.833

10.94
-10.94

0.039
j -0.008

1/Z33=

Z34
Z34= 29.800

5.760

Z34MAG= 30.352
1/Z34MAG= 0.033
1/Z34REAL= 0.032
1/Z34REAC= -0.006

10.94
-10.94

0.032
j -0.006

1/Z34=

Z35
34.767

Z35MAG= 35.410
1/Z35MAG= 0.028
1/Z35REAL= 0.028
1/Z35REAC= -0.005
1/Z35=

4.800

Z33MAG= 25.293
1/Z33MAG= 0.040
1/Z33REAL= 0.039
1/Z33REAC= -0.008

Z35=

3.840

Z32MAG= 20.235
1/Z32MAG= 0.049
1/Z32REAL= 0.049
1/Z32REAC= -0.009

6.720

j
10.94
-10.94

0.028
j -0.005

Sheet 66 of 97

Z36
Z36= 39.734

7.680

Z36MAG= 40.469
1/Z36MAG= 0.025
1/Z36REAL= 0.024
1/Z36REAC= -0.005

10.94
-10.94

0.024
j -0.005

1/Z36=

Z37
Z37= 12.866

9.082

Z37MAG= 15.749
1/Z37MAG= 0.063
1/Z37REAL= 0.052
1/Z37REAC= -0.037

35.22
-35.22

0.052
j -0.037

1/Z37=

Z38
Z38=

19.678
9.082

Z38MAG= 21.673
1/Z38MAG= 0.046
1/Z38REAL= 0.042
1/Z38REAC= -0.019

24.78
-24.78

0.042
j -0.019

1/Z38=

Z39
Z39= 4.840

5.134

Z39MAG= 7.056
1/Z39MAG= 0.142
1/Z39REAL= 0.097
1/Z39REAC= -0.103

46.68
-46.68

0.097
j -0.103

1/Z39=

Z40
Z40=

16.321
11.521

Z40MAG= 19.977
1/Z40MAG= 0.050
1/Z40REAL= 0.041
1/Z40REAC= -0.029

35.22
-35.22

0.041
j -0.029

1/Z40=

Z41
Z41=

1.822
2.361

Z41MAG= 2.982
1/Z41MAG= 0.335
1/Z41REAL= 0.205
1/Z41REAC= -0.265

52.35
-52.35

0.205
j -0.265

1/Z41=

Z42
Z42= 52.707

2.448

Z42MAG= 52.764
1/Z42MAG= 0.019
1/Z42REAL= 0.019
1/Z42REAC= -0.001

2.66
-2.66

0.019
j -0.001

1/Z42=

Z43
Z43= 130.465

14.516

Z43MAG= 131.270
1/Z43MAG= 0.008
1/Z43REAL= 0.008
1/Z43REAC= -0.001

6.35
-6.35

0.008
j -0.001

1/Z43=

Z44
Z44= 130.465

14.516

Z44MAG= 131.270
1/Z44MAG= 0.008
1/Z44REAL= 0.008
1/Z44REAC= -0.001

6.35
-6.35

0.008
j -0.001

1/Z44=

Z45
Z45= 327.955
Z45MAG= 328.309
1/Z45MAG= 0.003
1/Z45REAL= 0.003
1/Z45REAC= -0.0001

15.233

j
2.66
-2.66

0.003
j -0.0001
1.5937
j -1.36

1/Z45=
1/Zeq=
1/ZEQM = 2.0961
Zeq = 0.4771
Therefore, Maximum Fault level at F1

Base MVA

Sheet 67 of 97

Zeq

Maximum Fault level at F1 in KA

209.6

MVA

291.61

KA

Sheet 68 of 97

OBJECTIVE
The purpose of this document is to find the maximum Fault Level attained during a 3 phase Symmetrical fault, on different Buses. In order
to arrive at a more correct value, contribution of the Motors towards the fault ratings will also be considered.

REFERENCE DOCUMENT
Documents

Doc. No.

a) Overall Plant Electrical Key Single Line Diagram ( 33kV System)


b) Electrical Key Single Line Diagram

c) Electrical Design Basis

DH0008-ENG-E-DB-0001

d) Load List

DH0008-ENG-E-DC-0001

e) Specification for Transformer (Including Calculations)

DH0008-BE-E-SP-0006

NOTES
a) Base Voltage is 0.433kV and Base MVA is 100MVA throughout the system.
b) The impedance of busbars , circuit breakers , current transformers etc. which are negligibly small are not considered in this calculation.
c) Sub-transient reactance of low voltage Induction motor is considered to be 17%.
d) The short circuit current at the primary terminals (33kV) of the Transformers is 5.25KA for 3 sec as per 33KV fault current document.

BASIC DESIGN DATA

a.

System Data:

b.

c.

Source Voltage (Vs)

33

kV

Source Fault Current (IFS)

5.25

kA

Source Transformer (T1) Data ( 911-TR-002):


Primary Voltage

33

kV

Secondary Voltage

0.433

kV

Transformer capacity

2.5

Transformer Impedance

MVA
%

Cable data for Transformer


Cable between (911-TR-002) Transformer and 0.433KV Switchboard (911-SW3-002) Located in LPS302.
1CX630 mm 2,Cu,XLPE Insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

22

Cable Resistance

0.035

/Km, at 90C

Cable Reactance

0.084

/Km, at 90C

d.

Cable Data for DB :

Cable Between 911-SW3-001 Board and 912-SW3-001 DB

KV
Meters

4C x 400 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

253

Cable Resistance

0.054

/Km, at 90C

Cable Reactance

0.07

/Km, at 90C

kV
Meters

Cable Between 912-SW3-001 Board and (302-DB-004-MOV) DB


4C x50 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

300

Cable Resistance

0.388

/Km, at 90C

Cable Reactance

0.075

/Km, at 90C

kV
Meters

Cable Between 912-SW3-001 Board and 102-MCC-003-MIX DB


4C x 185 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

473

Cable Resistance

0.102

/Km, at 90C

Cable Reactance

0.072

/Km, at 90C

kV
Meters

Cable Between 912-SW3-001 Board and 102-MCC-007-MIX DB


4C x 120 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

473

Cable Resistance

0.156

/Km, at 90C

Cable Reactance

0.072

/Km, at 90C

kV
Meters

Cable Between 912-SW3-001 Board and 104-MCC-003-MIX DB


Cable Size & type

4C x300 mm 2, XLPE insulated

Sheet 69 of 97

No. of Cable Runs

Voltage

0.433

Cable length

275

Cable Resistance

0.066

/Km, at 90C

Cable Reactance

0.07

/Km, at 90C

kV
Meters

Cable Between 912-SW3-001 Board and 104-MCC-007-MIX DB


2

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

300

Cable Resistance

0.102

/Km, at 90C

Cable Reactance

0.072

/Km, at 90C

4C x 185 mm , XLPE insulated

kV
Meters

Cable Between 912-SW3-001 Board and P-920-02A (PRODUCT FEED PUMP) DB


2

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

252

Cable Resistance

0.728

/Km, at 90C

Cable Reactance

0.081

/Km, at 90C

3C x 25 mm , XLPE insulated

CALCULATION

A.

GENERAL

a)

Basic equation for short circuit calculation is =

kV
Meters

&

Where

Base MVA
Z p.u.
Short circuit MVA

Short Circuit MVA

Base MVA

IS

100

3 x Base kV

MVA

6.6kV Switchboard :

Base Voltage =
Zpu

Is

Fault MVA of source

Sheet 70 of 97

0.433

kV
Fault impedance per unit
Symmetrical short circuit current (kA)
VS X IFS X 1.732

b)

Machine Impedances are converted to 25MVA base per unit using the following equation :

Base MVA x p.u. impedanceat MachineMVA SystemkV


x
Machine MVA
Base kV

Per unit impedance =

B.

Fault at 0.415 KV DB : 911-SW3-001

a)

Source :
300

Fault MVA of source =


Source Impedance =
b)

Zs =

MVA

(= VS X IFS X 1.732)

0.333

(= Base MVA /Fault MVA)

Transformer:
Transformer rating

2.5

Transformer secondary No-load voltage =

MVA
0.433

KV

Impedance of Transformer T1 , at 0.433kV (Trafo No-load Voltage) =

0.06

p.u

Now, trafo impedance at Base MVA & 0.415 kV Bus Voltage =


= [ p.u. Trafo Impedance x [ (Trafo No-load Voltage/ Bus Voltage) ] x [ (Base MVA / Trafo MVA) ]
= 0.08 x (0.433/0.415) x (100 /3)
2.613 p.u
X t1

j 0.653
2.613 , 90

d)
1

Cable
0.433kVCable to (911-SW3-002) SWITCHBOARD
Size : 1Cx 630 mm
R = ( 0.035 x 22) / (5 x 1000)

X = ( 0.084 x 22) / (5 x 1000)

ZC2

0.0002
0.0004

Rpu = R x (Base MVA/(Base kV) )

0.0821

Xpu = X x (Base MVA/(Base kV) )

0.1971

0.2136

67.38

0.0205+j0.0493

0.433kV Cable to 912-SW3-001


Size : 4Cx 400 mm
R = ( 0.054 x253) / (4 x 1000)
X = ( 0.070 x253) / (4x 1000)

ZC2

=
=

0.003
0.004

Rpu = R x (Base MVA/(Base kV) )

Xpu = X x (Base MVA/(Base kV) )

0.455+j0.590

1.822
2.361
2.9825 52.35

0.433kV Cable to 302-DB-004-MOV


Size : 4Cx 50mm
R = (0.388 x 300) / (1 x 1000)
X = ( 0.075 x300) / (1 x 1000)

ZC2

=
=

0.116
0.023

Rpu = R x (Base MVA/(Base kV) )

62.084

Xpu = X x (Base MVA/(Base kV) )

12.001

= 15.521+j3.00

63.2329 10.94

0.433kV Cable to 102-MCC-003-MIX


Size : 4Cx 185mm
R = ( 0.102 x473) / (2 x 1000)
X = ( 0.072 x473) / (2 x 1000)

=
=

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
ZC2
5

12.866
9.082

15.7489 35.22

= 3.217+j2.271 =

=
=

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
ZC2

0.037
0.017
=
=

19.678
9.082

21.6727 24.78

= 4.919+j2.271 =

0.433kV Cable to 104-MCC-003-MIX


Size : 4Cx 300mm
R = ( 0.066 x275) / (2 x 1000)
X = ( 0.07 x275) / (2 x 1000)

=
=

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
ZC2
7

=
=

0.433kV Cable to 102-MCC-007-MIX


Size : 4Cx 120mm
R = ( 0.156 x473) / (2 x 1000)
X = ( 0.072x473) / (2 x 1000)

0.024
0.017

0.009
0.010
=
=

4.840
5.134
7.0557 46.68

= 1.210+j1.283 =

0.433kV Cable to 104-MCC-007-MIX


Size : 4Cx 185mm
R = ( 0.102 x300) / (1 x 1000)
X = ( 0.072 x300) / (1 x 1000)

=
=

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
ZC2

= 4.08+j2.88 =

0.031
0.022
=
=

16.321
11.521

19.9775 35.22

Sheet 71 of 97

0.433kV Cable to P-920-02A (PRODUCT FEED PUMP)


Size : 3Cx 25mm
R = (0.728 x252) / (1 x 1000)

0.183

X = ( 0.081 x252) / (1 x 1000)

0.020
=
=

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
ZC2

97.849
10.887

98.4527 6.35

= 24.462+j2.722 =
Z1=ZS+ZTR+ZC1+ZC2
ZS =

j 0.333
j 2.613

ZTR=
ZC1=

0.0821 +
j 0.1971

ZC2=

1.822
j 2.3615

1.9038
Z1=ZS+ZTR+ZC1+ZC2=
j 5.5046
5.8245
Z1MAG=
70.92
1/Z1MAG= 0.1717
-70.92
1/Z1REAL= 0.0561
1/Z1REAC= -0.1623
0.0561

1/Z1=

j -0.1623
Z2

Z2= 62.0836
Z2MAG= 63.2329
1/Z2MAG= 0.0158

j 12.0007
10.94
-10.94

1/Z2REAL= 0.0155
1/Z2REAC= -0.0030
0.0155

1/Z2=

j -0.0030
Z3

Z3= 12.8664
Z3MAG= 15.7489
1/Z3MAG= 0.0635

j 9.0821
35.22
-35.22

1/Z3REAL= 0.0519
1/Z3REAC= -0.0366
0.0519

1/Z3=

j -0.0366
Z4

Z4 =

19.6780

Z4MAG= 21.6727
1/Z4MAG= 0.0461

j 9.0821
24.78
-24.78

1/Z4REAL= 0.0419
1/Z4REAC= -0.0193
0.0419
j -0.0193

1/Z4=

Z5
Z5= 4.8403
Z5MAG= 7.0557
1/Z5MAG= 0.1417

j 5.1336
46.68
-46.68

1/Z5REAL= 0.0972
1/Z5REAC= -0.1031
0.0972

1/Z5=

j -0.1031
Z6

Z6 =

16.3210

Z6MAG= 19.9775
1/Z6MAG= 0.0501

j 11.5207
35.22
-35.22

1/Z6REAL= 0.0409
1/Z6REAC= -0.0289
0.0409
j -0.0289

1/Z6=

Z7
Z7= 97.8489
Z7MAG= 98.4527
1/Z7MAG= 0.0102

10.8870

j
6.35
-6.35

1/Z7REAL= 0.0101
1/Z7REAC= -0.0011
1/Z7=

0.0101
j -0.0011

1/Zeq=

0.3136
j -0.3543

1/ZEQM= 0.4732
Zeq = 2.1133
Therefore, Maximum Fault level at F1

Maximum Fault level at F1 in KA

Base MVA
Zeq

47.3

65.83

MVA
KA

Sheet 72 of 97

OBJECTIVE
The purpose of this document is to find the maximum Fault Level attained during a 3 phase Symmetrical fault, on different Buses. In order
to arrive at a more correct value, contribution of the Motors towards the fault ratings will also be considered.

REFERENCE DOCUMENT
Documents

Doc. No.

a) Overall Plant Electrical Key Single Line Diagram ( 33kV System)


b) Electrical Key Single Line Diagram

c) Electrical Design Basis

DH0008-ENG-E-DB-0001

d) Load List

DH0008-ENG-E-DC-0001

e) Specification for Transformer (Including Calculations)

DH0008-BE-E-SP-0006

NOTES
a) Base Voltage is 0.433kV and Base MVA is 25MVA throughout the system.
b) The impedance of busbars , circuit breakers , current transformers etc. which are negligibly small are not considered in this calculation.
c) Sub-transient reactance of low voltage Induction motor is considered to be 17%.
d) The short circuit current at the primary terminals (33kV) of the Transformers is 25KA for 3 sec as per Transformer Specification.

BASIC DESIGN DATA

a.

System Data:

b.

c.

Source Voltage (Vs)

33

kV

Source Fault Current (IFS)

25

kA

Source Transformer (T1) Data ( 911-TR-002):


Primary Voltage

33

kV

Secondary Voltage

0.433

kV

Transformer capacity

2.5

Transformer Impedance

MVA
%

Cable data for Transformer


Cable between (911-TR-002) Transformer and 0.433KV Switchboard (912-SW3-002) Located in LPS302.
1CX630 mm 2,Cu,XLPE Insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

22

Cable Resistance

0.035

/Km, at 90C

Cable Reactance

0.084

/Km, at 90C

d.

Cable Data for DB :

Cable Between 911-SW3-001 Board and 912-SW3-002

KV
Meters

4C x 120 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

276

Cable Resistance

0.156

/Km, at 90C

Cable Reactance

0.072

/Km, at 90C

kV
Meters

Cable Between 912-SW3-002 Board and 102-DB-002-TL (TANK FARM LIGHTING) DB


4C x 16 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

492

Meters

Cable Resistance

1.15

/Km, at 90C

Cable Reactance

0.081

/Km, at 90C

kV

Cable Between 912-SW3-002 Board and102-DB-006-TL (TANK FARM LIGHTING) DB


4C x 25 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

474

Cable Resistance

0.727

kV
Meters

Sheet 73 of 97

/Km, at 90C

Cable Reactance

/Km, at 90C

0.081

Cable Between 912-SW3-002 Board and 104-DB-002-TL(TANK FARM LIGHTING) DB


4C x25 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

300

Cable Resistance

0.727

/Km, at 90C

Cable Reactance

0.081

/Km, at 90C

kV
Meters

Cable Between 912-SW3-002 Board and 104-DB-006-TL (TANK FARM LIGHTING) DB


4C x 25 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

306

Cable Resistance

0.727

/Km, at 90C

Cable Reactance

0.081

/Km, at 90C

kV
Meters

Cable Between 913-SW3-002 Board and P-302-10A (SUMP PUMP) DB


2

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

336

Cable Resistance

0.728

/Km, at 90C

Cable Reactance

0.081

/Km, at 90C

3C x25 mm , XLPE insulated

kV
Meters

Cable Between 913-SW3-002 Board and P-302-10B (SUMP PUMP) DB


3C x 25 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

336

Cable Resistance

0.728

/Km, at 90C

Cable Reactance

0.081

/Km, at 90C

kV
Meters

Cable Between 913-SW3-002 Board and P-302-11 (SLOP PUMP) DB


3C x 10 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

336

Meters

Cable Resistance

1.83

/Km, at 90C

Cable Reactance

0.085

/Km, at 90C

CALCULATION

A.

GENERAL

a)

Basic equation for short circuit calculation is =

kV

&

Where

Base MVA
Z p.u.
Short circuit MVA

Short Circuit MVA

Base MVA

IS
25

3 x Base kV

MVA

6.6kV Switchboard :

Base Voltage =
Zpu

Is

Fault MVA of source

Sheet 74 of 97

0.433

kV
Fault impedance per unit
Symmetrical short circuit current (kA)
VS X IFS X 1.732

b)

Machine Impedances are converted to 25MVA base per unit using the following equation :

Base MVA x p.u. impedanceat MachineMVA SystemkV


x
Machine MVA
Base kV

Per unit impedance =

B.

Fault at 0.415 KV DB : 912-SW3-002

a)

Source :
1429

Fault MVA of source =


Source Impedance =
b)

Zs =

MVA

(= VS X IFS X 1.732)

0.017

(= Base MVA /Fault MVA)

Transformer:
Transformer rating

2.5

MVA

Transformer secondary No-load voltage =

0.433

KV

Impedance of Transformer T1 , at 0.433kV (Trafo No-load Voltage) =

0.06

p.u

Now, trafo impedance at Base MVA & 0.415 kV Bus Voltage =


= [ p.u. Trafo Impedance x [ (Trafo No-load Voltage/ Bus Voltage) ] x [ (Base MVA / Trafo MVA) ]
= 0.06 x (0.433/0.415) x (25 /2.5)
0.653 p.u
X t1

j 0.653
0.653 , 90

d)

Cable
0.433kVCable to 913-SW3-001 SWITCHBOARD
Size : 1Cx 630 mm
R = ( 0.035 x 22) / (5 x 1000)

X = ( 0.084 x 22) / (5 x 1000)

ZC2

0.0002
0.0004

Rpu = R x (Base MVA/(Base kV) )

0.0205

Xpu = X x (Base MVA/(Base kV) )

0.0493

0.0534

67.38

0.0205+j0.0493

Cable
1

0.433kV Cable to 912-SW3-002


Size : 4Cx 120 mm
R = ( 0.156 x276) / (1 x 1000)
X = ( 0.072 x276) / (1 x 1000)

ZC2
2

=
=

0.020

Rpu = R x (Base MVA/(Base kV) )

Xpu = X x (Base MVA/(Base kV) )

5.741+j2.650

5.741
2.650
6.3231 24.78

0.433kV Cable to 102-DB-002-TL


Size : 4Cx 16mm
R = ( 1.15 x 492) / (1 x 1000)

0.566

X = ( 0.081 x492) / (1 x 1000)

0.040

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
ZC2
3

0.043

75.444+j5.314

=
=

75.444
5.314

75.6313 4.03

0.433kV Cable to 102-DB-006-TL


Size : 4Cx 25mm
R = ( 0.727 x 474) / (1 x 1000)
X = ( 0.081 x474) / (1 x 1000)

=
=

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
ZC2
4

45.949+j5.120

ZC2

5.120
,

=
=

0.218
0.024
=
=

29.082
3.240

29.2617 6.36

29.082+j3.240 =

0.433kV Cable to 104-DB-006-TL


Size : 4Cx 25mm
R = ( 0.727 x 306) / (1 x 1000)
X = ( 0.081 x306) / (1 x 1000)

=
=

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
ZC2

29.663+j3.305

0.222
0.025
=
=

29.663
3.305

29.8469 6.36

0.433kV Cable to P-302-10A (SUMP PUMP)


Size : 3Cx25mm
R = (0.728 x 336) / (1 x 1000)
X = ( 0.081 x336) / (1 x 1000)

=
=

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
ZC2
7

45.949

0.433kV Cable to 104-DB-002-TL

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )

46.2334 6.36

Size : 4Cx 25mm


R = ( 0.727 x 300) / (1 x 1000)
X = ( 0.081 x300) / (1 x 1000)

0.345
0.038

= 32.616+j3.629

0.245
0.027
=
=

32.616
3.629

32.8176 6.35

0.433kV Cable to P-302-10B (SUMP PUMP)

Sheet 75 of 97

Size : 3Cx 25mm


R = ( 0.728 x 336) / (1 x 1000)
X = ( 0.081 x336) / (1 x 1000)

ZC2
8

0.245
0.027

Rpu = R x (Base MVA/(Base kV) )

32.616

Xpu = X x (Base MVA/(Base kV) )

3.629

32.8176 6.35

= 32.616+j3.629 =

0.433kV Cable to P-302-11 (SLOP PUMP)


Size : 3Cx10mm
R = ( 1.83 x336) / (1 x 1000)

0.615

X = ( 0.085 x336) / (1 x 1000)

0.029

ZC2

Rpu = R x (Base MVA/(Base kV) )

81.989

Xpu = X x (Base MVA/(Base kV) )

3.808

82.0772 2.66

= 3.679+j3.902 =
Z1=ZS+ZTR+ZC1+ZC2
ZS =

j 0.017

j 0.653
0.0205 +
j 0.0493

ZTR=
ZC1=

5.741
j 2.6498
5.7617
Z1=ZS+ZTR+ZC1+ZC2=
j 3.3697
Z1MAG= 6.6747
30.32
1/Z1MAG= 0.1498
-30.32
ZC2=

1/Z1REAL= 0.1293
1/Z1REAC= -0.0756
0.1293
j -0.0756

1/Z1=

Z2
Z2= 75.4444
Z2MAG= 75.6313
1/Z2MAG= 0.0132

j 5.3139
4.03
-4.03

1/Z2REAL= 0.0132
1/Z2REAC= -0.0009
0.0132

1/Z2=

j -0.0009
Z3

Z3 =

45.9491

Z3MAG= 46.2334
1/Z3MAG= 0.0216

j 5.1195
6.36
-6.36

1/Z3REAL= 0.0215
1/Z3REAC= -0.0024
0.0215

1/Z3=

j -0.0024
Z4

Z4 =

29.0817

Z4MAG= 29.2617
1/Z4MAG= 0.0342

j 3.2402
6.36
-6.36

1/Z4REAL= 0.0340
1/Z4REAC= -0.0038
0.0340
j -0.0038

1/Z4=

Z5
Z5 =

29.6633

Z5MAG= 29.8469
1/Z5MAG= 0.0335

j 3.3050
6.36
-6.36

1/Z5REAL= 0.0333
1/Z5REAC= -0.0037
0.0333
j -0.0037

1/Z5=

Z6
Z6= 32.6163
Z6MAG= 32.8176
1/Z6MAG= 0.0305

j 3.6290
6.35
-6.35

1/Z6REAL= 0.0303
1/Z6REAC= -0.0034
0.0303
j -0.0034

1/Z6=

Z7
Z7= 32.6163

3.6290

Z7MAG= 32.8176
1/Z7MAG= 0.0305

6.35
-6.35

1/Z7REAL= 0.0303
1/Z7REAC= -0.0034
0.0303
j -0.0034

1/Z7=

Z8
Z8= 81.9888
Z8MAG= 82.0772
1/Z8MAG= 0.0122

3.8082

j
2.66
-2.66

Sheet 76 of 97

1/Z8REAL= 0.0122
1/Z8REAC= -0.0006
0.0122

1/Z8=

j -0.0006

1/Zeq= 0.3040
Zeq = 3.2893
Therefore, Maximum Fault level at F1

Maximum Fault level at F1 in KA

Base MVA
Zeq

7.6

10.13

MVA
KA

Sheet 77 of 97

OBJECTIVE
The purpose of this document is to find the maximum Fault Level attained during a 3 phase Symmetrical fault, on different Buses. In order
to arrive at a more correct value, contribution of the Motors towards the fault ratings will also be considered.

REFERENCE DOCUMENT
Documents

Doc. No.

a) Overall Plant Electrical Key Single Line Diagram ( 33kV System)


b) Electrical Key Single Line Diagram

c) Electrical Design Basis

DH0008-ENG-E-DB-0001

d) Load List

DH0008-ENG-E-DC-0001

e) Specification for Transformer (Including Calculations)

DH0008-BE-E-SP-0006

NOTES
a) Base Voltage is 0.433kV and Base MVA is 100 MVA throughout the system.
b) The impedance of busbars , circuit breakers , current transformers etc. which are negligibly small are not considered in this calculation.
c) Sub-transient reactance of low voltage Induction motor is considered to be 17%.
d) The short circuit current at the primary terminals (33kV) of the Transformers is 5.25KA for 3 sec as per 33KV fault current rating document.

BASIC DESIGN DATA

a.

System Data:

b.

c.

Source Voltage (Vs)

33

kV

Source Fault Current (IFS)

5.25

kA

Source Transformer (T1) Data ( 911-TR-002):


Primary Voltage

33

kV

Secondary Voltage

0.433

kV

Transformer capacity

MVA

Transformer Impedance

Cable data for Transformer


Cable between (913-TR-002) Transformer and 0.433KV Switchboard (913-SW3-002) Located in LPS303.
1CX630 mm 2,Cu,XLPE Insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

22

Cable Resistance

0.035

/Km, at 90C

Cable Reactance

0.084

/Km, at 90C

KV
Meters

d.

Cable Data for DB :

Cable Between 913-SW3-002 Board and 415V LCS 301 DB (913-DB-001) DB

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

54

Cable Resistance

1.83

/Km, at 90C

Cable Reactance

0.085

/Km, at 90C

4C x 10 mm , XLPE insulated

kV
Meters

Cable Between 913-SW3-002 Board and WASTE WATER TREATMENT PLANT (WTP-DB-001) DB
4C x 25 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

426

Cable Resistance

0.727

/Km, at 90C

Cable Reactance

0.081

/Km, at 90C

kV
Meters

Cable Between 913-SW3-002 Board and AIR COMPRESSOR SHED (ACP-DB-001) DB


4C x 16 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

312

Meters

Cable Resistance

1.15

/Km, at 90C

Cable Reactance

0.081

/Km, at 90C

kV

Cable Between 913-SW3-002 Board and (303-DB-001-MOV) DB


2

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

204

Cable Resistance

0.388

/Km, at 90C

Cable Reactance

0.075

/Km, at 90C

4C x 50 mm , XLPE insulated

kV
Meters

Cable Between 913-SW3-002 Board and (303-DB-002-MOV) DB


Cable Size & type

4C x 50 mm 2, XLPE insulated

Sheet 78 of 97

10

11

No. of Cable Runs

Voltage

0.415

Cable length

222

Cable Resistance

0.388

/Km, at 90C

Cable Reactance

0.075

/Km, at 90C

kV
Meters

Cable Between 913-SW3-002 Board and (303-DB-003-MOV) DB


2

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

240

Cable Resistance

0.388

/Km, at 90C

Cable Reactance

0.075

/Km, at 90C

4C x 50 mm , XLPE insulated

kV
Meters

Cable Between 913-SW3-002 Board and (WTP-LCP-001) DB


2

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

426

Cable Resistance

0.195

/Km, at 90C

Cable Reactance

0.073

/Km, at 90C

4C x 95 mm , XLPE insulated

kV
Meters

Cable Between 913-SW3-002 Board and (HOH-LCP-001) DB


4C x 300 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

418

Cable Resistance

0.066

/Km, at 90C

Cable Reactance

0.07

/Km, at 90C

kV
Meters

Cable Between 913-SW3-002 Board and (105-MCC-003-MIX) DB


2

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

495

Meters

Cable Resistance

0.08

/Km, at 90C

Cable Reactance

0.071

/Km, at 90C

4C x 240 mm , XLPE insulated

kV

Cable Between 913-SW3-002 Board and (105-MCC-007A-MIX) DB


2

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

495

Meters

Cable Resistance

0.08

/Km, at 90C

Cable Reactance

0.071

/Km, at 90C

4C x 240 mm , XLPE insulated

kV

Cable Between 913-SW3-002 Board and (105-MCC-007B-MIX) DB


4C x 240 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

495

Meters

Cable Resistance

0.08

/Km, at 90C

Cable Reactance

0.071

/Km, at 90C

kV

Sheet 79 of 97

12

13

14

15

16

17

Cable Between 913-SW3-002 Board and HOH SYSTEM (990-DB-01A/B) DB


2

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

384

Cable Resistance

0.388

/Km, at 90C

Cable Reactance

0.075

/Km, at 90C

4C x 50 mm , XLPE insulated

kV
Meters

Cable Between 913-SW3-002 Board and 415V LCS DB 303 (E) (913-DB-001) DB
4C x10 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

54

Cable Resistance

1.83

/Km, at 90C

Cable Reactance

0.085

/Km, at 90C

kV
Meters

Cable Between 913-SW3-002 Board and OILY WATER PUMP(105-MCC-005-AUX) DB


4C x50 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

492

Cable Resistance

0.388

/Km, at 90C

Cable Reactance

0.075

/Km, at 90C

kV
Meters

Cable Between 913-SW3-002 Board and P-900-003 (SLOP PUMP) DB


2

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

400

Meters

Cable Resistance

1.15

/Km, at 90C

Cable Reactance

0.081

/Km, at 90C

3C x 16 mm , XLPE insulated

kV

Cable Between 913-SW3-002 Board and P-303-10A (SUMP PUMP) DB


3C x 25 mm 2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

336

Cable Resistance

0.728

/Km, at 90C

Cable Reactance

0.081

/Km, at 90C

kV
Meters

Cable Between 913-SW3-002 Board and P-303-10B (SUMP PUMP) DB


2

Cable Size & type

No. of Cable Runs

Voltage

0.415

Cable length

336

Cable Resistance

0.728

/Km, at 90C

Cable Reactance

0.081

/Km, at 90C

3C x 25 mm , XLPE insulated

CALCULATION

A.

GENERAL

a)

Basic equation for short circuit calculation is =

kV
Meters

&

Where

Base MVA
Z p.u.
Short circuit MVA

Short Circuit MVA

Base MVA

Base Voltage =
Zpu

Is

Fault MVA of source

Sheet 80 of 97

IS

100

0.433

3 x Base kV

MVA
kV

Fault impedance per unit


Symmetrical short circuit current (kA)
VS X IFS X 1.732

b)

Machine Impedances are converted to 100MVA base per unit using the following equation :

Per unit impedance =

Base MVA x p.u. impedanceat MachineMVA SystemkV


x
Machine MVA
Base kV

B.

Fault at 0.415 KV DB : 911-SW3-001

a)

Source :
Fault MVA of source =
Source Impedance Zs =

300
0.333

MVA

(= VS X IFS X 1.732)
(= Base MVA /Fault MVA)

PU
0.333

MVA

XS=
b)

, 90

Transformer:
Transformer rating

Transformer secondary No-load voltage =

0.433

KV

Impedance of Transformer T1 , at 0.433kV (Trafo No-load Voltage) =

0.07

p.u

Now, trafo impedance at Base MVA & 0.415 kV Bus Voltage =


= [ p.u. Trafo Impedance x [ (Trafo No-load Voltage/ Bus Voltage) ] x [ (Base MVA / Trafo MVA) ]
= 0.07 x (0.433/0.415) x (100 /3)
j
XTR=
d)
1

2.540

, 90

Cable
0.433kVCable to 913-SW3-001 SWITCHBOARD
Size : 1Cx 630 mm
R = ( 0.035 x 22) / (5 x 1000)

X = ( 0.084 x 22) / (5 x 1000)

ZC1=

0.0002
0.0004

Rpu = R x (Base MVA/(Base kV) )

0.082

Xpu = X x (Base MVA/(Base kV) )


0.082 +
j 0.197

0.197

0.214

67.38

0.433kV Cable to 913-DB-001


Size : 4Cx 10 mm
R = ( 1.83 x54) / (1 x 1000)

0.099

X = ( 0.085 x54) / (1 x 1000)

0.005

Rpu = R x (Base MVA/(Base kV) )

52.707

Xpu = X x (Base MVA/(Base kV) )

2.448

52.707 +

ZC2=

52.764

2.66

j 2.448

0.433kV Cable to WTP-DB-001


Size : 4Cx 25 mm
R = ( 0.727 x426) / (1 x 1000)
X = ( 0.081 x426) / (1 x 1000)

ZC3=

ZC4=

165.184

18.404

166.206

6.36

0.433kV Cable to ACP-DB-001


Size : 4Cx 16mm
R = ( 1.15 x 312) / (1 x 1000)

0.359

X = ( 0.081 x312) / (1 x 1000)

0.025

Rpu = R x (Base MVA/(Base kV) )

191.371

Xpu = X x (Base MVA/(Base kV) )


191.371 +
j 13.479

13.479

191.845

4.03

0.433kV Cable to 303-DB-001-MOV


=
=

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
42.217 +
j 8.160

0.079
0.015
=
=

42.217
8.160

42.998

10.94

0.433kV Cable to 303-DB-002-MOV


=
=

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
45.942 +
j 8.881

0.086
0.017
=
=

45.942
8.881

46.792

10.94

0.433kV Cable to 303-DB-003-MOV


Size : 4Cx 50mm
R = ( 0.388 x 240) / (1 x 1000)
X = ( 0.075 x240) / (1 x 1000)

ZC7=

0.035

Xpu = X x (Base MVA/(Base kV) )


165.184 +
j 18.404

Size : 4Cx 50mm


R = ( 0.388 x 222) / (1 x 1000)
X = ( 0.075 x222) / (1 x 1000)

ZC6=

0.310

Rpu = R x (Base MVA/(Base kV) )

Size : 4Cx 50mm


R = ( 0.388 x 204) / (1 x 1000)
X = ( 0.075 x204) / (1 x 1000)

ZC5=

=
=

=
=

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
49.667 +
j 9.601

0.093
0.018
=
=

49.667
9.601

50.586

0.433kV Cable to WTP-LCP-001


Sheet 81 of 97

10.94

Size : 4Cx 95mm


R = ( 0.195 x 426) / (1 x 1000)
X = ( 0.073 x426) / (1 x 1000)

ZC8=

=
=

Rpu = R x (Base MVA/(Base kV) )

44.307

Xpu = X x (Base MVA/(Base kV) )


44.307 +
j 16.587

16.587

X = ( 0.07 x418) / (1 x 1000)

10

ZC10=

11

ZC11=

12

47.310

20.52

0.433kV Cable to HOH-LCP-001


Size : 4Cx300mm
R = ( 0.066 x418) / (1 x 1000)

ZC9=

0.083
0.031

=
=

0.028
0.029

Rpu = R x (Base MVA/(Base kV) )

14.714

Xpu = X x (Base MVA/(Base kV) )


14.714 +
j 15.606

15.606

21.449

46.68

0.433kV Cable to 105-MCC-003-MIX


Size : 4Cx 240mm
R = ( 0.08 x495) / (3 x 1000)

0.013

X = ( 0.071 x495) / (3 x 1000)

0.012

Rpu = R x (Base MVA/(Base kV) )

7.040

Xpu = X x (Base MVA/(Base kV) )


7.040 +
j 6.248

6.248

9.413

41.59

0.433kV Cable to 105-MCC-007A-MIX


Size : 4Cx 240mm
R = ( 0.08 x495) / (3 x 1000)

0.013

X = ( 0.071 x495) / (3 x 1000)

0.012

Rpu = R x (Base MVA/(Base kV) )

7.040

Xpu = X x (Base MVA/(Base kV) )


7.040 +
j 6.248

6.248

9.413

41.59

0.433kV Cable to 105-MCC-007B-MIX


Size : 4Cx 240mm

ZC12=

13

R = ( 0.08 x495) / (3 x 1000)

0.013

X = ( 0.071 x495) / (3 x 1000)

0.012

Rpu = R x (Base MVA/(Base kV) )

7.040

Xpu = X x (Base MVA/(Base kV) )


7.040 +
j 6.248

6.248

X = ( 0.075 x384) / (1 x 1000)

=
=

Rpu = R x (Base MVA/(Base kV) )

14

Xpu = X x (Base MVA/(Base kV) )


79.467 +
j 15.361

15

16

17

18

=
=

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
101.817 +
j 19.681

0.029
=
=

79.467
15.361

80.938

10.94

0.099
0.005
=

52.707

2.448

52.764

2.66

0.191
0.037
=
=

101.817
19.681

103.702

10.94

0.433kV Cable to P-900-03


=
=

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
245.348 +
j 17.281

0.460
0.032
=
=

245.348
17.281

245.956

4.03

0.433kV Cable to P-303-10A (SUMP PUMP)


Size : 3Cx 25mm
R = ( 0.728 x336) / (1 x 1000)
X = ( 0.081 x336) / (1 x 1000)

ZC17=

0.149

0.433kV Cable to 105-MCC-005-AUX

Size : 3Cx 16mm


R = ( 1.15 x400) / (1 x 1000)
X = ( 0.081x400) / (1 x 1000)

ZC16=

=
=

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
52.707 +
j 2.448

Size : 4CX50mm
R = ( 0.388 x492) / (1 x 1000)
X = ( 0.075 x492) / (1 x 1000)

ZC15=

0.433kV Cable to 913-DB-002


Size : 4Cx 10mm
R = ( 1.83 x54) / (1 x 1000)
X = ( 0.085 x54) / (1 x 1000)

ZC14=

41.59

0.433kV Cable to 990-DB-01A/B


Size : 4Cx 50mm
R = ( 0.388 x384) / (1 x 1000)

ZC13=

9.413

=
=

Rpu = R x (Base MVA/(Base kV) )


Xpu = X x (Base MVA/(Base kV) )
130.465 +
j 14.516

0.245
0.027
=
=

130.465
14.516

131.270

0.433kV Cable to P-303-10B (SUMP PUMP)

Sheet 82 of 97

6.35

Size : 3Cx 25mm


R = ( 0.728 x336) / (1 x 1000)
X = ( 0.081 x336) / (1 x 1000)

ZC18=

=
=

0.245
0.027

Rpu = R x (Base MVA/(Base kV) )

130.465

Xpu = X x (Base MVA/(Base kV) )


130.465 +
j 14.516

14.516

Z1=ZS+ZTR+ZC1
ZS =

131.270

j 0.333
j 2.540
+

ZTR=
ZC1= 0.0821

j 0.1971
0.0821
j 3.0705
Z1MAG= 3.0716
88.47
1/Z1MAG= 0.3256
-88.47

Z1=ZS+ZTR+ZC1=

1/Z1REAL= 0.0087
1/Z1REAC= -0.3254
0.0087
j -0.3254

1/Z1=

Z2
Z2 =

52.7071
j 2.4481
2.66

Z2MAG= 52.7639
1/Z2MAG= 0.0190

-2.66

1/Z2REAL= 0.0189
1/Z2REAC= -0.0009
0.0189
j -0.0009

1/Z2=

Z3
Z3 =

165.1841

Z3MAG= 166.2062
1/Z3MAG= 0.0060

j 18.4043
6.36
-6.36

1/Z3REAL= 0.0060
1/Z3REAC= -0.0007
0.0060
j -0.0007

1/Z3=

Z4
Z4 =

191.3712

Z4MAG= 191.8453
1/Z4MAG= 0.0052

j 13.4792
4.03
-4.03

1/Z4REAL= 0.0052
1/Z4REAC= -0.0004
0.0052

1/Z4=

j -0.0004
Z5

Z5= 42.2169
Z5MAG= 42.9983
1/Z5MAG= 0.0233

j 8.1605
10.94
-10.94

1/Z5REAL= 0.0228
1/Z5REAC= -0.0044
0.0228
j -0.0044

1/Z5=

Z6
Z6 =

45.9419

Z6MAG= 46.7923
1/Z6MAG= 0.0214

j 8.8805
10.94
-10.94

1/Z6REAL= 0.0210
1/Z6REAC= -0.0041
0.0210
j -0.0041

1/Z6=

Z7
Z7= 49.6669

9.6006

Z7MAG= 50.5863
1/Z7MAG= 0.0198

10.94
-10.94

1/Z7REAL= 0.0194
1/Z7REAC= -0.0038
0.0194
j -0.0038

1/Z7=

Z8
Z8= 44.3066

16.5866

Z8MAG= 47.3095
1/Z8MAG= 0.0211

20.52
-20.52

1/Z8REAL= 0.0198
1/Z8REAC= -0.0074
0.0198
j -0.0074

1/Z8=

Z9
Z9= 14.7145
Z9MAG= 21.4493
1/Z9MAG= 0.0466

15.6062

j
46.68
-46.68

1/Z9REAL= 0.0320
1/Z9REAC= -0.0339

Sheet 83 of 97

6.35

0.0320

1/Z9=

j -0.0339
Z10

Z10= 7.0404

6.2484

Z10MAG= 9.4133
1/Z10MAG= 0.1062

41.59
-41.59

1/Z10REAL= 0.0795
1/Z10REAC= -0.0705
0.0795
j -0.0705

1/Z10=

Z11
Z11=

7.0404
6.2484

Z11MAG= 9.4133
1/Z11MAG= 0.1062

41.59
-41.59

1/Z11REAL= 0.0795
1/Z11REAC= -0.0705
0.0795
j -0.0705

1/Z11=

Z12
Z12=

79.4671
6.2484

Z12MAG= 79.7123
1/Z12MAG= 0.0125

4.50
-4.50

1/Z12REAL= 0.0125
1/Z12REAC= -0.0010
0.0125
j -0.0010

1/Z12=

Z13
Z13=

79.4671
15.3609

Z13MAG= 80.9381
1/Z13MAG= 0.0124

10.94
-10.94

1/Z13REAL= 0.0121
1/Z13REAC= -0.0023
0.0121
j -0.0023

1/Z13=

Z14
Z14=

52.7071
2.4481

Z14MAG= 52.7639
1/Z14MAG= 0.0190

2.66
-2.66

1/Z14REAL= 0.0189
1/Z14REAC= -0.0009
0.0189

1/Z14=

j -0.0009
Z15

Z15= 101.8172

19.6812

Z15MAG= 103.7019
1/Z15MAG= 0.0096

10.94
-10.94

1/Z15REAL= 0.0095
1/Z15REAC= -0.0018
0.0095
j -0.0018

1/Z15=

Z16
Z16=

245.3477
17.2810

Z16MAG= 245.9556
1/Z16MAG= 0.0041

4.03
-4.03

1/Z16REAL= 0.0041
1/Z16REAC= -0.0003
0.0041
j -0.0003

1/Z16=

Z17
Z17= 130.4653

14.5161

Z17MAG= 131.2703
1/Z17MAG= 0.0076

6.35
-6.35

1/Z17REAL= 0.0076
1/Z17REAC= -0.0008
0.0076
j -0.0008

1/Z17=

Z18
Z18= 130.4653

14.5161

Z18MAG= 131.2703
1/Z18MAG= 0.0076

6.35
-6.35

1/Z18REAL= 0.0076
1/Z18REAC= -0.0008
1/Z18=

0.0076
j -0.0008

1/ZEQ=

0.3850
j -0.530

1/ZEQMAG=

0.655
1.527

ZEQMAG=
Therefore, Maximum Fault level at F1

Base MVA
Zeq

Sheet 84 of 97

Maximum Fault level at F1 in KA

65.5

91.13

MVA
KA

Sheet 85 of 97

OBJECTIVE
The purpose of this document is to find the maximum Fault Level attained during a 3 phase Symmetrical fault, on different Buses. In order to
arrive at a more correct value, contribution of the Motors towards the fault ratings will also be considered.

REFERENCE DOCUMENT
Documents

Doc. No.

a) Overall Plant Electrical Key Single Line Diagram ( 33kV System)


b) Electrical Key Single Line Diagram

c) Electrical Design Basis

DH0008-ENG-E-DB-0001

d) Load List

DH0008-ENG-E-DC-0001

e) Specification for Transformer (Including Calculations)

DH0008-BE-E-SP-0006

NOTES
a) Base Voltage is 0.433kV and Base MVA is 100MVA throughout the system.
b) The impedance of busbars , circuit breakers , current transformers etc. which are negligibly small are not considered in this calculation.
c) Sub-transient reactance of low voltage Induction motor is considered to be 17%.
d) The short circuit current at the primary terminals (33kV) of the Transformers is 5.25KA for 3 sec as per 33KV Fault current document.

BASIC DESIGN DATA

a.

System Data:

b.

c.

Source Voltage (Vs)

33

kV

Source Fault Current (IFS)

5.25

kA

Source Transformer (T1) Data ( 914-TR-001):


Primary Voltage

33

kV

Secondary Voltage

0.433

kV

Transformer capacity

MVA

Transformer Impedance

Cable data for Transformer


Cable between (914-TR-001) Transformer and 0.433KV Switchboard (914-SW3-001) Located in Jetty Compact Substation.
1CX630 mm2,Cu,XLPE Insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

11

Cable Resistance

0.035

/Km, at 90C

Cable Reactance

0.084

/Km, at 90C

d.

Cable Data for DB :

Cable Between 914-SW3-001 Board and 600-SSB-001 DB

KV
Meters

4C x 400 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

kV

Cable length

1188

Meters

Cable Resistance

0.054

/Km, at 90C

Cable Reactance

0.07

/Km, at 90C

Cable Between 914-SW3-001 Board and 600-SSB-002 DB


4C x 185 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

kV

Cable length

1296

Meters

Cable Resistance

0.102

/Km, at 90C

Cable Reactance

0.072

/Km, at 90C

Cable Between 914-SW3-001 Board and FW-910-DB-01-A(FIRE WATER PUMP HOUSE) DB


Cable Size & type

No. of Cable Runs

4C x 10 mm2, XLPE insulated


1

Sheet 86 of 97

Voltage

0.433

Cable length

50

kV

Cable Resistance

1.83

/Km, at 90C

Cable Reactance

0.085

/Km, at 90C

Meters

Cable Between 914-SW3-001 Board and 600-DB-003-SL(OUTDOOR LIGHTING) DB


4C x6 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

60

Cable Resistance

3.08

/Km, at 90C

Cable Reactance

0.088

/Km, at 90C

kV
Meters

Cable Between 914-SW3-001 Board and 600-DB-SH-001 DB


4C x10 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

0.433

Cable length

250

Meters

Cable Resistance

1.83

/Km, at 90C

Cable Reactance

0.085

/Km, at 90C

CALCULATION

A.

GENERAL

a)

Basic equation for short circuit calculation is =

kV

Short Circuit MVA


&

Where

Base MVA

IS
=

Base Voltage =
Zpu

Is

Fault MVA of source

Sheet 87 of 97

Base MVA
Z p.u.

Short circuit MVA

100
0.433

3MVAx Base kV
kV
Fault impedance per unit
Symmetrical short circuit current (kA)
VS X IFS X 1.732

b)

Machine Impedances are converted to 100MVA base per unit using the following equation :

Base MVA x p.u. impedanceat MachineMVA SystemkV


x

Machine MVA
Base kV

Per unit impedance =

B.

Fault at 0.433 KV DB : 914-SW3-001

a)

Source :
Fault MVA of source =
Source Impedance Zs =

300
0.333

MVA

(= VS X IFS X 1.732)
(= Base MVA /Fault MVA)

PU
0.333

MVA

XS=
b)

, 90

Transformer:
Transformer rating

Transformer secondary No-load voltage =

0.433

KV
0.05

Impedance of Transformer T1 , at 0.433kV (Trafo No-load Voltage) =

p.u

Now, trafo impedance at Base MVA & 0.415 kV Bus Voltage =


= [ p.u. Trafo Impedance x [ (Trafo No-load Voltage/ Bus Voltage) ] x [ (Base MVA / Trafo MVA) ]
= 0.05 x (0.433/0.415) x (100 /1)
j
XTR=
d)
1

5.443

, 90

Cable
0.433kVCable to 914-SW3-001 SWITCHBOARD
Size : 1Cx 630 mm
R = ( 0.035 x 11) / (2 x 1000)

X = ( 0.084 x 11) / (2 x 1000)

0.0005

Rpu = R x (Base MVA/(Base kV) )

0.103

Xpu = X x (Base MVA/(Base kV) )

0.246

0.103 +
j 0.246

ZC1=

0.0002

0.267

67.38

0.433kV Cable to 600-SSB-001 DB


Size : 4Cx 400 mm
R = ( 0.054 x1188) / (3 x 1000)
X = ( 0.07 x188) / (3 x 1000)

0.021
0.028

Rpu = R x (Base MVA/(Base kV) )

11.405

Xpu = X x (Base MVA/(Base kV) )

14.785

11.405 +
j 14.785

ZC1=

=
=

18.673

52.35

0.433kV Cable to 600-SSB-002 DB


Size : 4Cx 185mm
R = ( 0.102 x 1296) / (2 x 1000)

X = ( 0.072 x1296) / (2 x 1000)

0.066
0.047

Rpu = R x (Base MVA/(Base kV) )

35.253

Xpu = X x (Base MVA/(Base kV) )

24.885

35.253 +
j 24.885

ZC1=

43.151

35.22

0.433kV Cable to FS-910-DB-01-A (FIRE WATER PUMP STATION)


Size : 4Cx 10mm
R = ( 1.83 x 50) / (1 x 1000)

0.092

X = ( 0.085 x50) / (1 x 1000)

0.004

Rpu = R x (Base MVA/(Base kV) )

48.803

Xpu = X x (Base MVA/(Base kV) )

2.267

48.803 +
j 2.267

48.855

ZC1=

2.66

0.433kV Cable to 600-DB-003-SL (OUTDOOR LIGHTING)


Size : 4Cx 6mm
R = ( 3.08 x 60) / (1 x 1000)

0.185

X = ( 0.088 x60) / (1 x 1000)

0.005

Rpu = R x (Base MVA/(Base kV) )

98.566

Xpu = X x (Base MVA/(Base kV) )

2.816

98.566 +
j 2.816

98.606

ZC1=

0.433kV Cable to 600-DB-SH-001 (SECURITY HUT)


Size : 4Cx 10mm
R = ( 1.83 x250) / (1 x 1000)

0.458

X = ( 0.085 x250) / (1 x 1000)

0.021

Sheet 88 of 97

1.64

ZC1=

Rpu = R x (Base MVA/(Base kV) )

244.014

Xpu = X x (Base MVA/(Base kV) )

11.334

244.014 +
j 11.334

244.277

Z1=ZS+ZTR+ZC1
ZS=

2.66

j 0.333
j 5.443

ZTR=
ZC1= 0.1027

+
j 0.2464

Z1=ZS+ZTR+ZC1=
Z1MAG= 6.0237
1/Z1MAG= 0.1660

0.1027
j 6.0228
89.02
-89.02

1/Z1REAL= 0.0028
1/Z1REAC= -0.1660
0.0028

1/Z1=

j -0.1660
Z2

Z2=

11.4055
j 14.7849
52.35

Z2MAG= 18.6729
1/Z2MAG= 0.0536

-52.35

1/Z2REAL= 0.0327
1/Z2REAC= -0.0424
0.0327

1/Z2=

j -0.0424
Z3

Z3=

35.2533
j 14.7849
22.75

Z3MAG= 38.2281
1/Z3MAG= 0.0262

-22.75

1/Z3REAL= 0.0241
1/Z3REAC= -0.0101
0.0241

1/Z3=

j -0.0101
Z4

Z4=

48.8029
j 2.2668
2.66

Z4MAG= 48.8555
1/Z4MAG= 0.0205

-2.66

1/Z4REAL= 0.0204
1/Z4REAC= -0.0009
0.0204

1/Z4=

j -0.0009
Z5

Z5=

98.5658
j 2.8162
1.64

Z5MAG= 98.6060
1/Z5MAG= 0.0101

-1.64

1/Z5REAL= 0.0101
1/Z5REAC= -0.0003
0.0101

1/Z5=

j -0.0003
Z6

Z6=

244.0143

Z6MAG= 244.2774
1/Z6MAG= 0.0041

j 11.3340
2.66
-2.66

1/Z6REAL= 0.0041
1/Z6REAC= -0.0002
0.0041

1/Z6=

1/Zeq=

j -0.0002
0.0943
j -0.2199

1/ZEQM 0.2393
Zeq = 4.1786
Therefore, Maximum Fault level at F1

Maximum Fault level at F1 in KA

Base MVA
Zeq

23.9

33.29

MVA
KA

Sheet 89 of 97

OBJECTIVE
The purpose of this document is to find the maximum Fault Level attained during a 3 phase Symmetrical fault, on different Buses. In order to
arrive at a more correct value, contribution of the Motors towards the fault ratings will also be considered.

REFERENCE DOCUMENT
Documents

Doc. No.

a) Overall Plant Electrical Key Single Line Diagram ( 33kV System)


b) Electrical Key Single Line Diagram

c) Electrical Design Basis

DH0008-ENG-E-DB-0001

d) Load List

DH0008-ENG-E-DC-0001

e) Specification for Transformer (Including Calculations)

DH0008-BE-E-SP-0006

NOTES
a) Base Voltage is 6.6kV and Base MVA is 15MVA throughout the system.
b) The impedance of busbars , circuit breakers , current transformers etc. which are negligibly small are not considered in this calculation.
c) Sub-transient reactance of high voltage Induction motor is considered to be 17%.
d) The short circuit current at the primary terminals (33kV) of the Transformers is 8.6KA for 1 sec as per SLEI Information.

BASIC DESIGN DATA

a.

System Data ( Details taken from SLEI):

b.

c.

Source Voltage (Vs)

33

kV

Source Fault Current (IFS)

8.6

kA

Source Transformer (T1) Data ( Details taken from SLEI):


Primary Voltage

33

kV

Secondary Voltage

6.9

kV

Transformer capacity

15

MVA

Transformer Impedance

10

Cable Data for HT Motors (075-PU-0007, 0008, 0009, 0010, 028-PU-1014B, 2014B) :
Cable Between 6.6kV Switch Board to HV Motor
3C x 95 mm2, XLPE insulated

Cable Size & type

No. of Cable Runs

Voltage

6.6

kV

Cable length

200

Meters

Cable Resistance

0.41

/Km, at 90C

Cable Reactance

0.0724

/Km, at 90C

DOC NO:
ANEWA ENGINEERING
PVT. LTD.

SHORT CIRCUIT
CALCULATIONS

Sheet 90 of 97

REV
R00

SINGLE LINE DIAGRAM

~ 33 kV Switchboard
T1
15 MVA
33/ 6.9 KV
Z= 10%

6.6kV Switchboard :

F1
C1

C1

C1

C1

C1

C1
F3

F2

M1
6

M2

M3

M5

M4

M6

IMPEDANCE DIAGRAM
33 kV Switchboard

ZT1

6.6kV Switchboard :

ZC1

ZC1

ZC1

ZC1

ZC1
ZC1

Zm1

Zm3

Zm2

CALCULATION

A.

GENERAL

a)

Basic equation for short circuit calculation is =

Zm4

Zm5

Zm6

&

Where

Base MVA

15

MVA

Base Voltage =

6.6

kV
Fault impedance per unit

Zpu

Is

Symmetrical short circuit current (kA)

VS X IFS X 1.732

Fault MVA of source

DOC NO:
ANEWA ENGINEERING
PVT. LTD.

SHORT CIRCUIT
CALCULATIONS

Sheet 91 of 97

REV
R00

b)

Machine Impedances are converted to 15MVA base per unit using the following equation :

Per unit impedance =

B.

Fault (F1) at 6.6kV Switchboard : 084-SB-0302

a)

Source :
492

Fault MVA of source =


Source Impedance =
b)

Zs =

MVA

(= VS X IFS X 1.732)

0.031

(= Base MVA /Fault MVA)

Transformer:
Transformer rating

15

MVA

Transformer secondary No-load voltage =

6.9

KV

Impedance of Transformer T1 , at 6.9kV (Trafo No-load Voltage) =

0.1

p.u

Now, trafo impedance at Base MVA & 6.6 kV Bus Voltage =


= [ p.u. Trafo Impedance x [ (Trafo No-load Voltage/ Bus Voltage) ] x [ (Base MVA / Trafo MVA) ]
= 0.1 x (6.9/6.6) x (15 /15)
=

0.109

X t1

p.u

j 0.109
, 90

c)

=
HV Motors

0.109

i)

525KW rated Motor (075-PU-0007, 0008, 0009, 0010)

R00

Motor rating = 525 KW =

656

KVA

Sub-transient reactance of HV motor = 17 %


Xm1 = Xm2 = Xm3 = Xm4 =

Xd"(p.u.) x (Base MVA x 1000/ Motor kVA) x [ (Trafo No-load Voltage/ Bus Voltage) ]
=

=
ii)

0.17 x (15*1000/656) x (6.9/6.6)


j 4.248

4.248

, 90

500KW rated Motor ( 028-PU-1014B, 2014B)


Motor rating = 500 KW =

625

KVA

Sub-transient reactance of HV motor = 17 %


Xm5 = Xm6 =

Xd"(p.u.) x (Base MVA x 1000/ Motor kVA) x [ (Trafo No-load Voltage/ Bus Voltage) ]
= 0.17 x (15*1000/625) x (6.9/6.6)
4.459
j4.459
=

=
d)

, 90

Cable
i)

6.6kVCable to HV Motors
Size : 3Cx 95 mm
R = ( 0.41 x 200) / (1 x 1000)

X = ( 0.0724 x 200) / (1 x 1000)

ZC1

0.082
=

0.014

Rpu = R x (Base MVA/(Base kV) )

0.028

Xpu = X x (Base MVA/(Base kV) )

0.005

0.028 + J 0.005

0.0287

, 10.12

10.014

DOC NO:
ANEWA ENGINEERING
PVT. LTD.

SHORT CIRCUIT
CALCULATIONS

Sheet 92 of 97

REV
R00

ZS = j 0.031
0.14
Zt1 = j 0.109
6.6kV Switchboard :

0.0287
, 10.1

0.0287
, 10.1

Zlm1 = j4.248

Zlm2 = j4.248

0.0287
, 10.1

0.0287
, 10.1

Zlm3 = j4.248

Zlm4 = j4.248

0.0287
, 10.1

Zlm5 = j4.459

0.0287
, 10.1

Zlm6 = j4.459

R00
ZS = j 0.031

Zt1 = j 0.109
6.6kV Switchboard :

R00
Z2 = 0.028
+ j4.253

Z3 = 0.0287
+ j4.253

Z5 = 0.0287
+ j4.253

Z4 = 0.0287
+ j4.253

Z6 = 0.0287
+ j4.464

Z7 = 0.0287
+ j4.464

6.6kV Switchboard :
ZS + Zt1 = Z1

Z1= j0.14

Z2 = 0.028

Z3 = 0.028

+ j4.253

+ j4.253

Z4 = 0.0287
+ j4.253

Z5 = 0.028

Z6 = 0.0287

Z7 = 0.0287

+ j4.253

+ j4.464

+ j4.464

Zeq = 0.1315
Therefore, Maximum Fault level at F1

Maximum Fault level at F1 in KA

a)

Base MVA
Zeq

114.1

114.1
6.6x1.732

MVA

9.98

KA

Cable
i)

6.6kVCable to HV Motors
Size : 3Cx 95 mm
R = ( 0.41 x 200) / (1 x 1000)
X = ( 0.0724 x 200) / (1 x 1000)

0.082
=

0.014

DOC NO:
ANEWA ENGINEERING
PVT. LTD.

SHORT CIRCUIT
CALCULATIONS

Sheet 93 of 97

168108-028-E-DCL-4-001

REV
R00

ZC1

Rpu = R x (Base MVA/(Base kV) )

0.0282

Xpu = X x (Base MVA/(Base kV) )

0.0050

0.028 + J 0.005

0.029

b)

HV Motors

i)

525KW rated Motor (075-PU-0007, 0008, 0009, 0010)

, 12.8

R00

Motor rating = 525 KW =

656

KVA

Sub-transient reactance of HV motor = 17 %


Xm1 = Xm2 = Xm3 = Xm4 =

Xd"(p.u.) x (Base MVA x 1000/ Motor kVA) x [ (Trafo No-load Voltage/ Bus Voltage) ]
=

0.17 x (15*1000/656) x (6.9/6.6)


j 4.248

4.248

IMPEDANCE DIAGRAM

, 90

33 kv Switchboard

Zt1
6.6kV Switchboard :

ZC1

F2

Zm1

ZS = j 0.031

Zt1 = j 0.109
6.6kV Switchboard :

ZC1 = 0.028 + J 0.006


F2
R00
Zm1 = j 4.248

0.017494752

6.6kV
Switchboard
6.6kV
6.6kV
Switchboard
Switchboard
: ::

Z2 = Zm1

Z1 = ZS + Zt1 + ZC1

R00
Z1 =

0.028 + j 0.146

Z2 =

j4.248

6.6kV
6.6kV
Switchboard
Switchboard
: :
0.149

Zeq = 0.1436

R00

Therefore, Maximum Fault level at F2

Base MVA
Zeq

DOC NO:
ANEWA ENGINEERING
PVT. LTD.

SHORT CIRCUIT
CALCULATIONS

Sheet 94 of 97

168108-028-E-DCL-4-001

REV
R00

Maximum Fault level at F2 in KA

104.5

104.5

6.6x1.732
9.14

D.

Fault at (F3) 6.6kV Motor : 028-PU-1014B

i)

500KW rated Motor ( 028-PU-1014B, 2014B)


Motor rating = 500 KW =

625

MVA

R00

KA

KVA

Sub-transient reactance of HV motor = 17 %


Xm5 = Xm6 =

Xd"(p.u.) x (Base MVA x 1000/ Motor kVA) x [ (Trafo No-load Voltage/ Bus Voltage) ]
= 0.17 x (15*1000/625) x (6.9/6.6)
4.459
j4.459
=

, 90

IMPEDANCE DIAGRAM
33 kv Switchboard

Zt
6.6kV Switchboard :

ZC1

F3

Zm5

ZS = j 0.031

Zt1 = j 0.109

6.6kV Switchboard :

ZC1 = 0.028 + J 0.005


F3

Zm1 = j 4.459

6.6kV Switchboard :
Zm1 = Z2
Z1 = ZS + Zt1 + ZC1

Z1 =
Z1=ZS+ZTR+ZC1
ZS=
j
ZTR=
j
0.0000
ZC1=
j
0.0280
Z1=ZS+ZTR+ZC1=
j
Z1MAG= 0.1487
1/Z1MAG= 6.7267

0.028 + j 0.146
0.000
0.000
+
0.0000
0.1460
79.14
-79.14

1/Z1REAL= 1.2670
1/Z1REAC= -6.6063
1/Z1=

1.2670
j -6.6063

Z1=ZC2+ZM
ZC2=
ZM=
Z2=ZC2+ZM=

+
j 0.0000
j 4.459
j 4.4590

Sheet 95 of 97

Z2 =

j 4.459

Z2MAG= 4.4590
1/Z2MAG= 0.2243
1/Z2REAL= 0.0491
1/Z2REAC= -0.2188

77.36
-77.36

0.0491
j -0.2188

1/Z2=

1.3160
6.951
0.144

-6.825

Zeq = 0.141
Therefore, Maximum Fault level at F3

Maximum Fault level at F3 in KA

Base MVA
Zeq

106.4

106.4

MVA

6.6x1.732
9.31
=
6.6kV
6.6kV
Switchboard
Switchboard
: :

KA

DOC NO:
ANEWA ENGINEERING
PVT. LTD.

SHORT CIRCUIT
CALCULATIONS

Sheet 96 of 97

168108-028-E-DCL-4-001

REV
R00

Source fault current


Fault Level at Incoming Site
Base MVA (For H.T beaker and Transformer Primary side)
Base KV (For H.T beaker and Transformer Primary side)
Base KV (For Transformer Secondary,LT Panel,D.B)

Transformer Rating
Transformer Impedance
Size of Cable from H.T Breaker To Transformer
Length of Cable from H.T Breaker To Transformer
R (T/C)
X (T/C)
R (T/C)
X (T/C)
Z(T/C)
Z p.u (C)
Total Z p.u (D) (Up to Transformer Primary)
Fault Level at Transformer Primary Side
% Reactance at Base KVA
Z P.U (T/C)
Total P.U Impedance up to T/C Secondary
Fault Level at Transformer Secondary Side
Fault Current at Transformer Secondary

25 KA
1429 MVA
25
33
6.6

7.5 MVA
6%