You are on page 1of 3

DESIGN BULLETIN

ISSUE
DATE:

30th August 2007

REVISION
:

00

SUBJECT:

VOLUME

DISC

SERIES

NO.

300

002

Supply & Return Air Grilles

Purpose :
This bulletine is being issued, to standardize the sizing and references of supply and return Grilles. The sizes
mentioned below are only for guidance.
This standardization will be implemented on all future projects.
Description:
The Supply & Return air grilles will be referenced as follows;

Type of Grilles

Reference
of Grille

Size
of Grille

Maximum Recommended
Air flow For a Grille

Double deflection Supply and


Return Air Grille

SG2 - A / RG2 - A

600 x 150

130.0 l/s

Double deflection Supply and


Return Air Grille

SG2 - B / RG2 - B

700 x 150

190.0 l/s

Double deflection Supply and


Return Air Grille

SG2 - C / RG2 - C

800 x 200

245.0 l/s

Double deflection Supply and


Return Air Grille

SG2 - D / RG2 - D

1000 x 200

290.0 l/s

Double deflection Supply and


Return Air Grille

SG2 - E / RG2 - E

1200 x 200

440.0 l/s

Double deflection Supply and


Return Air Grille

SG2 - F / RG2 - F

The Supply & Return air Bar Grilles will be referenced as follows;

Type of Grilles

Reference
of Grille

Height
of Grille

Maximum Recommended
Air flow for
1.0 m long Grille

Linear Bar Supply and Return Air


Grille

SLBG - A / RLBG - A

50

120.0 l/s - m

Linear Bar Supply and Return Air


Grille

SLBG - A / RLBG - A

100

230.0 l/s - m

Halcrow Yolles
PO Box 360 Dubai United Arab Emirates
Tel +971 43 3370380 Fax +971 43 3379239
halcrowyolles.com

DESIGN BULLETIN
ISSUE
DATE:

30th August 2007

REVISION
:

00

SUBJECT:

VOLUME

DISC

SERIES

NO.

300

002

Supply & Return Air Grilles

Linear Bar Supply and Return Air


Grille

SLBG - A / RLBG - A

150

300.0 l/s - m

Linear Bar Supply and Return Air


Grille

SLBG - A / RLBG - A

200

380.0 l/s - m

Notes:
Generally SG2-A to SG2 - E will be used along with FCU -01 to FCU-05 respectively i.e. SG2 A will
be used, when FCU -01 is being used on the project. Similarly SG2 B will be used, when FCU -02 is
being used on the project. Hence the grilles sizes for grille references SG2 A to E will be standard
as per above mentioned table. A corresponding return air grille will be used along with supply air
grille.
If any additional grilles are required for that particular project, then these would referenced as SG2-F
onward.

The maximum recommended air flow is for guidance only. For each project the design mechanical
engineer must review the selection of size, based on location of diffuser and height of the false ceiling
etc.
The above recommendations are based on achieving noise level of NC 30 in the occupied space. If
specified noise levels are below NC 30, please check the Manufacturers ratings.
For special application, please review your selection with Senior Mechanical Engineer.
The supply air Grille SG2 - X will be specified with opposed blade dampers and return air diffusers will
be without any damper.
The selection of supply air grilles for ref. A to E is based on airflow of proposed Fan Coil Units. Hence
for every project, once the Fan Coil Units are selected, the Senior Mechanical Engineer must review
the selection of proposed supply air grilles.
The sizes mentioned above are only for guidance and can be re-selected based on project
requirement. Diffusers for any other air flows to be selected based on Manufacturers ratings.

Based on above, Schedule of Grilles & Diffuser will be prepared and this Schedule will always be on
Mechanical services Legend & Symbol Drawing.
The specifications will also refer to various references mentioned above. A change in specification will be
carried out by the Sr. Mechanical Engineer.

Issued By:

Avinash P. Jawharkar
Head Of Mechanical Department

Halcrow Yolles
PO Box 360 Dubai United Arab Emirates
Tel +971 43 3370380 Fax +971 43 3379239
halcrowyolles.com

DESIGN BULLETIN
ISSUE
DATE:

30th August 2007

REVISION
:

00

SUBJECT:

VOLUME

DISC

SERIES

NO.

300

002

Supply & Return Air Grilles

Halcrow Yolles
PO Box 360 Dubai United Arab Emirates
Tel +971 43 3370380 Fax +971 43 3379239
halcrowyolles.com