VAV Terminal Units

VAV TERMINAL UNITS


All stated specications are updated at the printing date and subject to change without notice or obligation. The actual product might differ from pictures shown.
Introduction
ASLI Variable Air Volume (VAV) terminal units are volume ow rate controller for supply
air on variable air volume system. These units are designed to control the airow rate of
conditioned air into an occupied space in response to a control signal from thermostat
or Building Automation System (BAS). They could be used in stand alone system or
interfaced with LONWORKS or BACnet.
ASLI VAV terminal units consist of a casing with circular inlet spigot, rectangular outlet
connection with integral of berglass with black matt tissue for noise reduction, damper
blade for air volume control and cross ow differential pressure sensor for measuring
air volume.
ASLI VAV terminal units also incorporate control components, (VAV controller actuator,
and transformer) which are factory tted. ASLI in-house testing facility ensured that all
boxes that come out from the factory are calibrated and tested to match the controller
of individual size. This allow the terminals to monitor the desired ow rate, as dictated
by the thermostat or BAS, and compensate instantly for any changes in supply air
pressure that might tend to alter the supply air volume. Hence, the net result is a
pressure independent variable air volume system.
Features
Oval shape damper for better fow management.
Neoprene peripheral gasket to prevent leakage.
Multi-point averaging inlet differential pressure sensor.
1, 2 lbs fberglass with black matt tissue internal insulation for noise reduction.
Round inlet with beading for good inlet connection.
Square damper shaft for better grip mounting of actuator.
Shaft indicator indicating damper position.
Double layer heavy gauge damper blade.
Protective metal shroud for control components mounting.
Low pressure drop construction with round inlet and rectangular outlet- static regain.
Can be used for Constant Air Volume (CAV) application.
Rectangular discharge opening with slip and drive cleat duct connection.
Optional internal perforated sheet or aluminum foil facing.
Reheat coil available upon request.
Tube conceal (optional).
Materials
Casing: 0.7mm thickness galvanized steel.
Damper blade: Double layer 0.7mm thickness galvanized steel with a sandwiched
peripheral gasket.
Internal insulation: 25mm (1) 40 kg/m3 (2 lb) density fber glass with matt black
tissue facing.
Bearing: Engineering plastic.
Square shaft: 10mmX10mm galvanized steel.
Differential pressure sensor: Aluminum.
Air Volume Control Type
Variable Air Volume (VAV) Pressure Dependent Control
- Without differential pressure sensor.
- Pressure dependent.
- No monitoring of air volume.
Variable Air Volume (VAV) Pressure Independent Control
- With differential pressure sensor.
- Pressure independent.
- Air volume varies depending on design ow and signal by controller.
- Air volume could be monitored.
Constant Air Volume (CAV) Pressure Independent Control
- With differential pressure sensor.
- Pressure independent.
- Air volume is constant (design ow) provided that the minimum static pressure is achieved.
- Air volume could be monitored.
VAV page 1 of 15
Type I
Type II
VAV Terminal Units
VAV TERMINAL UNITS
All stated specications are updated at the printing date and subject to change without notice or obligation. The actual product might differ from pictures shown.
Construction Illustrations Type I
Physical Dimension Type I Unit:mm
General notes:
Internal insulation 25mm (1) 32 kg/m3 (2 lb) density coated to prevent air erosion.
Galvanized steel housing.
Mechanically seal-leak resistant construction.
Rectangular discharge opening have drive and slip cleat duct connections as standard.
Right hand control location standard, as shown above.
Turbulent fow approaching the terminal will create additional noise, pressure drop and greater air fow variation. It is therefore recom mended for optimum perfor mance there should be a
minimum of 4 duct diameters of straight inlet duct, same size as inlet, between the inlet and any transition, take off or ftting.

VAV page 2 of 15
D A B C E F G L H
100 305 203 394 120 220 310 700 100
150 305 203 394 120 220 310 700 100
200 305 254 394 120 220 310 700 100
250 356 318 394 120 220 310 700 100
300 406 381 394 120 220 310 700 100
350 508 445 396 120 220 310 700 100
400 610 457 396 120 220 310 700 100
609 X 406 965 460 395 120 220 310 700 100
Figure 2: VAV Terminal Unit (Type I) with Electric Reheat Coil
Figure 1: Basic VAV Terminal Unit (Type I)
VAV Terminal Units
VAV TERMINAL UNITS
All stated specications are updated at the printing date and subject to change without notice or obligation. The actual product might differ from pictures shown.
VAV page 3 of 15
Construction Illustrations Type II
Construction Illustrations Type II Unit:mm
General notes:
Internal insulation 25mm (1) 32 kg/m3 (2 lb) density coated to prevent air erosion.
Galvanized steel housing.
Mechanically seal-leak resistant construction.
Rectangular discharge opening have drive and slip cleat duct connections as standard.
Right hand control location standard, as shown above. Turbulent fow approaching the terminal will create additional noise, pressure drop and greater air fow variation. It is therefore
recommended for optimum performance there should be a minimum of 4 duct diameters of straight inlet duct, same size as inlet, between the inlet and any transition, take off or ftting.

D A B C E F G L H
100 305 203 444 120 220 310 700 100
150 305 203 444 120 220 310 700 100
200 305 254 444 120 220 310 700 100
250 356 318 444 120 220 310 700 100
300 406 381 444 120 220 310 700 100
350 508 445 546 120 220 310 700 100
400 610 457 546 120 220 310 700 100
609 X 406 965 460 445 120 220 310 700 100
Figure 2: VAV Terminal Unit (Type II) with Electric Reheat Coil
Figure 1: Basic VAV Terminal Unit (Type II)
VAV Terminal Units
VAV TERMINAL UNITS
All stated specications are updated at the printing date and subject to change without notice or obligation. The actual product might differ from pictures shown.
VAV page 4 of 15
VAV TERMINAL UNITS
ST-5000 Single Duct Variable Air Volume Terminal Selection Guide
VAV Terminal Units
All stated specifications are updated at the printing date and subject to change without notice or obligation. The actual product might differ from pictures shown.

VAV page 3 of 14
Air Volume Ranges
MOA Multi-Outlet Attenuator Section
CFM
26 - 225
62 - 450
110 - 800
180 - 1350
270 - 2100
400 - 3200
570 - 4000
2500 - 8000
liter/s
12 - 106
29 - 212
52 - 378
85 - 637
127 - 991
189 - 1510
269 - 1888
1800 - 3775
Air Volume Range (Min - Max)
100 (4)
150 (6)
200 (8)
250 (10)
300 (12)
350 (14)
400 (16)
609 X 406 (24X16)
Unit Size, mm (inch)
4 = 4 dia.
6 = 6 dia.
8 = 8 dia.
10 = 10 dia.
12 = 12 dia.
14 = 14 dia.
16 = 16 dia.
24X16 = 24X16 inlet
0 = Time proportional
1 = Single Stage
2 = Two Stage
3 = Three Stage
0 = Cooling Only
1 = Water Reheat
2 = Electric Reheat
A= DDC Control by ASLI
B = Bare Unit
C = Constant Volume Unit
D = DDC Control by Others
E = Electronic Control
F = Pneumatic Control
ST - 5
ATT Attenuator Section RDC Round Discharge Collar
36" (914)
A
4"(102)
3.625"(84) A
B B Normal Size
End View
End View
End View Side View
Side View
36" (914)
3.313" (84)
Typical
3.313" (84)
Typical
B
B
Notes:
Only one outlet size to be specified per M.O.A. - No
mixing
of outlet sizes on the same unit.
All round outlet c/w manual dampers.
Denotes air flow direction.
For special outlet sizes & arrangements, consult
Standard MOA Configuration
A B D C F E G
Non-Std.
Arrange
ments
NC = Without
Tube
Conceal
C = With Tube
Conceal
VAV Terminal Units
VAV TERMINAL UNITS
All stated specications are updated at the printing date and subject to change without notice or obligation. The actual product might differ from pictures shown.
VAV page 5 of 15
VAV TERMINAL UNITS
Electric Reheat Application
ASLI offers factory supplied and mounted electric coils for VAV terminal units. The electric reheat extension comes in separate unit which can be installed on
the existing basic VAV terminal units. The electric heater coils are removable from the side of the terminal units consoled within a shroud.
Features Of ASLI VAV Terminal Units With Electric Reheat Coils
Heaters are factory wired and tested ensuring a high level of quality.
Electric coil configuration and air flow is matched to eliminate hot spots, provide efficient heat transfer and to maintain element life.
Reheat units come with a manual reset thermal cut-out to protect unit from overheating.
25mm (1) 32 kg/m
3
(2 lb) density fiberglass internal insulation to prevent air erosion.
Magnetic contactors are provided as standard on stages heaters for de-energizing or disconnecting power to heating coils.
An air flow switch is provided as standard to ensure air is passing over the electric coil before it will energize. This is to ensure that the electric coil will not
energize when the system fan is shut-down or fails.
1. Locate the room heat loss on the MBH scale on the far left side of the chart.
Convert to kWh by moving horizontally to the right to the kWh scale
(1kWh = 3.413 MBH)
2. Calculate the kWh required to heat the primary air to room temperature
using the following equation,
3. Add the kWh value obtained in the step 2 to the kWh scale at the let
side. More horizontally to the right to the point where the kWh value
and the air flow volume intersect.
4. With the point of intersection from step 3, the air temperature rise (ATR),
can be obtained by interpolating between the air temperature rise lines
on the graph.
5. To verify the selection, sum the air temperature rise and the temperature
of the primary air. The sum total should be less then 120F.
Selection Example
Select electric coil for a size 10 VAV Terminal with a minimum air flow of
600 CFM. Space heat loss is estimated at 18 MBH and space design
temperature is 70F. The temperature of the primary air flow is 60F.
1. Space heat loss (18 MBH) = 5.2 kWh
2. heat required to raise the temperature of primary air:
3. Total heat required = 5.2 + 1.90 = 7.1 kWh
4. Referring to chart, air temperature rise ATR = 35F
5. Leaving air temperature = 60F + 35F = 95F. since the leaving air
temperature is less than the recommended maximum limit of 120F,
the selection is satisfactory
6. Select a suitable power supply from the reheat coil selection table
7. Verify minimum airflow requirement are met. (minimum 70 CFM/kW)
Reheat Selection Chart
VAV Terminal Units
All stated specifications are updated at the printing date and subject to change without notice or obligation. The actual product might differ from pictures shown.

VAV page 4 of 14
Electric Reheat Coil Selection Table
600V
3.0
6.0
11.0
17.0
30.0
49.5
49.5
49.5
Minimum kW Single phase = 0.5 kW/stage, three phase = 1.5 kW/stage.
Minimum air velocity should be 1m/s.
Minimum air volume must be greater than minimum air volume listed or 70 CFM per kilowatt.
Static pressure loss of coil is negligible, therefore the minimum static pressure drop is equal to basic unit value.
3 Phase
415V
3.0
6.0
11.0
17.0
30.0
34.5
34.5
34.5
208V
3.0
6.0
11.0
17.0
17.0
17.0
17.0
17.0
277V
3.0
6.0
11.0
13.0
13.0
13.0
13.0
13.0
Allowable Maximum kW
1 Phase
240V
3.0
6.0
9.5
11.5
11.5
11.5
11.5
11.5
120V
3.0
5.0
5.5
5.5
5.5
5.5
5.5
5.5
Stages
1,2
1,2
1,2,3
1,2,3
1,2,3
1,2,3
1,2,3
1,2,3
CFM Range
100 - 225
100 - 450
167 - 800
243 - 1350
333 - 2100
486 - 3000
600 - 4000
950 - 8000
Unit Size (inch)
4
6
8
10
12
14
16
24 X 16
Electric Reheat Coil Selection Guide
kWh =
CFM x T
3160
= 85 CFM/kW
600 CFM
7.1 kW
kWh = = 1.90kWh
600 x 10
3160
VAV Terminal Units
VAV TERMINAL UNITS
All stated specications are updated at the printing date and subject to change without notice or obligation. The actual product might differ from pictures shown.
VAV page 6 of 15
AIR FLOW SENSOR
PRIMARY AIR
DAMPER
ACTUATOR
CONTROLLER
DISCHARGE AIR
COOLING MODE
CoolOccSpt
THERMOSTAT
MAX
FLOW
(POS)
MIN
FLOW
(POS)
AIR FLOW SENSOR
PRIMARY AIR
DAMPER
ACTUATOR
CONTROLLER
DISCHARGE
AIR
COOLING MODE
CoolOccSpt
THERMOSTAT
MAX
FLOW
(POS)
MIN
FLOW
(POS)
CONTACTORS
STAGED REHEAT COIL
REHEAT
MODE
REHEAT
FLOW
STAGE 3
STAGE 2
STAGE 1 ON
ON
ON
HeatOccSpt
VAV TERMINAL UNITS
VAV Controller Control Mode (Cooling Only)
VAV Terminal Units
All stated specifications are updated at the printing date and subject to change without notice or obligation. The actual product might differ from pictures shown.

VAV page 5 of 14
This mode is used where only cooling application is required. The controller will modulate the VAV box damper according to the set point and room temperature
between the cooling mode minimum and maximum flow setting.
VAV Controller Control Mode (Cooling With Electric Stages Reheat)
During this mode, 2 or 3 stages reheat control the heater output by using 2 or 3 stages of heater control at different intervals. The heaters cut-in at different
stages depending on the heating set-point of reheat.
When the room temperature is above the cooling set point, the flow shall be maximum and when the room temperature fall below cooling set point (by more than
1 degree Celsius), the flow will be minimum.
When the room temperature fall beyond heating set point, the control should automatically increase to auxiliary flow (which is resettable) when the 1
st
stage of
heater cut in. when the room temperature continues to fall, the 2
nd
heater and 3
rd
heater will cut in accordingly. The interval for each stage of reheat to cut in is
determined by the room temperature and heating set point.
VAV Terminal Units
VAV TERMINAL UNITS
All stated specications are updated at the printing date and subject to change without notice or obligation. The actual product might differ from pictures shown.
VAV page 7 of 15
AIR FLOW
SENSOR
CONTROLLER
PRIMARY
AIR
FAN
DAMPER
ACTUATOR
FAN
RELAY
OPEN TO
PLENUM
VALVE
REHEAT
COIL (OPTIONAL)
DISCHARGE
AIR
THERMOSTAT
AIR FLOW
SENSOR
CONTROLLER
PRIMARY
AIR
FAN
DAMPER
ACTUATOR
FAN
RELAY
VALVE
REHEAT
COIL
DISCHARGE
AIR
THERMOSTAT
RETURN AIR
FROM PLENUM
VAV TERMINAL UNITS
VAV Controller Control Mode (Cooling With Series Fan And Reheat)
VAV Terminal Units
All stated specifications are updated at the printing date and subject to change without notice or obligation. The actual product might differ from pictures shown.

VAV page 6 of 14
VAV Controller Control Mode (Cooling With Parallel Fan And Reheat)
At this mode, the fan is intended to run continuously when the main air handler is on
and is in-line with the primary air flow through the box. The controller will activate the
fan when the primary flow is above minimum flow setting or a pre-determined flow
volume, say 50 CFM whichever is higher). The heater will cut in when the room
temperature drops below the heating set point.
A parallel fan is not located in the primary air stream, but is designed to add return air
from the plenum into the air stream delivered to the space. The controller turns on the
parallel fan when the space temperature falls below set point as a first stage of reheat,
or if the air flow falls below a minimum air flow set point to maintain a minimum air
flow to the space (parallel flow). The heater will cut in when the room temperature
drops below the heating set point.
AIR FLOW SENSOR
PRIMARY AIR
DAMPER
ACTUATOR
CONTROLLER
DISCHARGE AIR
THERMOSTAT
COOLING MODE
CoolOccSpt
MAX
(POS)
MIN
(POS)
REHEAT
MODE
REHEAT
FLOW
HeatOccSpt
VALVE
FLOATING
ACTUATOR
HOT WATER OR STEAM
REHEAT COIL
Periph Min Pos
100
PERCENT
OPEN
VAV Controller Control Mode (Cooling With Modulating Reheat)
During this mode, reheat coils or hot water coil are controlled with modulating output from controller.
When the room temperature is above the cooling set point, the flow shall be maximum and when the room temperature fall below cooling set point (by more than
1 degree Celsius), the flow will be minimum.
When the room temperature fall beyond heating set point, the air flow should automatically be increased to reheat flow (which is resettable). At the same time,
the peripheral output will gradually increase the valve position to increase the hot water volume. Hence the supply air temperature rises.
VAV Terminal Units
VAV TERMINAL UNITS
All stated specications are updated at the printing date and subject to change without notice or obligation. The actual product might differ from pictures shown.
VAV page 8 of 15
VAV TERMINAL UNITS
VAV Terminal Units
All stated specifications are updated at the printing date and subject to change without notice or obligation. The actual product might differ from pictures shown.
Performance Data (Radiated Sound Power Levels, Basic Assembly Unit)
Unit Size
Ps 125 Pa (0.5" W.G.)
Octave Band
Ps 250 Pa (1.0 W.G.)
Octave Band
Ps 500 Pa (2.0 W.G.)
Octave Band
Ps 750 Pa (3.0 W.G.)
Octave Band Air Flow
Sound Power Level, Lw dB, re 10
-12
watts
4
6
8
10
12
14
16
24 X 16
VAV page 7 of 14
7
28
31
34
36
31
34
37
39
34
37
40
42
40
43
45
47
38
41
44
46
48
39
43
46
48
50
39
42
46
49
51
53
54
56
45
48
52
55
6
35
38
41
43
38
41
44
46
41
44
47
49
47
50
52
54
45
48
51
53
55
46
50
53
55
57
46
49
53
56
58
60
61
63
52
55
59
62
5
40
43
45
47
43
46
48
50
46
49
51
53
52
54
56
58
51
54
56
58
60
52
56
58
60
62
52
55
59
61
63
65
66
68
58
61
65
67
4
44
47
51
52
47
50
54
55
50
53
57
58
56
60
61
62
55
58
62
63
64
56
60
63
65
66
54
57
61
64
66
67
71
72
60
63
67
70
3
47
50
55
58
50
53
58
61
53
56
61
64
59
64
67
68
58
61
66
69
70
59
63
67
71
72
57
60
64
68
72
73
77
78
63
66
70
74
2
48
51
56
59
51
54
59
62
54
57
62
65
60
65
68
70
58
61
66
69
71
59
63
67
71
73
57
60
64
68
72
74
77
79
63
66
70
74
7
23
26
31
34
25
28
33
36
28
31
36
39
34
39
42
46
32
35
40
43
47
33
37
41
45
49
33
36
40
44
48
52
51
55
39
42
46
50
6
30
33
38
41
33
36
40
43
36
39
43
46
42
46
49
52
40
43
47
50
53
41
45
49
52
55
41
44
48
52
55
58
58
61
47
50
54
58
5
36
39
43
46
39
42
45
48
42
45
48
51
48
51
54
57
47
50
53
56
59
48
52
55
58
61
48
51
55
58
61
64
64
67
54
57
61
64
4
40
43
48
50
43
46
50
52
46
49
53
55
52
56
58
60
51
54
58
60
62
52
56
59
62
64
50
53
57
60
63
65
68
70
56
59
63
66
3
45
48
52
55
48
51
54
58
51
54
57
61
57
60
64
65
56
59
62
66
67
57
61
64
68
69
55
58
62
65
69
70
74
75
61
64
68
71
2
47
50
54
57
49
52
57
60
52
55
60
63
58
63
66
67
56
59
64
67
68
57
61
65
69
70
55
58
62
66
70
71
75
76
61
64
68
72
7
17
20
28
32
19
22
30
34
22
25
33
37
28
36
40
44
26
29
37
41
45
27
31
37
43
47
27
30
34
40
46
50
49
53
33
36
40
46
6
26
29
34
39
27
30
36
41
30
33
39
44
36
42
47
50
34
37
43
48
51
35
39
45
50
53
35
38
42
48
53
56
56
59
41
44
48
54
5
33
36
41
45
34
37
43
47
37
40
46
50
43
49
53
55
42
45
51
55
57
43
47
52
57
59
43
46
50
55
60
62
63
65
49
52
56
61
4
37
40
45
48
38
41
47
50
41
44
50
53
47
53
56
59
46
49
55
58
61
47
51
56
60
63
45
48
52
57
61
64
66
69
51
54
58
63
3
44
47
49
53
45
48
51
54
48
51
54
57
54
57
60
61
53
56
59
62
63
54
58
61
64
65
52
55
59
62
65
66
70
71
58
61
65
68
2
45
48
53
56
47
50
54
57
50
53
57
60
56
60
63
65
54
57
61
64
66
55
59
63
66
68
53
56
60
64
67
69
72
74
59
62
66
70
7
12
15
25
30
13
16
26
31
16
19
29
34
22
32
37
43
20
23
33
38
44
21
25
33
40
46
21
24
28
36
43
49
46
52
27
30
34
42
6
21
24
31
37
22
25
32
38
25
28
35
41
31
38
44
48
29
32
39
45
49
30
34
41
47
51
30
33
37
44
50
54
53
57
36
39
43
50
5
29
32
39
44
30
33
40
45
33
36
43
48
39
46
51
54
38
41
48
53
56
39
43
49
55
58
39
42
46
52
58
61
61
64
45
48
52
58
4
33
36
42
46
34
37
43
47
37
40
46
50
43
49
53
57
42
45
51
55
59
43
47
52
57
61
41
44
48
53
58
62
63
67
47
50
54
59
3
42
45
46
50
43
46
47
51
46
49
50
54
52
53
57
58
51
54
55
59
60
52
56
59
61
62
50
53
57
60
62
63
67
68
56
59
63
66
2
44
47
51
54
45
48
52
55
48
51
55
58
54
58
61
62
52
55
59
62
63
53
57
61
64
65
51
54
58
62
65
66
70
71
57
60
64
68
L/s
37
60
83
106
74
120
166
213
132
214
296
378
223
361
499
638
347
508
669
831
992
529
774
1020
1266
1511
661
907
1152
1398
1643
1889
1322
1813
2304
2796
3287
3778
CFM
79
128
176
225
158
255
353
450
280
453
627
800
473
765
1058
1350
735
1076
1418
1759
2100
1120
1640
2160
2680
3200
1400
1920
2440
2960
3480
4000
2800
3840
4880
5920
6960
8000
Ps is the difference in static pressure from inlet to discharge of the unit.
VAV Terminal Units
VAV TERMINAL UNITS
All stated specications are updated at the printing date and subject to change without notice or obligation. The actual product might differ from pictures shown.
VAV page 9 of 15
VAV TERMINAL UNITS
VAV Terminal Units
All stated specifications are updated at the printing date and subject to change without notice or obligation. The actual product might differ from pictures shown.
Performance Data (Discharge Sound Power Levels, Basic Assembly Unit)
Unit Size
Ps 125 Pa (0.5" W.G.)
Octave Band
Ps 250 Pa (1.0 W.G.)
Octave Band
Ps 500 Pa (2.0 W.G.)
Octave Band
Ps 750 Pa (3.0 W.G.)
Octave Band Air Flow
Sound Power Level, Lw dB, re 10
-12
watts
4
6
8
10
12
14
16
24 X 16
VAV page 8 of 14
7
50
54
60
61
53
57
63
64
58
61
66
67
64
66
67
68
64
66
68
69
70
65
67
69
70
71
68
71
72
67
69
71
74
77
78
73
75
77
6
54
58
64
67
55
59
65
68
60
63
66
69
66
67
67
70
67
69
70
70
73
69
71
72
72
75
69
72
75
71
73
74
75
78
81
77
79
80
5
56
60
66
69
57
61
67
70
62
65
68
71
68
69
69
72
69
71
72
72
75
71
73
74
74
77
70
73
75
76
76
79
76
79
81
82
82
85
4
54
58
66
69
55
59
67
70
60
63
68
71
66
68
69
72
67
69
71
72
75
69
71
73
74
77
68
71
73
75
76
79
74
77
79
81
82
85
3
56
60
65
65
60
64
69
69
65
68
72
72
71
73
75
75
70
72
74
76
76
71
73
75
77
77
70
73
75
77
79
79
72
75
77
79
81
81
2
53
57
63
67
57
61
67
71
62
65
70
74
68
70
73
77
69
71
73
76
80
71
73
75
78
82
70
73
75
77
80
84
71
74
76
78
81
85
7
43
47
54
57
46
50
56
59
51
54
58
61
57
59
60
63
54
56
58
59
63
58
59
62
63
66
60
62
64
61
62
66
66
68
70
67
68
72
6
47
51
58
61
49
53
59
62
54
57
60
63
60
61
61
65
58
60
62
62
65
62
64
66
66
69
63
66
68
66
67
69
69
72
74
72
73
75
5
49
53
61
64
50
54
62
65
55
58
63
66
61
63
64
67
60
62
64
64
68
64
66
68
68
72
64
67
69
70
70
74
70
73
75
76
76
80
4
49
53
61
65
50
54
62
66
55
58
63
67
61
63
64
68
60
62
64
65
70
64
66
68
69
73
64
67
69
70
71
75
70
73
75
76
77
81
3
51
55
60
62
55
59
64
66
60
63
67
69
66
68
70
72
64
66
68
70
72
66
68
70
72
74
66
69
71
72
74
76
70
72
74
76
77
79
2
50
54
59
63
54
58
63
67
59
62
66
70
65
66
69
73
64
66
68
70
74
67
69
71
74
78
67
70
72
73
76
80
70
73
74
76
78
82
7
37
41
47
52
38
42
49
54
43
46
51
56
49
52
53
58
49
51
53
54
59
50
52
54
55
60
52
54
56
55
56
61
58
60
62
61
62
67
6
41
45
51
55
42
46
53
57
47
50
54
58
53
55
56
59
54
56
57
58
62
56
58
59
60
64
57
59
62
61
62
65
63
65
68
67
68
71
5
43
47
55
60
44
48
56
61
49
52
57
62
55
58
58
63
55
57
60
61
65
57
59
62
63
67
58
60
64
64
65
69
64
66
70
70
71
75
4
45
49
57
62
46
50
58
63
51
54
59
64
57
59
60
65
57
59
61
62
67
59
61
63
64
69
60
62
64
65
66
71
66
68
70
71
72
77
3
47
51
56
59
51
55
60
63
56
59
63
66
62
64
66
69
61
63
65
67
70
62
64
66
68
71
63
64
66
68
69
72
67
69
71
72
74
77
2
46
50
55
59
50
54
59
63
55
58
62
66
61
63
65
69
62
64
65
67
71
64
66
67
69
73
65
67
68
70
71
75
69
71
73
74
76
80
7
30
34
41
48
31
35
42
49
36
39
43
50
42
45
46
53
41
43
46
47
54
43
44
47
48
55
44
45
48
49
49
56
50
51
54
55
55
62
6
34
38
45
49
36
40
47
51
41
44
48
52
47
49
50
54
47
49
51
52
56
49
51
53
54
58
51
53
55
56
56
60
57
59
61
62
62
66
5
36
40
50
55
37
41
51
56
42
45
52
57
48
52
53
58
48
50
54
55
60
50
52
56
57
62
52
54
58
59
59
64
58
60
64
65
65
70
4
40
44
52
58
41
45
53
59
46
49
54
60
52
54
55
61
52
54
56
57
63
54
56
58
59
65
56
58
60
61
61
67
62
64
66
67
67
73
3
42
46
51
56
46
50
55
60
51
54
58
63
57
59
61
66
56
58
60
62
67
57
59
61
63
68
59
60
62
63
64
69
65
66
68
69
70
75
2
43
47
51
55
47
51
55
59
52
55
58
62
58
59
61
65
58
60
61
63
67
60
62
63
65
69
62
64
65
66
67
71
68
70
71
72
73
77
L/s
37
60
83
106
74
120
166
213
132
214
296
378
223
361
499
638
347
508
669
831
992
529
774
1020
1266
1511
661
907
1152
1398
1643
1889
1322
1813
2304
2796
3287
3778
CFM
79
128
176
225
158
255
353
450
280
453
627
800
473
765
1058
1350
735
1076
1418
1759
2100
1120
1640
2160
2680
3200
1400
1920
2440
2960
3480
4000
2800
3840
4880
5920
6960
8000
Ps is the difference in static pressure from inlet to discharge of the unit.
VAV Terminal Units
VAV TERMINAL UNITS
All stated specications are updated at the printing date and subject to change without notice or obligation. The actual product might differ from pictures shown.
VAV page 10 of 15
VAV TERMINAL UNITS
VAV Terminal Units
All stated specifications are updated at the printing date and subject to change without notice or obligation. The actual product might differ from pictures shown.
Performance Data (Typical Selection Guide)
Unit Size Air Flow
4
6
8
10
12
14
16
24 X 16
NC are derived from sound power level, which are obtained in accordance with ARI standard 885-98.
Ps is the difference in static pressure from inlet to discharge of the unit.
Pt is the difference in total pressure from inlet to discharge of the unit.
Ps for terminal units with electric coils is equal to basic unit. Resistance of the coil elements is negligible.
Dash(-) in space indicates NC less than 20.
VAV page 9 of 14
-
20
24
28
20
23
28
32
23
27
32
35
30
35
38
39
29
32
37
40
42
30
34
38
43
44
28
31
35
39
44
45
34
37
42
48
52
53
-
-
21
24
-
-
23
28
-
23
27
32
27
30
35
36
25
29
33
37
38
27
32
35
39
40
24
28
33
36
40
42
32
35
39
43
48
49
-
-
-
22
-
-
20
23
-
-
23
27
23
27
30
33
22
25
29
33
35
23
28
32
35
37
20
24
29
33
36
38
28
32
36
39
43
45
-
-
-
-
-
-
-
20
-
-
-
23
20
22
27
31
-
23
24
29
33
20
25
29
32
35
-
22
27
30
33
36
25
29
34
37
39
43
-
-
-
-
-
-
-
-
-
-
-
-
-
-
22
26
-
-
-
24
28
-
-
24
27
30
-
-
22
25
28
31
20
24
29
32
34
38
20
24
29
30
20
24
29
30
22
24
29
30
28
30
31
32
27
29
31
34
35
28
30
32
33
34
25
28
30
34
35
36
35
38
40
42
43
44
-
-
24
27
-
-
23
25
-
-
22
24
22
24
25
28
-
20
22
26
29
22
23
26
28
30
19
22
24
28
30
32
28
31
33
35
35
38
-
-
-
22
-
-
-
21
-
-
-
20
-
-
20
24
-
-
-
23
26
-
-
20
23
26
-
-
-
23
24
28
23
26
28
30
32
35
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
20
-
-
-
-
23
-
-
-
-
23
-
-
-
-
-
24
21
22
25
26
27
33
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
20
21
22
28
22
26
31
32
25
29
34
35
30
32
37
38
33
35
36
37
33
35
37
38
39
32
34
36
37
38
31
34
36
38
39
40
37
40
42
44
45
46
3.0"
W.G.
750
Pa
-
-
26
29
-
22
28
30
23
26
30
32
27
29
30
33
24
26
28
30
33
26
27
30
32
34
25
28
30
32
34
36
30
33
35
37
37
40
2.0"
W.G.
500
Pa
-
-
-
24
-
-
21
26
-
-
23
28
20
23
25
29
-
22
24
27
30
-
22
24
27
30
20
22
24
27
28
32
25
28
30
32
34
37
-
-
-
20
-
-
-
21
-
-
-
23
-
-
-
25
-
-
-
20
27
-
-
-
20
27
-
-
-
20
22
28
23
24
27
28
29
35
-
-
-
-
-
-
-
-
-

-
-
-
-
-
-
-
-
-
-
21
-
-
-
-
21
-
-
-
-
-
23
-
-
22
23
24
30
14
35
67
112
11
31
71
128
10
24
47
83
11
26
53
92
13
25
41
65
96
16
32
53
85
128
14
25
39
57
81
112
14
27
45
68
97
136
0.06
0.14
0.27
0.45
0.04
0.12
0.28
0.51
0.04
0.09
0.19
0.33
0.05
0.11
0.21
0.37
0.05
0.10
0.17
0.26
0.39
0.06
0.13
0.21
0.34
0.52
0.06
0.10
0.16
0.23
0.32
0.45
0.06
0.11
0.18
0.27
0.39
0.55
2
2
5
10
2
7
25
53
2
2
6
16
2
2
6
16
2
2
2
4
10
2
2
2
6
16
2
2
2
2
5
12
2
5
9
15
24
40
0.01
0.01
0.02
0.04
0.01
0.03
0.10
0.21
0.01
0.01
0.02
0.06
0.01
0.01
0.02
0.06
0.01
0.01
0.01
0.02
0.04
0.01
0.01
0.01
0.02
0.06
0.01
0.01
0.01
0.01
0.02
0.05
0.01
0.02
0.04
0.06
0.10
0.16
2
2
5
10
2
7
25
53
2
2
6
16
2
2
6
16
2
2
2
4
10
2
2
2
6
16
2
2
2
2
5
12
2
5
9
15
24
40
0.01
0.01
0.02
0.04
0.01
0.03
0.10
0.21
0.01
0.01
0.02
0.06
0.01
0.01
0.02
0.06
0.01
0.01
0.01
0.02
0.04
0.01
0.01
0.01
0.02
0.06
0.01
0.01
0.01
0.01
0.02
0.05
0.01
0.02
0.04
0.06
0.10
0.16
37
60
83
106
74
120
166
213
132
214
296
378
223
361
499
638
347
508
669
831
992
529
774
1020
1266
1511
661
907
1152
1398
1643
1889
1322
1813
2304
2796
3287
3778
79
128
176
225
158
255
353
450
280
453
627
800
473
765
1058
1350
735
1076
1418
1759
2100
1120
1640
2160
2680
3200
1400
1920
2440
2960
3480
4000
2800
3840
4880
5920
6960
8000
Minimum
Ps Across
Unit
Basic unit
Minimum
Ps Across
Unit With
Attenuator
Min Pt
Basic Unit
Discharge NC
Basic Unit
Ps Across unit
Discharge NC
c/w 36" Attenuator
Ps Across unit
Radiated NC
Basic Unit
Ps Across unit
0.5"
W.G.
125
Pa
Min
W.G Pa W.G Pa W.G Pa CFM L/s
1.0"
W.G.
250
Pa
3.0"
W.G.
750
Pa
2.0"
W.G.
500
Pa
0.5"
W.G.
125
Pa
Min
1.0"
W.G.
250
Pa
3.0"
W.G.
750
Pa
2.0"
W.G.
500
Pa
0.5"
W.G.
125
Pa
Min
1.0"
W.G.
250
Pa
VAV Terminal Units
VAV TERMINAL UNITS
All stated specications are updated at the printing date and subject to change without notice or obligation. The actual product might differ from pictures shown.
VAV page 11 of 15
Suggested Specication
General
Variable Air Volume (VAV) units shall be fully/truly pressure independent with multi-point velocity sensor, detachable fow transmitter, 3 point foating electric actuator,
room thermostat, and open protocol LonMark DDC (direct digital control) controller.
The unit including all the control components shall be supplied, installed and the complete unit tested at the factory by a qualifed VAV manufacturer. A qualifed VAV
manufacturer shall have both good manufacturing facility and a pressure independent test laboratory for variable air volume testing.
The warranty of the complete unit including the controls shall be the sole responsibility of the supplier.
The calibration of the VAV units shall be conducted in accordance with Industry Standard for Air Terminals Standard ARI 880 published jointly by Air Diffusion Council
(ADC) and Air conditioning and Refrigeration Institute (ARI).
The manufacturer shall maintain an air distribution laboratory capable of performing full testing of pressure independent boxes and airfow accuracy test.
Basic Assembly
The basic assembly shall be constructed of galvanized steel, not less than 0.7mm (24ga.) thickness.
Internal insulation shall be at least 25mm, 32kg/cu.m density fberglass black tissue to prevent erosion.
The damper shall be of heavy gauge metal, with peripheral tear resistant Neoprence lip seal to ensure a tight air seal at full shut off position. Damper shaft shall have
damper position indicator and of square shape to ensure a fool proof grip between damper and electric actuator. Round shaft shall not be accepted.
All control components shall be mounted inside a protective metal shroud.
Pressure Requirement
The static pressure drop across the terminal unit shall not be more than 53Pa (0.22 in. W.G.) at the selected design air fow.
The pressure independence shall be achieved using a differential pressure type velocity sensor on a feed forward control loop.
The velocity sensor shall be a differential pressure multi-point sensing type using the reliable pitot tube concept for air fow measurement.
The high and low tubing connection shall be air tight to prevent leakage affecting the accuracy of the air fow measurement. Airfow measurement accuracy must be
within +/- 5%.
Noise
Sound power level in each octave band 2 through 6 shall not exceed the following when operating at the rated air fow rate with 125Pa (0.5 in W.G.) static pressure
across the terminal unit:
Controls
The VAV controller shall be Lon based microprocessor based direct digital control (DDC) with open system concept to ensure ease of interfacing on site with others.
Each VAV unit shall have its own dedicated, stand-alone microprocessor-based, truly independent LonMark open system controller.
Each VAV controller shall accept standard thermistor input for temperature sensing.
All the VAV units shall be capable of stand-alone or networking operation. In networking mode, the DDC controller shall be truly open to be freely integrated to existing
LonWork BAS without any additional hardware or software.
As a minimum, the user shall have the capability of monitoring the following dynamics up-dated information through each of the operator interface devices :-
- zone temperature
- actual live airow
- desired set-point airow
- cooling set-point etc
- operating mode
The room thermostat shall have a LCD display for room temperature and set point adjustment capability.
The controller shall have an overriding function to occupied/unoccupied mode.
As a minimum the user shall have the ability to monitor and control the following set-points through each of the operator interface devices :-
- cooling set-point
- minimum and maximum air ows
- neutral zone
- occupied/unoccupied time schedule
- room temperature
- live actual air ow
VAV Terminal Units
VAV TERMINAL UNITS
All stated specications are updated at the printing date and subject to change without notice or obligation. The actual product might differ from pictures shown.
VAV page 12 of 15
Control Components
ASLI VAV terminal units are compatible with virtually all VAV controllers and thermostats. Below are some of the VAV controllers and thermostats combination that ASLI
offers. Please contact ASLI sales representative for more information of the control components.
Alerton BACtalk VAVi-SD
The Alerton BACtalk VAVi-SD controller with integrated actuator is a versatile BACnet-compliant
controller, providing pressure independent control of any single-duct Variable Air Volume (VAV)
box. As a native BACnet controller, the VAVi-SD integrates seamlessly with BACnet system,
communicating up to 76.8 Kbps on a BACnet MS/TP LAN.
BACtalk Microset II
BACtalk Microset II Wall Unit
BACtalk Microset II is an intelligent and attractive programmable wall unit that updates
the functions of a typical thermostat. Microset II connects to Alertons BACtalk VisualLogic
Controllers (VLCs) and serves as a tenant control center and eld service tool. Sleek styling, a
backlit Liquid Crystal Display (LCD) and simple pushbutton controls make operation intuitive.
The LCD simultaneously displays the setpoint, room and outside air temperatures in Fahrenheit
or Centigrade and fan status.
Trend IQLVAV
IQLVAV is a terminal unit controller with an integral damper actuator for pressure -independent
VAV applications. The IQLVAV supports communication with other IQL and LonMark devices
over a LonWorks network. A LINC unit provides an interface to other Trend IQ system current-
loop networked devices.
SDU-LON
The SDU-LON, Smart Display Unit, enables the user to view and adjust selected parameters
(sensors, knobs, drivers, switches, digital inputs) via a 4 x 20 character electro-luminescent
display, and four illuminated push buttons. It provides the IQLVAV with a real time clock, a time
zone, and a calendar. It is associated with a particular IQLVAV either using a combination of the
push-buttons or using IQLTool2. SDUs also support password protection, using the controllers
built-in security.
VAV Terminal Units
VAV TERMINAL UNITS
All stated specications are updated at the printing date and subject to change without notice or obligation. The actual product might differ from pictures shown.
VAV page 13 of 15
Control Components
ASLI VAV terminal units are compatible with virtually all VAV controllers and thermostats. Below are some of the VAV controllers and thermostats combination that ASLI
offers. Please contact ASLI sales representative for more information of the control components.
Siemens GDB181.1E/3
Compact controllers for plants with variable and constant air volume with the air volume as an
auxiliary variable. Comprised of pressure difference sensors, digital air volume controller and
actuator; Operating voltage AC 24 V; P-response, nominal torque 5/10 Nm, air damper working
range mechanically adjustable between 0 and 90, prewired with 0.9 m long connecting cable.
Suitable for stand alone system
ALE05U
The ALE05U series is a microprocessor based wall mounted proportional integral (PI)
temperature controller for controlling fan coil unit heating and cooling applications. It has a
large and clear LCD display which is both aesthetic in design and user friendly in operation.
Belimo NMV-D2M
The VAV-Compact NMV-D2M controller has PI control characteristics and is used for the
pressure independent control of VAV air control units. Stepped-mode constant ow control
e.g. switch or clock program. Variable ow with modulating reference variable based on, for
example, temperature, occupancy, room thermostat, DDC or LONWORKS system, allowing
demand-related, energy-saving ventilation of individual rooms or zones of air-conditioning
systems. Maintenance-free sensor technology, thoroughly proven in a great variety of previous
applications, means that the controllers can offer total reliability and dependability in various
climate conditions.
ALE05U
The ALE05U series is a microprocessor based wall mounted proportional integral (PI)
temperature controller for controlling fan coil unit heating and cooling applications. It has a
large and clear LCD display which is both aesthetic in design and user friendly in operation.
VAV Terminal Units
VAV TERMINAL UNITS
All stated specications are updated at the printing date and subject to change without notice or obligation. The actual product might differ from pictures shown.
VAV page 14 of 15
Control Components
ASLI VAV terminal units are compatible with virtually all VAV controllers and thermostats. Below are some of the VAV controllers and thermostats combination that ASLI
offers. Please contact ASLI sales representative for more information of the control components.
Matrix UAV0560L
UAV0560L is an application specifc DDC for pressure independent variable Air Volume
Terminal Boxes. It can work as a stand-alone controller as well as a controller on a twisted-
pair, unpolarized, free topology network. UAV0560L has an on-board differential pressure
transducer to measure airow through the VAV terminal box via a differential pressure pitol
tube sensor within the box. The controller has two triac outputs for driving oating position
damper actuator, and four additional triac outputs for heaters, fan and hot water valve control.
UAV0560L is a LonMarkTM compliant controller designed to communicate on LonTalkTM open
system network.
SAV3HD
The SAV3HD is a wall mount command module with display for Variable Air Volume terminal
boxes. SAV3HD works in conjunction with VAV Controllers such as Matrix iS21 UAV0520L &
UAV0506L in local mode stting by exchanging the zone temperature, temperature set-point,
bypass time via hard wire. It has a 92mm x 50mm LCD screen to display the time & date of the
day, zone temperature and remaining bypass time.
Invensys Micronet LonMark VAV Series
The I/A Series MicroNet LONMARK VAV Series (Variable Air Volume) Controllers are interoperable,
LONMARK-compliant controllers. When programmed using WorkPlace Tech Tool or loaded with
a pre-engineered application, they provide a wide range of control strategies for pressure
independent terminal boxes with, or without, reheat capabilities. Both models provide an
integral actuator with manual override, an integral patented pressure transducer, one digital
input, one universal input, Sensor Link (S-Link) support, LED indication, and over-the-shaft
damper mounting. In addition, the MNL-V2RVx model provides one analog output and three
digital outputs. These controllers can function either in a standalone mode or as part of a
LONWORKS FTT-10 Free Topology communications network.
Invensys Micronet Sensor
The I/A Series MicroNet Sensors (MN-SXXX series) are a family of digital wall temperature
and humidity sensors for use with I/A Series MicroNet controllers. These sensors feature a
Sensor Link (S-Link) communication protocol which provides a simple two-wire interface
for power and exchange of sensor and subbase information. Subbase information includes
selecting occupancy override, fan speed, operating mode, or emergency heat. Available in
twelve models, MN-SXXX series sensors provide an integral analog-to-digital conversion for
elimination of sensor-to-controller noise effects and wire resistance offset.
VAV Terminal Units
VAV TERMINAL UNITS
All stated specications are updated at the printing date and subject to change without notice or obligation. The actual product might differ from pictures shown.
VAV page 15 of 15
Control Components
ASLI VAV terminal units are compatible with virtually all VAV controllers and thermostats. Below are some of the VAV controllers and thermostats combination that ASLI
offers. Please contact ASLI sales representative for more information of the control components.
Honeywell Excel 10
Honeywells Excel 10 VAV Box Controller is an excellent, low-cost control solution for any size
commercial building. The standard energy-saving setpoint reset options, open communications
protocol and low-cost mounting design, make this controller a smart choice for all the right
reasons. Suitable for LONWORKS network.
Thermostat T7770
The T7770 are direct-wired wall modules used in conjunction with W7751B,D,F,H Controllers.
The zone controlled by the W7751 Controllers will typically use a T7770 wall module with a
temperature sensor for space temperature measurement in a minimum system conguration.
Additional features available in the T7770 model include analog setpoint input, override digital
input pushbutton, override status LED and E-Bus network access jack.
Yamatake VAV Controller with Damper Actuator
Inflex VC Model WY5306C is a damper actuator with DDC (direct digital control) inside
that controls a VAV (variable air volume) unit in a building air-conditioning system. Inlex
VC, integrated in a VAV unit cost-effectively controls temperature plus air volume. Comfort
therefore is compatible with energy saving. Besides, Inlex VC offers building owners and
operators the fexible and high-performance controls of various VAV units. It is a LONMARK
certied product.
Neoplate QY7290
The QY7290 Neoplate is a user terminal for use with specifc Yamatake controllers. Neoplate
is designed to look like regular lighting switch and ensures complete compatibility with any
interior design. The temperature set point change based on absolute value, relative value or
perception of temperature.