You are on page 1of 1

HV Modular induction motors

Technical data for totally enclosed squirrel


cage three phase motors

3000 V - 50 Hz

IP 55 - IC 611 - Insulation class F, temperature rise class B


Efficiency
Output Motor
kW
type

Full
3/4
Product Speed load
load
ID
r/min 100 % 75 %

500 r/min = 12 poles

Power factor

Current

Torque

Full
3/4
load
load
100 % 75 %

IN

IS

I0

TN

TS

Tmax

IN

Nm

TN

TN

Rotor
inertia
kgm2

Motor
weight
kg

Sound
pressure
level LP
dB(A)

3000 V 50 Hz

160

AMI 400L12A

10122

493

92.4

92.3

0.72

0.66

47

3.8

25

3099

0.7

1.7

19.3

2920

76

180

AMI 400L12A

10123

492

92.3

92.2

0.70

0.64

53

3.8

29

3492

0.8

1.8

19.1

2920

76

200

AMI 400L12A

10124

492

92.5

92.4

0.71

0.65

59

3.8

32

3879

0.8

1.8

20.5

3010

76

224

AMI 400L12A

10125

492

92.7

92.6

0.71

0.65

66

3.9

36

4343

0.8

1.8

21.9

3110

76

250

AMI 400L12A

10126

492

92.9

92.8

0.72

0.66

72

3.8

37

4848

0.8

1.7

24.8

3300

76

290

AMI 400L12A

10127

492

93.1

93.0

0.73

0.67

83

3.8

42

5624

0.8

1.7

27.7

3490

76

315

AMI 450L12A

10128

493

94.1

94.1

0.74

0.68

87

4.4

45

6099

0.9

1.9

39.7

3900

76

355

AMI 450L12A

10129

493

94.0

94.2

0.76

0.71

96

4.1

45

6882

0.8

1.8

42.3

4000

76

400

AMI 450L12A

10130

493

94.1

94.4

0.77

0.72

106

4.0

48

7752

0.7

1.7

45.2

4130

76

450

AMI 450L12A

10131

493

94.2

94.5

0.75

0.70

122

4.2

59

8721

0.8

1.8

47.7

4250

76

500

AMI 450L12A

10132

493

94.4

94.7

0.77

0.73

132

4.0

59

9687

0.7

1.7

53.3

4490

76

530

AMI 450L12A

10133

493

94.6

94.8

0.76

0.71

141

4.2

66

10260

0.8

1.8

56.0

4630

76

560

AMI 500L12A

10134

493

94.8

95.1

0.78

0.74

146

4.0

64

10839

0.6

1.8

70.7

5170

76

630

AMI 500L12A

10135

494

95.0

95.2

0.78

0.74

163

4.2

72

12186

0.6

1.9

79.6

5460

76

710

AMI 500L12A

10136

494

95.1

95.3

0.78

0.73

184

4.5

84

13734

0.7

1.9

88.0

5760

76

800

AMI 500L12A

10137

494

95.3

95.5

0.79

0.75

206

4.3

87

15458

0.7

1.8

97.8

6070

76

850

AMI 500L12A

10138

494

95.3

95.4

0.78

0.74

219

4.6

98

16435

0.7

1.9

105.9

6370

76

1000

AMI 560L12A B

10139

493

95.4

96.0

0.83

0.80

244

4.1

87

19371

0.6

1.9

160.8

7680

74

1120

AMI 560L12A B

10140

493

95.6

96.0

0.81

0.77

278

4.3

111

21682

0.6

2.0

160.8

7700

74

1250

AMI 560L12A B

10141

493

95.7

96.2

0.81

0.78

309

4.4

121

24191

0.6

2.0

176.9

8080

74

1400

AMI 560L12A B

10142

495

96.0

96.4

0.80

0.76

350

4.6

146

27033

0.7

2.1

194.1

8470

74

1600

AMI 560L12A B

10143

495

96.2

96.6

0.81

0.78

394

4.4

146

30865

0.7

1.9

227.1

9240

74

1800

AMI 560L12A B

10144

496

96.5

96.7

0.79

0.74

454

4.9

202

34649

0.7

2.1

262.1

10000

74

2000

AMI 630L12A B

10145

495

96.3

96.8

0.84

0.82

477

4.6

153

38566

0.7

1.9

351.9

11390

75

2240

AMI 630L12A B

10146

496

96.5

96.9

0.84

0.82

529

4.8

168

43165

0.7

1.9

424.3

12570

75

2500

AMI 630L12A B

10147

496

96.7

96.9

0.83

0.80

600

5.5

224

48135

0.9

2.2

478.5

13520

75

2650

AMI 630L12A B

10148

496

96.8

97.0

0.82

0.79

639

5.7

251

50969

0.9

2.3

510.5

14000

75

Data presented in rating lists are typical values. Guaranteed values on request.
All engineered motors are optimized for the specified application.
Accurate motor data will be given on request at quotation phase.
Legally binding performance and specification data is given to the end user once each order is confirmed.

ABB | BU Motors and Generators | HV induction motors, technical catalog for IEC motors EN 09-2011 83

You might also like