You are on page 1of 8

GEE ENTERPRI SES

LANE NO. 2, NEW MOHNI PARK,


P.O KHALSA COLLEGE, AMRITSAR.
Phone 0183-5067417,2221884, FAX NO-0183-5093507


Ref.No:GEE/AMW/12052014/01
Dated:May 12, 2014


M/s PWD
Srinagar.



Subject : Your requirement of Hot Water Generator Model AMW03

Dear Sir,

Thank you for your keen interest on our Hot Water Generator model AQUAMATIC 3 lac kcal, the
instant high efficiency Hot Water Generator.

You will appreciate that the AQUAMATIC not only brings you phenomenal savings in operating
cost but also ensures a constant uninterrupted supply of hot water. Our offfer for AMW comprises
following :

Scope of Supply
Battery Limit
PERFORMANCE CRITERIA
Scope of supply Exclusions
Price Schedule
Terms & Conditions
Product Catalogue
We trust that this is line with your requirement. Should you need further clarification, please do get
in touch with us.
Thanking you and assuring you of our best services at all times.

Yours faithfully,
For

Prabhpreet Singh
+91-9888413144












GEE ENTERPRI SES
LANE NO. 2, NEW MOHNI PARK,
P.O KHALSA COLLEGE, AMRITSAR.
Phone 0183-5067417,2221884, FAX NO-0183-5093507


SCOPE OF SUPPLY
MAIN UNIT

One Heat exchanger, consisting of two closely wound, helical, concentric coils,
arranged to give three passes on flue gas side and made of ERW tubes

One Shell assembly consisting of a single jacket, enclosing the heat exchanger coil to
serve as an integral Combustion Chamber, duly insulated externally

One Mono-bloc burner suitable for HSD firing with ON-OFF control

One Dust protected, pre-wired control panel housing a set of contactors & MCB,
motor protection and fuses

One Set of water piping connecting the unit & pump





ANCILLARIES

One Centrifugal pump with mechanical seal and motor for hot water circulation

PIPING

One Set of oil piping from flange battery limit to burner

One Inter connecting piping between pump outlet and inlet of Hot Water Generator


MOUNTINGS AND FITTINGS

One Safety relief valve in hot water out line
One Non-Return Valve at the fuel bypass line.
One Filter on fuel line

INSTRUMENTS, CONTROLS AND SAFETIES

One Temperature Indicator-cum-controller with 2 set points, one for burner ON-OFF
control and the other for safety for high outlet water temperature
One Pressure gauge at fuel pump outlet






GEE ENTERPRI SES
LANE NO. 2, NEW MOHNI PARK,
P.O KHALSA COLLEGE, AMRITSAR.
Phone 0183-5067417,2221884, FAX NO-0183-5093507





BATTERY LIMITS

Hot water line

Suction of feed water-circulating pump

Outlet of spring loaded safety valves

Outlet of Hot Water Generator.






Fuel circuit

Inlet of fuel filter.


Air and fuel gas

Suction of blower

Flue gas outlet of Hot Water Generator

Electrical

Terminal connections on control panel, instruments and motor
(P&I diagram attached)




GEE ENTERPRI SES
LANE NO. 2, NEW MOHNI PARK,
P.O KHALSA COLLEGE, AMRITSAR.
Phone 0183-5067417,2221884, FAX NO-0183-5093507



PERFORMANCE CRITERIA

In order to ensure that the boiler smoothly and reliably gives you a designed service it is
important that all the important input conditions are complied for best results. The input
parameters which
High Speed Oil (HSD)
Net Calorific Value - 10,200 Kcal/Kg
Flash Point - 32C
Water Content - 0.05% Vol.(Max.)
Kinematic Viscosity - 2.5 cst @ 50C
Pour Point - 5C
Sediment - 1% Wt Max.
Sulphur - 1 % Wt Max.

Water quality Water to be used in Hot water generator for primary circuit,
(Primary circuit) should be DM/soft water having the following specifications
Total dissolved solids : 100 ppm (max.)
Total hardness : Commercial zero
pH value : 8 to 9

Water quality Water being used in Hot Water Generator for Secondary
(Secondary circuit) circuit (utility) should meet the
Langelier Saturation Index : 0.5
The parameters for working out Index are as below:
Total hardness : <250 ppm
Total dissolved solids : <700 ppm
Turbidity : <2 NTV
Total alkalinity : < 250 ppm
pH value : 7.5 - 8.5
Chloride : < 30 ppm
Sulphate : < 300 ppm
Phosphate : < 5 ppm
Silica : < 25 ppm
Iron : < 0.1 ppm

Scheme Piping scheme should be followed as per P&I diagram

Electrical Power supply 415V5%, 50 Hz, 3%, 3, 4 wire









GEE ENTERPRI SES
LANE NO. 2, NEW MOHNI PARK,
P.O KHALSA COLLEGE, AMRITSAR.
Phone 0183-5067417,2221884, FAX NO-0183-5093507




Note:

Customer is advised to install CVT of the following specifications to take care of
voltage fluctuation
Rating : 0.35 Kva
Nominal output voltage : 220 volts
Output voltage variation : 3%
Correction speed : > 300 volts / sec
CVT should have fully in-built load to line isolation and should be connected as shown
in the electrical diagram. Data applicable for altitude of 600 mts, above mean sea level,
for operating altitude beyond 600 mts, above MSN check with Thermax HO.

Fuels to confirm to enclosed IS specification.




GEE ENTERPRI SES
LANE NO. 2, NEW MOHNI PARK,
P.O KHALSA COLLEGE, AMRITSAR.
Phone 0183-5067417,2221884, FAX NO-0183-5093507




EXCLUSIONS


1. Chimney and flue gas duct between main unit and chimney.

2. Fuel pipeline up to the inlet of the unit.

3. All cabling at site.

4. Power supply, fuel, water and other utilities.

5. All user equipment, their heat exchangers, automatic and manual valves and
temperature controllers.

6. Calorifier of unit, expansion cum make up tank, connected piping, valve &
strainer

7. Pipeline insulation.

8. All civil and structural work for installing the unit.

9. Hot water piping and insulation for utility

10. Water treatment system

11. Any other items not specifically mentioned in our offer




GEE ENTERPRI SES
LANE NO. 2, NEW MOHNI PARK,
P.O KHALSA COLLEGE, AMRITSAR.
Phone 0183-5067417,2221884, FAX NO-0183-5093507



SERVICES

SUPERVISION SERVICES OF ERECTION & COMMISSIONING

1. The unit covered under this offer comes in semi-assembled/ fully assembled
condition. Unloading and assembling at site of the heater, its accessories, mountings
and fittings have to be done by the customer.

2. The services of our Erection Engineer, who would offer guidance and supervision in
this matter, would be available at the charge mentioned in this quotation.

3. This service charge payable to us covers:

DRAWINGS: Terminal point, layout, foundation details (not foundation design)
electrical wiring diagram and P&I diagram.

TECHNICAL DOCUMENTS: Installation / Operation and Maintenance Manual

GUIDANCE ON: Selection & installation of heater house accessories and
commissioning.

TRAINING AT SITE: For purpose of user's education for equipment operation and
maintenance.

4. This service charge does not include:
- Labour (skilled and unskilled)
- Tools and tackles
- Utilities (including power, water, compressed air, fuel, gas etc.)
- Consumables etc.

These are to be supplied by the user, as and when required, for unloading and assembling
of the heater, its accessories, mountings and fittings, during erection and commissioning.

5. This charge does not include fees payable for inspection of the heater and its
accessories, if any. All such charges are to be paid by the purchaser




GEE ENTERPRI SES
LANE NO. 2, NEW MOHNI PARK,
P.O KHALSA COLLEGE, AMRITSAR.
Phone 0183-5067417,2221884, FAX NO-0183-5093507


PRICE SCHEDULE


Least Acceptable Price OF Model

AMW-03/HSD(with calorifier ) : Rs 7,23,000/-
AMW-03/HSD(without Calorifier) : Rs 4,53,000/-
Capacity-3,00,000 Kcal/Hr


- Packing & Forwarding : Inclusive
- Excise Duty : @10.36% extra
- Transit Insurance : @ 1% extra
- Sales Tax : @ 2% extra against form-C or full
tax @ 10.5%
- Freiight : Extra at actuals
- Octroi : Extra at actuals
- Price basis : Ex-Works, Pune
- Payment Terms : 40% advance along with the order
and balance against proforma
invoice prior to despatch.
(Note: The above referred taxes & duties are the prevailing rates and if there is any variation at the
time of despatch of the equipment, the same shall be to your account.
upervision of Erection & commissioning : (inclusive)

- Delivery : 12-14 Weeks from the date of
receipt of your order with requisite
advance

(Note - The above mentioned taxes and duties have been considered at the prevailing rates and if
there is any variation on the same at the time of despatch, the same shall be to your account. )

PAYMENT TERMS - For Equipment & Supervision Charges :

40% advance alongwith the order and the balance alongwith taxes & duties to be paid against
Proforma Invoice prior to despatch. We shall send you Proforma Invoice inclusive of all taxes
and incidental charges, around the time the ordered materials are ready for despatch in full or in part.