DEVELOPMENT OF I-BEAM TO CHS COLUMN MOMENT

CONNECTIONS WITH EXTERNAL DIAPHRAGMS FOR SEISMIC


APPLICATIONS
Alireza Bagheri Sabbagh, Tak-Ming Chan

School of Engineering, University of Warwick, Coventry, UK
a.bagheri-sabbagh@warwick.ac.uk; t.m.chan@warwick.ac.uk
ABSTRACT
In this paper monotonic FE analysis is used to develop I-beam to CHS column full
strength moment connections for earthquake applications. The main components
are external diaphragm plates bolted to the beam and welded to the whole
circumference of the column to transfer the beam forces to both near and far sides
of the column. In the FE models, connector elements are used in places of the
bolts to incorporate the connection bolt slip in the analysis. The target performance
is to produce large plastic deformation in the beam while the column remains
elastic. The web panel zone and other connection components are allowed to
partially contribute in the overall inelastic deformation of the connection. Excessive
yielding and distortion in the web panel and large stress concentration in the
diaphragms in front of the column walls should be avoided as these can lead to
weld fracture between the diaphragm plates and the column. Various ring widths
for the diaphragm plates were examined and the value designed for the full
strength of the beam flanges found to limit the web panel yielding and distortion. In
addition, different types of vertical stiffeners are used in the connection region to
eliminate the stress concentration in the diaphragms. Two pairs of triangular
vertical stiffeners with the length extended to the end of the diaphragm plates
provide the required performance. Cyclic FE analysis was also performed and
shown that a degree of cyclic deterioration occurs in the moment-rotation
behaviour, but similar conclusions as in the monotonic FE analyses can be drawn
for the developed connections.

1 INTRODUCTION
The integrity of the common I-beam to H- section column moment connections can
be provided by using continuity plates inside the column in front of the beam
flanges [1-3]. This well known detailing, however, cannot be easily employed for
tubular columns which typically produce higher load resistance in both framing
directions than H- section columns. Different configurations for I-beam to tubular
column connections have been investigated including through diaphragm, external
diaphragm and through plate connections [4-11]. Experimental work on various
2

details of I-beam-to-CHS column connections was performed by Alostaz and


Schneider to investigate their elastic and inelastic behaviour [5, 6]. They showed
that a direct connection to the tubular column wall causes premature flange
fracture and severe local distortion on the tube wall [5, 6]. External diaphragm
plates (Fig. 1a) have been used to transfer the beam forces around the column [4-
9]. It is found that if appropriately designed the inelastic behaviour of the
connections equipped with the diaphragm plates can be improved compared with
the direct connection [4-9]. Stress concentration and out-of-plane failure
deformation in the diaphragm plates as well as large web panel distortion have
been reported [5-9] which led to fracture of the plates, welds and columns (Fig. 1b).
Shifting the beam away from the face of column [5, 6] and designing the diaphragm
ring width for the full strength of the beam flange [9] have been recommended to
provide uniform stress flow around the column.







(a) (b)

Fig. 1 (a) Schematic drawing of external diaphragm connections (b) Fractures in
diaphragm plate, weld and column of an external diaphragm connection [6]
In this paper, an evolutionary process for I-beam to CHS column connections is
presented by means of FE analysis leads to an optimum ring width for external
diaphragm plates. The web panel excessive yielding and deformation need to be
avoided. Furthermore, appropriate stiffeners are developed to eliminate stress
concentration in the diaphragm plates in front of the column which potentially
causes weld fracture between the diaphragm and the column.
In the FE analyses presented in this paper, connector elements are used in places
of the bolts representing the slip-bearing action of the connections which found to
be highly beneficial to achieve stable hysteretic cycles [12-14]. This method has
already been used by Lim and Nethercot [15, 16] for monotonic FEA and by
3

Bagheri Sabbagh et al. [17, 18] for both monotonic and cyclic FEA. A more
complex method models the body of the bolts and accounts for contact interactions
to simulate the slip-bearing action [19-20]. This method can be excessively time
consuming especially for cyclic loading analysis and deals with more complicated
converging issues compared with the modelling method using connector elements.
2 Design considerations of the I-beam-to-CHS column connections
The connections were designed so as to accommodate plastic hinges in the beam
at the location after the connection while the column and connection components
remain elastic according to the well known strong-column-weak-beam concept. A
degree of inelastic behaviour was allowed in the column web panel [21].
Overstrength and strain hardening factors of 1.25 and 1.1, respectively were used
in the design of the connection according to Eurocode 8 [2]. The slip resistance
(R
n
) of the bolts using AISC Specification [22] was such that no slip occurs in the
elastic region up to the plastic moment of the beam. The connection slip, however,
was allowed in the inelastic region which in the cyclic loading results in stable
hysteresis behaviour [12, 13]. After a few cycles the slip resistances of the bolts
degrade significantly mainly due to the reduction of the frictional coefficient and
clamping forces of the bolts [12, 13& 18]. This was accounted for both in
monotonic and cyclic FEA by assuming 50% reduction in the design slip resistance
[13, 18].
A cantilever beam-to-column connection was used with 2m length column and
beam (Fig. 2), representing distances between inflection points of an external
frame with 4m span under lateral loading. The schematic view and dimensions of
the designed connection using standard beam, UB 20313330, CHS column,
24410 and the diaphragm plates are shown in Fig. 2. The diaphragm thickness is
15mm designed for the coupling forces projected to the connection from the
overstrength plastic moment in the beam using nominal yield stress of 275MPa.
The ring width of the diaphragm plates (w) varies to find out the optimum value as
presented in Section 5. A complete ring welded to the column circumference was
chosen because in a partial ring, stress concentration at the toes of the weld lines
can causes initiation of crack. A web plate with 8mm thickness and 160mm height
used to transfer the shear forces to the column.



4


w










Fig. 2 Dimensions and section sizes of the investigated I-beam-to-CHS column
connections with external diaphragm plates
3 Details of the FE models
FE analysis employing ABAQUS [23] was used for the investigation on the I-beam
to CHS column connections with external diaphragms. The boundary conditions,
lateral restraints and loading points are shown in Fig. 3a and the connector
elements in places of the bolts are shown in Fig. 3b. The lateral restraints were
applied at both the top and bottom flanges at the plastic hinge region and loading
end of the beams according to the AISC Seismic Provisions [3]. Tie constraints
were used for the welded connections between the diaphragm and web plates and
the column. Other parameters of the FE models are:
Element type: Shell elements with 8 nodes and reduced integration, S8R, Mesh
sizes: 1010mm for the beam and diaphragm and web plates and 2020mm for
the column, and Material: bi-linear stress-strain behaviour with yielding stress of
275MPa (S275) for the beams and the plates and yielding stress of 355MPa
(S355) for the columns, E=210GPa (modulus of elasticity), Es=E/100 (Second
modulus) and =0.33 (Poisson`s ratio). Kinematic hardening rule was applied to
the Von-Mises yielding surface for the cyclic analyses.
5

Hinge connections


Lateral restraints in Y direction




Loading points in Z direction
(a) (b)
Fig. 3 (a) Boundary conditions, lateral restraints and loading points (b) Connector
elements
The connector elements from ABAQUS library [23] were a parallel combination
(Fig. 4) of a CARTESIAN element for elastic- plastic behaviour and a STOP
element for limiting the movement range within the clearance of the bolt holes
(1mm by assuming the bolts at the centre of the holes). The behaviour of the
connector elements (Fig. 4) was rigid up to the slip resistance (R
n
) of the bolts,
movement of the bolts within the tolerances of the bolt holes (1mm) and rigid
bearing hardening. These assumptions were made since the exact positions of the
bolts in the holes and therefore contact behaviour are unknown in the actual
connection assemblies. This slip-bearing action model has already been used by
Shen and Astaneh-Asl [24] and Bagheri Sabbagh et al. [18].







Connector elements
6









Fig. 4 Slip-bearing action of the connector elements
4 FE results for development of I-beam-to-CHS column connections with
different diaphragm ring widths
An evolutionary process was used for the development of the external diaphragms
for the I-beam-to-CHS column connections. Stress distribution and failure
deformations of the FE analyses are shown in Fig. 5 and normalised moment-
rotation (M/M
p
-) curves calculated at the plastic hinge location are shown in Fig.
6. M
p
is the overstrength plastic moment of the beams (1.25 times the nominal
plastic moment). The horizontal portion of the M/M
p
- curves (Fig. 6) occurred at
around 0.5M
p
corresponds to the connection slip activated in the FE analyses as
discussed previously in Section 2.
The FEA without the external diaphragm plates (direct connection) showed large
yielding area and excessive distortion in the column web panel and no yielding in
the beam (Figs. 5 and 6, w= 0). By using a diaphragm ring tied to the whole
circumference of the column with the width of w= 30mm, a degree of yielding was
mobilised in the beam, although the distortion and yielding in the column web panel
still took over (Figs. 5 and 6, w= 30). By increasing the ring width from 30mm to
50mm, local buckling occurred in the beam after the connection region and the
column web panel contributed less in the overall deformation (Fig. 5, w= 50) than
the connection with w= 30mm. Local flange and web buckling in the beam led to
strength degradation at around 0.08rad in the moment-rotation curve (Fig. 6, w=
50). The connection with w= 70mm showed even less yielding in the web panel
(Fig. 5, w= 70) and strength degradation (Fig. 6, w= 70) due to the beam local
buckling initiated earlier (at around 0.07rad) than the connection with w= 50mm.
R
Rn
Rigidplastic
Stop
+1mm 1mm
hole`scentre
7



w= 0 w=30mm




Failure deformations


w= 50mm w= 70mm




Failure deformations

w= 90mm w= 110mm





Fig. 5 Failure deformations and Von-Mises stress contours of the I-beam-to-CHS
column connections with different diaphragm ring widths (w=0, 30, 50, 70, 90 and
110mm)
Web panel yielding at the peak load
8










Fig. 6 Moment-rotation curves of the I-beam-to-CHS column connections with
different diaphragm ring widths (w=0, 30, 50, 70, 90 and 110mm)
The failure deformations and moment rotation curves of the connections with w=90
and 110mm were close to those of the connection with w=70mm (Figs. 5 and 6).
Increasing the diaphragm ring width, however, reduced the yielding region in the
web panel (shown in Fig. 5, w=90 and 110mm) which in the connection with w=
110mm was nearly vanished. The diaphragm plate with w= 90mm showed a
degree of yielding in the web panel which is acceptable according to the current
design codes [1-3; 22] discussed by El-Tawil et al [21], therefore in this case
assumed as the optimum diaphragm width. The diaphragm width of w= 90mm also
meets the design criteria proposed by Wang et al. [9] to resist full strength of the
beam flanges.
In all the FE analyses presented in this section for different diaphragm widths (w=
0, 30, 50, 70, 90 and 110mm), stress concentration occurred in the diaphragm
plates in front of the column face. This potentially leads to weld fracture between
the diaphragm and the column as well as local buckling in the diaphragm plates
(reported by other researchers [5-9]). This stress concentration cannot be
eliminated in the compressive diaphragm either by increasing the diaphragm
thickness from 15mm to 20mm or the material yielding strength from 275MPa to
355MPa (Fig. 7). The reason can be second order effects in the compressive
diaphragm which can be intensified by initiation of the beam local buckling and
large deformations. This phenomenon is addressed in the next section.

0
0.2
0.4
0.6
0.8
1
1.2
1.4
0 0.02 0.04 0.06 0.08 0.1
M
/
M
p
(rad)
Noring
w=30mm
w=50mm
w=70mm
w=90mm
w=110mm
9

Diaphragm thickness= 20mm Diaphragm strength= 355MPa







Fig. 7 Stress concentration in the diaphragm plates with increased thickness from
15mm to 20mm and the material strength from 275MPa to 355MPa
5 FE results for development of I-beam-to-CHS column connections with
different diaphragm stiffeners
Different configurations of vertical stiffeners tied to the external diaphragms (with
w= 90mm) and the column were examined to minimise the stress concentration in
the diaphragm plates (Fig. 8). Firstly, the stiffeners inside the connection were
used between the diaphragm plates which have less architectural impact than the
outside stiffeners on top of the diaphragm plates. In the model equipped with
100mm length vertical stiffeners (Fig. 8, St1), the stress concentration initiated at
the tip of the stiffeners in the compressive diaphragm and propagated towards the
face of the column at the larger load increments. By extending the vertical
stiffeners further inside the connection (Fig. 8, St2), similar stress concentration
was observed. The stress concentration also occurred in the compressive
diaphragm plate in the connection with separated pairs of vertical stiffeners (with
50mm height) extended to the end of connection for each of the diaphragm plates
(Fig. 8, St3). The stress concentration, however, is minimised by using the same
vertical stiffeners as St3, but placed outside of the connection on top of the
diaphragm plates (Fig. 8, St4). The reason is higher connection stiffness provided
by using outside stiffeners and consequently less second order effects in the
diaphragm plates. By using a more effective triangular shape for the outside
vertical stiffeners with 100mm height in front of the column (Fig. 8, St5), the stress
concentration was completely removed in front of the column in the compressive
diaphragm, although a degree of yielding appeared at the toe of the tension
diaphragm. The reason is excessive transverse deformation of the diaphragm
plates by increasing the stiffness of the connection. By trimming the stiffeners (Fig.
8, St6) the stress concentration again initiated at the tip of the stiffeners and
propagated at the larger load increments similar to the behaviour of the
connections with St1 and St2. Therefore, using the vertical stiffeners with the
10

shorter length than the whole connection length should be avoided in this type of
connections.
St1 St2







St3 St4






St5 St6






Fig. 8 Stress concentration in the diaphragms of the connections with different
vertical stiffeners connected to the diaphragm plates and the column
Initiation of stress concentration
Initiation of stress concentration
Propagation of stress concentration
11

The moment-rotation curves of the connections with all the examined stiffeners
(Fig. 9, St1-6) are similar to that of the connection without stiffener. The strength
degradation starts at around 0.07rad due to local buckling in the beam after the
connection region. The slip resistance load level was increased by increasing the
connection stiffness (Fig. 9, St1-6). The moment-rotation curves of the connections
using St5 and with w=70, 90 and 110mm (shown by dashed lines in Fig. 9) are
very close to each other. The stress concentration in the connections with St5,
w=70 and 110mm was also removed in the compressive diaphragms in front of the
column similar to the connection with St5, w=90mm (Fig. 8, St5). The connection
with triangular stiffeners (St5) can be assumed as optimum in this case.









Fig. 9 Moment-rotation curves of the I-beam-to-CHS column connections with
different vertical stiffeners
6 Cyclic FE results for the developed connection configurations
Cyclic loading applied to the FE models using w= 70 and 90mm diaphragm plates
with and without the optimum vertical stiffeners, St5, examined in the previous
section. In the cyclic FEA, surface to surface contact was used between the
diaphragm plates and the beam flanges to avoid their penetration during the
buckling deformation. The cyclic moment-rotation curves as well as the monotonic
curves are shown in Figs. 10a and b. It is evident that the strength degradation
occurred earlier in the cyclic curves than the monotonic curves (Fig. 10) due to the
cyclic deterioration effect. The deterioration is even sharper in the cyclic FEA with
w= 70mm than that of the FEA with w=90mm (Fig. 10a). Similar to the results
obtained in the monotonic FE analyses (presented in the previous sections) it can
0
0.2
0.4
0.6
0.8
1
1.2
1.4
0 0.02 0.04 0.06 0.08 0.1
M
/
M
p
(rad)
withoutstiffener
St1
St2
St3
St4
St5,w=70
St5,w=90
St5,w=110
St6
12

be concluded that: (i) web and flange buckling after the connection region (Fig. 11)
is the main reason for the strength degradation, (ii) the connection using w= 90mm
showed less web panel yielding than the connection with w= 70mm and (iii) the
use of vertical stiffeners St5, eliminated the stress concentration in the diaphragms
in front of the column face.









(a) Without vertical stiffeners









(b) With vertical stiffeners St5
Fig. 10 Cyclic and monotonic moment-rotation curves of the connections using w=
70 and 90mm (a) without vertical stiffeners and (b) with St5
1.4
1.2
1
0.8
0.6
0.4
0.2
0
0.2
0.4
0.6
0.8
1
1.2
1.4
0.1 0.06 0.02 0.02 0.06 0.1
M
/
M
p
(rad)
monotonic,w=70
cyclic,w=70mm
monotonic,w=90
cyclic,w=90
1.4
1.2
1
0.8
0.6
0.4
0.2
0
0.2
0.4
0.6
0.8
1
1.2
1.4
0.08 0.04 0 0.04 0.08
M
/
M
p
(rad)
monotonic,w=70
monotonic,w=90
cyclic,w=70
cyclic,w=90
13







(a) (b)
Fig. 11 Failure deformations and Von-Mises stress contours for the cyclic FE
analyses of the connections using (a) w= 90mm and (b) w= 90mm with St5
7 CONCLUSIONS
Optimum configurations for I-beam-to-CHS column moment resisting connections
with external diaphragm plates were developed using monotonic FE analysis. Two
types of connection failure were eliminated: web panel distortion and stress
concentration in the diaphragm plates.
A full ring welded to the column as external diaphragm plates is needed to reduce
excessive yielding and distortion in the web panel zone. By designing the total ring
width for the full strength of the beam flanges (w= 90mm in this study) slight
yielding occurred in the web panel zone which is acceptable according to the
current design codes.
Two pairs of triangular vertical stiffeners found to eliminate the stress concentration
in the diaphragm plates in front of the column face. These stiffeners were welded
to the column face and to the top of the diaphragms outside the connection and
extended to the end of the diaphragms (St5 in this study).
Cyclic FEA also performed and confirmed the results achieved in the monotonic
FEA. Cyclic deterioration effect caused earlier strength degradation in the
developed connections (using w= 70 and 90mm with or without St5).
ACKNOWLEDGEMENTS
The authors are grateful to the Engineering and Physical Science Research
Council (EP/1020489/1) for the project funding and Dr Jos Miguel Castro from
University of Porto for his technical support.

14

REFERENCES
[1] Eurocode 3: Design of steel structures: Part 1.8: Design of joints, EN 1993-1-8: 2005
[2] Eurocode 8: Design of structures for earthquake resistance. Part 1, General rules, seismic
actions and rules for buildings. BS EN 1998-1: 2004
[3] ANSI/AISC 341-05, 2005, Seismic Provisions for Structural Steel Buildings, American Institute
of Steel Construction (AISC), Illinois
[4] Y. Kurobane, J. A. Packer, J. Wardenier, N. Yeomans, Design guide for structural hollow
section column connections, CIDECT, 2004
[5] Yousef. M. Alostaz & Stephen P. Schneider, Analytical behavior of connections to concrete-
filled steel tubes, Journal of Constructional Steel Research Vol. 40, No. 2 (1996), pp. 95-127
[6] Stephen P. Schneider & Yousef M. Alostaz, Experimental behavior of connections to Concrete-
filled steel tubes, Journal of Constructional Steel Research Vol. 45, No. 3 (1998), pp. 321352
[7] Lin-Hai Han, Wen-Da Wang, Xiao-Ling Zhao, Behaviour of steel beam to concrete-filled SHS
column frames: Finite element model and verifications, Engineering Structures 30 (2008) 1647
1658
[8] Wen-Da Wang, Lin-Hai Han, Brian Uy, Experimental behaviour of steel reduced beam section
to concrete-filled circular hollow section column connections, Journal of Constructional Steel
Research 64 (2008) 493504
[9] Wei Wang, Yiyi Chen, Wanqi Li and Roberto T. Leon, Bidirectional seismic performance of steel
beam to circular tubular column connections with outer diaphragm, Earthquake Engng Struct.
Dyn. 2011; 40:10631081
[10] Mirghaderi S.R., Torabian S., Keshavarzi F., I-beam to box column connection by a vertical
plate passing through the column, Engineering Structures, 32 (2010) 2034-2048
[11] Shahabeddin Torabian, Seyed Rasoul Mirghaderi, Farhad Keshavarzi, Moment-connection
between I-beam and built-up square column by a diagonal through plate, Journal of
Constructional Steel Research 70 (2012) 385401
[12] Kurt Michael McMullin, Abolhassan Astaneh-Asl, Steel Semirigid ColumnTree Moment
Resisting Frame, Journal of Structural Engineering, Vol. 129, No. 9, 2003
[13] Bagheri Sabbagh A., Petkovski M., Pilakoutas K., Mirghaderi R., Experimental work on cold-
formed steel elements for earthquake resilient moment frame buildings, Engineering Structures,
under review
[14] Bagheri Sabbagh A., Cold-formed steel elements for earthquake resistant moment frame
buildings, PhD thesis, University of Sheffield (2011)
[15] Lim J.B.P., Nethercot D.A., Finite element idealisation of a cold-formed steel portal frame,
Journal of Structural Engineering, 10, 1061/ (ASCE)0733-9445(2004) 130:1(78)
[16] Lim J.B.P., Nethercot D.A. , Ultimate strength of bolted moment-connections between cold-
formed steel members, Thin-Walled Structures 41 (2003) 10191039
[17] Bagheri Sabbagh A., Petkovski M., Pilakoutas K., Mirghaderi R., Development of cold-formed
steel elements for earthquake resistant moment frame buildings, Thin-Walled Structures, 53
(2012) 99108
[18] Bagheri Sabbagh A., Petkovski M., Pilakoutas K., Mirghaderi R., Cyclic behaviour of bolted
cold-formed steel moment connections: FE modelling verification including slip, Journal of
Constructional Steel Research, under review
[19] Swanson J.A., Kokan D.S., Leon R.T., Advanced finite element modeling of bolted T-stub
connection components, Journal of Constructional Steel Research 58 (2002) 10151031
[20] Citipitioglu A.M., Haj-Ali R.M. , White D.W., Refined 3D finite element modeling of partially
restrained connections including slip, Journal of Constructional Steel Research 58 (2002) 995
1013
[21] Sherif El-Tawil, Egill Vidarsson, Tameka Mikesell, and Sashi K. Kunnath, Inelastic behavior and
design of steel panel zones, Journal of Structural Engineering, Vol. 125, No. 2, February, 1999
[22] ANSI/AISC 360-05, Specification for Structural Steel Buildings, American Institute of Steel
Construction, 2005, Illinois
[23] Abaqus/CAE User's Manual, 2007, version 6.7, USA
[24] Shen J., Astaneh-Asl A., Hysteresis model of bolted-angle connections, Journal of
Constructional Steel Research 54 (2000) 317343