4HE TECHNICAL DATA SHOWN IN THE MANUAL ARE NOT BINDING 4HE IMAGES SHOWN IN THIS CATALOGUE ARE FOR DESCRIPTIVE PURPOSES ONLY 4HEY MAY THEREFORE DIFFER FROM SPECIüC MODELS
WHICH ARE SELECTED 5NIČAIR 0OLICY IS ONE OF CONTINUOUS TECHNOLOGICAL INNOVATION AND THE #OMPANY RESERVES THE RIGHT TO AMEND ANY DATA HEREIN WITHOUT PRIOR NOTICE
All rights reserved. Reproduction in whole or in part is prohibited
3
Uniflair Solutions
Product Range
AMICO LEONARDO
Chilled Water
Direct Expansion
AMICO LEONARDO
CAP
2-47 TR
Pg. 34
Cooling Solutions
High Density
ACTIVE FLOOR
Pg. 36
4
Uniflair Solutions
Product Range
ERAC
Air-cooled
ERAF
Free-Cooling
ARAF BREF
14-34 TR
Chillers
Pg. 42 - Pg.
g 44
Water Cooled
BRWC
Chillers
85-341 TR
Pg. 54
UTAT
ecoflair®
0.3 - 0.6 TR
Pg. 56
5
C OMPANY PROFIL E
6
C LOSE C ONTROL
The precision air conditioning range of solutions are able to control
the temperature and humidity inside technological rooms. Dissipation
of the heat generated by the equipment served is necessary to
ensure the operation and reliability of these complex systems and is
fundamental to avoid interruption of service.
These applications, of ten referred to as “mission critical”,
include medium to large size data centers, server rooms, control
centers, laboratories and communication rooms (fixed and mobile
telecommunications).
TECHNICAL C OOLING
High standards of design, development and production exist for
these products, the same applies to the “Aquaflair Technical
Cooling” product line, encompassing water chillers for industrial and
residential use. Synonymous with technical excellence, the “Uniflair
chiller” forms the heart of the installation which allows the chilled
water temperature to be maintained constant in industrial processes,
for precision air conditioning or any other type of ambient.
All the products are optimized to guarantee high energy efficiency,
above all at partial loads, offering free-cooling solutions and
integrated energy recovery incorporated within the unit.
E COFL AIR
A perfect example of the attention Uniflair dedicates to innovation is
represented by ecoflair® , a new modular system of air conditioning
integrated within the access floor. The ecoflair® system combines
the flexibility of operational design with the individual comfort of
the occupants who can choose their personal ambient temperature,
while at the same time guaranteeing higher energy savings compared
to traditional systems. Since this system is modular and integrates
perfectly in a modular access floor, it can be easily adapted over the
lifespan of the building itself.
7
W HY U NIFL AIR ?
Modern development in data centers, such as Blade Servers or Tera routers, and in high performance cooling, in terms of both comfort
process applications, has significantly increased the required levels of efficiency, reliability, flexibility and cooling capacity.
Combining cutting-edge technology with energy efficiency and environmental protection, Uniflair proposes solutions which ensure
continuous operation together with a high EER in all operating conditions.
Air conditioning solutions based on the use of perimeter units have evolved over recent years and are now able to cool high density loads to
such a degree as to obtain TÜV certification. Integration with the system of the Technical Cooling water chillers allows extremely high levels
of energy efficiency to be obtained together with reliability, precision and reduced acoustic impact.
Equipping the chillers with technology such as indirect Free Cooling, electronic expansion valves and double screw or multi compressors
operating in tandem leads to a greater COP even during partialization of the cooling capacity.
Optimized Management
All the Uniflair units, precision air conditioning
Security
units, Active Floor modules and chillers, can
The Uniflair range has been designed for mission
be linked together, maximizing the operating
critical installations requiring uncompromised
parameters and the real needs of the system.
reliability.
8
A DVANCED C ONTROL S
s Hot spot and humidity control: The Uniflair CRACs have precise control over
temperature and humidity and can monitor and maintain a constant pressure
in all operating conditions underneath the floor even during standard and
emergency maintenance, thus avoiding the creation of hot spots.
O P TIMIZED M ANAGEMENT
Management of the whole system allows energy consumption to be optimized and strategies of integrated
control to be implemented which would otherwise not be possible.
Uniflair ‘s precision air conditioning units, Active Floor modules and chillers can be linked together by a
LAN, maximising the operating parameters and the real needs of the system.
Particular attention has been paid to the management logic which is aimed at reducing the energy
requirement by means of a “tracking logic” for the current thermal load.
The temperature of the chilled water varies dynamically in such a way as to minimize compressor
consumption and the use of free-cooling, maintaining the desired temperature within the room.
7.0
25
6.0
Water Temperature [C°]
Energy Efficiency (EER)
20
5.0
4.0 15
3.0
10
2.0
5
1.0
0 0
Min load Middle load Middle load Max load
9
E LECTRONIC E XPANSION VALVE (EEV)
The very latest proven technologies have been applied in the new generation of Uniflair units,
including the use of electronic expansion valves in all models.
This innovation provides highly efficient electronic control of the flow of refrigerant in a precise
and stable fashion unmatched by any traditional mechanical expansion valve.
Under the control of the UNIFL AIR Control System, the EEV provides accurate control of
the refrigerant superheat in order to ensure an increase in the efficiency at low external
temperatures because it enables the unit to operate at much lower condensing pressures than
would be possible with a traditional mechanical valve.
The dehumidification function is also controlled through the operation of the EEV.
In this way dehumidification is achieved without a reduction in the airflow rate, ensuring
continuous and uniform air distribution in the space and avoiding any sudden variations in
discharge air temperature.
The management software of the unit is also capable of checking the complete state of
operation, activating policies of predictive maintenance and recording eventual anomalies. In
particular, for the chillers, the monitoring of the refrigerant load provides the possibility of rapid
intervention the event of leakage.
From 5% to 10%
Less than 5%
From 5% to 10%
10
TANDEM
Pressure
“double sized” evaporator coil - this maximisation of the
cooling effect leads to obvious increases in part load
efficiencies and resultant benefical rise in the part-load
COP (Coefficient Of Performance) . In order to compare Tevaporating Tevaporating
part-load efficiencies of different units, a number of Enthalpy Enthalpy
different parameters have been developed which take
into account the COP at 25%, 50%, 75% and 100% load fig. A - 100% Operation fig. B - part-load Operation
and calculate a weighted mean.
11
I NDIRECT F REE -C OOLING
Energy consumption continues to be a major constituent in the operating costs of modern systems. Guaranteeing the maximum reliability in
operation at the same time as reducing energy consumption to the minimum is the result of technical product choices.
The Energy-Saving versions have been designed to apply this concept to best effect.
The operating principle is based on the ability to provide free cooling for a space when the outdoor temperature is below that of the space
itself; and the lower the outdoor temperature, the greater is the energy saving.
Free-cooling is that which is provided without the need to operate compressors and, in this case, is indirect i.e.: it does not depend upon
pulling outside air into the space, so it is able to continue to guarantee stable humidity and air quality in the space.
Free-Cooling coil
pump
Free-Cooling pump
evaporator
pump
When a system is used for technological or industrial processes which operate all year round, it is important in terms of energy saving to
use solutions which exploit these conditions. Chillers equipped with free-cooling devices not only reduce energy consumption compared to
traditional systems but also limit CO2 emissions into the atmosphere, contributing therefore to reducing global warming.
When the external temperature is low enough, the free-cooling system produces chilled water using external air only, significantly reducing
energy consumption since it is limited to the fans.
12
I NTELLIGENT F REE -C OOLING
FREE-COOLING MODE
G LYCOL- FREE
Free-cooling coil
pump
Free-cooling pump
pump
evaporator
Created for applications where the use of anti-freeze solutions are not permitted, this solution, thanks to an intermediate
heat exchanger, isolates the principal hydraulic circuit from the free-cooling circuit.
Careful selection of the intermediate heat exchanger allows the delta T to be limited to only 2°C, reducing therefore the
energy drops which are intrinsic to this system.
13
Amico Series
SDCC-SUCC
Precision Air Conditioning chilled water unit with
forward curved blade fans
Power Supply
208 - 230 / 3 / 60 Hz
Range:
3 - 5 TR
Versions Available:
Downflow (SDCC)
Upflow (SUCC)
S TANDARD F E ATURES
s -ICROPROCESSOR CONTROL SYSTEM M0 LOCAL REMOTE USER s
WAY VALVE DRIVEN BY MODULATING SERVOMOTOR ELECTRONICALLY
terminal) controlled by the microprocessor control
s )MMERSED ELECTRODE BOILER HUMIDIFIER $ ( VERSIONS s &AN COMPAR TMENT WITH REMOVABLE INTERNAL PANEL FOR EASY
s ,OW SURFACE TEMPERATURE ELECTRICAL HEATERS WITH EXTENDED FINS maintenance and servicing
complete with safety thermostat for manual resetting s !DJUSTABLE FAN SPEED REGULATION DIRECTLY FROM USER TERMINAL
(T / H versions) s %LECTRIC PANEL HOUSED IN A DEDICATED COMPARTMENT IN COMPLIANCE
s $IRECT $RIVEN DOUBLE INLET &ORWARD #URVED "LADE &ANS EEC standards
s (IGH EFFICIENCY %5 PLEATED AIR FILTER HOUSED IN A METAL FRAME AND s )NTEGRATED ,!. -ANAGEMENT
filter differential pressure switch s &ULL FRONTAL ACCESSIBILITY FOR MAINTENANCE
s ,OW AIRFLOW DIFFERENTIAL PRESSURE ALARM SWITCH s 3MALL FOOTPRINT UNIT DEPTH MM
s $IRTY &ILTERS DIFFERENTIAL PRESSURE ALARM SWITCH s /UTSIDE PANELS COATED WITH EPOXY POWDER $ARK "LUE PAINT
s #OPPER AND ALUMINIUM COOLING COIL
14
TECHNICAL D ATA
Cooling capacity
Btu/hr/Btu/hr 31051/29623 43613/43613 64357/61768
Total/Sensible (3)
(kW/kW) (9.1/8.7) (12.8/12.8) (18.9/18.1)
Air flow rate @0.08in.w (20 Pa) CFM (m3/h) 1354 (2300) 1971 (3348) 2619 (4450)
Electric heat
Number of stages - 1 1 1
Number of elements - 1 1 2
Total power hp. (kW) 4.0 (3.0) 4.0 (3.0) 8.0 (6.0)
Humidifier
Nominal Steam Output lb/h (Kg/h) 4.4 (2.0) 4.4 (2.0) 6.6 (3.0)
Dimensions
Height in.(mm) 68.5 (1740) 68.5 (1740) 68.5 (1740)
Width in. (mm) 21.7 (550) 33.5 (850) 47.2 (1200)
Depth in. (mm) 17.7 (450) 17.7 (450) 17.7 (450)
Weight (Full version) (1) lbs. (kg) 287 (130) 408 (185) 573 (260)
O P TIONS
s (OT 7ATER (EATING s -OTORIZED $AMPER ON SUCTION SIDE FOR $OWNFLOW UNITS
s $EHUMIDIFICATION FOR # AND 4 6ERSIONS s /VERPRESSURE $AMPER FOR 5PFLOW UNITS
s 3ERIAL !DAPTOR 23 s &IRE $ETECTOR
s #LOCK #ARD s 3MOKE DETECTOR
s 4#0)0 #ARD s 7ATER LEAK $ETECTOR
s &RESH !IR -ODULE
15
SDCV-SUCV
Precision Air Conditioning chilled water unit with
Electronically Commutated (EC) backward curved
blade fans
Power Supply
208 - 230 / 3 / 60 Hz
Range:
3 - 5 TR
Versions Available:
Downflow (SDCV)
Upflow (SUCV)
S TANDARD F E ATURES
s -ICROPROCESSOR CONTROL SYSTEM M0 LOCAL REMOTE USER s
WAY VALVE DRIVEN BY MODULATING SERVOMOTOR ELECTRONICALLY
terminal) controlled by the microprocessor control
s )MMERSED ELECTRODE BOILER HUMIDIFIER $ ( VERSIONS s &AN COMPAR TMENT WITH REMOVABLE INTERNAL PANEL FOR EASY
s ,OW SURFACE TEMPERATURE ELECTRICAL HEATERS WITH EXTENDED FINS maintenance and servicing
complete with safety thermostat for manual resetting s !DJUSTABLE FAN SPEED REGULATION DIRECTLY FROM USER TERMINAL
(T / H versions) s %LECTRIC PANEL HOUSED IN A DEDICATED COMPARTMENT IN COMPLIANCE
s %LECTRONICALLY #OMMUTATED %# "ACKWARD #URVED "LADES &ANS EEC standards
s (IGH EFFICIENCY %5 PLEATED AIR FILTER HOUSED IN A METAL FRAME AND s )NTEGRATED ,!. -ANAGEMENT
filter differential pressure switch s &ULL FRONTAL ACCESSIBILITY FOR MAINTENANCE
s ,OW AIRFLOW DIFFERENTIAL PRESSURE ALARM SWITCH s 3MALL FOOTPRINT UNIT DEPTH MM
s $IRTY &ILTERS DIFFERENTIAL PRESSURE ALARM SWITCH s /UTSIDE PANELS COATED WITH EPOXY POWDER $ARK "LUE PAINT
s #OPPER AND ALUMINIUM COOLING COIL
16
TECHNICAL D ATA
Cooling capacity
Btu/hr / Btu/hr 31051/29623 43613/43613 70352/67962
Total/Sensible (3)
(kW /kW) (9.1/8.7) (12.8/12.8) (20.6/19.9)
Air flow rate @0.08in.w (20 Pa) CFM (m3/h) 1354 (2300) 1971 (3348) 2960 (5030)
Electric heat
Number of stages - 1 1 1
Number of elements - 1 1 2
Total power hp. (kW) 4.0 (3.0) 4.0 (3.0) 8.0 (6.0)
Humidifier
Nominal Steam Output lb/h (Kg/h) 4.4 (2.0) 4.4 (2.0) 6.6 (3.0)
Dimensions
Height in.(mm) 68.5 (1740) 68.5 (1740) 68.5 (1740)
Width in. (mm) 21.7 (550) 33.5 (850) 47.2 (1200)
Depth in. (mm) 17.7 (450) 17.7 (450) 17.7 (450)
Weight (Full version) (1) lbs. (kg) 287 (130) 408 (185) 573 (260)
O P TIONS
s (OT 7ATER (EATING s -OTORIZED $AMPER ON SUCTION SIDE FOR $OWNFLOW UNITS
s $EHUMIDIFICATION FOR # AND 4 6ERSIONS s /VERPRESSURE $AMPER FOR 5PFLOW UNITS
s 3ERIAL !DAPTOR 23 s &IRE $ETECTOR
s #LOCK #ARD s 3MOKE DETECTOR
s 4#0)0 #ARD s 7ATER LEAK $ETECTOR
s &RESH !IR -ODULE
17
SDAC-SUAC
Precision air Conditioning air-cooled direct expansion
units with forward curved blade fans
Power Supply
208 - 230 / 3 / 60 Hz
Range:
2 - 5 TR
Versions Available:
Downflow (SDAC)
Upflow (SUAC)
Refrigerant:
R410A
S TANDARD F E ATURES
s -ICROPROCESSOR CONTROL SYSTEM M0 LOCAL REMOTE USER s 2EFRIGERANT CIRCUIT INCLUDING LIQUID REFRIGERANT RECEIVER FILTER
terminal) dr yer, flow sight glass, thermostatic expansion valve, high
s 2! REFRIGERANT pressure switch
s 2OTARY ON MODEL ONLY OR 3CROLL COMPRESSOR WITH INBUILT s %LECTRONIC %XPANSION 6ALVE IS AVAILABLE AS AN OPTION
thermal protection s &AN COMPAR TMENT WITH REMOVABLE INTERNAL PANEL FOR EASY
s )MMERSED ELECTRODE BOILER HUMIDIFIER $ ( VERSIONS maintenance and servicing
s ,OW SURFACE TEMPERATURE ELECTRICAL HEATERS WITH EXTENDED FINS s !DJUSTABLE FAN SPEED REGULATION DIRECTLY FROM USER TERMINAL
complete with safety thermostat for manual reset ting (T / H s %LECTRIC PANEL HOUSED IN A DEDICATED COMPARTMENT IN COMPLIANCE
versions) EEC standards
s $IRECT $RIVEN DOUBLE INLET &ORWARD #URVED "LADE &ANS s )NTEGRATED ,!. -ANAGEMENT
s (IGH EFFICIENCY %5 PLEATED AIR FILTER HOUSED IN A METAL FRAME AND s &ULL FRONTAL ACCESSIBILITY FOR MAINTENANCE
filter differential pressure switch s 3MALL FOOTPRINT UNIT DEPTH MM
s ,OW AIRFLOW DIFFERENTIAL PRESSURE ALARM SWITCH s /UTSIDE PANELS COATED WITH EPOXY POWDER $ARK "LUE PAINT
s #OPPER AND ALUMINIUM COOLING COIL
18
TECHNICAL D ATA
Cooling capacity
Btu/hr / Btu/hr 24064/21263 35267/35267 38804/38657 55203/52439 61431/57119
Total/Sensible (3)
(kW /kW) (7.1/6.2) (10.3/10.3) (11.4/11.3) (16.2/15.4) (18.0/16.7)
3
Air flow rate @0.08in.w (20 Pa) CFM (m /h) 1030 (1750) 1736 (2950) 1942 (3300) 2619 (4450) 2619 (4450)
Compressors
Type Rotary Scroll Scroll Scroll Scroll
Number of refrigrant circuits 1 1 1 1 1
Electric heat
Number of stages - 1 1 1 1 1
Number of elements - 1 1 1 2 2
Total power hp. (kW) 2.7 (2.0) 4.0 (3.0) 4.0 (3.0) 8.0 (6.0) 8.0 (6.0)
Humidifier
Nominal Steam Output lb/h (Kg/h) 4.4 (2.0) 4.4 (2.0) 4.4 (2.0) 6.6 (3.0) 6.6 (3.0)
Dimensions
Height in.(mm) 68.5 (1740) 68.5 (1740) 68.5 (1740) 68.5 (1740) 68.5 (1740)
Width in. (mm) 21.7 (550) 33.5 (850) 33.5 (850) 47.2 (1200) 47.2 (1200)
Depth in. (mm) 17.7 (450) 17.7 (450) 17.7 (450) 17.7 (450) 17.7 (450)
Weight (Full version) (1) lbs. (kg) 287 (130) 331 (150) 408 (185) 573 (260) 573 (260)
O P TIONS
s (OT 7ATER (EATING s -OTORIZED $AMPER ON SUCTION SIDE FOR $OWNFLOW UNITS
s $EHUMIDIFICATION FOR # AND 4 6ERSIONS s /VERPRESSURE $AMPER FOR 5PFLOW UNITS
s 3ERIAL !DAPTOR 23 s &IRE $ETECTOR
s #LOCK #ARD s 3MOKE DETECTOR
s 4#0)0 #ARD s 7ATER LEAK $ETECTOR
s &RESH !IR -ODULE
19
SDAV-SUAV
Precision air Conditioning air-cooled direct expansion
units with Electronically Commutated (EC) backward
curved blade fans
Power Supply
208 - 230 / 3 / 60Hz
Range:
2 - 5 TR
Versions Available:
Downflow (SDAV)
Upflow (SUAV)
Refrigerant:
R410A
S TANDARD F E ATURES
s -ICROPROCESSOR CONTROL SYSTEM M0 s 2EFRIGERANT CIRCUIT INCLUDING LIQUID REFRIGERANT RECEIVER FILTER
(local / remote user terminal) dr yer, flow sight glass, thermostatic expansion valve, high
s 2! REFRIGERANT pressure switch
s 2OTARY ON MODEL ONLY OR 3CROLL COMPRESSOR WITH INBUILT s %LECTRONIC %XPANSION 6ALVE IS AVAILABLE AS AN OPTION
thermal protection s &AN COMPAR TMENT WITH REMOVABLE INTERNAL PANEL FOR EASY
s )MMERSED ELECTRODE BOILER HUMIDIFIER $ ( VERSIONS maintenance and servicing
s ,OW SURFACE TEMPERATURE ELECTRICAL HEATERS WITH EXTENDED FINS s !DJUSTABLE FAN SPEED REGULATION DIRECTLY FROM USER TERMINAL
complete with safety thermostat for manual resetting s %LECTRIC PANEL HOUSED IN A DEDICATED COMPARTMENT IN COMPLIANCE
(T / H versions) EEC standards
s %LECTRONICALLY #OMMUTATED %# "ACKWARD #URVED "LADES &ANS s )NTEGRATED ,!. -ANAGEMENT
s (IGH EFFICIENCY %5 PLEATED AIR FILTER HOUSED IN A METAL FRAME AND s &ULL FRONTAL ACCESSIBILITY FOR MAINTENANCE
filter differential pressure switch s 3MALL FOOTPRINT UNIT DEPTH MM
s ,OW AIRFLOW DIFFERENTIAL PRESSURE ALARM SWITCH s /UTSIDE PANELS COATED WITH EPOXY POWDER $ARK "LUE PAINT
s #OPPER AND ALUMINIUM COOLING COIL
20
TECHNICAL D ATA
Cooling capacity
Btu/hr / Btu/hr 24064/21263 35267/35267 38804/38657 55203/52439 62839/60790
Total/Sensible (3)
(kW /kW) (7.1/6.2) (10.3/10.3) (11.4/11.3) (16.2/15.4) (18.4/17.8)
Air flow rate @0.08in.w (20 Pa) CFM (m3/h) 1030 (1750) 1736 (2950) 1942 (3300) 2619 (4450) 3060 (5200)
Compressors
Type Rotary Scroll Scroll Scroll Scroll
Number of refrigrant circuits 1 1 1 1 1
Electric heat
Number of stages - 1 1 1 1 1
Number of elements - 1 1 1 2 2
Total power hp. (kW) 2.7 (2.0) 4.0 (3.0) 4.0 (3.0) 8.0 (6.0) 8.0 (6.0)
Humidifier
Nominal Steam Output lb/h (Kg/h) 4.4 (2.0) 4.4 (2.0) 4.4 (2.0) 6.6 (3.0) 6.6 (3.0)
Dimensions
Height in.(mm) 68.5 (1740) 68.5 (1740) 68.5 (1740) 68.5 (1740) 68.5 (1740)
Width in. (mm) 21.7 (550) 33.5 (850) 33.5 (850) 47.2 (1200) 47.2 (1200)
Depth in. (mm) 17.7 (450) 17.7 (450) 17.7 (450) 17.7 (450) 17.7 (450)
Weight (Full version) (1) lbs. (kg) 287 (130) 331 (150) 408 (185) 573 (260) 573 (260)
O P TIONS
s (OT 7ATER (EATING s -OTORIZED $AMPER ON SUCTION SIDE FOR $OWNFLOW UNITS
s $EHUMIDIFICATION FOR # AND 4 6ERSIONS s /VERPRESSURE $AMPER FOR 5PFLOW UNITS
s 3ERIAL !DAPTOR 23 s &IRE $ETECTOR
s #LOCK #ARD s 3MOKE DETECTOR
s 4#0)0 #ARD s 7ATER LEAK $ETECTOR
s &RESH !IR -ODULE
21
SDWC-SUWC
Precision Air Conditioning direct expansion water cooled
unit with forward curved blade fans
Power Supply
208 - 230 / 3 / 60 Hz
Range:
2 - 5 TR
Versions Available:
Downflow (SDWC)
Upflow (SUWC)
Refrigerant:
R410A
S TANDARD F E ATURES
s -ICROPROCESSOR CONTROL SYSTEM M0 LOCAL REMOTE USER s 2EFRIGERANT CIRCUIT INCLUDING LIQUID REFRIGERANT RECEIVER FILTER
terminal) dr yer, flow sight glass, thermostatic expansion valve, high
s 2! REFRIGERANT pressure switch, brazed plates condenser
s 2OTARY ON MODEL ONLY OR 3CROLL COMPRESSOR WITH INBUILT s %LECTRONIC %XPANSION 6ALVE IS AVAILABLE AS AN OPTION
thermal protection s &AN COMPAR TMENT WITH REMOVABLE INTERNAL PANEL FOR EASY
s )MMERSED ELECTRODE BOILER HUMIDIFIER $ ( VERSIONS maintenance and servicing
s ,OW SURFACE TEMPERATURE ELECTRICAL HEATERS WITH EXTENDED FINS s !DJUSTABLE FAN SPEED REGULATION DIRECTLY FROM USER TERMINAL
complete with safety thermostat for manual resetting s %LECTRIC PANEL HOUSED IN A DEDICATED COMPARTMENT IN COMPLIANCE
(T / H versions) EEC standards
s $IRECT $RIVEN DOUBLE INLET &ORWARD #URVED "LADE &ANS s )NTEGRATED ,!. -ANAGEMENT
s (IGH EFFICIENCY %5 PLEATED AIR FILTER HOUSED IN A METAL FRAME AND s &ULL FRONTAL ACCESSIBILITY FOR MAINTENANCE
filter differential pressure switch s 3MALL FOOTPRINT UNIT DEPTH MM
s ,OW AIRFLOW DIFFERENTIAL PRESSURE ALARM SWITCH s /UTSIDE PANELS COATED WITH EPOXY POWDER $ARK "LUE PAINT
s #OPPER AND ALUMINUM COOLING COIL
22
TECHNICAL D ATA
Cooling capacity
Btu/hr / Btu/hr 25169/21521 36704/35635 44442/39246 57819/53250 64895/64895
Total/Sensible (3)
(kW /kW) (7.4/6.3) (10.8/10.4) (13.0/11.5) (16.9/15.6) (19.0/19.0)
Air flow rate @0.08in.w (20 Pa) gpm (l/h) 5.15 (1406) 7.44 (2030) 9.14 (2494) 11.62 (3170) 13.43 (3662)
Compressors
Type Rotary Scroll Scroll Scroll Scroll
Number of refrigrant circuits 1 1 1 1 1
Electric heat
Number of stages - 1 1 1 1 1
Number of elements - 1 1 1 2 2
Total power hp. (kW) 2.7 (2.0) 4.0 (3.0) 4.0 (3.0) 8.0 (6.0) 8.0 (6.0)
Humidifier
Nominal Steam Output lb/h (Kg/h) 4.4 (2.0) 4.4 (2.0) 4.4 (2.0) 6.6 (3.0) 6.6 (3.0)
Dimensions
Height in.(mm) 68.5 (1740) 68.5 (1740) 68.5 (1740) 68.5 (1740) 68.5 (1740)
Width in. (mm) 21.7 (550) 33.5 (850) 33.5 (850) 47.2 (1200) 47.2 (1200)
Depth in. (mm) 17.7 (450) 17.7 (450) 17.7 (450) 17.7 (450) 17.7 (450)
Weight (Full version) (1) lbs. (kg) 287 (130) 331 (150) 408 (185) 573 (260) 573 (260)
O P TIONS
s (OT 7ATER (EATING s &RESH !IR -ODULE
s 0RESSOSTATIC 6ALVE s -OTORIZED $AMPER ON SUCTION SIDE FOR $OWNFLOW UNITS
s $EHUMIDIFICATION FOR # AND 4 6ERSIONS s /VERPRESSURE $AMPER FOR 5PFLOW UNITS
s 3ERIAL !DAPTOR 23 s &IRE $ETECTOR
s #LOCK #ARD s 3MOKE DETECTOR
s 4#0)0 #ARD s 7ATER LEAK $ETECTOR
23
SDW V-SUW V
Precision Air Conditioning direct expansion water cooled
unit with Electronically Commutated (EC) backward curved
blade fans
Power Supply
208 - 230 / 3 / 60 Hz
Range:
2 - 5 TR
Versions Available:
Downflow (SDWV)
Upflow (SUWV)
Refrigerant:
R410A
S TANDARD F E ATURES
s -ICROPROCESSOR CONTROL SYSTEM M0 LOCAL REMOTE USER s 2EFRIGERANT CIRCUIT INCLUDING LIQUID REFRIGERANT RECEIVER FILTER
terminal) dr yer, flow sight glass, thermostatic expansion valve, high
s 2! REFRIGERANT pressure switch, brazed plates condenser
s 2OTARY ON MODEL ONLY OR 3CROLL COMPRESSOR WITH INBUILT s %LECTRONIC %XPANSION 6ALVE IS AVAILABLE AS AN OPTION
thermal protection s &AN COMPAR TMENT WITH REMOVABLE INTERNAL PANEL FOR EASY
s )MMERSED ELECTRODE BOILER HUMIDIFIER $ ( VERSIONS maintenance and servicing
s ,OW SURFACE TEMPERATURE ELECTRICAL HEATERS WITH EXTENDED FINS s !DJUSTABLE FAN SPEED REGULATION DIRECTLY FROM USER TERMINAL
complete with safety thermostat for manual resetting s %LECTRIC PANEL HOUSED IN A DEDICATED COMPARTMENT IN COMPLIANCE
(T / H versions) EEC standards
s %LECTRONICALLY #OMMUTATED %# "ACKWARD #URVED "LADES &ANS s )NTEGRATED ,!. -ANAGEMENT
s (IGH EFFICIENCY %5 PLEATED AIR FILTER HOUSED IN A METAL FRAME AND s &ULL FRONTAL ACCESSIBILITY FOR MAINTENANCE
filter differential pressure switch s 3MALL FOOTPRINT UNIT DEPTH MM
s ,OW AIRFLOW DIFFERENTIAL PRESSURE ALARM SWITCH s /UTSIDE PANELS COATED WITH EPOXY POWDER $ARK "LUE PAINT
s #OPPER AND ALUMINUM COOLING COIL
24
TECHNICAL D ATA
Cooling capacity
Btu/hr / Btu/hr 25169/21521 36704/35635 44442/39246 57819/53250 64895/64895
Total/Sensible (3)
(kW /kW) (7.4/6.3) (10.8/10.4) (13.0/11.5) (16.9/15.6) (19.0/19.0)
Water flow rate gpm (l/h) 5.15 (1406) 7.44 (2030) 9.14 (2494) 11.62 (3170) 13.43 (3662)
Air flow rate @0.08in.w (20 Pa) CFM (m3/h) 1030 (1750) 1766 (3000) 1942 (3300) 2649 (4500) 3061 (5200)
Compressors
Type Rotary Scroll Scroll Scroll Scroll
Number of refrigrant circuits 1 1 1 1 1
Electric heat
Number of stages - 1 1 1 1 1
Number of elements - 1 1 1 2 2
Total power hp. (kW) 2.7 (2.0) 4.0 (3.0) 4.0 (3.0) 8.0 (6.0) 8.0 (6.0)
Humidifier
Nominal Steam Output lb/h (Kg/h) 4.4 (2.0) 4.4 (2.0) 4.4 (2.0) 6.6 (3.0) 6.6 (3.0)
Dimensions
Height in.(mm) 68.5 (1740) 68.5 (1740) 68.5 (1740) 68.5 (1740) 68.5 (1740)
Width in. (mm) 21.7 (550) 33.5 (850) 33.5 (850) 47.2 (1200) 47.2 (1200)
Depth in. (mm) 17.7 (450) 17.7 (450) 17.7 (450) 17.7 (450) 17.7 (450)
Weight (Full version) (1) lbs. (kg) 287 (130) 331 (150) 408 (185) 573 (260) 573 (260)
O P TIONS
s (OT 7ATER (EATING s &RESH !IR -ODULE
s 0RESSOSTATIC 6ALVE s -OTORIZED $AMPER ON SUCTION SIDE FOR $OWNFLOW UNITS
s $EHUMIDIFICATION FOR # AND 4 6ERSIONS s /VERPRESSURE $AMPER FOR 5PFLOW UNITS
s 3ERIAL !DAPTOR 23 s &IRE $ETECTOR
s #LOCK #ARD s 3MOKE DETECTOR
s 4#0)0 #ARD s 7ATER LEAK $ETECTOR
25
TDCR-TUCR
Precision air conditioning chilled water units with
direct driven backward curved blade fans
Power Supply
208 - 230 / 3 / 60Hz
Range:
7 - 44 TR
Versions Available:
Downflow (TDCR)
Upflow (TUCR)
S TANDARD F E ATURES
s 5NIGUARD -ICROPROCESSOR CONTROL SYSTEM LOCAL REMOTE USER s 3ELECTION OF THE FAN SPEED ACCORDING TO THE %30 REQUIRED BY THE
terminal) aeraulic system
s )MMERSED ELECTRODE BOILER HUMIDIFIER $ ( VERSIONS s 4OTAL FRONT ACCESS FOR UNIT MAINTENANCE
s ,OW SURFACE TEMPERATURE ELECTRICAL HEATERS WITH EXTENDED FINS s ,OW AIRFLOW DIFFERENTIAL PRESSURE ALARM SWITCH
complete with safety thermostat for manual resetting s $OWNFLOW AND 5PFLOW VERSIONS
(T / H versions) s )NTEGRATED -OD"US ON 23 SERIAL CARD
s $IRECT $RIVEN SINGLE INLET "ACKWARD #URVED "LADE &ANS s )NTEGRATED ,!. -ANAGEMENT
s #OPPER AND ALUMINIUM COOLING COIL s /UTSIDE PANELS COATED WITH EPOXY POWDER $ARK "LUE PAINT
s
WAY VALVE DRIVEN BY MODULATING SERVOMOTOR ELECTRONICALLY s %LECTRICAL PANEL HOUSED IN A DEDICATED COMPARTMENT IN COMPLIANCE
controlled by the microprocessor control with EEC standards
s (IGH EFFICIENCY %5 PLEATED AIR FILTER HOUSED IN A METAL FRAME AND
filter differential pressure switch
26
TECHNICAL D ATA
Dimensions
Height in.(mm) 77.1 (1960) 77.1 (1960) 77.1 (1960) 77.1 (1960)
Width in. (mm) 39.8 (1010) 51.6 (1310) 51.6 (1310) 67.7 (1720)
Depth in. (mm) 29.5 (750) 34.1 (865) 34.1 (865) 34.1 (865)
Weight (Full version) (1) lbs. (kg) 617 (280) 985 (447) 985 (447) 1232 (559)
Dimensions
Height in.(mm) 77.1 (1960) 77.1 (1960) 77.1 (1960) 85.6 (2175)
Width in. (mm) 85.4 (2170) 101.7 (2582) 101.7 (2582) 101.7 (2582)
Depth in. (mm) 34.1 (865) 34.1 (865) 34.1 (865) 34.1 (865)
Weight (Full version) (1) lbs. (kg) 1538 (698) 2006 (910) 2006 (910) 2006 (910)
(1) D version + electrical heaters
(2) Room at 75°F (23.9°C) -50% R.H. - Water inlet 45 °F (7°C) water outlet 55 °F (12.7°C), 0% of Glycol
(3) For 4300 size only downflow version available
O P TIONS
s 3ERIAL !DAPTOR 23 s -OTORIZED $AMPER FOR 5PFLOW UNITS
s #LOCK #ARD s /VERPRESSURE $AMPER FOR 5PFLOW UNITS
s 4#0)0 #ARD s &IRE $ETECTOR
s ,/. SERIAL CARD s 3MOKE DETECTOR
s !&03 +IT s 7ATER LEAK $ETECTOR
27
TDCV-TUCV
Precision air conditioning chilled water units with
Electronically Commutated (EC) backward curved
blade fans
Power Supply
208 - 230 / 3 / 60Hz
Range:
7 - 45 TR
Versions Available:
Downflow (TDCV)
Upflow (TUCV)
S TANDARD F E ATURES
s 5NIGUARD -ICROPROCESSOR CONTROL SYSTEM LOCAL REMOTE USER s 3ELECTION OF THE FAN SPEED ACCORDING TO THE %30 REQUIRED BY THE
terminal) aeraulic system
s )MMERSED ELECTRODE BOILER HUMIDIFIER $ ( VERSIONS s 4OTAL FRONT ACCESS FOR UNIT MAINTENANCE
s ,OW SURFACE TEMPERATURE ELECTRICAL HEATERS WITH EXTENDED FINS s ,OW AIRFLOW DIFFERENTIAL PRESSURE ALARM SWITCH
complete with safety thermostat for manual resetting s $OWNFLOW AND 5PFLOW VERSIONS
(T / H versions) s )NTEGRATED -OD"US ON 23 SERIAL CARD
s $IRECT $RIVEN SINGLE INLET %LECTRONICALLY #OMMUTATED %# s )NTEGRATED ,!. -ANAGEMENT
Backward Curved Blade Fans s /UTSIDE PANELS COATED WITH EPOXY POWDER $ARK "LUE PAINT
s #OPPER AND ALUMINIUM COOLING COIL s %LECTRICAL PANEL HOUSED IN A DEDICATED COMPARTMENT IN COMPLIANCE
s
WAY VALVE DRIVEN BY MODULATING SERVOMOTOR ELECTRONICALLY with EEC standards
controlled by the microprocessor control
s (IGH EFFICIENCY %5 PLEATED AIR FILTER HOUSED IN A METAL FRAME AND
filter differential pressure switch
28
TECHNICAL D ATA
Dimensions
Height in.(mm) 77.1 (1960) 77.1 (1960) 77.1 (1960) 77.1 (1960)
Width in. (mm) 39.8 (1010) 51.6 (1310) 51.6 (1310) 67.7 (1720)
Depth in. (mm) 29.5 (750) 34.1 (865) 34.1 (865) 34.1 (865)
Weight (Full version) (1) lbs. (kg) 617 (280) 985 (447) 985 (447) 1232 (559)
Dimensions
Height in.(mm) 77.1 (1960) 77.1 (1960) 77.1 (1960) 85.6 (2175)
Width in. (mm) 85.4 (2170) 101.7 (2582) 101.7 (2582) 101.7 (2582)
Depth in. (mm) 34.1 (865) 34.1 (865) 34.1 (865) 34.1 (865)
Weight (Full version) (1) lbs. (kg) 1538 (698) 2006 (910) 2006 (910) 2006 (910)
(1) D version + electrical heaters
(2) Room at 75°F (23.9°C) -50% R.H. - Water inlet 45 °F (7°C) water outlet 55 °F (12.7°C), 0% of Glycol
(3) For 4300 size only downflow version available
O P TIONS
s 3ERIAL !DAPTOR 23 s -OTORIZED $AMPER FOR 5PFLOW UNITS
s #LOCK #ARD s /VERPRESSURE $AMPER FOR 5PFLOW UNITS
s 4#0)0 #ARD s &IRE $ETECTOR
s ,/. SERIAL CARD s 3MOKE DETECTOR
s !&03 +IT s 7ATER LEAK $ETECTOR
29
TDAR-TUAR
Precision air conditioning air-cooled direct expansion
units with direct driven backward curved blade fans
Power Supply
208 - 230 / 3 / 60Hz
Range:
6 - 31 TR
Versions Available:
Downflow (TDAR)
Upflow (TUAR)
Refrigerant:
R410A
S TANDARD F E ATURES
s 5NIGUARD -ICROPROCESSOR CONTROL SYSTEM LOCAL REMOTE USER s $OWNFLOW AND 5PFLOW VERSIONS
terminal) s !IR FILTER INSTALLED INSIDE THE UNIT UP TO %5 EFFICIENCY
s 2! REFRIGERANT s !IR FILTER INSTALLED OUTSIDE THE UNIT WITH ADDITIONAL PLENUM OR FLOOR
s $IRECT $RIVEN SINGLE INLET "ACKWARD #URVED "LADE &ANS WITH stand up to EU8 efficiency
Asynchronous motor s %LECTRONIC EXPANSION VALVE INTEGRATED WITH THE MICROPROCESSOR
s (IGH EFFICIENCY %5 PLEATED AIR FILTER HOUSED IN A METAL FRAME AND and managed with exclusive Uniflair software
filter differential pressure switch s )NTELLIGENT DEHUMIDIFICATION CONTROL INTEGRATED WITH THE ELECTRONIC
s /NE OR TWO INDEPENDENT REFRIGERANT CIRCUITS EQUIPPED WITH 3CROLL expansion valve
compressors s )NTEGRATED -OD"US ON 23 SERIAL CARD
s 3ELECTION OF THE FAN SPEED ACCORDING TO THE %30 REQUIRED BY THE s )NTEGRATED ,!. -ANAGEMENT
aeraulic system s /UTSIDE PANELS COATED WITH EPOXY POWDER $ARK "LUE PAINT
s 4OTAL FRONT ACCESS FOR UNIT MAINTENANCE s %LECTRICAL PANEL HOUSED IN A DEDICATED COMPARTMENT IN COMPLIANCE
s ,OW AIRFLOW DIFFERENTIAL PRESSURE ALARM SWITCH with EEC standards
30
TECHNICAL D ATA
Dimensions
Height in.(mm) 77.1 (1960) 77.1 (1960) 77.1 (1960) 77.1 (1960) 77.1 (1960) 77.1 (1960)
Width in. (mm) 39.8 (1010) 39.8 (1010) 51.6 (1310) 51.6 (1310) 67.7 (1720) 67.7 (1720)
Depth in. (mm) 29.5 (750) 29.5 (750) 34.1 (865) 34.1 (865) 34.1 (865) 34.1 (865)
Weight (Full version) (1) lbs. (kg) 617(280) 683 (310) 985 (447) 985 (447) 1232 (559) 1232 (559)
Dimensions
85.6 (2175) TD** 85.6 (2175) TD** 85.6 (2175) TD**
Height in.(mm) 77.1 (1960) 77.1 (1960) 77.1 (1960)
77.1 (1960) TU** 77.1 (1960) TU** 77.1 (1960) TU**
Width in. (mm) 85.4 (2170) 85.4 (2170) 85.4 (2170) 101.7 (2582) 101.7 (2582) 101.7 (2582)
Depth in. (mm) 34.1 (865) 34.1 (865) 34.1 (865) 34.1 (865) 34.1 (865) 34.1 (865)
Weight (Full version) (1) lbs. (kg) 1538 (698) 1574 (714) 1574 (714) 2006 (910) 2024 (916) 2513 (1140)
(1) D version + electrical heaters
(2) Room at 75°F (23,9°C) -50% R.H. - Refrigerant R410A - 115°F (46°C) condensing temperature
O P TIONS
s 3ERIAL !DAPTOR 23 s -OTORIZED $AMPER FOR 5PFLOW UNITS
s #LOCK #ARD s /VERPRESSURE $AMPER FOR 5PFLOW UNITS
s 4#0)0 #ARD s &IRE $ETECTOR
s ,/. SERIAL CARD s 3MOKE DETECTOR
s !&03 +IT s 7ATER LEAK $ETECTOR
31
TDAV-TUAV
Precision air conditioning air-cooled direct expansion
units with Electronically Commutated (EC) backward
curved blade fans
Power Supply
208 - 230 / 3 / 60Hz
Range:
6 - 31 TR
Versions Available:
Downflow (TDAV)
Upflow (TUAV)
Refrigerant:
R410A
S TANDARD F E ATURES
s 5NIGUARD -ICROPROCESSOR CONTROL SYSTEM LOCAL REMOTE USER s $OWNFLOW AND 5PFLOW VERSIONS
terminal) s !IR FILTER INSTALLED INSIDE THE UNIT UP TO %5 EFFICIENCY
s 2! REFRIGERANT s !IR FILTER INSTALLED OUTSIDE THE UNIT WITH ADDITIONAL PLENUM OR FLOOR
s $IRECT $RIVEN SINGLE INLET %LECTRONICALLY #OMMUTATED %# stand up to EU8 efficiency
Backward Curved Blade Fans s %LECTRONIC EXPANSION VALVE INTEGRATED WITH THE MICROPROCESSOR
s (IGH EFFICIENCY %5 PLEATED AIR FILTER HOUSED IN A METAL FRAME AND and managed with exclusive Uniflair software
filter differential pressure switch s )NTELLIGENT DEHUMIDIFICATION CONTROL INTEGRATED WITH THE ELECTRONIC
s /NE OR TWO INDEPENDENT REFRIGERANT CIRCUITS EQUIPPED WITH 3CROLL expansion valve
compressors s )NTEGRATED -OD"US ON 23 SERIAL CARD
s 3ELECTION OF THE FAN SPEED ACCORDING TO THE %30 REQUIRED BY THE s )NTEGRATED ,!. -ANAGEMENT
aeraulic system s /UTSIDE PANELS COATED WITH EPOXY POWDER $ARK "LUE PAINT
s 4OTAL FRONT ACCESS FOR UNIT MAINTENANCE s %LECTRICAL PANEL HOUSED IN A DEDICATED COMPARTMENT IN COMPLIANCE
s ,OW AIRFLOW DIFFERENTIAL PRESSURE ALARM SWITCH with EEC standards
32
TECHNICAL D ATA
Dimensions
Height in.(mm) 77.1 (1960) 77.1 (1960) 77.1 (1960) 77.1 (1960) 77.1 (1960) 77.1 (1960)
Width in. (mm) 39.8 (1010) 39.8 (1010) 51.6 (1310) 51.6 (1310) 67.7 (1720) 67.7 (1720)
Depth in. (mm) 29.5 (750) 29.5 (750) 34.1 (865) 34.1 (865) 34.1 (865) 34.1 (865)
Weight (Full version) (1) lbs. (kg) 617(280) 683 (310) 985 (447) 985 (447) 1232 (559) 1232 (559)
Dimensions
85.6 (2175) TD** 85.6 (2175) TD** 85.6 (2175) TD **
Height in.(mm) 77.1 (1960) 77.1 (1960) 77.1 (1960)
77.1 (1960) TU** 77.1 (1960) TU** 77.1 (1960) TU**
Width in. (mm) 85.4 (2170) 85.4 (2170) 85.4 (2170) 101.7 (2582) 101.7 (2582) 101.7 (2582)
Depth in. (mm) 34.1 (865) 34.1 (865) 34.1 (865) 34.1 (865) 34.1 (865) 34.1 (865)
Weight (Full version) (1) lbs. (kg) 1538 (698) 1574 (714) 1574 (714) 2006 (910) 2024 (916) 2513 (1140)
(1) D version + electrical heaters
(2) Room at 75°F (23,9°C) -50% R.H. - Refrigerant R410A - 115°F (46°C) condensing temperature
O P TIONS
s 3ERIAL !DAPTOR 23 s -OTORIZED $AMPER FOR 5PFLOW UNITS
s #LOCK #ARD s /VERPRESSURE $AMPER FOR 5PFLOW UNITS
s 4#0)0 #ARD s &IRE $ETECTOR
s ,/. SERIAL CARD s 3MOKE DETECTOR
s !&03 +IT s 7ATER LEAK $ETECTOR
33
CAP
Air-cooled remote condenser
Power Supply:
208 - 230 / 3 / 60Hz
Range:
2 - 47 TR
Refrigerant:
R410A
S TANDARD F E ATURES
s 2! REFRIGERANT s (IGH EFFICIENCY %5 PLEATED AIR FILTER HOUSED IN A METAL FRAME AND
s ,OW .OISE !XIAL FANS WITH )0 CLASS &