DV 10
DV 15
DV 20
DV 25
DV 30
Modular air handling units DV
DV is a range of units constructed as modules, which offers numerous
design options. Units can be constructed as separate supply air and extract
air units or as a complete system with a rotating, cross-ow heat exchanger
or run around coils.
The plug fan units guarantee low sound levels.
Combination options
Te DV unit includes a number of well-
dimensioned functions. You can choose
between various systems for heat recovery
and several types of fan and flter. Difer-
ent types of heating coil and air cooler, etc.
Tat is why so many diferent versions of
DV units are available, from the simple unit
with few functions to the advanced ventila-
tion unit.
The unit housing
Te DV units are built to last. In order to
ensure that the unit housing is of a quality
that adheres to the high standards of the
functions, we have chosen to use frames
and panels made from top-quality corro-
sion-resistant aluzinc sheets, AZ185. Sheet
steel coated with aluzinc AZ185 provides
corrosion resistance equivalent to class C4
as per EN ISO 12944-2.
Fans
Belt-driven centrifugal fans with various
high-efciency impellers. Te direct-drive
plug fans ensure low sound levels at low
frequencies.
Heat exchanger
Te DV units can be supplied with 3 types
of heat exchanger: a rotating heat exchanger
with high efciency and a moisture recovery
option, a plate heat exchanger for separation
of the supply air and extract air fows with
the option to choose a corrosion-resistant
heat exchanger, or a heat exchanger with run
around coils for supply air and extract air in
separate locations.
Control system Systemair E28
DV can be ordered with the Systemair E28
control system.
Roof version
Sizes 10-150 are also available as outdoor
units with two diferent roof solutions, poly-
ester-reinforced bitumen roof or corrugated
sheet metal roof of aluzinc. Te roof units
are supplied assembled on base frames.
Available in 14 different sizes
Handles airows of
0.4-24 m
3
/s
Large number of combinations
4 fan options
3 heat exchanger options
Disc-Lock system for easy
assembly of sections
Made of aluzinc sheet metal
Can be supplied with control
system
Selection software
WORKING RANGE
The SFP graphs are based on data from the unit combination C1E, equipped with an effcient fan and motor, a rotating heat exchanger,
two sections of heating coil, an F7 supply air flter, an F5 extract air flter, and supply air and extract air dampers.
10, 15, 20, 25
Information on functions can be found on page 66. Information on control equipment can be found on page 72. Please visit our website
www.systemair.com for more detailed technical information in the form of our online catalogue, computer software and PDF documents!
54
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0
0
50
100
150
200
250
300
350
450
400
500
550
600
P
s

[
P
a
]
q
v
[m
3
/s]
q
v
[m
3
/h]
=SFP value (Specific Fan Power) x,x
5000 10000 15000 20000
2,5
1,5
2,0
1,5
2,0
2,5
3,0
1,5 2,0
3,0
2,5
1,5
2,0
3,0
2,5
1,5
2,0
3,0
2,5
DV 30
DV 40
DV 50
DV 60
DV 80
6 5 7 8 9 10 12 11
0
50
100
150
200
250
300
350
450
400
500
550
600
P
s

[
P
a
]
q
v
[m
3
/s]
q
v
[m
3
/h]
=SFP value (Specific Fan Power) x,x
25000 30000 35000 40000 20000
1,5
1,5
2,0
2,5
2,5
3,0
3,0
DV 80
DV 100
DV 120
DV 150
2,0
1,5
1,5
2,0
2,0
2,5
2,5
3,0
3,0
10 12 14 16 18 20 22 24
0
50
100
150
200
250
300
350
450
400
500
550
600
P
s

[
P
a
]
q
v
[m
3
/s]
q
v
[m
3
/h]
=SFP value (Specific Fan Power) x,x
70000 50000 60000 40000 80000
DV 150
DV 190
DV 240
1,5
1,5
1,5
2,0
2,0
2,0
2,5
2,5
2,5
3,0
3,0
3,0
30, 40, 50, 60
80, 100, 120
150, 190, 240
55
D
V
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
2.9m3/s and 300
pa.
In order to facilitate the work of designing an air handling unit
based on the numerous options available, we have provided speci-
fcations for the most common unit combinations for units with
DVE plug fans.
Tese examples should help to speed up the process of designing
your preferred units with the right functions. Choose the unit ver-
sion that best matches your preferences and then add or remove
functions as required.
ROTATING HEAT EXCHANGER
SIZE
10 15 20 25 30 40 50 60 80 100 120 150 190 240
Standard Wi dth 970 1120 1270 1420 1570 1720 2020 2170 2170 2370 2590 2890 3190 3490
Rotating heat exchanger
1)
Wi dth 2320 2520 2890 3040 3720 4020
Doubl e uni t (2-storey) Hei ght
2)
970 1120 1270 1420 1570 1720 2020 2240 2540 2840 3140 3440 4340 4940
C1E
Length 2160 2160 2460 2460 2760 3060 2910 3280 3210 3960 4260 4560 5010 5530
Wei ght 430 520 660 760 920 1100 1470 1980 2140 2630 3250 3990 6290 7610
C2E
Length 2910 2910 3210 3210 3510 3810 3660 4030 4030 4930 5230 5530 5980 6430
Wei ght 500 610 770 870 1080 1270 1690 2250 2470 3050 3890 4690 7220 8600
C3E
Length 2680 2680 3130 3130 3430 3880 4030 4400 4400 5450 5900 6200 6430 7100
Wei ght 480 580 730 810 1010 1220 1700 2230 2480 3160 3870 4660 6870 8280
C4E
Length 3430 3430 3880 3880 4180 4630 4780 5220 5220 6420 7020 7170 7400 8000
Wei ght 550 660 840 920 1180 1380 1850 2410 2670 3370 4280 5060 7790 9170
C5E
Length 2680 2680 3130 3130 3430 3880 3730 4100 4100 5080 5380 5680 6430 7100
Wei ght 480 570 720 800 1010 1220 1630 2120 2330 2970 3620 4390 6860 8280
C6E
Length 3430 3430 3880 3880 4180 4630 4480 4850 4850 6050 6350 6650 7400 8000
Wei ght 550 660 840 920 1180 1380 1850 2410 2670 3370 4280 5060 7790 9170
PLATE HEAT EXCHANGER
SIZE
10 15 20 25 30 40 50 60 80 100 120 150
Wi dth 970 1120 1270 1420 1570 1720 2020 2170 2170 2370 2590 2890
Doubl e uni t (2-storey) Hei ght
2)
970 1120 1270 1420 1570 1720 2020 2240 2540 2840 3140 3440
Q1E
Length 3210 3580 4030 4330 4780 5080 5230 5460 5230 5910 6960 7260
Wei ght 570 760 940 1130 1370 1640 2300 2550 2610 3210 4200 5130
Q2E
Length 3960 4330 4780 5080 5530 5830 5980 6210 5980 6880 7930 8230
Wei ght 660 850 1060 1260 1540 1810 2520 2880 2910 3660 4870 5790
Q3E
Length 3800 4100 4700 5000 5450 5900 6050 6280 6280 7330 8380 8680
Wei ght 650 820 1030 1140 1470 1760 2480 2720 2840 3620 4600 5550
Q4E
Length 4550 4850 5450 5750 6200 6650 6800 7030 6800 8000 9050 9350
Wei ght 720 900 1140 1310 1630 1930 2720 3030 3130 3980 5150 6130
Q5E
Length 3800 4100 4700 5000 5450 5900 6050 6280 6130 7030 8080 8680
Wei ght 640 810 1020 1170 1480 1750 2460 2700 2890 3690 4690 5840
Q6E
Length 4550 4850 5450 5750 6200 6650 6800 7100 6800 8000 9050 9350
Wei ght 720 900 1140 1300 1620 1920 2700 3030 3200 4120 5320 6380
Dimensions in mm. Weights in kg.
1)
The casing protrudes an equal distance on both sides.
2)
For DV 10-150 = height excluding base frame DVZ, For DV 190-240 = height including base frame DVZ.
= outdoor air = supply air = extract air = exhaust air
UNIT VERSIONS WITH DVE PLUG FANS
56
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
LIQUID-COUPLED
HEAT EXCHANGERS
SIZE
10 15 20 25 30 40 50 60 80 100 120 150 190 240
Wi dth 970 1120 1270 1420 1570 1720 2020 2170 2170 2370 2590 2890 3190 3490
Si ngl e uni t (1-storey) Hei ght
2)
520 595 670 745 820 895 1045 1120 1270 1420 1570 1720 2170 2470
Doubl e uni t (2-storey) Hei ght
2)
970 1120 1270 1420 1570 1720 2020 2240 2540 2840 3140 3440 4340 4940
R1E
Length 2540 2540 2690 2690 2840 2990 2990 3140 3140 3590 3890 4110 5010 5230
Wei ght 580 700 840 990 1170 1420 1980 2240 2460 2990 3800 4580 6290 7420
R2E
Length 3360 3360 3510 3510 3660 3810 3810 3960 3960 4560 4860 5010 5910 6060
Wei ght 680 820 980 1150 1360 1620 2220 2550 2790 3510 4340 5170 7050 8270
SUPPLY AIR UNITS
SIZE
10 15 20 25 30 40 50 60 80 100 120 150 190 240
Wi dth 970 1120 1270 1420 1570 1720 2020 2170 2170 2370 2590 2890 3190 3490
Si ngl e uni t (1-storey)
Hei ght
2)
520 595 670 745 820 895 1045 1120 1270 1420 1570 1720 2170 2470
Doubl e uni t (2-storey)
Hei ght
2)
970 1120 1270 1420 1570 1720 2020 2240 2540 2840 3140 3440 4340 4940
S1E
Length 1940 1940 2090 2090 2240 2390 2240 2390 2390 2690 2990 3140 4040 4260
Wei ght 220 260 320 370 430 510 700 800 880 1100 1400 1700 2250 2820
S2E
Length 2690 2690 2840 2840 2990 3140 2990 3140 3140 3590 3960 4110 5010 5160
Wei ght 310 370 450 520 620 730 960 1110 1230 1490 2020 2320 3170 3720
S3E
Length 1940 1940 2090 2090 2240 2390 2240 2390 2390 2690 2990 3140 4040 4260
Wei ght 340 400 500 580 690 830 1140 1320 1440 1790 2350 2800 3690 4560
S4E
Length 2690 2690 2840 2340 2990 3140 2990 3140 3140 3590 3960 4110 5010 5160
Wei ght 430 510 630 730 870 1040 1400 1630 1790 2180 2960 3410 4610 5460
UNITS WITH MIXING SECTION
SIZE
10 15 20 25 30 40 50 60 80 100 120 150 190 240
Wi dth 970 1120 1270 1420 1570 1720 2020 2170 2170 2370 2590 2890 3190 3490
Si ngl e uni t (1-storey) Hei ght
2)
520 595 670 745 820 895 1045 1120 1270 1420 1570 1720 2170 2470
Doubl e uni t (2-storey) Hei ght
2)
970 1120 1270 1420 1570 1720 2020 2240 2540 2840 3140 3440 4340 4940
M1E
Length 2240 2240 2390 2390 2540 2840 2690 2840 2990 3660 3810 3960 4410 5080
Wei ght 250 280 350 390 470 560 800 900 1000 1300 1560 1900 2320 3040
M2E
Length 3060 3060 3210 3210 3360 3660 3510 3660 3810 4410 4560 4710 5380 5980
Wei ght 330 400 480 560 640 780 1050 1180 1320 1660 2140 2460 3250 3940
M3E
Length 3580 3580 3880 3880 4180 4780 4480 4780 5080 5980 6350 6650 7550 8820
Wei ght 390 450 560 620 760 940 1270 1470 1630 2060 2660 3150 3930 5100
M4E
Length 4400 4400 4700 4700 5000 5600 5300 5600 5900 6950 7250 7620 8520 9720
Wei ght 480 560 690 790 940 1150 1550 1760 1960 2530 3250 3800 4850 6000
M5E
Length 2610 2610 2910 2910 3210 3660 3360 2990 2990 3590 3810 3960 4710 5080
Wei ght 360 430 530 580 750 910 1220 1360 1520 1950 2510 2990 4190 5150
M6E
Length 3430 3430 3730 3730 4030 4480 4180 3810 3880 4630 4780 4860 5680 5980
Wei ght 460 540 670 730 930 1150 1480 1650 1880 2430 3150 3570 5110 6050
Dimensions in mm. Weights in kg.
1)
The casing protrudes an equal distance on both sides.
2)
For DV 10-150 = height excluding base frame DVZ, For DV 190-240 = height including base frame DVZ.
57
D
V
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
Selected AHU
In order to facilitate the work of designing an air handling unit
based on the numerous options available, we have provided speci-
fcations for the most common unit combinations for units with
DVV radial fans.
Tese examples should help to speed up the process of designing
your preferred unit with the right functions. Choose the unit version
that best matches your preferences and then add or remove functions
as required.
ROTATING HEAT EXCHANGER
SIZE
10 15 20 25 30 40 50 60 80 100 120 150
Standard Wi dth 970 1120 1270 1420 1570 1720 2020 2170 2170 2370 2590 2890
Rotating heat exchanger
1)
Wi dth 2320 2520 2890 3040
Doubl e uni t (2-storey) Hei ght
2)
970 1120 1270 1420 1570 1720 2020 2240 2540 2840 3140 3440
C1V
Length 2090 2090 2090 2390 2390 2690 3140 3210 3510 4110 4560 4710
Wei ght 450 550 640 780 900 1110 1590 2040 2330 2860 3450 4010
C2V
Length 2910 2910 2910 3210 3210 3510 3960 4030 4330 4930 5530 5830
Wei ght 580 700 830 970 1120 1350 1920 2350 2650 3300 4020 4670
C3V
Length 2610 2610 2760 3060 3060 3510 3960 4030 4330 5230 5680 5830
Wei ght 510 600 730 840 990 1230 1760 2180 2530 3210 3820 4400
C4V
Length 3430 3430 3580 3880 3880 4330 4780 4850 5150 6050 6500 6950
Wei ght 640 760 910 1030 1220 1480 2100 2500 2860 3680 4410 5110
C5V
Length 2610 2610 2760 3060 3060 3510 3960 4030 4330 5230 5680 5980
Wei ght 500 600 730 850 990 1230 1760 2180 2530 3210 3820 4390
C6V
Length 3430 3430 3580 3880 3880 4330 4780 4850 5150 6050 6650 6650
Wei ght 630 750 910 1030 1210 1480 2100 2510 2860 3680 4410 5110
PLATE HEAT EXCHANGER

SIZE
10 15 20 25 30 40 50 60 80 100 120 150
Wi dth 970 1120 1270 1420 1570 1720 2020 2170 2170 2370 2590 2890
Doubl e uni t (2-storey) Hei ght
2)
970 1120 1270 1420 1570 1720 2020 2240 2540 2840 3140 3440
Q1V
Length 3210 3510 3660 4260 4410 4410 5010 5460 5460 6060 7260 7560
Wei ght 610 780 940 1160 1330 1580 2320 2640 2750 3430 4337 5110
Q2V
Length 4030 4330 4480 5080 5230 5230 5830 6280 6280 6880 8080 8230
Wei ght 740 940 1120 1340 1550 1790 2630 2950 3070 3830 4820 5580
Q3V
Length 3730 4030 4330 4930 5080 5230 5830 6280 6280 7180 8380 8680
Wei ght 670 840 1030 1220 1430 1700 2500 2820 2960 3770 4650 5460
Q4V
Length 4550 4850 5150 5750 5900 6050 6650 7100 7100 8000 9200 9350
Wei ght 790 990 1210 1400 1640 1910 2810 3100 3250 4170 5140 5940
Q5V
Length 3730 4030 4330 4930 5080 5680 6350 6800 6280 7180 8380 8680
Wei ght 660 840 1030 1220 1420 1770 2680 3000 3050 3920 4890 5730
Q6V
Length 4550 4850 5150 5750 5900 6500 7170 7550 7100 8000 9200 9350
Wei ght 790 990 1200 1400 1640 1980 2970 3250 3350 4320 5400 6230
1
Dimensions in mm. Weights in kg.
)
The casing protrudes an equal distance on both sides.
2)
Height excludes DVZ base frame.
= outdoor air = supply air = extract air = exhaust air
UNIT VERSIONS WITH DVV RADIAL FANS
58
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
LIQUID-COUPLED
HEAT EXCHANGERS
SIZE
10 15 20 25 30 40 50 60 80 100 120 150
Wi dth 970 1120 1270 1420 1570 1720 2020 2170 2170 2370 2590 2890
Si ngl e uni t (1-storey) Hei ght
2)
520 595 670 745 820 895 1045 1120 1270 1420 1570 1720
Doubl e uni t (2-storey) Hei ght
2)
970 1120 1270 1420 1570 1720 2020 2240 2540 2840 3140 3440
R1V
Length 2690 2690 2690 2840 2840 2990 3140 3140 3290 3740 4040 4190
Wei ght 630 770 870 1050 1200 1460 2120 2370 2630 3200 3840 4540
R2V
Length 3510 3510 3510 3660 3660 3810 3960 3960 4110 4710 5010 5160
Wei ght 720 880 1020 1200 1380 1620 2360 2650 2970 3610 4390 5180
SUPPLY AIR UNITS
SIZE
10 15 20 25 30 40 50 60 80 100 120 150
Wi dth 970 1120 1270 1420 1570 1720 2020 2170 2170 2370 2590 2890
Si ngl e uni t (1-storey) Hei ght
2)
520 595 670 745 820 895 1045 1120 1270 1420 1570 1720
Doubl e uni t (2-storey) Hei ght
2)
970 1120 1270 1420 1570 1720 2020 2240 2540 2840 3140 3440
S1V
Length 1940 1940 1940 2090 2090 2240 2390 2390 2540 2840 3290 3440
Wei ght 240 280 320 380 440 520 750 840 960 1240 1470 1710
S2V
Length 2760 2760 2760 2910 2910 3060 3210 3210 3360 3660 4260 4540
Wei ght 330 390 460 540 610 720 1020 1150 1300 1630 1990 2320
S3V
Length 1940 1940 1940 2090 2090 2240 2390 2390 2540 2840 3290 3440
Wei ght 370 450 500 610 700 870 1240 1400 1590 2070 2480 2890
S4V
Length 2610 2760 2760 2910 2910 3060 3210 3210 3360 3660 4260 4340
Wei ght 460 560 640 770 880 1060 1510 1710 1930 2460 3000 3500
UNITS WITH MIXING SECTION
SIZE
10 15 20 25 30 40 50 60 80 100 120 150
Wi dth 970 1120 1270 1420 1570 1720 2020 2170 2170 2370 2590 2890
Si ngl e uni t (1-storey) Hei ght
2)
520 595 670 745 820 895 1045 1120 1270 1420 1570 1720
Doubl e uni t (2-storey) Hei ght
2)
970 1120 1270 1420 1570 1720 2020 2240 2540 2840 3140 3440
M1V
Length 2090 2240 2240 2390 2390 2690 2840 2840 3140 3660 3810 4110
Wei ght 350 430 490 580 650 800 1100 1230 1400 1750 2140 2510
M2V
Length 3060 3060 3060 3210 3210 3510 3660 3660 3960 4410 4710 4560
Wei ght 330 400 480 560 640 780 1050 1180 1320 1660 2140 2460
M3V
Length 3430 3580 3580 3880 3880 4480 4780 4780 5380 6350 6800 7100
Wei ght 430 490 570 660 780 980 1400 1550 1790 2420 2810 3260
M4V
Length 4250 4400 4400 4700 4700 5300 5600 5600 6200 7100 7700 8000
Wei ght 520 610 700 820 940 1190 1660 1850 2120 2800 3330 3890
M5V
Length 2310 2460 2610 2760 2910 3060 3660 3060 3210 3810 4110 4260
Wei ght 380 450 540 620 740 910 1340 1460 1680 2260 2650 3090
M6V
Length 3280 3280 3430 3730 3730 4180 4330 3810 3960 4630 5080 5160
Wei ght 480 570 680 760 920 1150 1580 1730 2000 2670 3200 3720
Dimensions in mm. Weights in kg.
2)
Height excludes DVZ base frame.
59
D
V
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
Modular air handling units
NB
NB is probably the most exible unit on the market when it comes to de-
sign. As we do not have standard unit combinations, units can be adapted
to suit customer requirements.
WORKING RANGE
2, 3, 5, 8
q
v
[m
3
/h]
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.2 2.4 2.6 2.8 3.0 2.0
0
50
100
150
200
250
300
350
450
400
500
550
600
P
s

[
P
a
]
q
v
[m
3
/s] =SFP value (Specific Fan Power) x,x
1000 2000 3000 4000 5000 6000 7000 8000 9000 10000
NB2
NB3
NB5
NB8
NB11
1,5
1,5
2,0
2,0
2,5
2,5
3,0
1,5
2,0
2,5
3,0
1,5
2,0
2,5
3,0
1,5
2,0
2,5
Information on functions can be found on page 66. Information on control equipment can be found on page 72. Please visit our website
www.systemair.com for more detailed technical information in the form of our online catalogue, computer software and PDF documents!
Available in 15 different sizes
Handles airows of
500-90 000 m
3
/h
For use with low, intermediate
or high air pressure systems.
Heating and cooling units
Extensive range of lters
Heat recovery sections
Two different types of air
humidier
Unit housing
Te unit housing is made from galvanised
sheet steel and sandwiched panels. Te
outside of the unit housing has a stove-
enamelled surface in our characteristic blue
colour.
Panels are available in two diferent
versions:
25 mm which is the standard version.
Te panels are attached directly to the
framework.
50 mm which satisfes demands when
more efective heat insulation is required.
Tese panels are attached to a frame made
from 70x70 mm profled aluminium
sections.
All panels are flled with injected poly-
urethane insulation foam, which has excel-
lent heat and sound-insulating properties.
Rockwool panels are optional.
Range and software
Detailed information on NB units is avail-
able in our NB catalogue and product selec-
tion software. Both are easy to use and are
available from your nearest Systemair ofce.
60
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
q
v
[m
3
/h]
13 14 15 16 17 18 19 20 21 22 23 24
0
50
100
150
200
250
300
350
450
400
500
550
600
P
s

[
P
a
]
q
v
[m
3
/s] =SFP value (Specific Fan Power) x,x
50000 55000 60000 65000 70000 75000 800 00 85000
NB55
NB62
NB70
1,5
2,0
2,5
1,5
2,0
2,5
1,5
2,0
2,5
3,0
q
v
[m
3
/h]
5 6 7 8 9 10 11 12 13 14 15 16 17 18
0
50
100
150
200
250
300
350
450
400
500
550
600
P
s

[
P
a
]
q
v
[m
3
/s] =SFP value (Specific Fan Power) x,x
20000 30000 25000 35000 40000 45000 50000 55000 60000
NB29
NB35
NB42
NB49
NB55
1,5
2,0
2,5
1,5
2,0
2,5
1,5
2,0
2,5
1,5
2,0
2,5
1,5
2,0
2,5
55, 62, 70
11, 15, 18, 23
q
v
[m
3
/h]
2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0
0
50
100
150
200
250
300
350
450
400
500
550
600
P
s

[
P
a
]
q
v
[m
3
/s] =SFP value (Specific Fan Power) x,x
8000 12000 10000 14000 16000 18000 20000 22000 24000 26000 28000
NB11
NB15
NB18
NB23
NB29
1,5
2,0
2,5
3,0
1,5
2,0
2,5
1,5
2,0
2,5
1,5
1,5
2,0
2,0
2,5
2,5
29, 35, 42, 49
61
N
B
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
Dimensions in mm. Weights in kg.
1)
Does not include the height of the metal frame.
2)
Does not include the weight of the metal frame.
In order to facilitate the work of designing an air handling unit based on the numerous
options available, we have provided specifcations for the most common unit combinations.
Tese examples should help to speed up the process of designing your preferred unit with the
right functions. Choose the unit version that best matches your preferences and then add or
remove functions as required.
UNIT VERSIONS WITH CENTRIFUGAL FANS
= outdoor air = supply air = extract air = exhaust air
ROTATING HEAT EXCHANGER
SIZE
2 3 5 8 11 15 18 23 29 35 42 49 55 62 70
Panel 25
Wi dth 760 760 1130 1130 1480 1480 1830 2190 2190 2190 2540 2890 3240 3590 3940
Hei ght
1)
1170 1520 1560 2260 2260 2960 2960 2980 3680 4380 4380 4380 4380 4380 4380
Panel 50
Wi dth 810 810 1180 1180 1530 1530 1880 2230 2230 2230 2590 2920 3290 3620 3990
Hei ght
1)
1270 1620 1660 2360 2360 3060 3060 3060 3760 4460 4460 4460 4460 4460 4460
C1V
Panel
25
Length 2860 2860 2880 2880 3230 3230 3580 3940 4290 4640 4640 4990 5340 5340 5340
Weight
2)
481 576 813 1051 1289 1575 1852 2629 3105 3535 4891 5470 6030 6590 7150
Panel
50
Length 2940 2940 2940 2940 3290 3290 3640 3990 4340 4690 4690 5040 5390 5390 5390
Weight
2)
553 615 849 1098 1347 1644 1932 2693 3181 3622 5012 5605 6178 6751 7324
C2V
Panel
25
Length 2860 3035 3230 3405 3755 3755 4105 4465 4815 5165 5165 5515 5865 5865 5865
Weight
2)
549 658 917 1194 1453 1775 2074 2920 3450 3932 5321 5934 6529 7124 7719
Panel
50
Length 2940 3115 3290 3465 3815 3815 4165 4515 4865 5215 5215 5565 5915 5915 5915
Weight
2)
608 704 959 1248 1518 1861 2164 2992 3535 4029 5452 6080 6689 7298 7907
C3V
Panel
25
Length 3035 3035 3230 3405 3930 3930 4280 4815 5165 5690 6215 6565 6915 6915 6915
Weight
2)
519 622 878 1135 1392 1701 2000 2839 3353 3818 5282 5908 6512 7117 7722
Panel
50
Length 3115 3115 3290 3465 3990 3990 4340 4865 5215 5740 6265 6615 6965 6965 6965
Weight
2)
597 664 917 1186 1455 1776 2087 2908 3435 3912 5413 6053 6672 7291 7910
C4V
Panel
25
Length 3210 3385 3755 3930 4455 4455 4805 5340 5690 6215 6740 7090 7440 7440 7440
Weight
2)
593 711 990 1290 1569 1917 2240 3154 3726 4247 5747 6409 7051 7694 8337
Panel
50
Length 3290 3465 3815 3990 4515 4515 4865 5390 5740 6265 6790 7140 7490 7490 7490
Weight
2)
657 760 1036 1348 1639 2010 2337 3231 3818 4351 5888 6566 7224 7882 8540
C5V
Panel
25
Length 3035 3035 3230 3405 3930 3930 4280 4815 5165 5690 6215 6565 6915 6915 6915
Weight
2)
510 611 862 1114 1366 1670 1963 2787 3291 3747 5184 5798 6392 6985 7579
Panel
50
Length 3115 3115 3290 3465 3990 3990 4340 4865 5215 5740 6265 6615 6965 6965 6965
Weight
2)
586 652 900 1164 1428 1743 2048 2855 3372 3839 5313 5941 6549 7156 7763
C6V
Panel
25
Length 3210 3385 3755 3930 4455 4455 4805 5340 5690 6215 6740 7090 7440 7440 7440
Weight
2)
582 697 972 1266 1540 1882 2198 3095 3657 4168 5640 6290 6921 7551 8182
Panel
50
Length 3290 3465 3815 3990 4515 4515 4865 5390 5740 6265 6790 7140 7490 7490 7490
Weight
2)
644 746 1017 1323 1609 1973 2294 3172 3747 4271 5779 6445 7090 7736 8381
62
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
Dimensions in mm. Weights in kg.
1)
Does not include the height of the metal frame.
2)
Does not include the weight of the metal frame.
PLATE HEAT EXCHANGER
SIZE
2 3 5 8 11 15 18 23 29 35 42 49 55 62 70
Panel 25
Wi dth 760 760 1130 1130 1480 1480 1830 2190 2190 2190 2540 2890 3240 3590 3940
Hei ght
1)
1170 1520 1560 2260 2260 2960 2960 2980 3680 4380 4380 4380 4380 4380 4380
Panel 50
Wi dth 810 810 1180 1180 1530 1530 1880 2230 2230 2230 2590 2920 3290 3620 3990
Hei ght
1)
1270 1620 1660 2360 2360 3060 3060 3060 3760 4460 4460 4460 4460 4460 4460
Q1V
Panel
25
Length 2860 3035 3055 3230 3930 4280 4630 5165 5690 6040 6565 7090 7440 7440 7440
Weight
2)
553 662 935 1209 1482 1811 2130 3023 3571 4065 5625 6291 6935 7579 8223
Panel
50
Length 3080 3255 3255 3430 4130 4480 4830 5355 5880 6230 6755 7280 7630 7630 7630
Weight
2)
636 707 976 1263 1549 1891 2222 3097 3658 4165 5764 6446 7105 7764 8423
Q2V
Panel
25
Length 3035 3385 3580 3755 4455 4805 5155 5690 6215 6565 7090 7615 7965 7965 7965
Weight
2)
631 757 1055 1373 1671 2041 2385 3358 3968 4522 6119 6824 7508 8193 8877
Panel
50
Length 3115 3465 3640 3815 4515 4865 5215 5740 6265 6615 7140 7665 8015 8015 8015
Weight
2)
699 810 1103 1435 1746 2140 2489 3441 4065 4633 6270 6992 7692 8393 9093
Q3V
Panel
25
Length 3035 3210 3405 3755 4630 4980 5330 6040 6565 7090 8140 8665 9015 9015 9015
Weight
2)
597 715 1010 1305 1601 1956 2300 3265 3856 4390 6075 6794 7489 8185 8880
Panel
50
Length 3115 3290 3465 3815 4690 5040 5390 6090 6615 7140 8190 8715 9065 9065 9065
Weight
2)
687 764 1054 1364 1673 2042 2400 3345 3951 4499 6225 6961 7673 8385 9096
Q4V
Panel
25
Length 3210 3560 3930 4280 5155 5505 5855 6565 7090 7615 8665 9190 9540 9540 9540
Weight
2)
682 817 1139 1483 1805 2205 2576 3627 4285 4884 6609 7370 8109 8848 9587
Panel
50
Length 3290 3640 3990 4340 5215 5565 5915 6615 7140 7665 8715 9240 9590 9590 9590
Weight
2)
755 874 1191 1550 1885 2311 2688 3716 4390 5004 6771 7551 8308 9064 9820
Q5V
Panel
25
Length 3035 3210 3405 3755 4630 4980 5330 6040 6565 7090 8140 8665 9015 9015 9015
Weight
2)
586 702 991 1281 1571 1920 2258 3205 3785 4309 5962 6668 7351 8033 8716
Panel
50
Length 3115 3290 3465 3815 4690 5040 5390 6090 6615 7140 8190 8715 9065 9065 9065
Weight
2)
674 750 1035 1338 1642 2004 2355 3283 3878 4415 6110 6832 7531 8229 8928
Q6V
Panel
25
Length 3210 3560 3930 4280 5155 5505 5855 6565 7090 7615 8665 9190 9540 9540 9540
Weight
2)
669 802 1118 1455 1771 2164 2528 3559 4206 4793 6486 7234 7959 8684 9409
Panel
50
Length 3290 3640 3990 4340 5215 5565 5915 6615 7140 7665 8715 9240 9590 9590 9590
Weight
2)
741 858 1169 1521 1850 2269 2638 3647 4309 4911 6646 7412 8154 8896 9639
63
N
B
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
Dimensions in mm. Weights in kg.
1)
Does not include the height of the metal frame.
2)
Does not include the weight of the metal frame.
LIQUID-COUPLED HEAT EXCHANGERS
SIZE
2 3 5 8 11 15 18 23 29 35 42 49 55 62 70
Panel 25
Wi dth 760 760 1130 1130 1480 1480 1830 2190 2190 2190 2540 2890 3240 3590 3940
Hei ght
1)
1170 1520 1560 2260 2260 2960 2960 2980 3680 4380 4380 4380 4380 4380 4380
Panel 50
Wi dth 810 810 1180 1180 1530 1530 1880 2230 2230 2230 2590 2920 3290 3620 3990
Hei ght
1)
1270 1620 1660 2360 2360 3060 3060 3060 3760 4460 4460 4460 4460 4460 4460
R1V
Panel
25
Length 2160 2335 2530 2705 3055 3055 3230 3590 3765 3940 3940 4115 4290 4290 4290
Weight
2)
483 579 794 1045 1297 1488 1849 2706 3184 3666 4439 4975 5539 6103 6670
Panel
50
Length 2240 2415 2590 2765 3115 3115 3290 3640 3815 3990 3990 4165 4340 4340 4340
Weight
2)
529 619 829 1091 1355 1653 1930 2775 3260 3756 4548 5098 5675 6252 6829
R2V
Panel
25
Length 2685 2860 3055 3230 3580 3580 3755 4115 4290 4465 4465 4640 4815 4815 4815
Weight
2)
551 662 898 1187 1461 1688 2071 2997 3529 4062 4868 5439 6038 6637 7236
Panel
50
Length 2765 2940 3115 3290 3640 3640 3815 4165 4340 4515 4515 4690 4865 4865 4865
Weight
2)
610 707 939 1241 1526 1865 2161 3071 3616 4162 4988 5572 6187 6802 7417
SUPPLY AIR UNITS
SIZE
2 3 5 8 11 15 18 23 29 35 42 49 55 62 70
Panel 25
Wi dth 760 760 1130 1130 1480 1480 1830 2190 2190 2190 2540 2890 3240 3590 3940
Hei ght
1)
585 760 780 1130 1130 1480 1480 1490 1840 2190 2190 2190 2190 2190 2190
Panel 50
Wi dth 810 810 1180 1180 1530 1530 1880 2230 2230 2230 2590 2920 3290 3620 3990
Hei ght
1)
635 810 830 1180 1180 1530 1530 1530 1880 2230 2230 2230 2230 2230 2230
S1V
Panel
25
Length 1810 1985 2180 2355 2705 2705 2880 3240 3415 3590 3590 3765 3940 3940 3940
Weight
2)
207 243 338 449 570 700 827 1207 1424 1645 2024 2281 2552 2823 3064
Panel
50
Length 1890 2065 2240 2415 2765 2765 2940 3290 3465 3640 3640 3815 3990 3990 3990
Weight
2)
221 265 360 471 592 722 849 1237 1454 1675 2054 2311 2582 2853 3124
S2V
Panel
25
Length 2335 2510 2705 2880 3230 3230 3405 3765 3940 4115 4115 4290 4465 4465 4465
Weight
2)
276 326 441 592 735 903 1053 1499 1755 2028 2441 2733 3040 3347 3654
Panel
50
Length 2415 2590 2765 2940 3290 3290 3465 3815 3990 4165 4165 4340 4515 4515 4515
Weight
2)
295 354 469 620 763 931 1081 1535 1808 2080 2494 2786 3093 3400 3707
SIZE
2 3 5 8 11 15 18 23 29 35 42 49 55 62 70
Panel 25
Wi dth 760 760 1130 1130 1480 1480 1830 2190 2190 2190 2540 2890 3240 3590 3940
Hei ght
1)
1170 1520 1560 2260 2260 2960 2960 2980 3680 4380 4380 4380 4380 4380 4380
Panel 50
Wi dth 810 810 1180 1180 1530 1530 1880 2230 2230 2230 2590 2920 3290 3620 3990
Hei ght
1)
1270 1620 1660 2360 2360 3060 3060 3060 3760 4460 4460 4460 4460 4460 4460
S3V
Panel
25
Length 1810 1985 2180 2355 2705 2705 2880 3240 3415 3590 3590 3765 3940 3940 3940
Weight
2)
333 393 555 740 946 1147 1362 1969 2311 2678 3359 3804 4271 4758 5192
Panel
50
Length 1890 2065 2240 2415 2765 2765 2940 3290 3465 3640 3640 3815 3990 3990 3990
Weight
2)
357 430 592 777 983 1184 1399 2019 2381 2748 3428 3874 4347 4828 5309
S4V
Panel
25
Length 2335 2510 2705 2880 3230 3230 3405 3765 3940 4115 4115 4290 4465 4465 4465
Weight
2)
402 476 658 883 1111 1350 1588 2261 2642 3061 3776 4256 4759 5282 5782
Panel
50
Length 2415 2590 2765 2940 3290 3290 3465 3815 3990 4165 4165 4340 4515 4515 4515
Weight
2)
431 519 701 926 1154 1393 1631 2317 2735 3153 3868 4349 4858 5375 5892
64
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
UNITS WITH MIXING SECTION
SIZE
2 3 5 8 11 15 18 23 29 35 42 49 55 62 70
Panel 25
Wi dth 760 760 1130 1130 1480 1480 1830 2190 2190 2190 2540 2890 3240 3590 3940
Hei ght
1)
585 760 780 1130 1130 1480 1480 1490 1840 2190 2190 2190 2190 2190 2190
Panel 50
Wi dth 810 810 1180 1180 1530 1530 1880 2230 2230 2230 2590 2920 3290 3620 3990
Hei ght
1)
635 810 830 1180 1180 1530 1530 1530 1880 2230 2230 2230 2230 2230 2230
M1V
Panel
25
Length 1810 1985 2180 2355 2705 2705 2880 3240 3415 3765 3940 4115 4290 4290 4290
Weight
2)
215 254 361 467 606 729 862 1273 1469 1716 2135 2403 2685 2967 3234
Panel
50
Length 1890 2065 2240 2415 2765 2765 2940 3290 3465 3815 3990 4165 4340 4340 4340
Weight
2)
229 276 383 489 628 751 884 1304 1514 1761 2180 2448 2730 3012 3294
M2V
Panel
25
Length 2335 2510 2705 2880 3230 3230 3405 3765 3940 4290 4465 4640 4815 4815 4815
Weight
2)
283 341 472 610 765 920 1069 1564 1823 2115 2557 2852 3178 3497 3816
Panel
50
Length 2415 2590 2765 2940 3290 3290 3465 3815 3990 4340 4515 4690 4865 4865 4865
Weight
2)
303 372 493 638 799 960 1116 1603 1868 2167 2620 2922 3241 3560 3879
M3V
Panel
25
Length 2685 3210 3580 3930 4630 4630 4980 5690 6390 6740 7090 7790 8140 8140 8140
Weight
2)
339 416 512 734 960 1138 1347 2037 2403 2767 3513 4013 4495 4822 5149
Panel
50
Length 2765 3290 3640 3990 4690 4690 5040 5740 6440 6790 7140 7840 8190 8190 8190
Weight
2)
362 445 606 766 1003 1188 1405 2087 2462 2835 3599 4111 4605 5177 5504
M4V
Panel
25
Length 3150 3675 4025 4375 5075 5075 5425 6125 6825 7175 7525 8225 8575 8575 8575
Weight
2)
408 499 617 877 1124 1338 1569 2329 2748 3163 3942 4477 4944 5323 5650
Panel
50
Length 3290 3815 4165 4515 5215 5215 5565 6265 6965 7315 7665 8365 8715 8715 8715
Weight
2)
436 533 715 916 1175 1396 1637 2410 2816 3241 4039 4586 5117 5464 5791
SIZE
2 3 5 8 11 15 18 23 29 35 42 49 55 62 70
Panel 25
Wi dth 760 760 1130 1130 1480 1480 1830 2190 2190 2190 2540 2890 3240 3590 3940
Hei ght
1)
1170 1520 1560 2260 2260 2960 2960 2980 3680 4380 4380 4380 4380 4380 4380
Panel 50
Wi dth 810 810 1180 1180 1530 1530 1880 2230 2230 2230 2590 2920 3290 3620 3990
Hei ght
1)
1270 1620 1660 2360 2360 3060 3060 3060 3760 4460 4460 4460 4460 4460 4460
M5V
Panel
25
Length 1810 1985 2180 2355 2705 2705 2880 3240 3415 3765 3940 4115 4290 4290 4290
Weight
2)
339 416 512 734 960 1138 1347 2037 2403 2767 3513 4013 4495 4822 5149
Panel
50
Length 1890 2065 2240 2415 2765 2765 2940 3290 3465 3815 3990 4165 4340 4340 4340
Weight
2)
362 445 606 766 1003 1188 1405 2087 2462 2835 3599 4111 4605 5177 5504
M6V
Panel
25
Length 2335 2510 2705 2880 3230 3230 3405 3765 3940 4290 4465 4640 4815 4815 4815
Weight
2)
408 499 617 878 1124 1338 1569 2329 2748 3163 3942 4477 4944 5323 5650
Panel
50
Length 2415 2590 2765 2940 3290 3290 3465 3815 3990 4340 4515 4690 4865 4865 4865
Weight
2)
436 534 715 916 1175 1396 1637 2170 2816 3241 4039 4586 5117 5464 5791
Dimensions in mm. Weights in kg.
1)
Does not include the height of the metal frame.
2)
Does not include the weight of the metal frame.
65
N
B
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
Functions
This section briey describes the functional elements of the various units.
There is a general explanation of the purpose of the function as well as a
description of each unit.
CASING
Te units casings and doors are made
of rustproof sheet steel and are insulated
internally with 50 mm rock wool, which
has excellent sound and heat insulation
properties.
TA
Te units double-skin casing is made of
0.9 mm galvanised sheet steel surrounding
a 50 mm layer of rock wool insulation. TA
has large lockable doors for easy inspection
and service. Angle brackets for mounting in
ceilings or on walls.
F
Sound and heat insulation between the pan-
els comprises an A1 class fameproof material
in accordance with DIN 4102. In order to
avoid sharp edges, chamfered cast alumini-
um corners or plastic corners are used.
Maxi
Te units double-skin casing is made of
0.9 mm galvanised sheet steel. Maxi 1100
is supplied as a unit with a built-in by-pass
duct. In order to make delivery easier, the
large Maxi 2000 unit is supplied in two
parts with any by-pass ducts as a separate
third module.
Topvex, TIME, DV, DVCompact
Te units double-skin sheet metal casing is
treated with aluzinc 185 to protect against
rust and complies with corrosion class
C4 as per EN ISO 12944.2. TIME and
DV are constructed using a strong closed
frame profle. Topvex is constructed using
self-supporting panels. Te units have
chamfered cast aluminium corners that
guarantee a stable unit casing.
NB
Te unit casing is made of galvanised sheet
steel and has polyurethane foam or rock
wool insulation. Te exterior sheet metal is
stove-enamelled.
DAMPERS
Te various types of damper used in our
units are outdoor air dampers/exhaust air
dampers, mixing dampers and regulating
dampers. Tese comply with air tightness
class 3.
Te circular dampers comprise a pipe
union, equipped with damper blades and
shaft. Te connection ducts have seals of
silicone rubber.
Te rectangular shutter dampers comprise a
number of opposing blades housed in nylon
bushings in a sheet metal frame. Te blades
are connected via a link system, which is
insulated (protected), on the outside of the
frame. Te dampers are made of hot-dip
galvanised sheet metal and are prepared
for external insulation and have a position
indicator showing the percentage opening
of the damper.
TA, F, Maxi and Topvex
See general information.
TIME, DV, DVCompact
Te damper used in TIME and DV units
has aerodynamic blades of extruded alu-
minium with rubber seals.
NB
For two-way and three-way mixing, we use
a combination of outdoor air and regulat-
ing dampers. Te dampers are made of
aluminium or galvanised sheet metal.
Shut-off damper
Mixing damper
70
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
FILTERS
Tere are diferent types of flter material and
a variety of designs for diferent degrees of
air purifcation and thus diferent classes of
flter. With some units the flter type can be
adapted to satisfy specifc requirements for air
purifcation at the premises in question.
Te flters must be replaced at specifed in-
tervals and are mounted in a way that makes
it easy to carry out inspections and replace-
ment work. A monitoring function for flter
replacement is available for some units, using
either set time intervals or diferential pres-
sure sensors. Some flters can be cleaned.
Maxi
Maxi units are supplied with F7 class bag
flters as standard. G3 and F5 class bag
flters can be ordered separately. Te flters
are monitored by means of a diferential
pressure sensor.
Topvex
All Topvex units are supplied with bag
flters as standard. Both the flters are po-
sitioned before the rotating heat exchanger
to keep it clean. Topvex is supplied with an
F7 class flter on the supply air side and an
F5 flter on the extract air side. Filters are
monitored via a time interval in Topvex size
03-06 and a diferential pressure sensor in
Topvex size 07-15.
TIME
F5/F7 class bag flter.
DV/NB/DVCompact
Te bag flter DVF is made up of flter
cells and is available in classes G3-H14 in
accordance with EN779. Te large surface
area guarantees a long service life. Te flter
employs a simple system of lateral locking
rails, which makes replacing the flters easier,
and the tight seal complies with EN1886.
Compact lter
Bag lter
CENTRIFUGAL FAN
Te fan is the heart of an air handling unit.
It is the fan that creates the pressure required
by the unit. Each type of fan is chosen to
ensure optimum performance with regard to
airfow, sound level and efciency.
F
F has two fan options: a direct-driven fan
with external rotor motor or a centrifu-
gal fan with a single or double inlet with
forward-curved blades. Te impeller and
casing are made of galvanised steel. Te
wheels are made of galvanised steel or
polyamide (PA).
Maxi
Maxi has direct-driven centrifugal fans
with external rotor motors. Te impellers
have forward-curved blades and generate
very little duct noise. A built-in transformer
controls the fans in two stages.
DV
DVV is a double-inlet, belt-driven centrifugal
fan integrated into a soundproof unit housing.
Te BK fan, with backward-curved blades,
has an efciency of 82%. Te FK fan, with
forward-curved blades, has an efciency of
73%. Te multiple fan blades on the wheel
give the FK fan good sound properties and
generate low sound levels. DVV is supplied
with a 1 or 2-speed motor and is also available
with running stand-by motor. Standard fans
are belt-driven and ftted with the highly
efcient RE-X V-belts, with an efciency of
98%. Supplied for sizes 10-150.
NB
Te centrifugal fan has double inlets with
an anchor bedplate, drive pulley and has
three fan options. Two of these options
have forward-curved blades and are in-
tended for use in low-speed airfow units,
while the third, which has forward-curved
blades and is designated RDH, has been
developed for use with intermediate and
high-speed airfow units. Te fan motor is
driven by a pulley and V-belts.
TA
TA units are supplied with F5 bag flters as
standard. F3 and F7 class bag flters can be
ordered separately. Te flter is positioned
before the fan and heating coil and is moni-
tored via time intervals.
F
F comes with three diferent flter options:
panel flter, bag flter and carbon flter.
Te panel flters absorb oil and grease and dis-
courage bacteria. Can withstand temperatures
of up to 80C. Bag flters are available in flter
classes G3-F9 for bag flters 360 mm long and
F5-F9 for bag flters 625 mm long. Carbon
flters are intended for kitchen extractor fans.
Te individual carbon cartridges comprise
one inner and one outer cylinder made of
galvanised steel and a cover.
71
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
PLUG FANS
Tis type of fan is chosen to ensure opti-
mum performance with regard to airfow,
sound level and efciency. A plug fan is a
single-inlet, free-blowing fan with the unit
casing acting as the fan casing.
TA
TA has a direct-drive plug fan with an
external rotor motor. Te impellers have
backward-curved blades. TA can also be
supplied with an external extract air fan
that can be connected to the unit and con-
trolled parallel to the TA unit.
Topvex with Standard controller
Topvex SR03-06 uses efcient plug fans
with backward-curved blades and main-
tenance-free external rotor motors. Te
units have EC motors achieving excellent
efciency. Te EC motors are controlled in
three stages via the control unit. All stages
are infnitely variable between 0 and 100%.
Electrical cables have quick connectors so
that the fans can be released quickly and
easily.
Topvex with Advanced controller
Topvex TR units have efcient plug fans
with EC motors. Both impellers have
backward-curved blades. Te infnitely
variable RPM control is integrated into the
fan motors. Te air volumes are individu-
ally controlled by measuring the pressure
diference across the inlet cone (CAV) or by
measuring the pressure in the ventilation
duct (VAV). Electrical cables have quick
connectors so that the fans can be released
quickly and easily.
TIME, DV, DVCompact, NB
Have highly efcient built-in plug fans with
low sound levels and a low pressure drop at
the duct connection. Te plug fans achieve
an efciency of up to 75%. TIME and
DV (DVE) are supplied with single-speed
motors. With direct-drive plug fans (no belt
drive), the unit requires very little servicing.
Fans and motors are mounted on efective
vibration dampers and are thus isolated
from the unit casing. It is possible to add a
built-in frequency converter to ensure the
desired pressure and airfow. Status alarm
as standard.
Topvex FR03-11, Topvex TR03-06,
Topvex SR03-06
Te heat exchanger is non-hygroscopic,
i.e. does not recover moisture. Efciency is
up to 85% for balanced airfows. Te heat
exchanger can be removed and has quick
connectors on its electrical cables.
Topvex TR09-15, Topvex SR07-11 E
Te heat exchanger is non-hygroscopic, i.e.
does not recover moisture. Efciency is up
to 85% for balanced airfows. Te heat
exchanger in Topvex TR09-15 can be
removed and has quick connectors on its
electrical cables.
ROTATING HEAT
EXCHANGER
Te rotating heat exchanger is a functional
element that recovers heat from indoor air
to warm up the cold outdoor air. A belt
drive transfers power from a rotor motor to
the heat exchanger. A rotor monitor emits
an alarm if the rotating heat exchanger
stops. Te design of the rotor with its cor-
rugated aluminium has been optimised to
ensure high efciency and a low pressure
drop. A stabilising rotor shaft guarantees
smooth and steady operation.
TIME, DVCompact
Te rotating heat exchanger is extremely
efcient, up to 85%. Heat exchangers are
controlled by a built-in motor and have var-
iable RPM control. Tey are also supplied
with purging sectors that prevent extract air
from mixing with supply air.
DV
DVC is also available in a hygroscopic ver-
sion, i.e. does recover moisture. Tis type of
heat exchanger saves the most energy. Te
standard version has an efciency of up to
80%, and there is an even more efcient
version that can achieve 87% efciency de-
pending on the operating conditions. It has a
short overall length. Heat exchangers can be
equipped with purging sectors that prevent
extract air from mixing with supply air.
NB
Rotating heat exchanger with an efciency
of up to 70% with purging sectors available
for all sizes.
72
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
CROSS-FLOW HEAT
EXCHANGER
Te cross-fow heat exchanger is a functional
element that recovers heat from indoor air
to warm up the cold outdoor air. Tese are
made of corrugated aluminium sheets. Heat
transfer between the sheets is improved
by the turbulence created by the surface.
Turbulence is created without any dirt being
collected and causing changes in velocity.
Te design of the plates means that the
entire surface of the heat exchanger can be
used to maximum efect. With balanced air-
fows, efciency can exceed 70% but around
50-60% is normal. In units where separate
airfows are required, it can be useful to
have a plate heat exchanger to perform this
function, for example, if you want to avoid
supply air being tainted by odours.
Maxi
Maxi 1100 has a built-in by-pass duct as
standard. Tis by-pass duct is available as
an accessory for Maxi 2000.
TIME, DVCompact
TIME with plate heat exchanger has a
build in by-pass and is supplied with a high
efciency heat exchanger type.
Topvex TX/SX
Topvex TX/SX has a built-in by-pass duct
as standard.
DV, NB
In units where separate airfows are
required, it can be useful to have a plate
heat exchanger to perform this function,
for example, if you want to avoid supply air
being tainted by odours. In cases where no
moisture is transferred between the airfows,
the plate heat exchanger DVQ can be used
as a dehumidifer and can be delivered with
a standard or a high efciency type. Tere
are two versions of this heat exchanger, both
of which are suitable for diferent types of
environment. Te aluminium version is used
in commercial ventilation, for example, in
schools, day nurseries, ofces and hotels,
where the air does not contain corrosive
particles that could damage the material.
Corrosion-resistant versions ftted with
surface-treated aluminium elements are used
in environments where the extract air could
contain aggressive particles. Heat recovery is
controlled via a built-in by-pass damper.
RUN AROUND COIL
HEAT EXCHANGER
DV
Te run around coil heat exchanger DVR
is a system where a mixture of water and
glycol is circulated between two coils. DVR
are used where the two airfows must be
completely separated.
73
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
AIR COOLER WATER
Air coolers are used to cool supply air. Air
coolers are made of copper tubing and have
aluminium elements. Te refrigerant is
water. Can be ftted with a drip tray.
TA, Maxi, Topvex
Ordered as an external accessory. Control-
led via the units built-in control system.
TIME
Te cooling coil is positioned after the
fan. Diferent capacities are available. Te
cooling capacity is controlled via the units
control system. Te coils are ftted with a
drip tray. Aluzinc 185-coated steel panel
frame.
DV
Te cooling coil DVK, is calculated and
designed for each air handling unit. Aluzinc
185-coated steel panel frame. Are ftted
with a drip tray. Change over coil, where
the same coil is used for both heating and
cooling, are available.
DVCompact
Te electric heating coil, witch have several
capacities, are positioned after the fan
and are ftted with condensation insulated
aluzinc 185-coated steel panel frame and
vertical pipe connections.
DV
Te heating coil DVH, is calculated and
designed for each air handling unit. Aluzinc
185-coated steel panel frame. Change over
coil, where the same coil is used for both
heating and cooling, are available.
DVCompact
Te coil is positioned after the fan and two
capacities per size are available. Aluzinc
185-coated steel panel frame and vertical
pipe connections.
HEATING COIL WATER
A water heating coil is used to supplement
the warmth of the air after any installed
heat exchanger so that the air (the supply
air) enters the unit at the correct tempera-
ture. Te coil is made of copper tubing with
a galvanised sheet steel frame and alumini-
um elements.
Maxi
Te coil is positioned in front of the fan.
TIME
Te coil is positioned after the fan and two
capacities per size are available. Aluzinc
185-coated steel panel frame.
HEATING COIL
ELECTRIC
Te heating coil is positioned after the fan
to provide a comfortable supply air tempera-
ture even at low outdoor air temperatures. It
comprises a frame of galvanised sheet steel
with stainless steel elements.
Maxi
Te coil is positioned before the fan.
DV
Te electric heating coils will be designed
and calculated for each air handling unit.
DVCompact
Te electric heating coil is positioned after
the fan and will be designed and calcu-
lated for each air handling unit. Aluzinc
185-coated steel panel frame.
74
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
F
With integrated sound-damping screens in
thicknesses of 100 or 200 mm.
TIME
Silencers can be integrated as a part of the
unit. Always as double silencers (inlet and
exhaust).
DV
Sound attenuator DVD is an absorptive
silencer ftted with bafes. For environmen-
tal reasons, the screens have been surface-
treated to prevent wear to the sound-
absorbing material. Tere are 3 diferent
types of surface treatment:
SILENCERS
Silencers are a functional element used
to reduce the transfer of unit noise to the
building and surroundings.
All our units can be equipped with silenc-
ers, as integrated or loose duct silencers.
For TA, Maxi, and Topvex, silencers are
available as an external accessory.
1. Standard coating ideal for all forms of
commercial ventilation.
2. Bafes coated with a strong, durable
material that is extremely resistant to
mechanical wear. Tis is used when baf-
fes will only be cleaned by brushing or
vacuuming.
3. Plastic-coated bafes are preferable when
they are likely to be cleaned by wash-
ing. In order to facilitate inspections and
cleaning of DVD, the unit housing has
large inspection panels for types 2 and 3.
Te bafes are designed so that they can
be removed for cleaning.
DVCompact
Te sound attenuator are ftted with aluzinc
185-coated steel panel frames and bafels.
Order as external accessory.
NB
Te bafes are flled with a soundproof
fbreglass material. Tere are two options to
choose from:
PA the soundproof material has a protec-
tive fameproof layer to discourage erosion
caused by airfows.
PAM has the same properties as PA, but
with an additional protective layer compris-
ing polyester flm (Melinex).
AIR COOLER DX
Air coolers are used to cool supply air and
employ the direct expansion principle (ex-
pansion valve). Air coolers are made of cop-
per tubing and have aluminium elements.
Te refrigerant does not contain freon.
Can be ftted with a drip tray.
TA, Maxi, Topvex
Ordered as an external accessory. Control-
led via the units built-in control system.
Topvex size 03-06 and FR03-11 also
requires the accessory: Signal converter
SC2/D.
TIME
Te Cooling coil is positioned after the
fan. Diferent capacities are available. Te
cooling capacity is controlled via the units
control system. Are ftted with a drip tray.
Aluzinc 185-coated steel panel frame.
DV
Te cooling coil DVK, is calculated and
designed for each air handling unit. Aluzinc
185-coated steel panel frame. Are ftted
with a drip tray. Change over coil, where
the same coil are used for both heating and
cooling are available. Cooler DVU in size
10-40 is a complete cooling system with all
cooling components and control system In-
tegreted in a DV casing. Stepless operation
from 0 to max capacity by advanced control
system and speed controlled compressor.
DVCompact
Te electric heating coil, witch have several
capacities, are positioned after the fan
and are ftted with condensation insulated
aluzinc 185-coated steel panel frame and
vertical pipe connections.
75
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
Control equipment
Systemair offers two different control equipment options, Standard and
Advanced, depending on the unit to be controlled. Both systems have
the same menu structure and use the same technical terms to ensure
easy operation.
Topvex FR03, 06, 08 and 11 will have E28 controller in April 2011. FR
units with E17S controller will thereafter be expired.
1)
Maxi 1100 has a built-in by-pass damper as standard
2)
TA 450-1100 EL, 1500-2000EL or HW and 3000-4500HW
3)
Requires by-pass damper
4)
Requires step controller SC2/D. Converts 0..10V signal to output relay
5)
Exoline, Modbus via RS485 and built-in Web via TCP/IP standard for Topvex TR/SR03-06 CAV/VAV
6)
Option for Topvex TR/SR03-06 CAV/VAV
S = Standard setting
P =Potential setting
C = Choose on order
O =Optional
T
o
p
v
e
x

T
R
/
S
R

0
3
,

0
4
,

0
6

C
A
V
/
V
A
V
T
o
p
v
e
x

F
R
0
3
,

0
6
,

0
8
,

1
1
T
o
p
v
e
x

T
X
/
S
X

0
3
,

0
4
,

0
6
T
A
T
o
p
v
e
x

T
R

0
9
,

1
2
,

1
5
T
i
m
e
D
V
D
V
C
o
m
p
a
c
t
M
a
x
i
T
o
p
v
e
x

S
R

0
7
,

0
9
,

1
1
CONTROL EQUIPMENT
E15S E17S E17S E28 E28 E28 E28 2xE28
St andard Advanced
Cont rol panel Separate with 10-metre cable S S S S S S S S
Repeater For installations with >10 metres between unit and panel O O O O O O O O
Sof t ware E-Tool O O O O O
Temperature cont rol Exhaust air P P P S S C C S
Supply air S S S P P C C C
Outdoor air temperature compensation supply air P P P P P C C O
Room air control P P C C C
Outdoor air temperature-dependent exchange between
supply air/exhaust air or supply air/room air control
P P C C C
Control of airfow 7-day timer with two separate operational periods S S S S S S S S
Fan speed cont rol Transformer S S
Individual variable voltage regulation S S
Air volume control, CAV C C C C
Constant duct pressure, VAV C C C C
Airfow compensated for outdoor air temperature S S P C C
Heat exchanger Cross-fow heat exchanger S S C C C
By-pass damper, variable S O
1)
C S S
Rotating S S C C S
Liquid-coupled C C
Recirculation C C C
Without C C
Heater Hot water C
2)
C C C C C C C
Electrical C
2)
C C C C C C C
Cool er Cold water coil. 0.10VDC output signal. P P P P P C C C
Cold water coil. Built-in.
DX cooling. 24VAC (1, 2 or 3-stage binary) output. P
4)
P
4)
P
4)
P P
4)
C C
DX cooling. Built-in. C C C
Free cool i ng P P P P P
3)
P C C
Cool recycl i ng - P P P P
3)
P C C
Demand vent i l at i on, CO
2
2-stage, CO
2
sensor with potential-free contact P P P P
Variable, CO
2
sensor with 0...10VDC signal P P C C
Pump cont rol Heat, 24VAC output signal (230V relay for Time and DV) P P C C S
Cooling, 24VAC output signal (potential-free relay for DV) P P C C S
Heat exchanger effciency Requires duct-mounted extract air temperature sensor P P (S) (S) S
Extended operat i on S S S S S S C S
7-day program Alternates between operating modes normal, reduced or off. S S S S S S S S
Damper cont rol Fresh air/Extract air S S S S S S C S
Al arm Alarm notifcation S S S S S S S S
High and low priority S S S S S
Buzzer alarm (24VAC output signal) S S S S S S C S
Timed flter alarm (monthly) S S S
Filter alarm triggered by pressure difference (Pa) S S S C S
Communi cat i on Exoline, Modbus via RS 485 O O O S
5)
S C C C
LON, Exoline via TCP/IP C
6)
O C C C
72
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
DIFFERENCES BETWEEN STANDARD AND ADVANCED
Standard controller is designed to be easy to use and controls smaller units with airfows of
up to 2500 m
3
/h. Advanced controller includes all the necessary functions demanded by
the market.
CONTROL EQUIPMENT Standard - E15S/E17S Advanced - E28
Uses E-Tool PC-based sof t ware No. Yes.
Temperature control 3 control options. 6 control options.
Timed airfow
7-day timer.
7-day timer + Holiday + Duct for digital
timer, e.g. for door locks.
Fan speed control
Individual variable voltage regulation be-
tween 0 and 100%. Transformer.
CAV, air volume control. VAV, constant duct
pressure. Airfow compensated for outdoor
air temperature.
Heat exchanger control Rotating, on/off. By-pass damper, on/off. Rotating, variable. By-pass damper, variable.
Demand control Option of using external equipment with
an output relay to increase airfow by one
setting.
Option of using external equipment with an
analogue output to increase airfow continu-
ously or with an output relay.
DX cool i ng control (external DX cool er) Requires a step controller that converts an
analogue control signal to digital 2-stage
binary control (accessory).
Up to 3-stage binary control as standard.
Hot water/Col d water pump control No. Yes.
Fi l ter moni tor Timed. Pressure difference.
73
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
FUNCTIONS INCLUDED IN STANDARD E15S/E17S
Menu l anguage Over 20 different languages.
Temperature control Constant supply air.
Constant supply air with compensation for outdoor air temperature.
Extract air (cascade).
Control of airfow 7-day timer with two separate operational periods/24 hours.
Fan speed control Individual variable voltage regulation between 0 and 100%.
Transformer.
Heat exchanger control Rotating heat exchanger, on/off.
By-pass damper, cross-fow heat exchanger (on/off).
Heat control Water coil (0...10V control signal).
Electric heating.
Control of col d water cool i ng External coil (010V control signal).
DX cool i ng control External coil (requires step controller SC2/D, accessory).
Cool i ng energy recover y Automatically recovers the cooled indoor air to cool the warmer outdoor air.
Ni ght cool i ng Night cooling is used during the summer to cool the property during the night using cold outdoor air. As the
need for cooling drops during the day, energy savings are possible.
Demand-control l ed venti l ati on The units have a digital input for extended/boosted operation through an external signal from an exter-
nal timer, presence detector, CO
2
sensor or similar sensors with a volt-free contact.
Extended/boosted operation is used when the unit switches from off, low or medium fan speed to a
selected fan speed.
Extended operati on The units have a digital input for extended/boosted operation. This function is activated by an external
signal from a button or timer. The function can also be activated via the control panel. Extended op-
eration can be set to run for 0 to 240 minutes.
7-day program Two separate operational periods/week and day.
Damper control 24V output signal controlling one or two shut-off dampers.
Al arm Alarm notifcation in clear text.
Buzzer alarm output signal (24V).
Fire alarm input (potential-free contact). Stops the unit or switches it to continuous operation.
Communi cati on A repeater (E0R, accessory) is required when the cable between the unit and control panel is longer
than 10 metres. E0R can control up to 6 air handling units.
Standard Exoline and Modbus via RS 485.
74
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
FUNCTIONS INCLUDED IN ADVANCED E28
Menu l anguage Over 20 different languages.
Temperature control Supply air.
Supply air with compensation for outdoor air temperature.
Extract air (cascade).
Room air control (cascade).
Outdoor air temperature-dependent exchange between room air control and supply air control.
Outdoor air temperature-dependent exchange between extract air control and supply air control.
Fan speed control Constant air volume control, CAV.
Constant duct pressure control, VAV.
Airfow/duct pressure compensated for outdoor air temperature.
Heat exchanger control Rotating heat exchanger (variable).
By-pass damper, cross-fow heat exchanger (variable).
Liquid-coupled heat exchanger (0...10V control signal or via two digital outputs).
Mixing damper (0...10V control signal).
Heat control Water coil (0...10V control signal).
Electric heating.
Water coil and electric heating.
Control of col d water cool i ng (010V control signal).
DX cool i ng control (up to 3-stage binary control).
Cool i ng energy recover y Automatically recovers the cooled indoor air to cool the warmer outdoor air.
Free cool i ng Free cooling is used to save energy by using the cold outdoor air, e.g. during night time, to
cool down the building.
Demand-control l ed venti l ati on For applications with varying loads, the fan speed and mixing damper can be controlled by the air
quality, measured using a CO
2
sensor. It is also possible to use a digital input for extended/boosted
operation via an external signal from an external timer, presence detector or similar sensors with a
volt-free contact.
Extended operati on The units have a digital input for extended/boosted operation. This function is activated by an external
signal from a button or timer. The function can also be activated via the control panel. Extended op-
eration can be set to run for 0 to 240 minutes.
Yearl y program A yearly clock function means you can store a 7-day program with holiday periods. Each day has up to
two individual operational periods for normal and reduced speed. Duct for digital timer, e.g. door locks,
lighting, etc.
Damper control 24V output signal controlling one or two shut-off dampers.
Al arm Alarm notifcation in clear text.
Alarm prioritisation. Alarms can be assigned different priorities, A, B and C alarms or inactive.
Buzzer alarm output signal (24V).
Fire alarm input (potential-free contact). Different fan modes in the event of a fre.
Communi cati on A repeater (E0R, accessory) is required when the cable between the unit and control panel is longer
than 10 metres. E0R can control up to 6 air handling units.
Standard Exoline and Modbus via RS 485.
Option Exoline via TCP/IP, built-in web. Standard to Topvex TR/SR03-06 CAV/VAV.
Option LON.
E-Tool sof t ware PC-based software.
75
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
www.systemair.com
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m
C
l
i
c
k

t
o

b
u
y

N
O
W
! P
D
F
-
X
C
hange V
ie
w
e
r
w
w
w
. d
o
cu-trac
k
.
c
o
m

You might also like