You are on page 1of 88

RM6 up to 24 kV

Medium Voltage Distribution


Catalogue I 2013
Gas Insulated Ring Main Unit
Make the most of your energy
SM
Gas Insulated Switchgear (GIS)
Ring Main Unit up to 24 kV


Contents
1
Contents
RM6 up to 24 kV
Presentation A-1
The RM6 range B-1
Unit characteristics C-1
Network remote control D-1
Accessories E-1
MV connection F-1
Installation G-1
Order form H-1
2
Your needs
FIABILITY
SIMPLICITY
SAFETY
3
RM6 solution
The RM6 is a compact unit combining all MV functional units to enable connection, supply
and protection of transformers on an open ring or radial network:
it is a complete range to meet the needs of sectors of the energy, of the industry and the building.
An uncomparable field-proven
experience: with over 1 300 000
functions installed worldwide.
High Quality: thanks to the stringent
application of the standards of ISO
quality 9001 and ISO 9002 during
the Conception, Manufacture, and
rigorous Tests and Control of the
product.
An assurance of maintain of
continuity of service: the conception
of the RM6 confers it a real complete
insulation which ensures to the
switchgear a total resistance against
severe environments, whether it is
the dust, or humidity.
A simple and limited maintenance:
with a periodicity from 5 to 10 years
Easy to install: due to its compact
dimensions and quick settle. If your
installation evolves, RM6 adapts
itself to respond to your growing
needs: on-site extensibility without
manipulation of gas nor particular
preparation of the ground allow you
to develop your installation simply
and safely.
Operate safely: The safety of the
person is for us a major commitment.
RM6 guarantees a total safety thanks
to the internal arc proof.
Contact of earthing is clearly visible.
The voltage indicators are located on
the front face.
Ultra-reliable device and a natural
interlocking ensured by a simple to
understand overview diagram on the
front side.
Safety for operator: the real position
of the contact on earth position
before working on the cubicle. The
moving contacts of the earthing
switch are visible in the closed
position through transparent
windows.
Transformer protection with a circuit
breaker: offering adjustable tripping
curve, overload protection, earth
fault protection always ready, and
avoiding fuse replacement, and
stock. In addition it allows immediate
reclosing possibility even remotely.
1700 000
RM6 protects persons and installations
all around the world with 1 700 000
functions installed in applications
of Medium Voltage secondary
distribution networks.
1


7
0
0

0
0
0
Contents
Presentation
Applications A-2
Range advantages A-5
Experience of a world leader A-6
Protecting the environment A-7
Quality - Standards A-8
A-1
Applications
Presentation
The RM6 can be adapted to meet all Medium Voltage power distribution needs, up to 24 kV.
The RM6 is a compact unit combining all MV functional units to enable connection,
supply and protection of transformers on an open ring or radial network:
by a fuse-switch combination, up to 2000 kVA ;
by a circuit breaker with protection unit, up to 8000 kVA.
The switchgear and busbars are enclosed in a gas-tight chamber, flled with SF6
and sealed for life.
D
E
5
9
7
8
5
R
E
-
I
I
D
E
-
B
C
D
E
-
M
t
D
E
-
D
D
E
-
I
NE-IDI
NE-IQI
NE-IIDI
M
T
5
5
1
4
7
M
T
5
5
1
4
8
M
T
5
5
1
4
6
HV/MV substation HV/MV substation
A-2
Applications
Presentation
A complete range, enabling you to equip MV network points, and enhance electrical power dependability.
Operating a distribution network sometimes requires switching points in addition to the HV/MV substations, in order to limit the effect of
a fault on the network.
The RM6 offers a choice of solutions to make 2, 3, 4 or 5 directional connections
with line protection by 630 A circuit breakers
with network switching by switch-disconnectors
with integrated power supply telecontrol devices.
NE-IBI
NE-IDI
NE-IBI NE-II NE-TIII
NE-IDI NE-IDI
NE-BIBI
R
E
-
O
D
E
-
M
t
D
E
-
B
NE-D NE-D
D
E
5
9
7
6
1
A-3
Applications
Presentation
Choosing RM6 offers you the experience of a world leader in the feld of Ring Main Units
The choice for your peace mind
The new RM6 generation benefits from the accumulated experience acquired from the 1,000,000 functional units that equip electrical
networks in more than 50 countries in Africa, America, Asia, Europe and Australasia.
With 20 local production units around the world, Schneider Electric offer products can be made available to you in the shortest possible time.
Advantages of a proven design
RM6 switchgear
Ensures personal safety:
internal arc withstand in conformity with
IEC 62271-200
visible earthing
3 position switchgear for natural interlocking
dependable position indicating devices.
Is insensitive to the environment:
stainless steel sealed tank
disconnectable, sealed, metallized fuse chambers.
Is of approved quality:
conforms to national and international standards
design and production are certified to ISO 9000
(version 2008)
benefits from the experience accumulated from
1,000,000 functional units installed world-wide.
Respects the environment:
end-of-life gas recovery possible
ISO 14001 approved production site.
Is simple and rapid to install:
front cable connections at the same height
easily fixed to the fl oor with 4 bolts.
Is economical:
from 1 to 5 functional units, integrated within the
same metal enclosurefor which insulation and
breaking take place in SF6 gas
lifetime of 30 years.
Has maintenance free live parts:
in conformity with IEC 62271-1, pressure system,
sealed for life.
Ring Main Unit, long experience
1983: marketing launch of the first RM6
compact with integrated insulation.
1987: creation of the circuit breaker
version, with integrated protection
unitneeding no auxiliary power supply.
1990: creation of the RM6 1 functional unit.
1994: creation of the Network Point,
integrating the RM6 and telecontrol.
1998: creation of the 630 A line protection
integrated relay circuit breaker and launch of an
RM6 range that is extensible on site.
2007: creation of the MV metering offer and
associated functions (metering module, busbar
coupling module, cable connection module).
2011: creation of RM6 Free Combination.
2012: creation of the RM6 5 functions (3 fixed
and 2 free).
0
4
4
8
9
0
3
8
1
7
8
0
5
5
4
0
8
A-4
Range advantages
Presentation
Compact and scalable, the RM6 range covers all of your requirements
Compact
RM6 Medium Voltage switchgear cubicles are perfectly suited for very simple
configuration of 2, 3, 4 or 5 directional connections.
Choice of all in one units integrated in a single metal enclosure
Cubicles insensitive to climatic conditions
Optimized dimensions
Quick installation through floor fixing with four bolts and front cable connection.
Extensible
Just as compact and insensitive to climatic
conditions the extensible RM6 is modular to suit your
requirements.
The addition of functional unit modules, allows you to
build the Medium Voltage switchboard suited to your
requirements.
Your organization develops, you build a new building -
RM6 adapts with you.
It can be extended on site without handling gases or
requiring any special floor preparation to develop your
installation simply and in complete safety.
On standard range only : see the exception.
Possibilities
to add cubicle
1
st
position 2
nd
position 3
rd
position Last position
RE-x DE-x DE-x LE-x
RE-x* DE-x DE-x LE-x
* It is not possible to add RE-x if switchboard with a station DE is in frst position
P
E
5
6
8
1
1
Circuit breakers, for greater safety and lower costs
The RM6 range offers 200 A and 630 A circuit breakers to protect both transformers
and lines. They are associated with independent protection relays that are
selfpowered via current sensors or with auxiliary supply protection relays.
Greater operating staff safety and improved continuity of service
increased protection device co-ordination with the source substation, circuit
breaker and the LV fuses
rated current is normally high, allowing use of a circuit breaker to provide
disconnection
the isolating system is insensitive to the environment.
Simplified switching operations and remote control
Reduction of losses thanks to the low value of RI2 (the fuse-switches of a 1000
kVA transformer feeder can dissipate 100 W).
Reduced maintenance costs no work in progress to replace fuses.
P
E
5
8
2
9
2
P
E
5
6
8
2
8
Trip coil
Sepam
series10 relay
+ auxiliary
supply
MITOP
VIP
relay
D
E
5
7
9
8
3
E
N
D
E
5
7
9
8
2
E
N
A-5
Experience of a world leader
Presentation
RM6, a world-wide product
Oceania
Eau et Electricit
de Caldonie
New-Caledonia
Enercal,
New-Caledonia
United Energy,
Australia
Main references
Asia/Middle East
BSED, Bahrein
DEWA, Duba
WED, Abu Dhabi
Tianjin Taifeng
Industrial Park, China
TNB, Malaysia
China Steel
Corporation, Taiwan
TPC, Taiwan
SCECO/SEC,
Saudi Arabia
PSB, China
Africa
Electricit de Mayotte
EDF Reunion
Total, Libya
SONEL, Cameroon
South Africa
South America/Pacific
CELESC,
Santa Catarina, Brazil
PETROBRAS,
Rio de Janeiro, Brazil
Guarulhos International
Airport
Sao Paulo, Brazil
CEMIG, Minas Gerais,
Brazil
EDF, French Guiana
Tahiti Electricity
Mtro de Mexico,
Mexico
Europe
EDF, France
Channel tunnel, France
Iberdrola, Spain
Compagnie Vaudoise
dlectricit
SEIC, Switzerland
Electrabel, Belgium
Union Fenosa, Spain
ENHER, Spain
Oslo Energie, Norway
STOEN, Poland
Bayernwerke, Germany
London Electricity,
United Kingdom
Mosenergo, Russia
M
T
5
5
1
5
6
Norway
P
5
0
4
0
0
2
0
_
K
S
A
Saudi Arabia
M
T
5
5
1
5
7
Sweden
M
T
5
5
1
5
8
Spain
E
I
I
M
I
N
I
S
U
B
South Africa
M
T
5
5
1
6
0
Australia
M
T
5
5
1
5
9
Russia
A-6
Protecting the environment
Presentation
The Schneider Electrics recycling procedure for SF6 based products is subject to rigorous
management, and allows each device to be traced through to its fnal destruction documentation
The RM6 recycling procedure
Schneider Electric is
committed to a long term
environmental approach.
As part of this, the RM6
range has been designed
to be environmentally
friendly, notably in
terms of the products
recycleability.
The materials used, both
conductors and insulators,
are identified and easily
separable.
At the end of its life,
RM6 can be processed,
recycled and its materials
recovered in conformity
with the draft European
regulations on the end-
of-life of electronic and
electrical products,
and in particular without
any gas being released
to the atmosphere nor
any polluting fluids being
discharged.
The environmental
management system
adopted by Schneider
Electric production sites
that produce the RM6
have been assessed and
judged to be in conformity
with requirements in the
ISO 14001 standard.
P
E
5
6
8
1
7
IDI IQI
Ferrous metal 78.5% 72.5%
Non-ferrous metal 13.3% 11.3%
Thermohardening 4.7% 11.3%
Thermoplastics 2% 4.1%
Fluids 0.5% 0.4%
Electronic 0.7% 0%
Other 0.4% 0.4%
D
E
5
5
7
4
6
-
2
AFNOR CERTIFICATION
I SO 14001
Qua l i t
A-7
Quality - Standards
Presentation
IEC standards
RM6 is designed in accordance with the following standards:
General operation conditions for indoor switchgears
IEC 62271-1 (common specifications for high voltage switchgear and controlgear)
Ambient temperature: class 25C indoor
lower than or equal to 40C without derating
lower than or equal to 35C on 24 hours average without derating
greater than or equal to 25C.
Altitude :
lower than or equal to 1000 m
above 1000 m, and up to 2000 m with directed field connectors
greater than 2000 m: please consult us for specific precaution.
DE-Mt needs voltage derating after 1 000m.
Please consider altitude and temperature when selecting Q function fuses.
IEC 62271-200 (A.C. metal enclosed switchgear and controlgear for rated voltage
above 1 kV and up to and including 52 kV)
Switchgear classification: PM class (metallic partitioning)
Loss of service continuity: LSC2B class for circuit breaker and switch
(LSC2A for fuse-switch combinations)
Internal arc classification: class A-FL up to 20 kA 1 s on request
(access restricted to authorized personnel only, for front and lateral access).
Maximum relative humidity: 95%
Switch-disconnectors
IEC 62271-103 (high voltage switches for rated voltage above 1 kV and less
than 52 kV)
Class M1/E3
100 CO cycles at rated current and 0.7 p.f.
1000 mechanical opening operations.
Circuit breakers: 200 A feeder or 630 A line protection
IEC 62271-100 (high voltage alternating current circuit breakers)
Class M1/E2
2000 mechanical opening operations,
O-3 min.-CO-3 min.-CO cycle at rated short circuit current.
Other applicable standards
IEC 62271-100 (high voltage alternating current circuit breakers)
Switch-fuse combinations: IEC 62271-105:
alternating current switch-fuse combination.
Earthing switch: IEC 62271-102:
alternating current disconnectors and earthing switches.
Electrical relays: IEC 60255.
A-8
Quality - Standards
Presentation
A major plus point
Schneider Electric has integrated a functional organization into each of its units,
the main purpose of which is to check quality and ensure the adherence to
standards.
This procedure is:
the same throughout the different departments
recognized by numerous approved customers and organizations.
Above all, it is our strict application of this functional organization that has enabled
us to obtain the recognition of an independent organization, the French Association
for Quality Assurance (Association Franaise pour lAssurance Qualit, or (AFAQ).
The RM6 design and production quality system has been certified as being
in conformity with the requirements of the ISO 9001: 2008 quality assurance
model.
Rigorous, systematic checks
During the manufacture of each RM6, it undergoes systematic routine tests,
the aim of which is to check quality and conformity:
tightness check
filling pressure check
opening and closing speed measurement
operating torque measurement
partial discharge check
dielectric check
conformity with drawings and diagrams.
The quality control department records and signs the results obtained on the test
certificate for each device.
There is zero SF6 emission during the gas filling and tightness control
process.
RM6 platform of test
P
E
5
8
2
9
0
A-9
wide choice
The RM6 range brings together
all the MV functions enabling
connection, power supply and
protection of transformers; protection
of lines and now production of private
MV/LV substations.
w
i
d
e

c
h
o
i
c
e
Contents
The RM6 range
RM6 switchgear description B-2
Safety of people B-3
RM6 for Marine applications B-5
A wide choice of functions B-6
B-1
RM6 switchgear description
The RM6 range
RM6 switchgear comprises 2, 3, 4 or 5 directionnal connections integrated, low dimension functional units.
This self-contained, totally insulated unit comprises:
a stainless steel, gas-tight metal enclosure, sealed for life, which groups together the live parts, switch-disconnector, earthing switch,
fuse switch or the circuit breaker
one to four cable compartments with interfaces for connection to the network or to the transformer
a low voltage cabinet
an electrical operating mechanism cabinet
a fuse chamber compartment for fused switch-disconnectors or fuse switches.
A range that is extensible on site
When harsh climatic conditions or environmental
restrictions make it necessary to use compact
switchgear, but the foreseeable evolution of the power
distribution network makes it necessary to provide
for future changes, RM6 offers a range of extensible
switchgear.
The addition of one or more functional units can
be carried out by simply adding modules that are
connected to each other at busbar level by directed
field bushings.
This very simple operation can be carried out on-site:
without handling any gas
without any special tooling
without any particular preparation of the floor.
The only technical limitation to the evolution of an
extensible RM6 switchboard is therefore the rated
current acceptable by the busbar: 630 A at 40C.
Insensitivity to the environment
Complete insulation
A metal enclosure made of stainless steel, which
is unpainted and gas-tight (IP67), contains the live
parts of the switchgear and the busbars.
Three sealed fuse chambers, which are
disconnectable and metallized on the outside,
insulate the fuses from dust, humidity...
Metallization of the fuse chambers and directed
field terminal connectors confines the electrical
field in the solid insulation.
Taken together, the above elements provide
the RM6 with genuine total insulation which makes
the switchgear completely insensitive to environmental
conditions, dust, extreme humidity, temporary soaking.
(IP67: immersion for 30 minutes, as laid down in
IEC standard 60529, 14.2.7).
The performance characteristics obtained by the RM6 meet the definition
of a sealed pressure system laid down in the IEC recommendations.
The switch-disconnector and the earthing switch offer the operator all necessary
usage guarantees:
Tightness
The enclosure is fi lled with SF6 at a 0.2 bar gauge pressure. It is sealed for life
after filling. Its tightness, which is systematically checked at the factory, gives
the switchgear an expected lifetime of 30 years. No maintenance of live parts
is necessary with the RM6 breaking.
Switch-disconnector
Electrical arc extinction is obtained using the SF6 puffer technique.
Circuit breaker
Electrical arc extinction is obtained using the rotating arc technique plus SF6
auto-expansion, allowing breaking of all currents up to the short-circuit current.
P
E
5
6
8
1
2
P
E
5
8
2
9
3
0
5
5
7
4
9
B-2
Safety of people
The RM6 range
Switchgear
Switch-disconnectors and circuit breakers have
similar architecture:
a moving contact assembly with 3 stable
positions (closed, open and earthed) moves
vertically (see sketch). Its design makes
simultaneous closing of the switch or circuit
breaker and the earthing switch impossible.
the earthing switch has a short-circuit making
capacity, as required by the standards.
the RM6 combines both the isolating and
interrupting function.
the earth collector has the correct dimensions for
the network.
access to the cable compartment can be
interlocked with the earthing switch and/or
the switch or circuit breaker.
The electrical and mechanical operating
mechanisms are located behind a front
plate displaying the mimic diagram of
the switchgear status (closed, open, earthed):
closing: the moving contact assembly is
manipulated by means of a fast-acting operating
mechanism. Outside these manipulations,
no energy is stored. For the circuit breaker
and the fuse-switch combination, the opening
mechanism is charged in the same movement
as the closing of the contacts.
opening: opening of the switch is carried
out using the same fast-acting mechanism,
manipulated in the opposite direction. For the
circuit breaker and fuse-switch combination,
opening is actuated by:
a pushbutton
a fault.
earthing: a specific operating shaft closes and
opens the earthing contacts. The hole providing
access to the shaft is blocked by a cover which
can be opened if the switch or circuit breaker is
open, and remains locked when it is closed.
switchgear status indicators: are placed
directly on the moving contact assembly
operating shafts. They give a definite indication
of the position of the switchgear (attachment A of
IEC standard 62271-102).
operating lever: this is designed with an anti-
reflex device which prevents any attempt to
immediately reopen the switch-disconnector or
the earthing switch after closing.
padlocking facilities: 1 to 3 padlocks can be
used to prevent:
access to the switch or circuit breaker operating shaft
access to the earthing switch operating shaft
operation of the opening pushbutton.
Earthing switch closed position indicators:
these are located on the upper part of the RM6.
They can be seen through the transparent earthing
covers, when the earthing switch is closed.
Internal arc withstand
The robust, reliable and environmentally
insensitive design of the RM6 makes it highly
improbable that a fault will appear inside the
switchgear. Nevertheless, in order to ensure
maximum personal safety, the RM6 is designed
to withstand an internal arc supplied by a rated
short-circuit current for 1 second, without any
danger to the operator.
Accidental overpressure due to an internal arc
is limited by the opening of the safety valve,
at the bottom of the metal enclosure. The internal
arc withstand of the tank is of 20 kA 1 s.
With the option of the internal arc in cable
compartment, the RM6 cubicle has an internal arc
withstand up to 20 kA 1 s, which meets all
the criteria of IAC class A-FL as defined by
IEC 62271-200 standard, appendix A. The gas
is released to the rear or to the bottom of the RM6
without affecting conditions in the front. When
the gas is exhausted to the rear, the maximum
internal arc withstand is of 16 kA 1 s. In case
the gas is exhausted to the bottom, the internal
arc withstand is up to 20 kA 1 s.
Reliable operating mechanisms
Earthing display
0
5
5
7
4
6
0
5
5
7
5
2
0
5
5
7
5
0
P
E
5
8
2
9
4
3 stable position switch
B-3
Safety of people
The RM6 range
Operating safety
Arc short-circuiting
Voltage indicator lamps
Cable insulation test
In order to test cable insulation or look for faults,
it is possible to inject a direct voltage of up to
42 kVdc for 15 minutes through the cables via
the RM6, without disconnecting the connecting
devices.
The earthing switch is closed and the moving
earthing connection is opened in order to inject
the voltage via the earthing covers. This system,
a built-in feature of the RM6, requires the use of
injection fingers (supplied as an option).
The moving contacts of the earthing switch
shall be visible in the closed position through
transparent covers.
RM6 Arc short-circuiting device : Arc Killer,
safety of persons, environnment friendly
Transforms an internal arc in the tank into short
-circuit.
Prevent overpressure inside the gas tank in case
of internal arc fault (no gaz outside the tank).
Available on switch function (I). No Extensible
or not on a side of extension.
A device (supplied as an option) on all functional
units makes it possible to check
the presence (or absence) of voltage in the cables.
Two types of indicator can be proposed according
to network operating habits:
a device with built-lamps, of the VPIS type
(Voltage Presence Indicating System) complying
with standard IEC 62271-206.
or a system with separate luminous modules,
of the VDS type (Voltage Detection System)
complying with standard IEC 61243-5.
0
5
5
7
5
7
P
E
5
6
4
1
8
P
E
5
6
3
6
6
B-4
RM6 for Marine applications
The RM6 range
P
E
9
0
0
0
7
RM6 Marine: benefi ts of the MV loop adapted to the boat
The RM6 has the DNV type approval certifi cate for Marine applications.
A MV loop confi guration offers significant advantages:
main MV switchboard smaller (only two cells to feed a MV loop)
length of MV cables reduced (shortening average ratio > 30% for
the configuration)
the maintainability and availability of the network are also improved.
Actually:
a failed cable section on the MV loop can be disconnected
an automatic reconfiguration of the MV loop after a fault detection
can be achieved.
Safety for personal
If RM6 is equipped with special filter LRU (internaL arc Reduction Unit), internal
arc classification is AFLR 20 kA 1 s defined in the standard IEC 62271-200.
Resistance to vibrations
Conform to IACS marine standards
RM6 has a very low centre of gravity.
Resistance to vibrations
Resist to agressive atmosphere.
Some Marine references
Aker Yards:
NCL Cruise Liner
Genesis 1 & 2.
Meyer Werft:
Ada ships
Norvegian Gem
Norvegian Pearl
Pride of Hawa,
Norvegian Jewel
Jewel of the seas
Example of a cruise liner architecture
RM6
substation
RM6
substation
RM6
substation
RM6
substation
RM6
substation
RM6
substation
RM6
substation
RM6
substation
Radial configuration
MV loop configuration
RM6
substation
RM6
substation
RM6
substation
RM6
substation
RM6
substation
RM6
substation
RM6
substation
RM6
substation
Radial configuration
MV loop configuration
D
E
5
7
9
8
4
E
N
B-5
A wide choice of functions
The RM6 range
RM6 range functions
Device designation
The RM6 range brings together all of the MV functions enabling:
connection, power supply and protection of transformers on a radial or open-ring network via 200 A circuit
breakers with an independent protection chain or via combined fuse-switches
protection of lines by a 630 A circuit breaker
and now production of private MV/LV substations with MV metering.

Function Network switch Line feeder Transformer feeder Network coupling Cable connection MV metering
Functional unit I B D Q IC BC O Mt
Device Circuit breaker 630 A circuit breaker 200 A circuit breaker Combined fuse-switch Switch 630 A circuit breaker
Single line diagrams
D
E
5
9
7
5
9
D
E
5
9
7
3
5
D
E
5
9
7
3
6
D
E
5
9
7
3
7
D
E
5
9
7
3
8
D
E
5
9
7
3
9
D
E
5
9
7
4
0
D
E
5
9
7
4
1
200 A 630 A

Type of tank Multifunction confgurations * Unit confgurations
NE: non-extensible
RE: extensible to the right
LE: extensible to the left
DE: extensible module
to the right or left
(one function)
I
B
D
Q
I
I
B
D
Q
I
I
B
D
Q
IC
BC
O
Mt
N 4 N 3 N 2 N 1 N 1
Examples of designation RM6 NE-DIDI
RM6 RE-IDI
RM6 NE-IQI
RM6 DE-I
RM6 NE-D
RM6 DE-Mt
* Refer to the table on page 68 for the choice of different combinations
B-6
A wide choice of functions
The RM6 range

Function Network switch Line feeder Transformer feeder Network coupling Cable connection MV metering
Functional unit I B D Q IC BC O Mt
Device Circuit breaker 630 A circuit breaker 200 A circuit breaker Combined fuse-switch Switch 630 A circuit breaker
Single line diagrams
D
E
5
9
7
5
9
D
E
5
9
7
3
5
D
E
5
9
7
3
6
D
E
5
9
7
3
7
D
E
5
9
7
3
8
D
E
5
9
7
3
9
D
E
5
9
7
4
0
D
E
5
9
7
4
1
630 A
B-7
characteristics
Detailed characteristics for each
function, combinations...
c
h
a
r
a
c
t
e
r
i
s
t
i
c
s
Contents
Unit characteristics
Main characteristics C-2
Detailed characteristics for each function C-3
Medium Voltage metering C-11
RM6 Free Combination C-12
RM6 5 functions C-14
Circuit breaker function
Protection relays selection C-15
Transformer protection by circuit breaker
VIP 40, VIP 45 C-16
General protection by circuit breaker
VIP 400 & VIP 410 C-17
VIP integrated system C-18
Line and transformer protection by circuit breaker
Sepam series 10 C-19
Core balance CTs CSH120, CSH200 C-20
Transformer protection by fuse-switches C-21
C-1
Main characteristics
Unit characteristics
Electrical characteristics
Rated voltage Ur (kV) 12 17.5 24
Frequency f (Hz) 50 or 60
Insulation level
Industrial frequency 50 Hz 1 mn Insulation
(1)
Up (kV rms) 28 38 50
Isolation
(2)
Ud (kV rms) 32 45 60
Impulse 1.2/50 s Insulation
(1)
Up (kV peak) 75 95 125
Insulation
(1)
Up (kV peak) 85 110 145
Tank internal arc withstand 20 kA 1 s
(1) Phase-to-phase, phase-to-earth
(2) Across the isolating distance
Climatic conditions
(C) 40 45 50 55 60
Busbars 630 A Ir (A) 630 575 515 460 425
Busbars 400 A Ir (A) 400 400 400 355
Functions: I, O, B (with bushing type C) (A) 630 575 515 460 425
Function D (with bushing type B or C) (A) 200 200 200 200 200
Function Q (A)
(3) (4) (4) (4) (4)
(3) Depends on fuse selection
(4) Please consult us
Accessories
Raising plinth
Set of 3 MV fuses Fusarc CF
Phase comparator
Test box for circuit breaker relay (VAP6)
Additional operating handle.
Additional instructions:
Installation and civil Engineering instructions.
Protection index
Tank with HV parts: IP67
Low voltage control compartment: IP3X
Front face + mechanism: IP3X
Cable compartment: IP2XC
Protection against mechanical impact: IK07.
P
E
5
6
8
1
1
Global options
Manometer or pressure switch
Additional earth busbar in cable compartment
Internal arc cable box 20 kA 1 s for I, D or B
functions.
Option for operation
Voltage indicator
VPIS
VDS.
Connectors and adaptaters for RM6
Connectors for 630 A (1 set = 1 function)
Connectors for 400 A (1 set = 1 function)
Connectors for 250 A (1 set = 1 function).
C-2
Detailed characteristics for each function
Unit characteristics
Rated voltage Ur (kV) 12 17.5 24 24 24 24
Short-time withstand current Ik (kA rms) 25 21 12.5 16 16 20
tk Duration (s) 1 1 or 3 1 1 1 1 or 3
Rated current busbars Ir (A) 630 630 400 400 630 630
Network switch (I function)
Rated current Ir (A) 630 630 400 400 630 630
Breaking capacity Active load Iload (A) 630 630 400 400 630 630
Earth fault Ief1 (A) 320 320 320 320 320 320
Cable charging Icc (A) 110 110 110 110 110 110
Making capacity of switch
and earthing switches
Ima (kA peak) 62.5 52.5 31.25 40 40 50
Bushing C C B or C B or C C C
Network points with switch-disconnector (I function)
Accessories and options (I function)
Remote operation
Motorization including auxiliary contacts (LBSw 2 NO -
2 NC and ESw 1 O/C).
Auxiliary contacts alone
For main switch position indication LBSw 2 NO - 2
NC and ESw 1 O/C (this option is included in remote
operation option).
Front door of cable connection compartment
Bolted
Removable with ESw interlocking
Removable with ESw interlocking and LBSw
interlocking.
Self-powered fault passage and load current indicators
Flair 21D
Flair 22D
Flair 23D
Flair 23DM
Amp 21D.
Key locking devices
Type R1
Type R2.
Arc Killer: RM6 arc short-circuiting device.
Transforms an internal arc into short-circuit
Available for Non Extensible cubicle or not on a side
of extension because arc Killer block is not compatible
with the extension bushing.
See decision tree (or Elonet) for applicable offers.
Metallic VT in some RM6 cubicles

Non-extensible switchgear
NE-I NE-II NE-III NE-IIII

Extensible switchgear to the right
RE-II RE-III RE-IIII

Double extensible switchgear
DE-III DE-IIII
D
E
5
9
7
4
2
D
E
5
9
7
4
3
D
E
5
9
7
4
6
C-3
Detailed characteristics for each function
Unit characteristics
Network points with 630 A disconnecting circuit breaker (B function)
Rated voltage Ur (kV) 12 17.5 24 24
Short-time withstand current Ik (kA rms) 25 21 16 20
tk Duration (s) 1 1 or 3 1 1 or 3
Rated current busbars Ir (A) 630 630 630 630
Network switch (I function)
Rated current Ir (A) 630 630 630 630
Breaking capacity Active load Iload (A) 630 630 630 630
Earth fault Ief1 (A) 320 320 320 320
Cable charging Icc (A) 110 110 110 110
Making capacity of switch
and earthing switches
Ima (kA peak) 62.5 52.5 40 50
Bushing C C C C
Line protection feeder (B function)
Rated current Ir (A) 630 630 630 630
Short-circuit breaking capacity Isc (kA) 25 21 16 20
Making capacity Ima (kA peak) 62.5 52.5 40 50
Bushing C C C C

Extensible switchgear to the right
RE-IBI RE-IIBI RE-BIBI

Double extensible switchgear
DE-IBI DE-IIBI
D
E
5
9
7
4
5
D
E
5
9
7
4
7

Non-extensible switchgear
NE-B NE-BI NE-IBI NE-IIBI NE-BIBI
D
E
5
9
7
4
4
Accessories and options (B function)
Remote operation
Motorization including shunt trip coil and auxiliary
contacts circuit breaker (CB 2 NO - 2 NC and ESw
1 O/C).
Auxiliary contacts alone
For circuit breaker position indication CB 2 NO -
2 NC and ESw 1 O/C (this option is included in remote
operation option).
Front door of cable connection compartment
Bolted
Removable with ESw interlocking
Removable with ESw interlocking and CB
interlocking.
Shunt trip coil for external tripping
24 Vdc
48/60 Vdc
120 Vac
110/125 Vdc - 220 Vac
220 Vdc/380 Vac.
Undervoltage coil
24 Vdc
48 Vdc
125 Vdc
110-230 Vac.
Protection relay for CB transformer protection
(VIP 400, 410 or Sepam series 10)*
Forbidden closing
under fault 1 NC
Auxiliary contact D or B
tripping
Key locking devices
Type R1
Type R2.
C-4
* In case of such relays,
ring-core CTs are
mandatory
Detailed characteristics for each function
Unit characteristics
Transformer feeder 200 A with disconnecting circuit breaker (D function)

Extensible switchgear to the right
RE-IDI RE-IIDI RE-DIDI

Double extensible switchgear
DE-IDI DE-IIDI
D
E
5
9
7
4
5
D
E
5
9
7
4
7

Non-extensible switchgear
NE-D NE-DI* NE-IDI NE-IIDI NE-DIDI
D
E
5
9
7
4
4
Accessories and options (D function)
Remote operation
Motorization including shunt trip coil and auxiliary
contacts circuit breaker (CB 2 NO - 2 NC and ESw
1 O/C).
Auxiliary contacts alone
For circuit breaker position indication CB 2 NO - 2
NC and ESw 1 O/C (this option is included in remote
operation option).
Front door of cable connection compartment
Bolted
Removable with ESw interlocking
Removable with ESw interlocking and CB
interlocking.
Shunt trip coil for external tripping
24 Vdc
48/60 Vdc
120 Vac
110/125 Vdc - 220 Vac
220 Vdc/380 Vac.
Undervoltage coil
24 Vdc
48 Vdc
125 Vdc
110-230 Vac.
Protection relay for CB transformer protection
(VIP 40, 45, 400, 410 or Sepam series 10)
Forbidden closing
under fault 1 NC
Auxiliary contact D or B
tripping
Key locking devices
Type R6
Type R7
Type R8.
Rated voltage Ur (kV) 12 17.5 24 24 24 24 24
Short-time withstand current Ik (kA rms) 25 21 12.5 16 12.5 16 20
tk Duration (s) 1 1 or 3 1 1 1 1 1 or 3
Rated current busbars Ir (A) 630 630 400 400 630 630 630
Network switch (I function)
Rated current Ir (A) 630 630 400 400 630 630 630
Breaking capacity Active load Iload (A) 630 630 400 400 630 630 630
Earth fault Ief1 (A) 320 320 320 320 320 320 320
Cable charging Icc (A) 110 110 110 110 110 110 110
Making capacity of switch
and earthing switches
Ima (kA peak) 62.5 52.5 31.25 40 31.25 40 50
Bushing C C B or C B or C C C C
Transformer feeder by disconnecting circuit breaker (D function)
Rated current Ir (A) 200 200 200 200 200 200 200
No-load transformer breaking capacity I3 (A) 16 16 16 16 16 16 16
Short-circuit breaking capacity Isc (kA) 25 21 12.5 16 12.5 16 20
Making capacity Ima (kA peak) 62.5 52.5 31.25 40 31.25 40 50
Bushing C C A B or C A B or C C
* For NE-DI, the rated current is of 200 A for the I and D functions.
C-5
Detailed characteristics for each function
Unit characteristics
Transformer feeder with fuse-switch combinations (Q function)
Accessories and options (Q function)
Remote operation
Motorization including auxiliary contacts fuse-switch
combinations (2 NO - 2 NC).
Auxiliary contacts alone
For fuse-switch combinations position indication
LBSw 2 NO - 2 NC (this option is included in remote
operation option).
Auxiliary contact for fuses blown
Shunt trip coil for external tripping
24 Vdc
48/60 Vdc
120 Vac
110/125 Vdc - 220 Vac
220 Vdc/380 Vac.
Undervoltage coil
24 Vdc
48 Vdc
125 Vdc
110-230 Vac.
Key locking devices
Type R6
Type R7
Type R8.
Rated voltage Ur (kV) 12 12 17.5 24 24 24 24
Rated current busbars Ir (A) 630 630 630 400 400 630 630
Network switch (I function)
Rated current Ir (A) 630 630 630 400 400 630 630
Breaking capacity Active load Iload (A) 630 630 630 400 400 630 630
Earth fault Ief1 (A) 320 320 320 320 320 320 320
Cable charging Icc (A) 110 110 110 110 110 110 110
Short-time withstand current Ik (kA rms) 21 25 21 12.5 16 16 20
tk Duration (s) 1 1 1 or 3 1 1 1 1 or 3
Making capacity of switch
and earthing switches
Ima (kA peak) 52.5 62.5 52.5 31.25 40 40 50
Bushing C C C B or C B or C C C
Transformer feeder with fuse-switch protection (Q function)
Rated current Ir (A) 200 200 200 200 200 200 200
No-load transformer breaking capacity I3 (A) 16 16 16 16 16 16 16
Short-circuit breaking capacity Isc (kA) 21 25 21 12.5 16 16 20
Making capacity Ima (kA peak) 52.5 62.5 52.5 31.25 40 40 50
Bushing A A A A A A A
Please consider altitude and temperature when selecting Q function fuses.

Non-extensible switchgear
NE-QI* NE-IQI NE-IIQI NE-QIQI
D
E
5
9
7
4
8

Double extensible switchgear
DE-IQI DE-IIQI
D
E
5
9
7
5
2
* For NE-QI, the rated current is of 200 A for the I and D functions.

Extensible switchgear to the right
RE-IQI RE-IIQI RE-QIQI
D
E
5
9
7
4
9
C-6
Detailed characteristics for each function
Unit characteristics
Rated voltage Ur (kV) 12 17.5 24 24 24 24
Short-time withstand current Ik (kA rms) 25 21 12.5 16 16 20
tk Duration (s) 1 1 or 3 1 1 1 1 or 3
Rated current busbars Ir (A) 630 630 630 630 630 630
Network switch (DE-I function)
Rated current Ir (A) 630 630 400 400 630 630
Breaking capacity Active load Iload (A) 630 630 400 400 630 630
Earth fault Ief1 (A) 320 320 320 320 320 320
Cable charging Icc (A) 110 110 110 110 110 110
Making capacity of switch
and earthing switches
Ima (kA peak) 62.5 52.5 31.25 40 40 50
Bushing C C B or C B or C C C
Extensible modules (DE-I function)
Accessories or options (I function)
Remote operation
Motorization including auxiliary contacts (LBSw 2 NO -
2 NC and ESw 1 O/C).
Auxiliary contacts alone
For main switch position indication LBSw 2 NO -
2 NC and ESw 1 O/C (this option is included in remote
operation option).
Front door of cable connection compartment
Bolted
Removable with ESw interlocking
Removable with ESw interlocking and LBSw
interlocking.
Self-powered fault passage and load current indicators
Flair 21D
Flair 22D
Flair 23D
Flair 23DM
Amp 21D.
Key locking devices
Type R1
Type R2.

DE-B

DE-I
D
E
5
9
7
5
1
D
E
5
9
7
5
0
Network points with 630 A disconnecting circuit breaker (DE-B function)
Rated voltage Ur (kV) 12 17.5 24 24
Short-time withstand current Ik (kA rms) 25 21 16 20
tk Duration (s) 1 1 or 3 1 1 or 3
Rated current busbars Ir (A) 630 630 630 630
Network disconnecting circuit breaker (DE-B function)
Rated current Ir (A) 630 630 630 630
Short-circuit breaking capacity Isc (kA) 25 21 16 20
Making capacity Ima (kA peak) 62.5 52.5 40 50
Bushing C C C C
Accessories and options
Remote operation
Motorization including shunt trip coil and auxiliary
contacts circuit breaker (CB 2 NO - 2 NC and ESw
1 O/C).
Auxiliary contacts alone
For circuit breaker position indication CB 2 NO -
2 NC and ESw 1 O/C (this option is included in remote
operation option).
Front door of cable connection compartment
Bolted
Removable with ESw interlocking
Removable with ESw interlocking and CB
interlocking.
Shunt trip coil for external tripping
24 Vdc
48/60 Vdc
120 Vac
110/125 Vdc - 220 Vac
220 Vdc/380 Vac.
Undervoltage coil
24 Vdc
48 Vdc
125 Vdc
110-230 Vac.
Protection relay for CB transformer protection
(VIP 40, 400 or Sepam series 10)
Forbidden closing under fault 1 NC
Auxiliary contact D or B tripping
Key locking devices
Type R1
Type R2.
C-7
Detailed characteristics for each function
Unit characteristics
Transformer feeder 200 A with disconnecting circuit breaker (DE-D function)
Extensible modules (DE-Q function)
Accessories and options
Remote operation
Motorization including shunt trip coil and auxiliary
contacts circuit breaker (CB 2 NO - 2 NC and ESw
1 O/C).
Auxiliary contacts alone
For circuit breaker position indication CB 2 NO -
2 NC and ESw 1 O/C (this option is included in remote
operation option).
Front door of cable connection compartment
Bolted
Removable with ESw interlocking
Removable with ESw interlocking and CB
interlocking.
Shunt trip coil for external tripping
24 Vdc
48/60 Vdc
120 Vac
110/125 Vdc - 220 Vac
220 Vdc/380 Vac.
Undervoltage coil
24 Vdc
48 Vdc
125 Vdc
110-230 Vac.
Protection relay for CB transformer protection
(VIP 40, 45, 400 or Sepam series 10)
Forbidden closing under fault 1 NC
Auxiliary contact D or B tripping
Key locking devices
Type R6
Type R7
Type R8.

DE-B
D
E
5
9
7
5
1

DE-Q
D
E
5
9
7
5
3
Rated voltage Ur (kV) 12 17.5 24 24 24
Short-time withstand current Ik (kA rms) 25 21 12.5 16 20
tk Duration (s) 1 1 or 3 1 1 1 or 3
Rated current busbars Ir (A) 630 630 400 400 630
200 A disconnecting circuit breaker (DE-D function)
Rated current Ir (A) 200 200 200 200 200
No-load transformer breaking capacity I3 (A) 16 16 16 16 16
Short-circuit breaking capacity Isc (kA) 25 21 12.5 16 20
Making capacity Ima (kA peak) 62.5 52.5 31.25 40 50
Bushing C C A B or C C
Rated voltage Ur (kV) 12 12 17.5 24 24 24
Rated current busbars Ir (A) 630 630 630 630 630 630
Fuses (DE-Q function)
Rated current Ir (A) 200 200 200 200 200 200
Off-load transformer laking capacity I3 (A) 16 16 16 16 16 16
Short-circuit breaking capacity Isc (kA) 21 25 21 12.5 16 20
Making capacity Ima (kA peak) 52.5 62.5 52.5 31.25 40 50
Bushing A A A A A A
Please consider altitude and temperature when selecting Q function fuses.
Accessories and options
Remote operation
Motorization including auxiliary contacts fuse-switch
combinations (2 NO - 2 NC).
Auxiliary contacts alone
For fuse-switch combinations position indication
LBSw 2 NO - 2 NC (this option is included in remote
operation option).
Auxiliary contact for fuses blown
Shunt trip coil for external tripping
24 Vdc
48/60 Vdc
120 Vac
110/125 Vdc - 220 Vac
220 Vdc/380 Vac.
Undervoltage coil
24 Vdc
48 Vdc
125 Vdc
110-230 Vac.
Key locking devices
Type R6
Type R7
Type R8.
C-8
Detailed characteristics for each function
Unit characteristics
Rated voltage Ur (kV) 12 17.5 24 24
Short-time withstand current Ik (kA rms) 25 21 16 20
tk Duration (s) 1 1 or 3 1 1 or 3
Rated current busbars Ir (A) 630 630 630 630
Network switch (DE-I function)
Rated current Ir (A) 630 630 630 630
Breaking capacity Active load Iload (A) 630 630 630 630
Earth fault Ief1 (A) 320 320 320 320
Cable charging Icc (A) 110 110 110 110
Making capacity of switch
and earthing switches
Ima (kA peak) 62.5 52.5 40 50
Bus coupler by switch-disconnector (DE-IC function)
Accessories and options
Remote operation
Motorization including auxiliary contacts (LBSw 2 NO -
2 NC and ESw 1 O/C).
Auxiliary contacts alone
For switch position indication LBSw 2 NO - 2 NC and
ESw 1 O/C (this option is included in remote operation
option).
Front door of cable connection compartment
Bolted
Removable with ESw interlocking
Removable with ESw interlocking and LBSw
interlocking.
Key locking devices
Type R1
Type R2.
With or without earthing switch
Bus coupler by 630 A disconnecting circuit breaker (DE-BC function)
Rated voltage Ur (kV) 12 17.5 24 24
Short-time withstand current Ik (kA rms) 25 17.5 16 20
tk Duration (s) 1 1 or 3 1 1 or 3
Rated current busbars Ir (A) 630 630 630 630
Network disconnecting circuit breaker (DE-B function)
Rated current Ir (A) 630 630 630 630
Short-circuit breaking capacity Isc (kA) 25 21 16 20
Making capacity Ima (kA peak) 62.5 52.5 40 50

DE-IC
D
E
5
9
7
5
4
Accessories and options
Remote operation
Motorization including shunt trip coil and auxiliary
contacts circuit breaker (CB 2 NO - 2 NC and ESw
1 O/C).
Auxiliary contacts alone
For circuit breaker position indication CB 2 NO -
2 NC and ESw 1 O/C (this option is included in remote
operation option).
Front door of cable connection compartment
Bolted
Removable with ESw interlocking
Removable with ESw interlocking and CB
interlocking.
Shunt trip coil for external tripping
24 Vdc
48/60 Vdc
120 Vac
110/125 Vdc - 220 Vac
220 Vdc/380 Vac.
Undervoltage coil
24 Vdc
48 Vdc
125 Vdc
110-230 Vac.
Protection relay for CB transformer protection
(VIP 400, 410 or Sepam series 10)
Forbidden closing under fault 1 NC
Auxiliary contact D or B tripping
Key locking devices
Type R6
Type R7
Type R8.
With or without earthing switch

DE-IC
D
E
5
9
7
5
5
C-9
Detailed characteristics for each function
Unit characteristics
Cable connection cubicles LE-O, RE-O, DE-O
Metering module DE-Mt

LE-O

RE-O

DE-O
D
E
5
9
7
5
6

DE-Mt
D
E
5
9
7
5
7
Voltage transformers configuration
Schneider Electric models or DIN 42600 type section 9.
2 phase-phase VT, 2 phase-earth VT, 3 TT phase-
earth VT.
Fitted right or left of the CTs.
Optional fuse protection.
Current transformers configuration
Schneider Electric models or DIN 42600 type section 8.
2 CT or 3 CT.
Accessories and options
Additional low voltage unit
Door key locking devices
Type R7 tubular.
Rated voltage Ur (kV) 12 12 17.5 17.5 24 24 24
Rated current busbars Ir (A) 630 630 630 630 630 630 630
Cable connection (O function)
Rated current Ir (A) 200 630 200 630 200 630 630
Short-time withstand current Ik (kA rms) 25 25 21 21 16 16 20
tk Duration (s) 1 1 3 3 1 1 1 or 3
Bushing C C C C C C C
Rated voltage Ur (kV) 12 17.5 24 24
Rated current busbars Ir (A) 630 630 630 630
MV metering (DE-Mt function)
Rated current Ir (A) 630 630 630 630
Short-time withstand current Ik (kA rms) 25 21 16 20
tk Duration (s) 1 1 or 3 1 1 or 3
Cubicle internal arc withstand 16 kA 1 s 16 kA 1 s 16 kA 1 s 16 kA 1 s
C-10
Medium Voltage metering
Unit characteristics
P
E
5
6
8
1
4
The RM6 is boosted by the DE-Mt module
This air-insulated cubicle is ftted with conventional current transformers and voltage transformers enabling invoicing of MV power. It has an
internal arc withstand and is integrated in the RM6 unit by a direct connection to the adjacent busbars.
Increased environmental insensitivity
By eliminating risks related to MV cables (incorrect connection, non-
compliance with radius of curvature between two adjacent cubicles, etc...).
Completely closed module (no opening to the bottom, no ventilation grid).
Factory tested module.
A clear separation between MV and LV
Everything is done to avoid having to act on the MV compartment.
The secondary of CT and VTs are cabled to the customer terminal in an LV
compartment.
This LV compartment enables:
connection to a remote power meter (in another room)
or connection to the LV unit mounted on the LV compartment (option).
An LV unit adapted to your requirements
This unit allows the installation of active power meters, a reactive power meter,
and all auxiliaries for monitoring current, voltage and consumed power.

RE-II DE-BC DE-Mt DE-D
P
E
5
6
8
1
5
D
E
5
9
7
5
8
Metering harsh environment
Current and voltage transformers for metering tough environnement.
Produce auxiliary voltage :
Adding metalic VT in some RM6 cubicles (I function).
The VRT4 is a phase-to-earth screened voltage transformer, placed behind
the cables. Totally insensitive to harsh atmosphere effects, it does not require any
fuse protection. A fexible connection to the front T-type cable plugs can be easily
disconnected for commissionning tests.
Standard IEC 60044-2
Voltage (kV) 7.2 - 20 - 60 7.2 - 32 - 60 12 - 28 - 75 12 - 42 - 75 17.5 - 38 - 95
Primary (kV) 6/3 6.6/3 6/3 10/3 11/3 10/3 13.8/315/3
1
st
secondary (V) 100/3 110/3 100/3 100/3 110/3 100/3 110/3 100/3
Rated output and
accurancy class
10 VA cl 0.2
2
nd
secondary (V) 100/3 110/3 100/3 100/3 110/3 100/3 110/3 100/3
Rated output and
accurancy class
30 VA 3P
The ARC5 is a ring-type current transformer used in core unit.
Compact dimensions for easy installation.
Cost-effective compared to standard MV block CTs.
Rated & Insulation voltage (kV) 0.72/3
Thermal withstand 25 kA x 2 s
Transformation ratio 100/5 200/5 400/5 600/5
Rated output with class 0,2S Fs
5 (VA)
5
VRT4
ARC5
C-11
RM6 Free Combination - Configuration
Unit characteristics
RM6 Free Combination is a new range extension and allows a higher confguration fexibility of
switchboards to meet all your needs:
Free choice of functions and options
Compatible with standard RM6 offer
Tanks including from 2 to 3 free choice functions
More economical compared to several single extension function in line.
Examples
Type of tank:
NE: non extensible
RE: extensible to
the right
LE: extensible to
the left
DE: extensible to
the right and left.
Quick and simple site installation
Compactness
Innovative choice of arrangement inside the tank
Reduced maintenance operations
700 possible combinations for RM6 2 or 3 functions
Possible combinations of RM6 2 functions
2
nd
function 1
st
function
I
B
D
Q
O
I
B
D
Q
O
Possible combinations of RM6 3 functions
3
rd
function 2
nd
function 1
st
function
* Possible only when RM6 is RE or DE.
I
B
D
Q
Ic
Bc
O
*
*
I
B
D
Q
O
I
B
D
Q
O

RM6 3 functions combinations
RE-IDD RE-IOO RE-IIBc RE-QQQ DE-BBD
D
E
5
9
7
7
2

RM6 2 functions combinations
RE-QD DE-DD DE-QQ LE-IO
D
E
5
9
7
7
1
C-12
RM6 Free Combination - Applications
Unit characteristics
Examples of typical applications

Switching large site
Possible confguration with Free Combination: DE-BB; DE-IDIc; DE-BB; DE-DI

Large transformer substation
Possible confguration with Free Combination: RE-QIQI; DE-QQ

Separate MV consumer substation
Possible confguration with Free Combination: RE-IIBc; DE-Mt; LE-DD

Satellite MV consumer substation
Possible confguration with Free Combination: NE-BDD
D
E
5
9
7
7
4
D
E
5
9
7
7
5
D
E
5
9
7
7
6
D
E
5
9
7
7
7
P
E
9
0
1
6
0
P
E
9
0
0
7
6
P
E
9
0
0
7
5
P
E
9
0
2
1
0
P
E
9
0
1
5
9

Private metering
Possible confguration with Free Combination: RE-IIBc; DE-Mt; LE-DD
D
E
5
9
7
7
3
630 A 200 A 200 A
630 A 630 A 200 A 630 A 630 A 200 A
Connection
to MV network
Connection
to MV network
Connection
to the open ring
Cable connection
to utility network
Connection
to MV network
Connection
to MV network
630 A 200 A 200 A
200 A 200 A 630 A
C-13
RM6 5 functions - Configuration
Unit characteristics
RM6 5 functions is an evolution and allows a higher confguration fexibility of switchboards
to meet all your needs:
5 functions: 3 fxed and 2 free
Compatible with standard RM6 offer
Tanks including 5 functions
More economical compared to several single extension function in line.
Examples
Quick site installation
Compactness
Reduced maintenance operations
Possible combinations of RM6 5 functions
Type of tank:
NE: non extensible
RE: extensible to the right
LE: extensible to the left
DE: extensible to the right and left.
5
th
function 4
th
function 3
rd
function 2
nd
function 1
st
function
I I I
B
D
Q
O
I
B
D
Q
O
I

Non extensible switchgear
NE-IIIII NE-IDIDI
D
E
5
9
7
8
6

Extensible switchgear to the right
RE-IIIDI
D
E
5
9
7
9
0

Double extensible switchgear
DE-IQIQI
D
E
5
9
7
9
1
C-14
Circuit breaker function
Protection relays selection
Unit characteristics
VIP 40, 45, 400, 410 & Sepam series 10 selection guide relays

Non extensible switchgear
NE-IIIII NE-IDIDI

Extensible switchgear to the right
RE-IIIDI

Double extensible switchgear
DE-IQIQI
VIP series Sepam series
Integrated self-powered protection
optimised for RM6
General
Transformer
protection
General
protection
Sepam series 10
ANSI code VIP 40 VIP 45 VIP 400 VIP 410 B A
Protection functions
Phase overcurrent 50-51
Earth fault phase Standard (sum of current method) 51N
High sensitivity (earth fault CTs)
Thermal overload 49
Logic discrimination Blocking send 68
Blocking reception
Cold load pick-up
Other protection functions
(1)

Measurement functions
Phase current
Earth current
Phase peak demand current
Load histogram
Control and monitoring functions
CB tripping Mitop Mitop Mitop Mitop Coil Coil
Trip circuit supervision 74TC
Time-tagged events Local on display (5 last trips)
Remote, via communication
External tripping input
Cumulative breaking current, number of trip orders
Overcurrent and breaking profle Number of phase and earth trips
(2)

Serial communication port Modbus RS485
Logic relay inputs (except TCS) used for: 1 0 or 2 0 or 2
External tripping 1 1 1
Local / Remote 1 1
Logic relay ioutputs used for: 3 3 or 7 3 or 7
Circuit breaker closing
by remote control
1 1
Logic discrimination
(Blocking send)
1 1
Watchdog By
modbus
1 1
Customised output via setting 3 4 4
Power supply
Type of supply Self-powered or auxiliary Self Self Self DUAL
Power
(1)
Auxiliary Auxiliary
Minimum 3 phase load currents
to activate the VIP
4 A 4 A 7 A
(3)
(1) The protection is self-powered. Auxiliary power is used only for communication and high sensitive earth fault protection.
(2) The number of trips is displayed in 4 levels:
For D01 and D02: < 200 A, < 2 kA, < 8 kA, > 8 kA
For D06 and D06H: < 630 A, < 10 kA, < 20 kA, > 20 kA.
(3) 14 A with 630 A CBs
Function available
Function availability depends on the Sepam model.
C-15
Transformer protection by circuit breaker
VIP 40, VIP 45
Unit characteristics
D
M
1
0
0
0
0
9
P
M
1
0
0
5
7
4
Applications
b Entry level MV/LV transformer protection
b Dependent-time phase overcurrent tripping curve dedicated to MV/LV transformer
protection
b Defnite-time earth fault protection
b Phase current and peak demand current measurement.
Main features
Self-powered operation
b Energised by the CTs: no auxiliary power needed.
Complete pre-tested protection system
b Functional block ready to be integrated.
Phase overcurrent protection
b Tripping curve optimised for MV/LV transformer protection
b Protection against overloads and secondary and primary short-circuits
b Second harmonic restraint fltering
b Only one setting (I >)
b Discrimination with LV circuit breakers or LV fuses
b Compliant with TFL (Time Fuse Link) operating criteria.
Earth fault protection
b Defnite-time tripping curve
b Settings: Io > (phase current sum method) and to >
b Second harmonic restraint element.
Measurement
b Load current on each phase
b Peak demand current.
Front panel and settings
b Current measurements displayed on a 3 digit LCD
b Settings with 3 dials (I >, Io >, to >) protected by a lead-sealable cover
b Trip indication powered by dedicated integrated battery with reset by pushbutton
or automatically.
Other features
b Complete pre-tested solution that eliminates complicated CT selection
b Complies with MV protection relay standard IEC 60255
b No PC or specifc tool required for setting or commissioning
b Maximum setting possibilities consistent with circuit breaker features
b Self-powered by dual core CTs: Cuar
b Environment: -40C / +70C.
Test with the Pocket Battery module
b This accessory can be connected on the VIP 40 and VIP 45 front plate to energise
the relay to carry out a quick test even when the relay is not powered
(the temporary VIP 40/45 test mode can be activated for the circuit breaker).
Rated protection current setting selection by VIP 40 and VIP 45
Operating
voltage (kV)
Transformer rating (kVA)
50 75 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 6300
3 10 15 20 25 36 45 55 68 80 115 140 170 200
3.3 10 15 18 22 28 36 45 56 70 90 115 140 200
4.2 8 12 15 18 22 28 36 45 55 70 90 115 140 200
5.5 6 8 12 15 18 22 28 36 45 55 68 90 115 140 170
6 5 8 10 12 18 20 25 36 45 55 68 80 115 140 170 200
6.6 5 8 10 12 15 18 22 28 36 45 56 70 90 115 140 200
10 5* 5 8 8 10 12 15 20 25 30 37 55 68 80 115 140 170 200
11 5* 5* 6 8 10 12 15 18 22 28 36 45 55 68 90 115 140 170
13.8 5* 5* 5 6 8 10 12 15 18 22 28 36 45 55 68 90 115 140 170
15 5* 5* 5 6 8 8 10 15 18 20 25 36 45 55 68 80 115 140 170 200
20 5* 5* 5* 5* 6 6 8 10 12 15 20 25 30 37 55 68 80 115 140 170 200
22 5* 5* 5* 5* 5 6 8 10 12 15 18 22 28 36 45 55 68 90 115 140 170
* Short-circuit protection, no over-load protection
Schneider Electric recommends circuit breakers for
transformer protection instead of fuses.
They offer the following advantages:
b Easy to set
b Better discrimination with other MV and LV
protection devices
b Improved protection performance for inrush currents,
overloads, low magnitude phase faults and earth
faults
b Greater harsh climate withstand
b Reduced maintenance and spare parts
b Availability of additional functions such as
measurement, diagnostics and remote monitoring
b And with the recent development of low cost circuit
breakers and self-powered relays, life time costs are
now equivalent to those of traditional MV switch fuse
solutions.
Dual core CTs: for power and for measurement
Dual core CTs
in a block under
the core unit
Mitop
VIP
C-16
General protection by circuit breaker
VIP 400 & VIP410
Unit characteristics
Applications
b MV distribution substation incomer or feeder protection relay
b MV/LV transformer protection.
Main features
VIP 400: Self-powered protection relay
This version is energised by the current transformers (CTs).
It does not require an auxiliary power supply to operate.
b Overcurrent and earth fault protection
b Thermal overload protection
b Current measurement functions.
Other features
b Designed for RM6 circuit breakers
b Complete pre-tested solution that eliminates complicated CT selection
b Complies with MV protection relay standard IEC 60255
b No PC or specifc tool required for setting or commissioning
b Self-powered by dual core CTs
b Environment: - 40C / +70C.
Test with the Pocket Battery module
b This accessory can be connected on the VIP relay front plate to energise the relay
to carry out a quick test even though the relay is not powered. This module also
makes it possible to test the circuit breaker.
VIP 410: Dual powered protection relay
b Offers the same self-powered functions as the VIP 400
b In addition, the VIP 410 has an AC or DC auxiliary supply to power certain
additionnal functions that cannot be self-powered:
sensitive earth fault protection
exernal tripping input
cold load pick-up
communication (Modbus RS485 port)
signaling.
b If the auxiliary power falls during an MV short-circuit, the protection functions are
maintained.
Ready for smart grids
Dual supply for communication with
b DMS and RTUS
b Remote alarming
b Time stamped events
b Measurements of current, load history, overcurrent and breaking profle.
Dedicated to intelligent MV loops with automation
b Remote confguration
b Setting groups selectable according to the confguration of the MV loop
b Remote asset management
b Plug and play system with Easergy RTUs (R200) to integrate all protocols
IEC 60870-104, DNP3, IEC 61850) and remote web pages.
VIP 400 is a self-powered relay energised by the CTs;
it does not require an auxiliary power supply
to operate.
VIP 410 is a dual powered relay offering self-powered
functions and additional functions powered by an AC
or DC auxiliary supply.
D
M
1
0
0
0
4
0
E
N
VIP
Test
pocket
battery
P
M
1
0
0
5
8
0
Master
Response
Interrogation
Slaves
C-17
Unit characteristics
D
M
1
0
0
0
2
9
-
1
D
M
1
0
0
0
2
9
-
2
High sensitivity sensors
VIP integrated protection system
The VIP integrated protection system is composed of sensors, a processing unit and
an actuator, designed together to provide the highest level of reliability and sensitivity
from 0.2 A to 20 In for VIP 400, VIP 410 and 5 A to 20 In for VIP 40 and VIP 45.
Sensors
The sensors are made up of one block of three CTs with rated and insulation
voltages of 0.72 kV / 3 kV - 1 min, providing both measurement and power outputs.
b The measurement sensor is based on Low Power Current Transformer (LPCT)
technology as defned by standard IEC 60044-8, ensuring excellent accuracy:
v 5P30 for protection
v class 1 for measurement.
b The power supply winding ensures calibrated self-powering of the relay even for
currents of just a few Amperes
v e.g. 7 A is suffcient for operation of the VIP 400 with a 200 A circuit breaker,
up to its saturation level
v e.g. 4 A is for operation of the VIP 40 up to its saturation level.
b Optionally, the VIP 410 can be associated with an earth fault current transformer
(a single zero-sequence CT) dedicated to sensitive earth fault protection with a low
threshold down to 0.2 A.
Actuators
b The actuator is a dedicated low power tripping coil (Mitop) specifcally designed
to operate with the sensors and the processing unit with minimum energy.
b The integrity of the Mitop circuit is continuously supervised
(Trip Circuit Supervision function).
Connection diagrams
The VIP series is an integrated protection system:
b Dedicated sensors located under the core unit
provide protection and measurement outputs
b Optional additional earth fault sensors are available
b Actuators are low power tripping coils (Mitop).
VIP 40, VIP45 & VIP 400
VIP 410
Test pocket
battery
Test pocket
battery
AC/DC
supply
Thermal EF OC Ext trip
Mitop
L1
L2
L3
Mitop
L1
L2
L3
Communication
RS485
Transformer protection by circuit breaker
VIP integrated system
C-18
Line and transformer protection by circuit breaker
Sepam series 10
Unit characteristics
Main features
Protection system
The protection system includes:
b 3 current transformers mounted on the bushings (same as VIP)
b 1 specially designed homopolar transformer CSH120 or CSH200
for the measurement of residual current (only for high sensitivity models)
b 1 Sepam series 10 relay
b 1 trip coil of RM6.
The Sepam series 10 needs an auxiliary power supply (not included in RM6).
The Sepam series 10 of 24 or 48 Vdc can be supplied by T200 I with option dc/dc
converter.
Simplicity and User-friendliness
b Easy operation: User-Machine Interface with screen, keys and pictograms.
Parameter setting directly on the relay without need of computer.
b Operating languages: English, Spanish, French, Italian, German, Turkish and
Portuguese.
Characteristics
b 4 logic inputs
b 7 relay outputs
b 1 communication port.
Sepam series 10 protection relays
b Protection against phase to phase faults and earth
faults, capable to detect the earth faults from 0.2 A.
b Possibility of communication with Easergy T200 I
and remote circuit breaker control.
b Thermal image overload protection (ANSI 49RMS).
b Logic discrimination for shorter tripping time.
b Record of last fault or last fve events.
P
E
5
7
7
7
0
A
B
C
D
E
5
9
7
8
7
P
E
5
7
1
7
0
CSH120
or
CSH200
Functions ANSI
code
Sepam series 10
B A
Protections
Earth-fault protection Standard 50N/51N v v
High sensitivity v v
Phase-overcurrrent protection 50/51 b b
Thermal overload protection 49RMS b b
Phase-overcurrent and earth fault protection
cold load pick-up
b b
Logic discrimination Blocking send 68 b b
Blocking reception b
External tripping b
Measurements
Earth-fault current b b
Phase currents b b
Peak demand currents b b
Control and supervision
Circuit breaker tripping and lockout 86 b b
Tripping indication b b
Trip-circuit supervision b
Remote circuit-breaker control b
Record of last fault b
Record of last fve events b
Communication
Modbus b
IEC 60870-5-103 b
Inputs / Outputs (Number)
Earth-fault current inputs 1 1
Phase-current inputs 2 or 3 3
Logic relay outputs 3 7
Logic inputs - 4
RS 485 communication port - 1
b Function available.
v Function availability depends on the Sepam model.
C-19
Unit characteristics
D
E
5
3
4
4
6
E
N
Characteristics
CSH120 CSH200
Inner diameter 120 mm (4.7 in) 200 mm (7.9 in)
Weight 0.6 kg (1.32 lb) 1.4 kg (3.09 lb)
Accuracy 5% to 20 C (68 F)
6 % max. from -25C to 70C (-13F to +158F)
Transformation ratio 1/470
Maximum permissible current 20 kA - 1 s
Operating temperature -25C to +70C (-13F to +158F)
Storage temperature -40C to +85C (-40F to +185F)
Dimensions
The specifcally designed CSH120 and CSH200
core balance CTs are used for direct residual current
measurement. The only difference between them is
the diameter. Due to their low voltage insulation,
they may be used only on cables with earthed
shielding.
Line and transformer protection by circuit breaker
Core balance CTs CSH120, CSH200
Dimensions A B D E F H J K L
CSH120 mm 120 164 44 190 76 40 166 62 35
in 4.72 6.46 1.73 7.48 2.99 1.57 6.54 2.44 1.38
CSH200 mm 200 256 46 274 120 60 257 104 37
in 7.87 10.1 1.81 10.8 4.72 2.36 10.1 4.09 1.46
4 horizontal fixing
holes, Diam. 5 mm
4 vertical fixing
holes, Diam. 5 mm
Core balance CTs CSH120 and CSH200
P
E
5
0
0
3
2
C-20
Transformer protection by fuse-switches
Unit characteristics
Characteristics
Ratings for fuses for transformer protection depend, among other points,
on the following criteria:
b service voltage
b transformer rating
b thermal dissipation of the fuses
b fuse technology (manufacturer).
Type of fuse may be installed:
b Fusarc CF type: according to IEC 60282-1 dimensional standard,
with or without striker.
Example (using the selection table below) general case, for protection of a 400 kVA
transformer at 10 kV, Fusarc CF fuses with a rating of 50 A are chosen.
Correct operation of the RM6 is not guaranteed when using fuses from other
manufacturers.
Fuse replacement
IEC recommendations stipulate that when a fuse has
blown, all three fuses must be replaced.
Selection table
(Rating in A, no overload, 25C < q < 40C)
Fuse type Fusarc CF and SIBA
(1)
(General case, IEC 60282-1 standard, IEC 62271-105 (to replace IEC 60420) and DIN 43625 standard)
Operating
voltage (kV)
Transformer rating (kVA) Rated
voltage (kV)
50 75 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000
3 20 31.5 40 50 50 63 80 100 125
(2)
160
(1) (2)
12
3.3 20 25 40 40 40 63 80 80 125
(2)
125
(2)
160
(1) (2)
4.2 20 25 25 40 50 50 63.5 80 80 100 125
(2)
160
(1) (2)
5.5 16 20 25 25 40 40 50 63 80 80 100 125
(2)
160
(1) (2)
6 16 20 25 25 31.5 40 50 50 63 80 100 125
(2)
160
(1) (2)
6.6 10 20 25 25 31.5 40 50 50 63 63 80 100 125
(2)
160
(1) (2)
10 10 10 16 20 25 25 31.5 40 50 50 63 80 100 125
(2)
11 10 10 16 20 20 25 25 40 40 50 50 63 80 100 125
(2)
13.8 10 10 10 16 16 20 25 31.5 40 40 50 50 63 100
(2)
24
15 10 10 10 10 16 20 25 31.5 31.5 40 50 50 63 80 100
(2)
20 10 10 10 10 16 16 20 25 25 31.5 40 40 63 63 80 100
(2)
22 10 10 10 10 10 16 16 20 25 31.5 40 40 50 63 80 100
(2)
D
E
5
7
4
6
7
Fuses dimensions
Fusarc CF
6 45
33
L 23
33
Ur (kV) Ir (A) L (mm) (mm) Mass (kg)
12 10 to 25 292 50.5 1.2
31.5 to 40 292 55 1,8
50 to 100 292 76 3.2
125 442 86 5
24 10 to 25 442 50.5 1.7
31.5 to 40 442 55 2.6
50 to 80 442 76 4.5
100 442 86 5.7
C-21
network
Schneider Electric offers you a
complete solution, including remote
control and monitoring interface and
MV switchgear that is adapted for
telecontrol.
n
e
t
w
o
r
k
Contents
Network remote control
Architecture and SCADA L500 D-2
Easergy T200 I control unit D-3
Automatic transfer systems D-4
Motorization D-8
D-1
Network remote control
Architecture and SCADA L500
Continuity of service guaranteed by an overall telecontrol offer
Schneider Electric offers you a complete solution, including:
b the Easergy T200 I telecontrol interface
b MV switchgear that is adapted for telecontrol.
Easergy L500 is a SCADA providing all the
functions needed to operate
the MV network in real time
b Pre-confgured with Easergy range products for
monitoring and control
of MV networks:
v MV/LV substations equipped with T200 I or
Flair 200C
v Overhead LBS equipped with T200 P
v Overhead line equipped with Flite 116/G200
v Overhead CB equipped with ADVC ACR U and N
series
b Broad range of transmission supports: Radio, GSM,
GPRS, 3G, PSTN, LL, FO.
Advantages
b Simple implementation:
v One to two weeks only for 20 MV/LV units
v Confguration, training and handling within a few
days
b Simple and fast evolutions by operations managers
b Short return on investment
b Service quality and operations rapidly improved.
Easergy L500, a low cost solution to immediately improve
your SAIDI (System Average Interruption Duration Index)
D
E
5
7
9
5
9
E
N
Network control centre
HV/MV
Communication network
RM6 IIII RM6 IDI RM6 IIII
RM6 IIII RM6 IDI
Easergy T200
Easergy T200
Easergy T200
RM6 IDI
MV ring
P
E
5
6
3
1
2
L500 network monitor screen
D
E
5
7
9
9
5
Communication
network: radio,
PSTN, GSM/GPRS,
Ethernet, 3G
Easergy L500 Existing SCADA
D-2
Easergy T200 I control unit
Network remote control
Easergy T200 I: an interface designed
for telecontrol of MV networks
Easergy T200 I is a plug and play or multifunction
interface that integrates all the functional units
necessary for remote supervision and control
of the RM6:
b acquisition of the different types of information:
switch position, fault detectors, current values...
b transmission of switch open/close orders
b exchanges with the control center.
Required particularly during outages in the network,
Easergy T200 I is of proven reliability and availability,
being able to ensure switchgear operation at any
moment.
It is simple to set up and to operate.
Functional unit designed for the Medium Voltage network
b Easergy T200 I is designed to be connected directly to the MV switchgear,
without requiring a special converter.
b It has a simple front plate for local operation, which allows management of
electrical rating mechanisms (local/remote switch) and display of information
concerning switchgear status.
b It has an integrated MV network fault current detection system (overcurrent and
zero sequence) with detection set points that can be confgured channel by
channel (current value and fault current duration).
Medium Voltage switchgear operating guarantee
b Easergy T200 I has undergone severe MV electrical stress withstand tests.
b It is a backed up power supply which guarantees continuity of service for several
hours in case of loss of the auxiliary source, and supplies power to the Easergy
T200 I and the MV switchgear motor mechanisms.
b Ready to plug
v Easergy T200 I is delivered with a kit that makes it easy to connect the motor
mechanisms and collect measurements.
v The telecontrol cabinet connectors are polarized to avoid any errors during
installation or maintenance interventions.
v Current measurement acquisition sensors are of the split type (to facilitate
their installation) or of closed type mounted on RM6 bushings.
v Works with 24 Vdc and 48 Vdc motor units.

Please consult the Easergy T200 I documentation for any further information.
Split sensors
6
1
0
2
1
N
P
E
5
6
3
1
1
Local information
and control
Monitoring and control
P
E
5
6
4
2
1
P
E
5
6
4
2
2
Polarized connectors
P
E
5
6
8
2
4
Back up power supply
P
E
5
6
4
2
3
CT on bushings
P
E
5
7
7
7
5
D-3
Network remote control
Automatic transfer systems
Because a MV power supply interruption
is unacceptable especially in critical applications,
an automatic system is required for MV source
transfer.
An ATS solution is made of:
2 VPIS-VO
Voltage sensor:
dedicated version of
VPIS with voltage output
signal.
2 VD23
Voltage detector: a relay
is activated when a loss
of voltage is detected
from the VPIS voltage
output signal.
2 CTs for FPI
Fault Passage Indicator
(included in T200 I): if a
fault current is detected,
the Automatic Transfer
System is locked in order
to avoid closing the
healthy line on the fault.
1 T200 I +
switch
function
motorized
From the digital input
coming from the VD23
and the FPI information,
T200 I takes the decision
to switch from one line to
the other.
Communication to
SCADA: optionally,
communication facilities
may be added.
Modems: PSTN,
Radio, GSM/GPRS/3G,
Ethernet,
Protocols: Modbus,
Modbus IP, IEC 870-5-
101 and 104,
DNP3, DNP3 IP,
Functions: dual port,
remote confguration,
For your peace of mind, RM6 gives automatic control
and management of power sources in your Medium
Voltage secondary distribution network with a short
transfer time (less than 10 seconds), guaranteeing
the hi-reliability of your installation.
Automatic control is performed by Easergy T200 I.
This T200 I device can also be used for remote control
with a wide range of modems and protocols.
By default, the T200 I is provided with the RS232
modem and the Modbus/IP protocol.
P
E
5
7
7
7
1
M M
SCADA
T200 I
VD23
L1 L2
VD23
D-4
Automatic transfer systems
Network remote control
SW1 SW2
D
E
5
9
7
6
8
Line 1 Line 2
Network ATS (1/2): changeover between two MV network sources.
3 operating modes (selected from the T200 I Web server)
1 - Auto SW1 or Auto SW2 mode
In the event of a voltage loss on the distribution line in service (SW1), the ATS
changes over to the backup line (SW2) after a confgurable time delay (T1).
[opening of SW1, closing of SW2]
As soon as voltage returns on the main line (SW1), the ATS changes back to the
main line after a time delay (T2).
[opening of SW2, closing of SW1 if the paralleling option is not activated]
[closing of SW1, opening of SW2 if the paralleling option is activated]
2 - Semi-Auto SW1XVSW2
In the event of a voltage loss on the distribution line in service (SW1), the ATS
changes over to the backup line (SW2) after a confgurable time delay (T1).
[opening of SW1, closing of SW2]
The ATS does not change back to the main line, except in the event of a voltage loss
on the backup line [opening of SW2, closing of SW1]
3 - Semi-Auto SW1VSW2 or Semi-Auto SW2VSW1
In the event of a voltage loss on the distribution line in service (SW1), the ATS
changes over to the backup line (SW2) after an adjustable time delay (T1).
[opening of SW1, closing of SW2]
The ATS maintains the backup line in service (SW2) irrespective of the voltage
on the two lines.
D
E
5
7
9
8
9
E
N
SW2 voltage
SW1 voltage
SW1 voltage
Network ATS - Auto Mode SW1
(with paralleling upon automatic return)
Network ATS - Semi-Auto Mode
(without paralleling upon automatic return)
T1
Vn
SW1
SW2
TR
Vn
Vn
0
0
C
0
C
0
0
C
0
0
C
T1 T2
TR
SW2
TR TR
TR TR
SW1 T1 TR TR
Characteristics
TR: switch response time (< 2 s).
b Time delay before changeover (T1)
Confgurable from 0 s to 200 s in increments of 100 ms (factory setting = 1 s).
This time delay is also used to delay return to the initial channel
in Semi-Auto mode SW1XVSW2
b Time delay before return to the initial channel (T2) (Auto mode only)
Confgurable from 0 s to 30 min. in increments of 5 s (factory setting = 15 s).
D-5
Network remote control
Automatic transfer systems
Generator ATS (1/2): changeover between a distribution system line and a generator.
3 operating modes
1 - Auto SW mode
In the event of a voltage loss on the distribution line in service (SW), after a time
delay T1, the ATS sends the opening command to SW and at the same time the
Generator start-up order.
The remaining operation of the changeover sequence depends on the confguration
of the Generator channel closing option:
b Case 1 Generator channel closing after Generator power on: the Generator
channel closing order is sent only when Generator voltage is detected.
b Case 2 Generator channel closing after Generator start-up order: immediately
after sending the Generator start-up order, the closing order is given to the
Generator channel, without waiting until the Generator is actually started.
[opening of SW, closing of SWG]
As soon as voltage returns on the main line (SW), after a time delay T2, the ATS
changes back to the main line and the generator stoppage order is activated.
[opening of SWG, closing of SW if the paralleling option is not activated]
[closing of SW, opening of SWG if the paralleling option is activated]
2 - Semi-Auto SWXVSWG
The ATS does not change back to the main line, except in the event of a voltage loss
on the generator due to generator stoppage or the opening of a switch upstream
of the SWG channel.
3 - Semi-Auto SWVSWG
In the event of a voltage loss on the distribution line in service (SW), after a time
delay T1, the ATS sends the opening command to SW and at the same time
the Generator start-up order.
The remaining operation of the changeover sequence depends on the confguration
of the Generator channel closing option:
b Case 1 Generator channel closing after Generator power on
b Case 2 Generator channel closing after Generator start-up order
[opening of SW, closing of SWG]
The ATS maintains the backup line in service (SWG) and there is no automatic return.
Characteristics
TR: switch response time
b Time delay before changeover (T1): confgurable from 0 s to 200 s in increments
of 100 ms (factory setting = 1 s).
This time delay is also used to delay return to the initial channel in Semi-Auto mode
SWXVSWG
b Time delay before return to the initial channel (T2)
b (Auto mode only). Confgurable from 0 s to 30 min. in increments of 5 s (factory
setting = 15 s).
b Tg1: Generator start-up, depending on the generator type, not confgurable
(max. waiting time: 60 s). If Tg1 is greater than 60 s, changeover is suspended.
b Tg2: Generator stoppage, depending on the generator type, not confgurable
(max. waiting time: 30 s).
Note: the generator stoppage command is sent 6 s after the end of changeover
D
E
5
7
9
9
8
E
N
SW1 voltage
GE Command
GE voltage
Tg1
Vn
0
1
0
Vg
0
Tg2
T1 6s
TR TR
TR
C
O
T2
TR T2
TR
C
O
C
O
TR SWG
SW
SWG
Generator ATS - Auto SW mode
(without paralleling upon automatic return)
Case : Generator channel closing after Generator power
on (confgurable option)
Case : Generator channel closing after Generator start-up
command (confgurable option)
D
E
5
9
7
6
9
Line
SW SWG
G
D-6
Automatic transfer systems
Network remote control
Bus tie coupling (2/3): source changeover between 2 incoming lines (SW1 and SW2)
and a busbar coupling switch (SW3)
2 operating modes (selected from the Easergy T200 I confgurator)
1 - Standard mode
In the event of a voltage loss on the distribution line in service (SW1), the ATS
changes over to the backup line (SW2) after a confgurable time delay (T1).
[opening of SW1, closing of SW3]
As soon as voltage returns on the main line (SW1), the ATS changes back to
the main line after a time delay (T2).
[opening of SW3, closing of SW1 if the paralleling option is not activated]
[closing of SW1, opening of SW3 if the paralleling option is activated]
2 - Mode with locking upon voltage loss after changeover
In the event of a voltage loss on the distribution line in service (SW1), the ATS
changes over to the backup line (SW2) after an adjustable time delay (T1).
[opening of SW1, closing of SW3].
Voltage presence is monitored during a confgurable period T3. If the voltage
disappears during this period, coupling switch SW3 is opened and the automatic
transfer system is locked.
Other functions
ATS in ON/OFF mode
The ATS system can be switched on or off from the local control panel (T200 I)
or remotely (Scada system).
When the ATS is OFF, the RM6 switches can be electrically actuated by local
or remote control (operation in parallel mode is therefore possible).
ATS in parallel mode upon Auto return
Activating this option enables paralleling of the channels by the automatic transfer
system, during the phase of automatic return to the priority channel.
To be used when the ATS is in Auto mode.
Application: synchronization of the voltages of the main power supply line and
the backup line allows return to the main line without any interruption.
Generator ON override command
Activation of the ATS and transfer on Generator can be activated upon an order:
remotely or through dedicated digital input.
Applications:
b Periodic maintenance tests of the ATS/Generator system
b Switch on Generator when the Network is overloaded.
During peak hours, and if network is overloaded, Utility can send a remote order that
will activate Generator. Having this facility, it will allow a private customer to negotiate
better tariff of electricity.
D
E
5
9
7
7
0
SW1 SW2 SW3
SW1 SW2 SW3
D
E
5
7
9
9
9
E
N
SW2 voltage
SW1 voltage
Vn
Vn
0
0
TR TR T2
TR TR T1
T3
SW1
SW3
C
O
C
O
Characteristics
TR: switch response time (< 2 s).
b Time delay before changeover (T1)
Confgurable from 100 ms to 60 s in increments of 100 ms (factory setting = 5 s).
b Time delay before return to the initial channel (T2)
Confgurable from 5 s to 300 s in increments of 1 s (factory setting = 10 s).
b Monitoring time (T3)
Confgurable from 100 ms to 3 s in increments of 100 ms (factory setting = 1 s).
Changeover conditions
b Validation of the ATS (from the confgurator)
b The ATS is in operation (local control panel or remote control)
b The external closing digital input is OFF
b The switch for the main line is closed and the backup line switch is open
b No fault detected on the line in service
b The earthing switch is open on both switches.
BTA - Standard mode
(without paralleling upon automatic return)
D-7
Network remote control
Motorization - Switch, circuit breaker
and fuse-switch combination
Motor mechanism
Switch operating mechanism
b The switch operating mechanism includes a space that is reserved for the
installation of a geared motor. This can be installed at the factory, but it can also
the installed on-site, by the customer, without de-energizing the unit, and without
dismantling the operating mechanism.
b An electrical interlocking assembly prohibits any false operations.
Once motorized, the RM6 integrates perfectly into a telecontrol system
Circuit breaker and fuse-switch combination
operating mechanism
b Circuit breaker or fuse protection functions can be motorized.
Functional units of circuit breaker or fuse-switch protection can be equipped.
The motorization can be installed at the factory, but it can also be installed on-site,
by the customer, without de-energizing the unit, and without dismantling the
operating mechanism.
b Electrical locking prohibits any false operations. This functionality is an option for
circuit breaker and is by default for fuse-switch function. Once motorized, the RM6
integrates perfectly into a telecontrol system.
This option becomes particularly useful in the context of the protection
of a secondary ring, with supervision by a telecontrol system.
Unit applications
Operating mechanism types CIT CI1 CI1
Switch Circuit breaker Fuse switch combination
Main circuit switch Closing Opening Closing Opening Closing Opening
Manual operating mode Hand lever Hand lever Hand lever Push button Hand lever Push button
Remote control option Motor Motor Motor Coil Motor Coil
Operating time 1 to 2 s 1 to 2 s max. 13 s 65 to 75 ms 11 to 13 s 60 to 85 ms
Earthing switch Closing Opening Closing Opening Closing Opening
Manual operating mode Hand lever Hand lever Hand lever Hand lever Hand lever Hand lever
Motor option for switch-units and circuit breakers
The operating mechanism I, D, B and Q functions may be motorized
DC AC (50 Hz) *
Un power supply (V) ** 24 48 60 110 125 220 120 230
Power (W) 240
(VA) 280
(*) Please consult us for other frequencies.
(**) At least a 20 A power supply is necessary when starting the motor.
P
E
5
7
7
7
2
P
E
5
7
7
7
3
P
E
5
7
7
7
6
D-8
Network remote control
D-9
accessories
Indication and tripping, DIN indicators,
power supply, protection relay test,
cable compartment, opertaing handle,
key locking...
a
c
c
e
s
s
o
r
i
e
s
Contents
Accessories
Indication and tripping E-2
DIN indicators E-3
Fault current and load current E-3
Fault current and voltage detection combination E-3
Other accessories E-5
Operating handle E-6
Key locking E-7
E-1
Accessories
Indication and tripping
Auxiliary contacts
b Each switch or circuit breaker can be ftted with 4 auxiliary contacts with the
following positions: 2 NO and 2 NC.
b The earthing switch (except fuse-switch combination) can be ftted with 1 auxiliary
contact with the following position: (opening/closing).
b Each circuit breaker can receive 1 auxiliary contact for tripping indication
(protection by VIP).
b Each fuse-switch combination can be ftted with 1 blown fuse indication auxiliary
contact.
0
5
5
7
4
8
B
Undervoltage coil
Available on the circuit breaker function and on the combined fuse-switch,
this trip unit causes opening when its supply voltage drops below a value
under 35% of its rated voltage.
The time delay can be equipped with the undervoltage coil with the setting
from 0.5 to 3 s.
DC AC
(50 Hz) *
Un power supply (V) 24 48 60 110 125 220 120 230
Power


Excitation (W or VA) 200 (during 200 ms) 200
Latched (W or VA) 4.5 4.5
Threshold


Opening 0.35 to 0.7 Un 0.35 to 0.7
Closing 0.85 Un 0.85
(*) Please consult us for other frequencies
P
E
5
6
4
2
4
Opening release
Each circuit breaker or fuse-switch combination can be ftted a switch-on opening
release (shunt trip).
Opening release option for each circuit breaker or fuse-switch combination
DC AC
(50 Hz) *
Un power supply (V) 24 48 60 110 125 220 120 230
Power (W) 200 250 250 300 300 300
(VA) 400 750
Response time (ms) 35 35
(*) Please consult us for other frequencies
0
5
5
7
4
7
E-2
Accessories
DIN indicators - Fault current and load current
Fault current and voltage detection combination
Increase your power availability with the indicators suitable for the location of fault and MV network load management.
Available in DIN format which provides easy installation in RM6.
Each switch function on RM6 switchboard can be equipped independently from other functional unit with:
b Fault current indicator
b Ammeter
b Voltage detector.
An advanced range of FPI having Voltage
detection, programmable voltage presence/
absence relays with Modbus communication
having the capability to work on all types of
neutral networks. An easy solution for Smart Grid.
Flair Fault Passage Indicator
Built in Voltage Presence/ Absence relays: 2 output
contacts, confgurable.
Fault detection for compensated and isolated networks
requires a VPIS_VO for whole range except Flair 21D.
Fault current indicator
The updated Easergy Flair 21D - 22D - 23D - 23DM is a family of fault passage
indicators in DIN format, effcient, self-powered and self adapted to the network
providing hassle free installation. Capable to work on all types of neutral networks.
Well equipped with LCD for better visibility of detailed parameters having an option of
external outdoor lamp indication.
Functions
b Indication of phase-phase and phase-earth faults
b Display of parameters & settings
b Display of the faulty phase
b Display of load current, maximum current for each phase, frequency and direction
of fow of energy
b Fault passage indication and voltage detection combination (only Flair 23D)
Easy and reliable to use
b Automatic setting on site
b Fault indication by LED, LCD and outdoor light indicator (optional)
b Battery life of 15 years (Flair 22D)
b Accurate Fault detection by validation of fault with voltage loss using VPIS
(except Flair 21D)
b Possible to be mounted on RM6 in factory or to be added on site
b Adaptation on site can be facilitated by using the current sensor of split type,
without removing MV cables.
Voltage detection relay
Flair23DM: An advanced range of FPI having Voltage detection, programmable
voltage presence/ absence relays with Modbus communication having the capability
to work on all types of neutral networks. An easy solution for Smart Grid.
b Combination fault passage indicator and voltage detector.
b Ideal for use with an Automatic Transfert of Source System.
b Needs a stabilised external DC power supply to supply power to the Flair 23DM.
b Requires the VPIS-VO option on the VPIS for interfacing with it, in order to acquire
the image of the mains voltage.
b With the communication option it is the ideal detector to be integrated in the cell as
a communicating fault detector.
P
E
5
7
7
8
7
Flair23DM
Load current indicator
The ammeter Amp21D of Easergy range is dedicated to Medium Voltage network
load monitoring.
Functions
b Display of 3 phase current: I1, I2, I3
b Display of the maximum current: I1, I2, I3.
Easy and reliable to use
b Automatic setting on site
b Possible to be mounted on RM6 in factory or to be added on site
b Adaptation on site can be facilitated by using the current sensor of split type,
without removing MV cables.
P
E
5
7
7
8
6
Amp21D
P
E
5
6
8
1
0
6
1
0
2
1
N
RM6 can also be provided with Alpha M or Alpha E (Hortzmann) type short-circuit indicators.
P
E
5
7
7
8
4
E
M
S
5
8
3
5
1
E
M
S
5
8
3
5
4
E
M
S
5
8
3
5
5
Flair 22D Flair 21D Flair 23D Flair 23DM
E-3
Accessories
DIN indicators - Fault current and load current
Fault current and voltage detection combination
Characteristics
Flair 21D Flair 22D & 23D Flair 23DM
Frequency (auto-detection) 50 Hz and 60 Hz 50 Hz and 60 Hz 50 Hz and 60 Hz
Operating voltage Un: 3 to 36 kV - Vn: 1,7 to 24 kV Un: 3 to 36 kV - Vn: 1,7 to 24 kV Un: 3 to 36 kV - Vn: 1,7 to 24 kV
Neutral Phase-to-phase fault All systems All systems All systems
Phase-to-earth fault Impedance-earthed, directly
earthed
Impedance-earthed, directly compensated, isolated Flair 22D: (type
B), Flair 23D, type (B,C)
(4)
Measurements
Load Minimum current > 2 A > 2 A > 2 A
Current (A)
(resolution 1 A)
For each phase
Accuracy: (2% + 2 digits)
Ammeter
Maximeter
Ammeter
Maximeter
OFF or AUTO or 100 to
800 A (50A increments)
Voltage (% of rated voltage) With VPIS-VO option
Accuracy: 1%
Phase-to-neutral or phase-to-
phase voltage
Fault detection
Threshold confguration Via microswitches
Via front panel buttons Via front panel buttons
Overcurrent fault
Accuracy 10%
Auto-calibration Yes Yes Yes
Thresholds AUTO or 200, 400, 600, 800 A
OFF or AUTO or 100 to 800 A
(50 A increments)
OFF or AUTO or 100 to 800 A
(50 A increments)
Earth fault
With 3 phase CTs
Accuracy 10%
Auto-calibration Yes Yes Yes
Algorithm 3I + di / dt 3I + di / dt 3I + di / dt
Thresholds OFF or AUTO or 40, 60, 80, 100,
120, 160 A
OFF or 5
(2)
to 30 A (5 A increments) and 30 to 200 A (10 A increments)
Earth fault
With zero sequence CT
Accuracy 10% or 1 A
Auto-calibration -
No No
Thresholds -
OFF or AUTO
(5)
or 5 to 30 A (5 A increments) and from
Fault acknowledge time delay 60 ms
30 to 200 A (10 A increments) (1)
Fault confrmation time delay 70 s 3 s, 70 s or OFF
Inrush Time delay 3 s, 70 s or OFF
Reset Automatic Upon current return 2 A
(70 s or OFF)
Upon current return 2 A
(3 s, 70 s or OFF)
Manual via front panel Yes Yes Yes
External contact Yes Yes Yes
Deferred 4 h
1, 2, 3, 4, 8, 12, 16, 20, 24 h. Factory setting = 4 h
Indications LED Yes Yes Yes
External contact Yes Yes Yes
External indicator lamp Yes (with battery) Yes (without battery) Yes (without battery)
Phase indication Yes Yes Yes
Communication
RS485 2-wire, connector with LEDs No No Yes
Speed: auto-detection 9600, 19200, 38400 bits/s - Class A05
Accessible data: Phase and earth faults; Fault passage counters including transient faults; Current measurements (I1, I2, I3, I0), max. current, voltage (U, V,
residual); Resetting of fault indication, counters and max. values; Fault and voltage presence/absence detection parameters; Communication parameters; Time
synchronisation and time-tagged events
Power supply
Self-powering On measuring CTs Yes (I load > 3 A) Yes Yes
Battery (Service life: 15 years) No Lithium (Flair 22D), No (Flair 23D) No
External power supply No No (Flair22D), 24 to 48 Vcc
(Conso mac: 50 mA) (Flair 23D)
24 to 48 Vdc (conso mac: 50 mA)
Display
Display
4-digits LCD 4-digits LCD 4-digits LCD
Fault Red LED
Red LED Red LED
Phase at fault Yes Yes Yes
Setting Yes (CT type) Yes Yes
Sensors
Phase CT 3 phase CTs 2 or 3 phase CTs 2 or 3 phase CTs
Zero sequence CT No Diameter: 170 mm Diameter: 170 mm
Test mode
By button on front panel Product name - Software version -
Network frequency - Residual
current - Digits test
Product name - Software version - Network frequency - Residual
current - VPIS presence - Direction of energy - Digits test
(1) The minimum threshold 5 A can only be reached with the earth CT ref CTRH2200.
(2) 20 A minimum for resistive neutral type, 5A minimum for isolated or compensated neutral type
(3) Flair 23D & Flair 23DM: Launched in 2013.
(4) Type C mounting is not available on compensated neutral
(5) only with isolated and compensated neutral
E-4
Accessories
Other accessories
PS100 high-availabililty power supply
The PS100 is associated with a backup battery, ensuring the uninterrupted
power supply up to 48 hours in the event of micro outages and power
interruptions.
The battery is a standard sealed lead-acid 12 Vdc battery with a 10-year
service that can be purchased easily anywhere in the world.

The backup solution with PS100 allows an easy maintenance with only one
battery and withstands harsh substation environments.
The PS100 backup power supply unit:
Reserves an additional energy backup to restart the installation after an
extended power interruption
b Includes a regulated and temperature-compensated charger
b Stops the battery before deep discharge
b Carries out a battery check every 12 hours
b Measures battery ageing
b Forwards monitoring information via a modbus communication port and
output relays, which allows the preventive battery replacement before the end
of its life.
MV switchgear:
b Motor mechanisms
b Control unit
b Protection relays
b Other devices
Uninterrupted
power supply
24 or 48 Vdc
Uninterrupted
power supply
12 Vdc
Charging or
supplying
LV main
power supply
100-250 Vac
PS100
12 Vdc
battery
Power supply
Information
Communication
devices:
b RTU
b Modem
Protection relay test
This unit is used to power the VIP 40, VIP 45 ,
VIP 400 and VIP 410 units, making it possible to
operate and test the protection system.
It can also be used to power and test Schneider
Electric LV circuit breakers.
P
B
1
0
3
7
9
0
Options for cable compartment
Standard equipment:
b A closing panel
b Cable binding
b Connection of cable earthing.
Optional equipment:
b Panel with window to display liquid type
overcurrent indicators installed around
the cables
b Deeper panel to enable to adding of a lightning
arrester
b ESw interlocking to prohibit access to
the connection compartment when
the earthing switch is open
b LBSw or CB interlocking to prohibit closing of
the switch or circuit breaker when
the connection compartment panel is open
b Internal arc withstand for the cable
compartment up to 20 kA 1s.
P
E
5
6
8
0
6
VRT7 auxiliary power supply
b A phase-to-phase screened voltage transformer.
b Compact dimensions and screened design for easy
installation; insensitivity to harsh environments.
b Designed to withstand power frequency tests (no need
for disconnection during commissionning)
b Power: 300 VA continuous, 500 VA for 1 mn.
Voltages*
(kV)
7.2 - 20 - 60 7.2 - 32 - 60 12 - 28 - 75 12 - 42 - 75 24 - 50 - 125
Primary
(kV)
6 & 6.6 6 10 - 11 10 13.8 - 15
Secondary
(V)
230
Power and
accuracy
class
30 VA cl. 3
* Rated Voltage -Rated power-frequency withstand voltage kVms- Rated lightning
impulse withstand voltage kV peak
P
E
5
6
8
3
0
Phase concordance unit
This unit is used to check phase concordance.
E-5
Accessories
Operating handle
3 types of operating handle (standard, longer and super long) are proposed in RM6 offer for different combination of cubicles.
The longer operating handle is necessary:
b For RM6 of with 2, 3, 4 or 5 functions, when circuit breaker is motorized
and is on the left side of switch function
The super long operating handle is necessary:
b For RM6 of 1 function extensible, when circuit breaker is manual and
is on the left side of a fuse-switch function
The standard operating handle
For all other possible cubicle combinations, the standard operating handle is
enough to operate the RM6 switchgears.
b For RM6 of 1 function extensible, when circuit breaker is motorized and
is on the left side of a fuse-switch function
b For RM6 of 1 function extensible, when two fuse-switch functions are connected
b For DE-Q, DE-D, DE-B, DE-Bc, when the metering cubicle DE-Mt is on its right side
P
E
5
7
7
7
8
P
E
5
7
7
7
9
P
E
5
7
7
8
0
P
E
5
7
7
8
1
P
E
5
7
7
8
2
Means that the circuit breaker function is motorized M
Means that the circuit breaker function is motorized M
Functional unit marked in orange need longer or super long handle
to be operated.
Functional unit marked in orange need longer or super
long handle to be operated.
Functional units marked in orange need longer or super long handle
to be operated.
E-6
Accessories
Key locking
The markings (O, S, and X) are engraved on the keys and the locks.
They are given here only as an aid to understanding of the diagrams.
When the switchgear is locked in the open position, the remote control cant work.
: no key : free key : captive key
M
T
5
5
1
5
4
On network switches or 630 A circuit breaker feeder
Semi-crossed locking
b Prohibits the closing of the earthing switch of the downstream switchgear unless
the upstream switchgear is locked in the open position
M
T
5
5
0
4
0
O
O
Type R1 diagram
M
T
5
5
0
4
1
O X
O X
Type R2 diagram
Crossed locking
b Prohibits closing of the earthing switches unless the upstream and downstream
switchgear is locked in the open position.
On transformer feeders
RM6/transformer
b Prohibits access to the transformer unless the earthing switch has been locked
in the closed position.
M
T
5
5
0
4
2
Type R7 diagram
O
O
M
T
5
5
0
4
3
Type R6 diagram
O
O
RM6/low voltage
b Prohibits closing of the earthing switch and access to any protection unit fuses
unless the main LV circuit breaker has been locked in the open or disconnected
position.
M
T
5
5
0
4
4
Type R8 diagram
S
S
O
O
RM6/transformer/low voltage
b Prohibits closing of the earthing switch and access to any protection unit fuses
unless the main LV circuit breaker has been locked in the open or disconnected
position.
b Prohibits access to the transformer unless the earthing switch has already been
closed.
E-7
connection
Selecting bushings and connectors,
cable and other compatible
connections...
c
o
n
n
e
c
t
i
o
n
Contents
MV connection
Selecting bushings and connectors F-2
Compatible cable connections F-3
Other types of compatible connections F-5
F-1
MV connection
Selecting bushings and connectors
General
b The profles, contacts and dimensions of the RM6 connection interfaces are defned by the IEC 60137 standard.
b 100% of the epoxy resin interfaces undergo dielectric testing at power frequency and partial discharge tests.
b An insulated connector must used in order to guarantee the dielectric performance over time. Schneider Electric recommends using
nkt connectors.
Types of connection interface
M
T
5
5
0
3
9
type B / C type A
Appropriateness for use
The bushings carry the electrical current from the outside to the inside
of the enclosure, which is flled with SF6 gas, ensuring insulation between
the live conductors and the frame.
There are 3 types of bushing, which are defned by their short-time withstand
current:
b Type A: 200 A: 12.5 kA 1 s and 31.5 kA peak (plug-in)
b Type B: 400 A: 16 kA 1 s and 40 kA peak (plug-in)
b Type C: 630 A: 25 kA 1 s, 21 kA 3 s and 62.5 kA peak (disconnectable M16).
How to defne the connection interface
The connection interfaces depend on specifc criteria, such as:
Installation
b Current rating of the connected equipment: 200, 400, 630 A
b Short-time withstand current for 12.5 kA, 16 kA, 25 kA switch and circuit breaker
functions
b For the fuse-switch combination function, as the short-circuit current is limited
by the fuse, the connection interface will be of type A (200 A)
b Minimum phase expansion length
b Connection type:
v plug in: multicontact ring
v disconnectable: bolted.
b Output position: straight, elbow.
Cable
b Specifed voltage:
v of the cable
v of the network.
b Type of conductor:
v aluminium
v copper.
b Cross section in mm
2
b insulation diameter
b Cable composition:
v single-core
v 3-core.
b Insulation type:
v dry
v paper impregnated (non-draining type).
b Type of screen
b Armature.
This information must be specifed for better defnition of the connection interfaces.
F-2
MV connection
Compatible cable connections
Type A bushing
Directed feld plug-in connector
Dry single-core cable
Performance Connection Supplier Reference Cross section Remarks
7.2 to 10 kV
200 A -95 kV impulse
Plug-in Elastimold 158LR 16 to 120 T-shaped elbow
Elastimold 151SR 16 to 120 Straight, Q function
only
Prysmian FMCE 250 16 to 95
7.2 to 17.5 kV
200 A -95 kV impulse
Plug-in nkt cables GmbH EASW 12/250 A 25 to 95 Shaped elbow
nkt cables GmbH EASG 12/250 A 25 to 95 Straight
Tycoelectronics RSES-52xx 25 to 120 Shaped elbow
Tycoelectronics RSSS-52xx 25 to 95 Straight connection
7.2 to 24 kV
200 A -125 kV impulse
Plug-in Elastimold K158LR 16 to 95 T-shaped elbow
24 kV
200 A -125 kV impulse
Plug-in nkt cables GmbH EASW 20/250 A 25 to 95 Shaped elbow
nkt cables GmbH EASG 20/250 A 25 to 95 Straight
Tycoelectronics RSES-52xx 25 to 120 Shaped elbow
Tycoelectronics RSSS-52xx 25 to 95 Straight connection
Type A/M8 bushing
Non-directed feld disconnectable connector (*)
Dry single and 3-core cable
Performance Connection Supplier Reference Cross section Remarks
7.2 to 17.5 kV
200 A -95 kV impulse
Heat shrinkable Tycoelectronics EPKT + EAKT + RSRB 16 to 150
Insulating boots Kabeldon KAP70 70 max.
(*) 520 mm plinth must be used
Type B bushing
Directed feld plug-in connector
Dry single-core cable
Performance Connection Supplier Reference Cross section Remarks
7.2 to 10 kV
400 A-95 kV impulse
Plug-in Elastimold 400 LR 70 to 240 Limited to Us = 10 kV
7.2 to 17.5 kV
400 A-95 kV impulse
Plug-in nkt cables GmbH CE 12-400 25 to 300
Tycoelectronics RSES-54xx 25 to 300 Shaped elbow
24 kV
400 A-125 kV impulse
Plug-in Prysmian FMCE 400 70 to 300
Elastimold K400LR 35 to 240
Kabeldon SOC 630 50 to 300
nkt cables GmbH CE 24-400 25 to 300
Tycoelectronics RSES-54xx 25 to 300 Shaped elbow
For cross section > 300 mm
2
, please consult us.
F-3
MV connection
Compatible cable connections
Non-directed feld disconnectable connector
Dry single and three-core cable
Performance Connection Supplier Reference Cross section Remarks
7.2 to 10 kV
630 A -95 kV impulse
Heat shrinkable Tycoelectronics EPKT + EAKT + RSRB 16 to 300
Sigmaform Q-CAP 16 to 300
Insulating boots Kabeldon SOC 630 50 to 300 Completed by a kit for
three core-pole cable
Simplifed
disconnectable
Tycoelectronics RICS + EPKT 25 to 300
Euromold 15TS-NSS 50 to 300 Limited to Us = 20 kV
24 kV
630 A -125 kV impulse
Disconnectable nkt cables GmbH AB 12-630 25 to 300 (+ATS) For 3-core cable
Simplifed
disconnectable
Tycoelectronics RICS + EPKT 25 to 300
Performance Connection Supplier Reference Cross section Remarks
7.2 to 17.5 kV
630 A-95 kV impulse
Insulating boots Kabeldon SOC 25 to 300
Simplifed
disconnectable
Tycoelectronics RICS - EPKT 25 to 300
Heat shrinkable Tycoelectronics EPKT+EAKT+RSRB 95 to 300
24 kV
630 A-125 kV impulse
Simplifed
disconnectable
Tycoelectronics RICS - EPKT 25 to 300
Non-directed feld disconnectable connector
Single-core cable, paper impregnated, non-draining type
Performance Connection Supplier Reference Cross section Remarks
7.2 to 17.5 kV
630 A-95 kV impulse
Insulating boots Kabeldon SOC 630 25 to 300
Simplifed
disconnectable
Tycoelectronics RICS - EPKT 25 to 300
Heat shrinkable Tycoelectronics EPKT+EAKT+RSRB 16 to 300
24 kV
630 A-125 kV impulse
Simplifed
disconnectable
Tycoelectronics RICS - EPKT 25 to 300
For cross section > 300 mm
2
, please consult us.
Non-directed f eld disconnectable connector
Three-core cable, paper impregnated, non-draining type
Type C bushing
Directed feld disconnectable connector
Dry single-core cable
Performance Connection Supplier Reference Cross section Remarks
7.2 to 10 kV
630 A-95 kV impulse
Disconnectable Elastimold 440 TB 70 to 240
7.2 to 17.5 kV
630 A-95 kV impulse
Disconnectable nkt cables GmbH CB 12-630 25 to 300
Tycoelectronics RSTI-58xx 25 to 300 T-shaped connector
7.2 to 24 kV
630 A-125 kV impulse
Disconnectable Prysmian FMCTs 400 70 to 300
Elastimold K400TB 35 to 240
Kabeldon SOC 630 50 to 300
24 kV
630 A-125 kV impulse
Disconnectable nkt cables GmbH CB 24-630 25 to 300
Tycoelectronics RSTI-58xx 25 to 300 T-shaped connector
F-4
MV connection
Other types of compatible connections
Connectors with lightning arrestors
Disconnectable connector
Single-core dry cable and lightning arrestor
Performance Connection Supplier Reference Cross section Remarks
7.2 to 17.5 kV
630 A-95 kV impulse
Disconnectable nkt cables GmbH AB 12-630 + ASA12
(5 or 10 kA)
25 to 300 Non-directed feld
CB 24-630 + CSA 24
(5 or 10 kA)
25 to 300 Directed feld
24 kV
630 A-125 kV impulse
Disconnectable nkt cables GmbH AB 12-630 + ASA12
(5 or 10 kA)
25 to 300 Non-directed feld
CB 24-630 + CSA 24
(5 or 10 kA)
25 to 300 Directed feld
7.2 to 17.5 kV
630 A-95 kV impulse
Disconnectable Tycoelectronics RICS+EPKT
RDA 12 or 18
25 to 300
Elastimold K400TB + K400RTPA
+ K156SA
35 to 300 Cable box enlarged
24 kV
630 A-125 kV impulse
Disconnectable Tycoelectronics RICS + EPKT
RDA 24
25 to 300
Elastimold K440TB + K400RTPA
+ K156SA
35 to 300 Cable box enlarged
Tycoelectronics RSTI-58 + RSTI-CC-
58SAxx05
25 to 300 Directed feld
5 kA arrestor
Tycoelectronics RSTI-58 + RSTI-CC-
66SAxx10M16
25 to 300 Directed feld
10 kA arrestor
For cross section > 300 mm
2
, please consult us.
F-5
installation
Dimensions and installation conditions,
civil works...
i
n
s
t
a
l
l
a
t
i
o
n
F-4
Contents
Installation
Dimensions and installation conditions G-2
Civil works G-6
G-1
Installation
Dimensions and installation conditions
1 function modules
1142
437
703
L 30 30
L' 710
670
703
D
E
5
9
7
7
8 Function Weight (kg) Length (mm)
Regular RM6
NE I 135 L = 472
D L = 572
B L = 572
DE I 135 L' = 472 + 30 + 30 = 532
D L' = 572 + 30 + 30 = 632
B L' = 572 + 30 + 30 = 632
Q 185 L' = 472 + 30 + 30 = 532
RE O 135 L' = 472 + 30 = 502
LE L' = 472 + 30 = 502
DE L' = 472 + 30 + 30 = 532
DE Ic 145 L' = 572 + 30 + 30 = 632
Bc L' = 572 + 30 + 30 = 632
2 functions modules
703
L 30 30
L'
1142
710
670
703
145 145 145 145
D
E
5
9
7
7
9
_
2
Function Weight (kg) Length (mm)*
Regular RM6
NE Q I 180 L = 829
D I, B I L = 829
I I 155 L = 829
RE I I 155 L' = 829 + 30 = 859
RM6 Free Combination
NE L = 1052
LE L' = 1052 + 30 = 1082
RE L' = 1052 + 30 = 1082
DE L' = 1052 + 30 + 30 = 1112
* Dimensions only for RM6 Free combination
3 functions modules
145 145
L 30 30
L' 710
670
703
703
1142
107107
D
E
5
9
7
8
0
Function Weight (kg) Length (mm)
Regular RM6
NE I Q I 275 L = 1186
I I I 240 L = 1186
I D I L = 1186
I B I 250 L = 1186
RE I Q I 275 L' = 1186 + 30 = 1216
I I I 240 L' = 1186 + 30 = 1216
I D I L' = 1186 + 30 = 1216
I B I 250 L' = 1186 + 30 = 1216
DE I Q I 275 L' = 1186 + 30 + 30 = 1246
I I I 240 L' = 1186 + 30 + 30 = 1246
I D I L' = 1186 + 30 + 30 = 1246
I B I 250 L' = 1186 + 30 + 30 = 1246
RM6 Free Combination
NE L = 1532
LE L' = 1532 + 30 = 1562
RE L' = 1532 + 30 = 1562
DE L' = 1532 + 30 + 30 = 1592
RM6 Free Combination with bus coupler
RE L' = 1532 + 30 = 1562
DE L' = 1532 + 30 + 30 = 1592
Type of tank
NE: non-extensible
RE: extensible to the right
LE: extensible to the left
DE: extensible module to the right or left
(one function)
G-2
Installation
Dimensions and installation conditions
4 functions modules
L 30 30
L' 710
670
703
703
1142
145 145 107107
D
E
5
9
7
8
1
Function Weight (kg) Length (mm)
Regular RM6
NE I I Q I 355 L = 1619
I I I I 320 L = 1619
I I D I 330 L = 1619
I I B I 330 L = 1619
Q I Q I 390 L = 1619
B I B I 340 L = 1619
RE I I Q I 355 L' = 1619 + 30 = 1649
I I I I 320 L' = 1619 + 30 = 1649
I I D I 330 L' = 1619 + 30 = 1649
I I B I 330 L' = 1619 + 30 = 1649
Q I Q I 390 L' = 1619 + 30 = 1649
D I D I 340 L' = 1619 + 30 = 1649
DE I I Q I 355 L' = 1619 + 30 + 30 = 1679
I I I I 320 L' = 1619 + 30 + 30 = 1679
I I D I 330 L' = 1619 + 30 + 30 = 1679
I I B I 330 L' = 1619 + 30 + 30 = 1679
5 functions modules
30 30
710
670
1142
107107 145 145
703
L
L'
D
E
5
9
7
8
9
Function Weight (kg) Length (mm)
Regular RM6
NE IDIDI 470 L = 2000
IQIQI 520 L = 2000
IBIQI 495 L = 2000
RE IDIDI 475 L' = 2000 + 30 = 2030
IIIII 455 L' = 2000 + 30 = 2030
DE IDIDI 480 L' = 2000 + 30 + 30 = 2060
IIIQI 495 L' = 2000 + 30 + 30 = 2060
Arrester option
D
E
5
9
7
8
3
710
175
859
1142
Metering cubicle
Function Weight (kg) Length (mm)
RM6 metering cubicle with LV compartment
DE DE-Mt 420 L = 1106
RM6 metering cubicle without LV compartment
DE DE-Mt 400 L = 1106
D
E
5
9
7
8
2
1106
880
901
840
1174
1606
G-3
Installation
Dimensions and installation conditions
Dimensions of RM6 REs with an extension module
1142
43
B (*)
A
710
670
703
D
E
5
7
9
9
3
(*) B = 900 for 1 DE function
B = 1600 for 3 DE functions
B = 2000 for 4 DE functions
These dimensions can be reduced under special conditions, consult us.
Nb of RE units DE single unit type A Length (mm)
RM6 standard functional units
2 units Type 1 1374
Type 2 1474
3 units Type 1 1731
Type 2 1831
4 units Type 1 2164
Type 2 2264
RM6 Free Combination functional units
2 units Type 1 1597
Type 2 1697
3 units Type 1 2077
Type 2 2177
Type 1: DE-I, DE-Q, DE-O
Type 2: DE-B, DE-D, DE-IC, DE-BC
Layout
Floor mounting
The RM6 is supported by 2 metal feet with holes for
mounting:
b on a fat foor ftted with trenches, passages or ducts
b on concrete footing
b on studs
b on metal rails etc.
For reminder see the only one restriction of installation on standard range (see page A-5). For standard range, as a rule,the installation is made from left
to right by leaving of the heaviest station.

Standard non-extensible RM6 (top view)
4 functional units 3 functional units 2 functional units 1 functional unit
645
1563
1689
645
1130
1256
645
773
899
10,2
645
516
642
645
43
F
G
10,2
D
E
5
7
9
7
3

RM6 Free Combination (top view)
3 functional units 2 functional units
D
E
5
9
7
8
4
645
E
D
645
E
D
10,2
Nb of units Length (mm)
D E
RM6 Free Combination functional units
2 units 1122 996
3 units 1602 1476

Extensible RM6 (top view)
3 or 4 functional units with extensibility module
645
1563
1689
645
1130
1256
645
773
899
10,2
645
516
642
645
43
F
G
10,2
D
E
5
7
9
7
3
Nb of RE units DE single unit type Length (mm)
F G
RM6 standard functional units
2 units Type 1 1414 1288
Type 2 1514 1388
3 units Type 1 1771 1645
Type 2 1871 1745
4 units Type 1 2204 2078
Type 2 2304 2178
RM6 Free Combination functional units
2 units Type 1 1637 1511
Type 2 1737 1611
3 units Type 1 2117 1991
Type 2 2217 2091
G-4
Possibilities
to add cubicle
1
st
position 2
nd
position 3
rd
position Last position
RE-x DE-x DE-x LE-x
RE-x* DE-x DE-x LE-x
* It is not possible to add RE-x if switchboard with a station DE is in frst position
Installation
Dimensions and installation conditions
D
E
5
9
7
6
5
1200
minimum
D
E
5
7
9
6
4
38
1023
12
70 minimum
Wall mounting
There are two holes allowing the unit
to be fxed on the wall as well as mounted
on the foor.
Ceiling clearance
For substations with fuse-holders,
provide a minimum ceiling clearance
of 1200 mm.
Installation of the substation for internal arc withstand
When there is a requirement for installations with protection against internal arc faults,
refer to the following diagrams.
Gas removal to the bottom
N.B.: parts for guiding the gases to vent openings and cooling walls are not part
of the switchgear supply. These must be adapted to each specifc case.
D
E
5
7
9
6
5
70 minimum
Gas removal to the rear
D
E
5
7
9
6
6
G-5
Installation
Civil works
For connection to network or transformervia circuit breaker
Trench depth P or RM6 without plinth
Note: trench depths can be reduced and sometimes eliminated by adding a plinth.
The network cables can be run either:
b through trenches, passages, ducts
b through the left or the right side.
D
E
5
8
0
6
0
P
50 maxi
40 mini
P
50 maxi
40 mini
90 mini
R
80 maxi
70 mini
120 maxi
Cable
insulation
Cable Cross-section
(mm
2
)
Bending
radius
Cable entry through a trench Cable entry through a duct
P (plug-in) P (disconnectable) P (plug-in) P (disconnectable)
Dry insulation Single y 150 500 400 400
185 to 300 600 520 520
Three y 150 550 660 660
185 650 770 770
Paper
impregnated
non-draining
type
Single y 150 500 580 580
185 to 300 675 800 800
Three y 95 635 750 750
150 to 300 835 970 970
For transformer connection via fuse-switch
The cross-sections of transformer cables are
generally smaller than those of the network cables.
All the cables are then run through the same space.
When straight MV connectors are used, the depth P
indicated below can be greater than that of the
network cables.
Cable
insulation
Cable Cross-section
(mm
2
)
Bending
radius
Plug-in
Elbow connector
Plug-in
Straight connector
Disconnectable
(2)
P
Dry insulation Single 16 to 35 335 100 520 335
50 to 70 400 100 520 440
95 to 120 440 100 550 440
Three 35 435 520 725
50 to 70 500 520 800
95 545 550 860
(1) Leave a clearance of 100 mm
(2) 520 mm plinth must be used
(1)
D
E
5
7
9
6
2
G-6
G-7
order form
Units, options and accessories.
o
r
d
e
r

f
o
r
m
Contents
Order form
Available functions H-2
Basic unit and options H-3
Options and accessories H-5
H-1
Order form
Available functions
Basic unit characteristics
Rated voltage (kV) 12 12 12 12 17.5 17.5 17.5 17.5 24 24 24 24 24 24 24 24 24 24
Short-time withstand
current
(kA rms) 21 21 25 25 21 21 21 21 12.5 12.5 12.5 16 16 16 20 20 20 20
Duration (s) 1 1 1 1 1 3 1 3 1 1 1 1 1 1 1 3 1 3
Rated current (A) 200 630 200 630 200 200 630 630 200 400 630 200 400 630 200 200 630 630
Extensions Functions
NE I
b b b b b b b
D
b b b b b b
B
b b b b b
QI
b b b b b b
DI
b b b b b b
BI
b b b b b
II
b b b b b b
IQI
b b b b b b b b b
IIQI
b b b b b b b b b
QIQI
b b b b b b b b b
IDI
b b b b b b b b b
IIDI
b b b b b b b b b
DIDI
b b b b b b b b b
III
b b b b b b b b
IIII
b b b b b b b b
IBI
b b b b b b
IIBI
b b b b b b
BIBI
b b b b b b
RE O
b b b b b b b b
IQI
b b b b b b b b b
IIQI
b b b b b b b b b
QIQI
b b b b b b b b b
IDI
b b b b b b b b b
IIDI
b b b b b b b b b
DIDI
b b b b b b b b b
II
b b b b b b
III
b b b b b b b b
IIII
b b b b b b b b
IBI
b b b b b b
IIBI
b b b b b b
BIBI
b b b b b b
LE O
b b b b b b b b
DE I
b b b b b b b b
BC
b b b b b
IC
b b b b b
O
b b b b b b b b
Q
b b b b b b b b
D
b b b b b b b
B
b b b b b b
IQI
b b b b b b b
IIQI
b b b b b b b
IDI
b b b b b b b
IIDI
b b b b b b b
III
b b b b b b
IIII
b b b b b b
IBI
b b b b b b
IIBI
b b b b b b
Mt
b b b b b
N.B.: D and Q functions limited to 200 A
NE: non-extensible, RE: extensible to the right, LE: extensible to the left, DE: double extensible.
All the performances are available for RM6 Free Combination cubicles.
H-2
Order form
Basic unit and options
Basic unit confguration
Quantity
5
th
4
th
3
rd
2
nd
1
st
function function function function function
Confguration (one function per box, fll in from the right)
5 functions choice V I I I
Option for I, D, B, Ic, Bc functions
Auxiliary contacts alone
For main switch position indication 2 NO - 2 NC and ESw 1 O/C (this option is included in remote operation option)
Option for I or Ic function
Arc killer device
Front door of cable connection compartment
Bolted
Removable with ESw interlocking
Removable with ESw interlocking and LBSw
interlocking
Fault or load current indicator and voltage detection
Amp 21D
Flair 21D
Flair 22D
Flair 23DM*
VD23
Alpha M Short-circuit current 400 A 600 A
Alpha E setting 800 A 1000 A
CT on bushings
CT for T200 I on bushings
CT for T200 I on bushings + VD23
Remote operation on I function 50 Hz 60 Hz 120 Vac 220 Vac
Motor mechanism and auxiliary contacts LBSw
2 NO - 2 NC and ESw 1 O/C
Add metallic VT in some RM6 cubicle (I function)
24 Vdc 48 Vdc 60 Vdc
110 Vdc 125 Vdc 220 Vdc
Option for D, B, Bc functions
Front door of cable connection compartment
Bolted
Removable with ESw interlocking
Removable with ESw interlocking and C.B.
interlocking
Protection relay for lines or transformer protection by circuit breaker (only one type of relay by unit)
Relay Sepam series 10 Standard Very sensitive
Without com. With communication
Auxiliary power supply 24 to 115 Vdc
100 to 240 Vac 120 to 250 Vdc
Relay VIP 40 (over current)
Relay VIP 45 (over current and earth fault)
Relay VIP 410
Relay VIP 400 (over current & earth fault/multi curve
in accordance with IEC 255-3)
Motor disabled when CB trips
Fault tripping auxiliary contact
Shunt trip coil for external tripping 50 Hz 60 Hz 120 Vac 220 Vac
24 Vdc 48 Vdc 60 Vdc
110 Vdc 125 Vdc 220 Vdc
Remote operation on D, B, Bc functions 50 Hz 60 Hz 120 Vac 220 Vac
Motor mechanism and auxiliary contacts C.B. 2 NO - 2
NC and ESw 1 O/C (including shunt trip coil)
24 Vdc 48 Vdc 60 Vdc
110 Vdc 125 Vdc 220 Vdc
DE -D et DE-B only. Possibility to add ring type CT in some RM6 cubicle
Option for Q function
Auxiliary contacts alone
For position indication 2 NO - 2 NC
Auxiliary contact for fuses blown
Shunt trip coil for external tripping 50 Hz 60 Hz 120 Vac 220 Vac
24 Vdc 48 Vdc 60 Vdc
110 Vdc 125 Vdc 220 Vdc
Remote operation on Q function 50 Hz 60 Hz 120 Vac 220 Vac
Motor mechanism and auxiliary contacts 2 NO - 2 NC
(including shunt trip coil)
24 Vdc 48 Vdc 60 Vdc
110 Vdc 125 Vdc 220 Vdc
Option for D, B, Q functions
Undervoltage coil 120 Vac 220 Vac
24 Vdc 48 Vdc 110 Vdc
* Contact us for availabilities
Only one of the boxes (ticked X or flled

with the needed value) has to be considered between each horizontal line.
Grey box

X

corresponds to none priced functions.
H-3
Order form
Basic unit and options
Basic unit confguration (continued)
Quantity
5
th
4
th
3
rd
2
nd
1
st
function function function function function
Confguration (one function per box, fll in from the right)
Example V I I I
Option for operation
Voltage indicator
VPIS Network service voltage (kV) 10 15
VPIS Voltage Output (compulsory if with VD23 or
Flair 22D*, 23D*, 23DM*, 23DV)
6 11 20
6.6 13.8 22
VDS
Key locking devices Flat key type Tubular key type
Type R1 (on I and B functions) On switch or circuit breaker
On earth switch
Type R2 (on I and B functions)
Type R6 (on Q or D functions)
Type R7 (on Q or D functions)
Type R8 (on Q or D functions)
* contact us for availability
Only one of the boxes (ticked X or flled

with the needed value) has to be considered between each horizontal line.
Grey box

X

corresponds to none priced functions.
H-4
Order form
Only one of the boxes (ticked X or flled

with the needed value) has to be considered between each horizontal line.
Grey box

X

corresponds to none priced functions.
Options and accessories
Specifc option for one function
Bushing for I function
Plug in 400 A type B
Bolted M16 screw type C (compulsory with 17.5 or 24 kV-630 A)
Bolted 5/8" ANSI
Bushing for D function
Plug in 200 A type A (limited to 12.5 kA 1 s)
Plug in 400 A type B (limited to 16 kA 1 s)
Bolted M16 screw type C (compulsory with 17.5 or 24 kV-630 A)
Bushing well ANSI (limited to 12.5 kA 1 s)
Bushing for B function
Bolted M16 type C
Bolted 5/8" ANSI
Bushing for Q function
Plug in 200 A
Heat shrinkable terminal for fuse chamber
Cable type for I, Ic functions Single core Three-core
Bottom plate in cable box (compulsory in case of three-core cable)
Cable type for D, B, Bc functions Single core Three-core
Bottom plate in cable box (compulsory in case of three-core cable)
Cable type for O function Single core Three-core
Bottom plate in cable box (compulsory in case of three-core cable)
In and fuse type for Q function 6 kV 10 kV 12/24 kV & 10/100 A
(fuses to be procured separately) 16 to 100 A 125 A
Global option
Pressure detection Without
Manometer Arabic Scandinavian Standard
or pressure switch Scandinavian Standard
Door with window (for I, D and B functions)
Deep cable box for I and D or B
functions
(enables surge arrestors to be ftted)
Additional earth busbar
(compulsory if earth fault > 6 kA 1 s)
Internal arc cable box 20 kA 1 s for I, D, B, O, Ic, Bc functions
(unable to coexist with door with window)
Autotransfer system for I function I (48 Vdc electrical motorization compulsory)
Fixation support T200 I to RM6 Without With
Changeover type ATS 1/2 network ATS 1/2 genset BTA 2/3
Communication modem GSM/GPRS FSK (radio) RS485
Protocol IEC101/104 DNP3/IP
Current measurement (only cables, if CT on RM6 bushings)
sensors + cables Single core Single core Three-core Three-core
AC 5 m AC 10 m AH 5 m AH 10 m
Connection cable to motorization 1 3 m 5 m 10 m
Connection cable to bus tie (only for BTA 2/3) 5 m 10 m
Connection cable to motorization 2 3 m 5 m 10 m
Accessories
Raising plinth h = 260 mm h = 520 mm
Set of 3 MV fuses Fusarc CF Rating (A)
Phase comparator
Test box for circuit breaker relay (VAP 6)
PS100 backup power supply
Exhaust gas To the bottom To the rear
Additional operating handle Standard Longer Super long
Additional extension kit 1 fct 2 fct 3 fct 4 fct 5 fct DE Mt
Additional instructions
Installation and civil engineering instructions French English
H-5
Notes
H-6
Notes
H-7
H-8
Notes
As the standards, specifcations and designs change from time to time, please ask for
confrmation of the information given in this publication.
Design: SYNTHESE ECA, Schneider Electric Industries SAS
Photos: Schneider Electric Industries SAS
Printing: Altavia Connexion - Made in France
This document has been printed
on ecological paper
AMTED398032EN 12-2013
A
R
T
9
3
6
4
3

-


S
c
h
n
e
i
d
e
r

E
l
e
c
t
r
i
c

I
n
d
u
s
t
r
i
e
s

S
A
S

-

A
l
l

r
i
g
h
t
s

r
e
s
e
r
v
e
d