You are on page 1of 2

C O N T R O L S

CAT

CONTROL PANELS
Electromechanical
EMCP II
EMCP II
+
EMCP II
+
P
Switchgear Conversion
The Caterpillar family of control panels provides
basic to complete generator set monitoring.
Control panels use a standard mounting and
wire harness and are easily upgraded to the
next higher specification. The Electronic
Modular Control Panels (EMCP II, EMCP II
+
,
and EMCP II
+
P) are compatible with a complete
line of local or remote annunciators, and with
remote communication and expansion modules.
PANEL DESCRIPTION
ELECTROMECHANICAL
This manual or auto start/stop electromechanical
panel, equipped with analog gauges, provides
basic generator set metering, engine monitoring
and protection, indicator lights, and emergency
stop shutdown. Optional protective and control
devices are available.
EMCP II, II+, AND II+P
The EMCP II, II+ and II+P, equipped with high-tech
electronics and digital LCD readouts, provide
the most complete generator set monitoring,
metering, control, and indication. A full range
of optional protective devices, controls, and
local and remote annunciators are available.
The EMCP II, II+ or II+P may be used for remote
generator set monitoring and control via a direct
connection or modem. The EMCP II, II+ and
II+P use environmentally sealed, solid state,
microprocessor-based modules.
SWITCHGEAR CONVERSION
The switchgear conversion (SGC) panel provides
basic engine monitoring, protection, and control.
It is equipped with a digital LCD display, electronic
gauges, and indicator lights. The panel is
designed to interface with switchgear or remote
mounted controls. Optional protection and
control devices are available.
Switchgear Conversion
EMCP II and EMCP II
+
W H E R E T H E W O R L D T U R N S F O R P O W E R
Electromechanical
EMCP II
+
P
LEHX9295-02
Common Design EMCP II
C O N T R O L S
CONTROL PANEL FEATURES
Electromechanical Panels EMCP Panels
Switchgear
(all gauges are analog) (all gauges are digital)
Conversion
PGS 225-400 PGS 225-2250 PGS 450-900F (digital gauges)
Switchgear Auto II II+ II+P
PGS 450-2250
Generator Metering
Voltmeter S S S S
Ammeter S S S S
Phase selector switch S S S S
Frequency S S S S
kW S S
kVAR S S
kVA S S
Power factor S S
Generator Set Monitoring
DC voltage S S S S S S
Coolant temperature S S S S S S
Oil pressure S S S S S S
Hours run time S S S S S S
rpm S S S S S S
Oil temperature S
(6)
S
(6)
S
L/R exhaust manifold temperature S (3500 only)
Controls
Start/stop control Man/Auto Man/Auto Man/Auto Man/Auto Man/Auto
Emergency stop control S S S S S S
Lamp test S S S S S S
Cycle cranking (adjustable cranking times) S S S S S S
Voltage control S S S S
Cooldown timer S S S
Panel lights S S S
Load share module (shipped loose) O O O S
(5)
O
Alarm horn & silence switch local O O O S
Frequency control O O O S
Electronic isochronous governor O O O S O
Ether starting aid control O O O O
Synchronizing control S
Breaker control S
Standard Indicating Lights
Low oil pressure shutdown S S S S S S
High coolant temperature shutdown S S S S S S
Overspeed shutdown S
(1)
S
(1)
S S S S
(1)
Overcrank shutdown S S S S S S
Emergency stop shutdown S
(1)
S
(1)
S S S S
(1)
Generator voltage match S
Generator frequency match S
Generator phasing match S
Miscellaneous Protective Devices include indicating light select one only select one or several
(4)
select one only
Over/under frequency S
(2)
S
(2)

Overcurrent S
(2)
S
(2)

Reverse power S
(2)
S
(2)

Over/under AC voltage O O S
(2)
S
(2)

Low fuel level O O O O O O


(3)
Low coolant level O O O O O O
Ground (earth) fault shutdown O O O O
Generator winding overtemp prealarm O
(3)
O O O O
(3)
Generator winding overtemp shutdown O
(3)
O O O O
(3)
Generator bearing overtemperature O
(3)
O O O O
(3)
Low battery voltage O O O
Miscellaneous Controls select one or more
Common alarm/shutdown volt-free contact S O O O O S
Overload relay (kW level) S S

Computer communication data link S S S


Integral battery charger 5 amp (non UL) O O O O O O
Automatic fuel transfer system control O O O O O O
JWH/space heater/battery charger disconnect O O O O O O
Generator running volt free contact O O O O
Remote annunciators (avail. in 8- & 16-light panels) O O O
Custom Alarm Module O O S
Enclosure
Vandal door S S S
(7)
S
(7)
S S
Dust proof (IP52 per IEC 34-5) O O O
Control Panel Features
(1) Combined emergency
stop/overspeed light
(2) Common indicating light with
separate diagnostic codes for
each function
(3) Contact only provided
indicating light is not provided
(4) EMCP II, II+, and II+P alarm
modules available in a
configuration of eight lamps.
(5) Installed in EMCP II+P
(6) Except 3300, 3406
(7) Not available on 3406C and 3456
S = Standard
O = Optional
= not available
www.CAT-ElectricPower.com
2003 Caterpillar
All rights reserved.
European sourced Printed in U.S.A.
LEHX9295-02 (7-03) Materials and specifications are subject to change without notice.
The International System of Units (SI) is used in this publication.

You might also like