Professional Documents
Culture Documents
CONTENTS
1. INTRODUCTION .................................................................................................................................... 3
2. ELECTRICAL POWER AVAILABILITY .................................................................................................. 4
2.1. Downtime cost analysis ....................................................................................................................... 4
2.2. Calculating power supply availability ................................................................................................... 5
2.3. Redundancy ........................................................................................................................................ 6
3. CLASSIFICATION OF DATA CENTRES ............................................................................................... 8
4. CHOOSING THE DISTRIBUTION SCHEME OF THE ELECTRICAL POWER SYSTEM ..................... 9
4.1. Fundamental schemes ........................................................................................................................ 9
4.1.1. Single radial scheme ..................................................................................................................... 9
4.1.2. Dual radial scheme ..................................................................................................................... 10
4.1.3. Comparison between fundamental schemes .............................................................................. 10
4.1.4. Variants of the fundamental schemes ......................................................................................... 11
5. SIZING A STATIC UPS SYSTEM ........................................................................................................ 15
5.1. Power ................................................................................................................................................ 15
5.2. Autonomy .......................................................................................................................................... 16
6. PROTECTION AGAINST INDIRECT CONTACT ................................................................................. 16
6.1. Power supply from the mains ............................................................................................................ 16
6.2. Standalone operation ........................................................................................................................ 17
7. EMERGENCY LIGHTING POWER SUPPLY ....................................................................................... 18
7.1. Back-up lighting ................................................................................................................................. 18
7.2. Safety lighting .................................................................................................................................... 19
8. SAFETY AND EMC DISTURBANCES ................................................................................................. 19
8.1. Connection to the earthing system: functional aspects ..................................................................... 19
8.2. Connection to the earthing system: safety aspects ........................................................................... 20
8.2.1. High reliability protective conductors .......................................................................................... 20
8.2.2. Monitoring the continuity of the protective conductor .................................................................. 21
8.2.3. Use of transformers .................................................................................................................... 21
8.3. Effects of the Uninterruptible Power Supply ...................................................................................... 21
9. ENERGY EFFICIENCY AND RELIABILITY ......................................................................................... 22
10. CONCLUSIONS ................................................................................................................................. 23
3
The failure rate () of a complex system can in turn be calculated from the failure rates of the individual
components, bearing in mind the following two rules:
the failure rate of elements in series is the sum of the failure rates of the individual elements
the failure rate of elements in parallel is the reciprocal of the sum of the failure rates of the individual elements
However, the unavailability of reliable statistical data on the availability of the various system components
typically constitutes the main obstacle to this analysis, which is why qualitative considerations sometimes take
precedence over quantitative evaluations.
In
Table 2
Table 2 - Reference failure rate values of MV/LV components
Element Failure rate [h
-1
] MTTF [h] MTTR [h]
MV/LV line (m)
1
0.1000 10
-6
10 000 000 8-30
Switch disconnector or
1.0000 10
-6
1 000 000 4-72
6
UPS
(maximum current value from the UPS);
t
UPS
(time for which UPS is sustainable);
load
(overload current required by the load);
t
load
(theoretical overload time required by the load).
the apparent power required for sizing the UPS will be:
UPS
load
RL UPS
I
S S with t
load
t
UPS
Typical values of
UPS
and t
UPS
can range from typical current values of 150% of nominal current for one minute up
to 200% per 100ms without mains power or for UPS systems not equipped with bypass.
The typical cold inrush current of an appliance of the type under consideration is equal to 6 - 8 times the nominal
current, and in practice is only limited by the impedance of the UPS and the conductors comprising the part of the
distribution network affected by the event.
5.2. Autonomy
Autonomy is essentially linked to the time that the data centre is able to guarantee continued operation and if
necessary perform a controlled shutdown (typically 30-60 min).
If service must be guaranteed for a long time (roughly 60-90 min), as is often the case, a rotary generator should
be provided to supply power to the static system, implementing procedures to ensure fuel replenishment if
necessary.
6. PROTECTION AGAINST INDIRECT CONTACT
Protection against indirect contact in the presence of static UPS systems, as applied typically to data centres, is
relatively complex since the downstream circuits can be powered either by battery in standalone operation,
independently from the network, or from the network through the inverter or directly.
At the design stage it is important to give due thought to this choice so as not to risk compromising personal
safety on the one hand, and nullifying the availability of the power supply on the other.
6.1. Power supply from the mains
The options typically available are the adoption of a single residual-current device (RCD) upstream of the static
system or a RCD for each user or group of users downstream.
Even if tripping of the RCD occurs whether the power is fed from the mains or from the inverter, due to different
dynamics.
Consider the TT system as an example. In the first case (Figure 11), since the neutral conductor of the mains
power supply is not interrupted by the static system, an earth fault would cause the upstream RCD to trip, in the
absence of the downstream device or if not an S-type device.
An earth fault in the group upstream of the transformer, if present, also causes the RCD to trip, Figure 12.
17