Utility Fault Current amperes kVA = 300


E = 240
I = kVA x 1000 = trans. FLA trans. FLA = 1250

Isca = trans. FLA x 100 PF = 90%
transformer Z Z = 3% %
Isca = ampere short-circuit current RMS symmetrical. Isca = 46,296 amperes
Point to Point Method
Length (distance) L = 150
2 x L x I (ASC) Isca = 46,296
N x C x E L-N # conductors per phase N = 1
C = 13,923
E L - L = 240 Volt
f = 4.156
C = 13,923
Multiplier E L - N = 120 Volt
f = 8.313
M = 1
1 + f Line to Line M = 0.194
Line to Neutral M = 0.107
Fault Current at Service Equipment
Isca x M = fault current at terminals of main disconnect L- L = 8,978 amperes
Isca x M = fault current at terminals of main disconnect L- N = 7,457 amperes
Fault Current from
Length (distance) L = 40
2 x L x I (ASC) Isca = 8,978 Phase 7,457
N x C x E L-N # conductors per phase N = 1
C = 2,430 Phase Conductor
Volt Line to Line E L - L = 240 Volt
f = 1.231
C = 1,995 Neutral Conductor
Volt Line to Neutral E L - N = 120 Volt
Multiplier f = 2.492
M = 1 Line to Line M = 0.448
1 + f Line to Neutral M = 0.286
Job Name
Company Name
Available Fault Current Calculation
E
Volt Line to Line
Neutral conductor constant Neutral Conductor
Volt Line to Neutral
=
'f ' factor =
Phase conductor constant Phase Conductor
Neutral conductor constant
Service disc. to panel "_____"
Single Phase Feeder
'f ' factor =
Phase conductor constant
Step 1b: Insert the kVA
rating (PF) power factor and (Z)
impedence of transformer.
When you insert the kVA rating, power
factor and impedence you must select a
voltage from the select the Voltage and
Phase from dropdown box before the value
will be calculated.)

or
Step 1a: Insert available
fault current ampere rating
from local utility
Step 3: Insert the Length of one
conductor
Step 4: Insert the number of
conductors per phase.
Step 2: Select type of
conductor and conduit
Step 5b: Select neutral
conductor size.
Step 5a: Select phase
conductor size size.
Finished product
CALCULATED FAULT
CURRENT
Personalize by entering
the 'Job Name' and
'Your Company Name'
Continue by entering next point
to point
4,024 amperes
2,135 amperes
Branch Circuit Fault from
Length (distance) L = 30
2 x L x I (ASC) Isca = 4,024 Phase 2,135
N x C x E L-N # conductors per phase N = 1
C = 617 Phase Conductor
Volt Line to Line E L - L = 240 Volt
f = 1.630
C = 617 Neutral Conductor
Volt Line to Neutral E L - N = 120 Volt
Multiplier f = 1.730
M = 1 Line to Line M = 0.380
1 + f Line to Neutral M = 0.366
1,530 amperes
782 amperes
Isca x M = fault current at terminals of the panel L- L =
Isca x M = fault current at terminals of the panel L- N =
Calculation does not include motor contribution
Neutral conductor constant
Isca x M = fault current at terminals of the panel L- L =
Isca x M = fault current at terminals of the panel L- N =
Calculation does not include motor contribution
Point to Point
Single Phase Branch
'f ' factor =
Phase conductor constant
Ver. 4.00
Neutral
Available Fault Current Calculation
Step 1b: Insert the kVA
rating (PF) power factor and (Z)
impedence of transformer. (Note:
When you insert the kVA rating, power
factor and impedence you must select a
voltage from the select the Voltage and
Phase from dropdown box before the value
Step 5b: Select neutral
conductor size.
Neutral
by: John Sokolik Ver. 6.6
26,456 amperes kVA =
E = 240
I = kVA x 1000 = trans. FLA trans. FLA = 0

Isca = trans. FLA x 100 x PF PF =
transformer Z Z =
Isca = ampere short-circuit current RMS symmetrical. Isca = 0 amperes
Point to Point Method
Length (distance) L = 150
2 x L x I (ASC) Isca = 26,456
N x C x E L-N # conductors per phase N = 1
C = 13,923
E L - L =
240 Volt
f = 2.375
C = 13,923
Multiplier E L - N = 120 Volt
f = 4.750
M = 1
1 + f Line to Line M = 0.296
Line to Neutral M = 0.174
Isca x M = fault current at terminals of main disconnect L- L = 7,838 amperes
Isca x M = fault current at terminals of main disconnect L- N = 6,901 amperes
Job Name
Your Company Name
Available Fault Current Calculation
E
jmp1jds@comcast.net
Neutral conductor constant Neutral Conductor
Volt Line to Neutral
Fault Current at Service Equipment
Volt Line to Line
Utility Symmetrical Fault Current
'f ' factor =
Phase conductor constant Phase Conductor
=