Transmission Surge Arresters

2
3P8SR336 Series Parallel Surge Arrester - Fin Grid installation - Finland 1997
3
Tyco Electronics Energy Division
covers a wide range of porcelain and
polymeric transmission surge
arresters. The Bowthorpe EMP range
of arresters have demonstrated
reliable performance in
environments all over the world for
over 60 years.
Bowthorpe EMP recognise that
some Power Utilities require the
need to maintain the conventional
ZnO porcelain surge arrester.
A program of continuous design
update and development on the
porcelain arrester has provided a
range of surge arresters to meet the
demands of most system voltages.
Design Evaluated and Type Tested at
our HV Laboratory in Brighton and
also at external Laboratories.
Bowthorpe EMP were the first
manufacturer to develop the
polymeric housed arrester for
commercial operation (1983).
Range of HV surge arresters in
service under the severest climatic
conditions up to 550kV system.
The range of arresters are
covered by worldwide patents to
protect the companys extensive
investment in R & D.
Surge Arresters
Porcelain Housed
Surge Arrester
MBA Class 2, 10kA (11-156kV)
MAA Class 2, 10kA (11- 220kV)
MCA, Class 3, 10kA (11- 400kV)
MDA, Class 4, 20kA (11- 400kV)
Polymeric Housed
Surge Arrester
PSRB, Class 2, 10kA (66- 220kV)
PSRA, Class 3/4, 10/20kA (66- 220kV)
Modular Single Column
Polymeric Surge Arrester
2H & 3H, Class 2, 10kA (66- 132kV)
Modular Series Parallel
Polymeric Surge Arrester
2P, Class 3, 10kA (11- 150kV)
3P, Class 3/4, 10/20kA (66- 400kV)
4P, Class 4, 20kA (132- 500kV)
5P, Class 5, 20kA (300- 500kV)
4
The module core design was
developed in the early 80s and has
over 15 years service experience,
with the housing material changing
in the early 90s.
The modular single column
polymeric surge arrester design is
available up to 132kV systems.
The essential feature of the internal
patented construction is the
permanent homogenous resin and
glass fibre bond over the complete
insulated service of the ZnO
elements. The arrester module has
an inherently high mechanical
strength and provides a uniform
dielectric at the insulated surface of
the ZnO elements.
Routine tests are carried out to show
that the manufacturing conforms to
the current International standard.
2HSR & 3HSR Modular Single Column
Polymeric Surge Arresters
Stainless Steel Terminal Assembly
Die Cast Aluminium Sealing End
Aluminium End Block
Thermal Barrier
Silicone Rubber Housing
Heat Sink
ZnO Varistor Element
Finland 132kV system Fin Grid installed 1997
Norway 52kV Hafslund Energei
5
2H & 3H Arrester Type Rating MCOV
with M16 Studs & nuts both ends kV kV
2HSRB30L1E1M0 30 24
2HSRB45L1E1M0 45 36
2HSRB48L1E1M0 48 38
2HSRB60L1E1M0 60 48
2HSRC48L1E1M0 48 38
2HSRC60L1E1M0 60 48
2HSRC72L1E1M0 72 58
2HSRC84L1E1M0 84 67
3HSRC96L1E1M0 96 77
3HSRC108L1E1M0 108 86
3HSRC120L1E1M0 120 96
3HSRC126L1E1M0 126 101
2HSR & 3HSR Modular Single Column
Polymeric Surge Arresters Accessories
2H & 3H Arrester Type Rating MCOV
with pedestal base kV kV
2HSRBP30L1E1M5 30 24
2HSRBP45L1E1M5 45 36
2HSRBP48L1E1M5 48 38
2HSRBP60L1E1M5 60 48
2HSRCP48L1E1M5 48 38
2HSRCP60L1E1M5 60 48
2HSRCP72L1E1M5 72 58
2HSRCP84L1E1M5 84 67
3HSRCP96L1E1M5 96 77
3HSRCP108L1E1M5 108 86
3HSRCP120L1E1M5 120 96
3HSRCP126L1E1M5 126 101
Example: 3 HSRC 96 L1 E1 M0
Mounting
Earth Terminal
Line Terminal
Stages
Arrester Housing
Voltage
L6
Aluminium Stem
30mm x 80mm high
L5
Line Clamp to suit
cables up to 35mm
L2
Line Clamp to suit
cables up to 16mm
M5
4 hole Pedestal Base
127-140 PCD
M10
Single Polyfibre
Base Insulator
M3
Set of 4 Polyfibre
Base Insulators
used with M5
E5
Earth Clamp to suit
cables up to 35mm
E2
Earth Clamp to suit
cables up to 16mm
L1,E1 = M16 Studs with 2 Full Nuts and Washers L1 = M16 Studs with 2 Full Nuts and Washers
E1 = 2 x M10 Screws
6
The series parallel surge arrester
was developed in the late 80s. We
have over 12 years service
experience in over 60 countries.
The series parallel construction
comprises individual surge arrester
modules rated between 30 and 45kV
interconnected by means of corona
free silicon aluminium alloy plates.
Each surge arrester module is
completely impervious to the
ingress of moisture and utilises the
high mechanical strength properties
of the ZnO varistor bonded by cured
resin impregnated glass fibre.
The external geometry and materials
provide an arrester that is a virtually
perfectly graded voltage field such
that no grading ring is required.
The overall diameter of the series
parallel arrester has been calculated
to reduce the radial field stress to a
minimum, even under adverse
environmental conditions.
The electrostatic capacitance
coupling between each silicon
aluminium interconnection provides
an even voltage field across the
surface of the silicon housing.
This arrangement has been proven
under the severest of monitored
natural pollution conditions (NGC).
The very large surface area allows
this design to maintain thermal
equilibrium after lightning or
switching duty.
The seismic performance of 500kV
arrester has been proven in two
leading test facilities. Bonneville
Power USA performed at Portland
State University and NEL East
Kilbride UK. Test performed and
passed to IEEE 693 Annex K and the
IEEE Recommended Practice for
Seismic Design of Substations.
Routine tests are carried out to show
that the manufacturing conforms to
the current International standard.
Series Parallel Polymeric Surge Arresters
132kV Fin Grid installed in 1996
132kV SCECO Central Saudi Arabia installed in 1997
500kV Tallas Valley Kyrgystan
installed in 1997
7
Series Parallel Arrester Type Rating MCOV
kV kV
2P1SR30L2E2M2 30 24
2P1SR36L2E2M2 36 29
2P1SR42L2E2M2 42 34
2P2SR60L2E2M2 60 48
2P2SR75L2E2M2 75 60
2P2SR84L2E2M2 84 68
2P3SR96L2E2M2 96 77
2P3SR108L2E2M2 108 87
2P3SR120L2E2M2 120 96
2P4SR132L2E2M2 132 105
2P4SR138L2E2M2 138 110
2P4SR144L2E2M2 144 115
2P4SR150L2E2M2 150 120
2P4SR168L2E2M2 168 134
M2 = 4 Hole Pedestal Base M16 on 280mm PCD
3P3SR96L2E2M7 96 77
3P3SR108L2E2M7 108 87
3P3SR120L2E2M7 120 96
3P4SR132L2E2M7 132 105
3P4SR138L2E2M7 138 110
3P4SR144L2E2M7 144 115
3P4SR150L2E2M7 150 120
3P4SR168L2E2M7 168 134
3P5SR180L2E2M7 180 144
3P5SR192L2E2M7 192 154
3P5SR198L2E2M7 198 158
3P6SR216L2E2M7 216 173
3P6SR228L2E2M7 228 182
3P7SR240L2E2M7 240 192
3P7SR264L2E2M7 264 211
3P7SR288L2E2M7 288 230
3P8SR312L2E2M7 312 250
3P8SR336L2E2M7 336 269
3P9SR360L2E2M7 360 288
4P8SR336L2E2M7 336 269
4P9SR360L2E2M7 360 288
4P10SR360L2E2M7 360 288
4P11SR396L2E2M7 396 237
4P11SR420L2E2M7 420 336
4P11SR444L2E2M7 444 355
4P12SR468L2E2M7 468 374
5P9SR360L2E2M7 360 288
5P10SR360L2E2M7 360 288
5P11SR396L2E2M7 396 237
5P11SR420L2E2M7 420 336
5P11SR444L2E2M7 444 355
5P12SR468L2E2M7 468 374
5P13SR525L2E2M7 525 420
Series Parallel Polymeric Surge Arresters
Accessories
Example: 3P 8SR 336 L2 E2 M7-4
Mounting
Earth Terminal
Line Terminal
Parallel Paths
Series Stages
Voltage
L2
Aluminium Stem
35mm x 80mm high
L3
Line Clamp to suit
cables up to 16mm
(2P/3P/4P/5P)
2P/M4
4 Polyfibre Base Insulators M16 on 280mm PCD
3P/M7
3 Polyfibre Base Insulators M16 on 332mm PCD
4P/M7
4 Polyfibre Base Insulators M16 on 412mm PCD
5P/M7
5 Polyfibre Base Insulators M16 on 590mm PCD
E2/2P
Clamp to suit cables
up to 16mm
L5
Line Clamp to suit
cables up to 35mm
(2P/3P/4P/5P)
E5
Earth Clamp to suit
cables up to 35mm
(2P/3P/4P/5P)
E2
Clamp to suit
cable up to 16mm
(3P/4P/5P)
3P-Class 4 use suffix -4
8
The PSRA & B surge arresters are
available for applications for up to
220kV systems.
Both designs utilise the same
housing construction, which is a
resin and glass fibre pultruded tube
and aluminium flanges.
High cantilever mechanical strength
is achieved on this design with the
internal assembly similar to that of
the porcelain.
The design has been tested to IEC
and demonstrated a 63kA pressure
relief performance.
Routine tests are carried out to show
that the manufacturing conforms to
the current International standard.
PSRA & PSRB Single Column
Polymeric Housed Surge Arresters
Pressure Relief Diaphragm
Compression Spring
Aluminium Spacer
Slicone Rubber Housing
ZnO Varistor Block
Locating Ring
Glass Fibre Pultruded Tube
Aluminium Flange
Dry Air
Korea 154kV Young Chun Substation installed 2001
9
PSRA & PSRB Single Column
Polymeric Housed Surge Arresters Accessories
PSRB Arrester Type Rating MCOV
kV kV
PSRB160L2E1M4 60 48
PSRB175L2E1M4 75 60
PSRB296L2E1M4 96 77
PSRB2108L2E1M4 108 86
PSRB2120L2E1M4 120 96
PSRB2132L2E1M4 132 106
PSRB2138L2E1M4 138 110
PSRB2144L2E1M4 144 115
PSRB2150L2E1M4 150 120
PSRB2168L2E1M4 168 134
PSRB3198L2E1M4 198 158
PSRB3228L2E1M4 228 182
PSRB Arrester Type Rating MCOV
kV kV
PSRA160L2E1M4 60 48
PSRA175L2E1M4 75 60
PSRA296L2E1M4 96 77
PSRA2108L2E1M4 108 86
PSRA2120L2E1M4 120 96
PSRA2132L2E1M4 132 106
PSRA2138L2E1M4 138 110
PSRA2144L2E1M4 144 115
PSRA2150L2E1M4 150 120
PSRA2168L2E1M4 168 134
PSRA3198L2E1M4 198 158
PSRA3228L2E1M4 228 182
Example: PSRB 2138 L2 E1 M5
Mounting
Earth Terminal
Line Terminal
Arrester Housing
Voltage
L2
Aluminium Stem
35mm x 80mm high
L3/E2
Line/Earth Clamp to suit
cables up to 16mm
L5/E5
Line/Earth Clamp to suit
cables up to 35mm
L6
4 hole Nema Pad
M6
4 Polyfibre Base Insulators
on 280mm PCD
E1 = 2 x M10 Screws
M4 = 4 Hole Pedestal Base on 280mm PCD
10
Porcelain surge arresters are
available for applications up to
400kV systems.
Porcelain housing designs have
been used by us for over 60 years.
From 1936 we produced porcelain
surge arresters to the gapped
silicone carbide pattern and since
1980 we have produced arresters to
the gapless ZnO design.
The design consists of a porcelain
housing which conforms to IEC-815
with an Aero Dynamic shed profile.
The varistors, spacers and locating
rings are assembled under
compression with pressure relief
diaphragms at either end, The air
void is evacuated and replaced with
dry air, then sealed.
All arrester designs have been
proved by Type Testing IEC60099-4.
Routine tests are carried out to show
that the manufacturing conforms to
the current International standard.
Porcelain Housed Surge Arresters
Aluminium End Flange
Pressure Relief Diaphragm
Dry Air
Porcelain Housing
ZnO Varistor Block
Locating Ring
Aluminium Spacer
Four Vent Ports
Compression Spring
UK 132kV Seeboard installed in 1975 Kuwait 300kV system MEW installed 1982
11
Porcelain Housed Surge Arresters
Accessories
Voltage MCOV MBA Porcelain MAA Porcelain MCA Porcelain MDA Porcelain
Max Arrester Type Arrester Type Arrester Type Arrester Type
Rating
kV kV L2E1M1 L2E1M2 L2E1M2 L2E1M2
3 2.4 MBA0 MAA0 MCA0 MDA0
6 4.8 MBA0 MAA0 MCA0 MDA0
12 9.6 MBA0 MAA0 MCA0 MDA0
15 12 MBA0 MAA0 MCA0 MDA0
18 14 MBA0 MAA0 MCA0 MDA0
21 17 MBA0 MAA0 MCA0 MDA0
24 19 MBA0 MAA0 MCA0 MDA0
27 22 MBA1 MAA1 MCA1 MDA1
30 24 MBA1 MAA1 MCA1 MDA1
36 29 MBA1 MAA1 MCA1 MDA1
39 31 MBA1 MAA1 MCA1 MDA1
42 34 MBA1 MAA1 MCA1 MDA1
60 48 MBA2 MAA2 MCA2 MDA2
75 60 MBA2 MAA2 MCA2 MDA2
96 77 MBA3 MAA3 MCA3 MDA3
108 86 MBA3 MAA3 MCA3 MDA3
120 96 MBA3 MAA3 MCA3 MDA3
126 101 MBA3 MAA3 MCA3 MDA3
132 106 MBA3 MAA3 MCA3 MDA3
144 115 MBA4 MAA4 MCA4 MDA4
150 120 MBA4 MAA4 MCA4 MDA4
144 115 MBA3.0 MAA3.0 MCA3.0 MDA3.0
150 120 MBA3.1 MAA3.1 MCA3.1 MDA3.1
150 120 MBA3.2 MAA3.2 MCA3.2 MDA3.2
150 120 MBA3.3 MAA3.3 MCA3.3 MDA3.3
150 120 MBA4.0 MAA4.0 MCA4.0 MDA4.0
198 158 MAA4.1 MCA4.1 MDA4.1
198 158 MAA4.2 MCA4.2 MDA4.2
198 158 MAA4.3
198 158 MAA4.4
240 192 MCA4.3 MDA4.3
288 230 MCA4.4 MDA4.4
360 288 MCA3.3.3 MDA3.3.3
Example: MCA4.2 198 L2 E1 M2
Mounting
Earth Terminal
Line Terminal
Arrester Housing
Voltage
L2
Aluminium Line Stem
30mm x 80mm high
L3/E2
Line/Earth Clamp to suit
cables up to 16mm
L5/E5
Line/Earth Clamp to suit
cables up to 35mm
L6
4 hole Nema Pad
M3/M4
M3 = MBA - 210mm PCD
M4 = MAA/MCA/MDA - 280mm PCD
4 Polyfibre Base Insulators
E1 = 2 x M10 screws
MBA-M2 = 4 Hole Pedestal Base on 210mm PCD MAA, MCA, MDA = 4 Hole Pedestal Base on 280mm PCD
Max Rating MBA = 156kV, MAA = 198kV, MCA & MDA = 360kV
BKK Nett Norway
Transmission Line Surge Arrester.
To provide customer solutions for
their lines.
Utilising a series parallel arrester to
protect a 45kV system today and at
a later stage give protection at
120kV, without removing the
installed arrester.
Surge Arrester Special Applications
12
Surge Arrester with extended
creepage up to 55mm/kV
The extended creepage module
could be used on
2HSR/3HSR/2P/3P/4P/5P designs.
13
Surge Counters
Surge Counters SC13, SC12 designed to be used with Surge Arresters
Both SC12/SC13 counters can be supplied with an auxiliary
contact rated 0.5 amps 250V for connection to remote
signalling equipment. If required put suffix AC e.g. SC12/AC
Meter : 6 digit cyclometer at least 5 counts/second
Minimum count current : 200 amps 8/20 microsecond wave
Maximum High Current Withstand : 100 kA 4/10 microsecond wave
Nominal Residual Voltage at 100 kA : 5 kV peak
with 4/10 Microsecond Wave
Meter scale : 0 - 30 mA (bilinear scale) Ref SC13
SC13 leakage : 0 - 50 mA (bilinear scale) Ref SC13L
Surge Counter installation
Surge Arrester insulated from
earth with earth connected through
Surge Counter.
Polyfibre Base Insulators
Surge Counter
Earth Cable
14
Committed to Quality
Our HV Laboratory at Brighton - UK
Tyco Electronics at Shannon - Ireland
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and
reliable. Users, however, should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of
any particular quality or performance. Such an assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for these
products is set forth in our standard terms and conditions of sale.
ALR, AMP, AXICOM, B&H, Bowthorpe EMP, Critchley, Dorman Smith, Dulmison, Hellstern, La Prairie, Morlynn, Raychem, SIMEL and SUCOFIT are trademarks.
Argentina
Phone: ++54-11-4733 2277
Fax: ++54-11-4733 2267
Australia
Phone: ++61-2-4390 1111
Fax: ++61-2-4353 2497
Brazil
Phone: ++55-11-3611 1862
Fax: ++55-11-3611 2457
Canada
Phone: ++1-905-475 6222
Fax: ++1-905-470-4453
France
Phone: ++33-3-80583200
Fax: ++33-3-80341015
Mexico
Phone: ++52-5-729 0405
Fax: ++52-5-361-8545
Thailand
Phone: ++66-2-7394026 - 32
Fax: ++66-2-3260563 - 64
United States of America
Phone: ++1-800-327-6996
Fax: ++1-800-527-8350
United Kingdom
Phone: ++44-1772-325400
Fax: ++44-1772-726276
Tyco Electronics Bowthorpe EMP
Stevenson Road, Brighton, East Sussex, England BN2 0DF
Phone: +44 (0) 1273 692591, Fax: +44 (0) 1273 601741
http:www.bowthorpe-emp.com
Tyco Electronics Raychem GmbH
Energy Division
Haidgraben 6, 85521 Ottobrunn/Munich, Germany
Phone: ++49-89-6089-0, Fax: ++49-89-6096345 http://energy.tycoelectronics.com


T
y
c
o

E
l
e
c
t
r
o
n
i
c
s

B
O
W
-
E
P
P

0
0
0
1
-
0
8
-
0
2
For further information contact hvsurgearresters@tycoelectronics.com

You might also like