You are on page 1of 45

1

In this program, were going to build a hydronic system step by step, and piece by
piece from Heat Loss through start-up.
2
This may be an oversimplification but any hydronic system needs to start with a heat loss. Do the
MATH! This establishes a target for your heating system, as well as some documentation for your
customer. There are tons of heat loss calculation methods out there but all stem from IBR,
ASHRAE or ACCAs Manual J . These, plus all the heat loss calculators available in software form all
use the same math formula. They may differ in what might be loosely termed as safety or fudge
factor. Suffice it to say, however, that all neat loss formulas have plenty of safety built in and theres
no need on our part to add any extra!
Heat loss comes from two separate elements the first is air infiltration, or heat lost due to heated air
leaking from the inside of the house to the outside and being replaced by cold air coming in to
replace it. This air will need to be heated up to comfortable levels. Infiltration heat loss is along
with window loss the largest single heat loss element. Heat loss calculations will also need to
made for conductive heat transmission through walls, ceiling and floors, as well as through doors,
windows and skylights. By any measure, however, heat loss is an educated estimation. You can go
to great lengths to be as accurate as possible, but acceptable results can be found by simply
rounding up your calculations.
Its also important to do a room by room heat loss analysis. This will enable you to adequately size
the heat emitters baseboard, radiators, radiant floor heat for each room. A whole house heat loss
is faster and simpler and will help you size the heating plant, but it doesnt help you when it comes to
making each room comfortable.
3
Lets do a quick example. This exercise is meant to show you how a heat loss is done manually. Taco has training
programs to help you do a more in depth heat loss analysis, as well as computer software that can design an entire system
for you. Its important, however, to know how to do a heat loss manually so that youll know what the numbers mean and
how the software came up with them.
For this example, lets do a simple 10 by 15 room with 9 foot ceilings. The room has two outside walls with windows. When
conducting a heat loss analysis, we need to determine the indoor design temperature meaning the indoor temperature we
wish to maintain during the heating season in most cases the number to use is 70 degrees. The other number we need to
determine is the outdoor design temperature, or the coldest day of the year. Our goals when designing a heating system is
to keep the structure at 70 degrees when the weather reaches that outdoor design temperature. ASHRAE publishes
recommended design temperatures for different parts of the country. For our example, lets use an Outdoor Design
Temperature of 0. Some people like to exaggerate this number to make sure their customers have enough heat if the
temperature ever drops below the recommended temperature. This practice can often lead to needless oversizing of a
boiler, which can add unnecessary cost to the job, as well as lower the overall efficiency of the system, since oversized
boilers dont run efficiently.
In our example, we have an indoor design temperature of 70, with an outdoor design temperature of 0. Well use this
information during the calculations in the form of DTD, or Design Temperature Difference. Thats the difference between
what we want indoors when its at design conditions outdoors. We want 70 indoors when its 0 outdoors, so thats a DTD of
70 degrees.
Another factor needed for heat loss is the so-called infiltration factor. This is a number that helps us determine the rate of air
leakage, and can vary based on how old the house is and how well sealed the structure may be. New construction tends to
have rather low infiltration rates, while older homes may leak quite a bit. For our purposes, well use the IBR factors for
infiltration: 0.012 for rooms with one outside wall, 0.018 for rooms with two outside walls, and 0.027 for rooms with entries or
with three outside walls. By way of explanation, 0.012 represents 2/3rds of an air change per hour, and the BTUs needed to
warm that air up again. Technically, 0.012 is the amount of heat needed to raise 2/3rds of a cubic foot of air one degree.
Lets do the math. To find the infiltration heat loss, we first need to find the volume of air in the room. We do that by
multiplying the length times the width times the height. That tells us how many cubic feet of air were dealing with. We then
multiply that times the DTD, and then multiply by the infiltration factor. In this example, we do that following calculation:
L x W x H x DTD x Infiltration factor =infiltration loss.
10 x 15 x 9 x 70 x .018 =1,701 BTUH
4
Now lets do the rest which is all conductance heat loss through the walls, ceiling (if theres a cold space above), floor (if
theres a cold space below), windows, doors and skylights. The formula for all these losses is the same: L x W X DTD x U.
Length times width gives us the area and DTD is the design temperature difference. U represents the U-Value of the
assembly. U-value represents the assemblys ability to conduct heat from one side to the other. Obviously, when it comes to
heat loss, wed like as low of a U-value as possible. In fact, U-value is the inverse of R-value, which is an assemblys ability
to resist the flow of heat. If you know the R-value, simply divide 1 by the R-value and youll get the U-value.
Lets do the windows first. We look at the plan and see that we have two 3x5 windows on one wall and one 6x5 window on
the other. Windows have U-values on their stickers when theyre installed, but there is plenty of data available especially in
heat loss computer programs to help you determine the u-value of an existing window. For our purposes, were using
standard wood framed, double-pane, low-E windows, which have an average U-value of .36. To find the window heat loss,
we total up the square footage of all the windows, and count them as one big window its easier that way. In this case, the
room has 60 square feet of window area. We multiply 60 times the DTD of 70, and then multiply again by the U-value of .36,
and we come up with a window loss of 1,512 BTUH.
Walls are next we want to use the NET area of the walls, and then multiply by the DTD and U-value. We have two outside
walls here one ten feet long and the other 15 feet long. To make it easier, well simply add the lengths together and make it
one big wall. (NOTE with heating, north, south, east or west facing walls dont matter because often well be trying to heat
the room when its dark out). In this case, we have 25 linear feet of wall times 9 feet high for a total area of 225 square feet.
We then need to subtract the window area from that total 225 minus 60 equals 165 square feet of net wall area. This is the
number well use for our calculations.
We also need to find the U-value for the wall. Typically, we look at the level of insulation in the wall in this case its 6
inches of fiberglass at an R-19. You can also look up the associated R-values for the exterior sheathing, house wrap and
finish, as well as for the inside sheetrock, and that would be more accurate. But in the name of simplicity and safety margin,
many folks will simply use the insulation R-value for the calculations. In this case, we divide 1 by 19 to find the wall U-value
of .05.
Lets multiply it all out 165 x 70 x .05 equals 578 BTUH lost through the walls.
Outside doors, if there were any, would be calculated in the same way and their area would also be deducted from the Net
Wall area.
5
Lets finish up with the ceilings and the floors. We would only need to calculate
either of these items if there were unheated spaces above or below the room. If the
area below the room was heated, there would be no heat loss through the floor, nor
would there be any loss through the ceiling if there was a heated space above the
room.
We use the same math formula. For the ceiling we multiply the length times the
width times the DTD times the U-value. Again, for simplicity well look at the
insulation values. With R-38 in the ceiling, the math tells us the U-value would be
0.02. We multiply out 10 x 15 x 70 x .02 and we come up wth a ceiling loss of 210
BTUH. The floors have R-19 insulation, so we calculate a U-value of 0.05. We
then multiply 10 x 15 x 70 x .05 for a floor loss of 525 BTUH.
Finally, we add them all together for find the total heat loss of 4,526 BTUH for the
room.
6
7
Lets define some of the terms used in the chart. First is AGA Input for a gas boiler. This is the Gas
Input needed per hour for the boiler to operated as rated. In this example, the AGA input is 120,000
BTUH. Since one therm of natural gas contains 100,000 BTUH, this means the input rate of the
selected boiler is 1.2 therms per hour.
Next is the DOE or Department of Energy Capacity. This is a federal rating note on the boiler
weve selected to DOE output is 101,000 BTUH. If we divide the DOE output by the AGA input, we
come up with 84.1%, which happens to be the AFUE rating of the boiler. What is means is that for
every 120,000 BTUs worth of fuel you put into the boiler, the DOE says youll get 101,000 usable
BTUs out of it. Another item of note with the DOE capacity it assumes the boiler and all the
distribution piping is installed in a heated area and that any jacket losses and piping losses are
usable heat that will help offset the heating load of the building.
The I-B-R net output de-rates the DOE capacity by about 15%, under the assumption that 15% of the
boilers output will be lost through the piping and jacket, or is needed to warm up the thermal mass of
the boiler and the piping following an off-cycle. This is called the pickup allowance, and accounts
for warming up cool cast iron boiler sections as well as cool steel or copper distribution piping. The
IBR Net Output assumes the boiler and the distribution piping is in cold or unheated areas.
Which one should you use? Well, it depends on where the boiler is to be installed. If the boiler and
distribution piping are in a heated space such as in a mechanical room in a finished, heated
basement, then the DOE capacity would suffice. If the boiler and a good portion of the distribution
piping is to be installed in an unheated basement, garage or crawlspace, then the IBR number is
suitable.
8
Lets fast forward now to the completed heat loss, which is 75, 421 BTUH. We
need to select a boiler that will handle that load. Heres a chart from a gas boiler
manufacturer showing their different size boilers. The numbers we want to look at
for sizing are either the DOE capacity or the NET IBR RATING. Well explain those
in a moment, but if we consider the heating load of 75,421 BTUH, is appears we
could use either the S-90 model, which has a DOE capacity of 76,000, but only
66,000 NET IBR, or we could use the S-120, which has a DOE of 101,000 with a
NET IBR of 88,000. both will cover the job without being oversized, but lets look at
it a little closer.
9
Weve talked about pressure loss and pressure differential. In hydronics, pressure
is typically referred to as head pressure. Technically, head is the total mechanical
energy content of a fluid at a given point in a piping system. We use it to express
pressure loss in the piping system. When water flows through the system, it will
encounter friction loss due to the piping. The greater the flow through a given
system, the greater the pressure loss. The circulator needs to produce the required
amount of flow while overcoming that pressure loss.
Pressure is generally measured in pounds per square inch, or PSI. In hydronics,
we use head loss. Converting PSI to head loss is very simple. A column of water
2.31 feet, or 28 inches high, will have a gauge pressure at the bottom of 1 PSI. So
simple math tells us that 1 PSI of pressure drop in a system equals 2.31 feet of
head.
10
Why are residential hydronic systems typically filled to 12 psi? Well, if you have a
plumbing license, you know that a column of water 2.31 feet (or 28 inches) high has
a gauge pressure at the bottom of 1 psi. It doesnt matter how big around the
column is, the pressure is still 1 psi. If we multiply 2.31 feet by 12 pounds, well
come up with 27.72 feet. That means if the boilers in the basement, 12 psi is
enough to pressurize the water in a closed loop system on the third floor of a
structure, with a little extra for safety. Obviously, taller buildings, particularly
commercial buildings, may need a higher static fill pressure. Those jobs also use
boilers with higher pressure ratings as well as higher rated pressure relief valves.
11
Its important to remember than when sizing a circulator, you do not need to
take into account the height of the building. The physical height of the
building does NOT equal the feet of head. Remember, this is a circulator,
not a pump, and were dealing with a closed loop system, not a well or a
sump pump system. The circulator does not need to lift the water to the top
of the building due to the simple fact that what goes up must come down.
The circulator doesnt have to lift the water to the upper floors the weight of
the water coming back down the return side is a counterbalance. Think of
the circulator as the motor on a ferris wheel. The motor doesnt have to lift
the weight of the people up there are people on the other side of the wheel
coming back down. All it has to do is overcome the friction loss of the
bearing assemblies in the wheel. A circulator doesnt have to lift the water
it only has to overcome the friction loss or head loss of the system.
12
Next on the to-do list is the pressure reducing valve ( and backflow preventer, if required by code), air
eliminator and expansion tank assembly. The PRV, of course, reduces the water pressure going in
to the system down from street pressure to whatever the static fill pressure is, usually 12 psi. The air
eliminator controls and removes air bubbles from the system, and the expansion tank allows for
pressurization of the system and gives the expanding water somewhere to go as it heats up.
Why place the PRV here? Well, the way these things work is that there is in internal diaphragm and
spring that exert pressure on the city water inlet side. When the system side reaches the desired
pressure, the spring and diaphragm will close the city side inlet. The PRV will close and wont allow
any more water into the system as long as the system pressure is at least the desired, set amount
again, usually 12 psi. The only way the PRV will allow more water into the system is if the system
pressure drops below 12 psi, but that wont happen here.
The point where the expansion tank connects to the heating system is called the point of no pressure
change. The pressure at this point will always be at least the static fill pressure (unless theres a leak
in the system!). Because of this point of no pressure change, the PRV wont be allowed to let more
water into the system under normal working conditions. Well discuss the point of no pressure
change in greater detail in a few moments.
This is the Taco 3350 cartridge type pressure reducing valve. It works as a fast-fill type valve as
well. When filling or purging the system, you simply press down on the top of the green cartridge
this manually opens the diaphragm and allows the system to be rapidly filled at street pressure.
Release the cartridge and the system will stop filling. The pressure may be set by rotating the black
dial on the side of the cartridge they come preset to 12 psi. The 3350 can be installed in any
positon and has a fully replaceable cartridge in case service is ever needed. In addition, the unique
design allows you to replace the cartridge without having to drain the system, which can save lots of
time and hassle. The cartridge also rotates, so no matter how its installed, you can always read the
pressure indicator.
13
Heres a picture of what this part of the system should look like. Youll note the
4900 air separator with the expansion tank and cold water fill connected to the
tapping at the bottom. As mentioned earlier, this is the perfect spot for the
automatic fill/pressure reducing valve to connect to the system, because this is the
one part of the system where the static pressure cannot change when the circulator
operates. This spot, where the expansion tank connects to the piping system, is
known as the point of no pressure change.
14
Why is this the point of no pressure change? Well, its the only area in the system
where the circulator cant change the pressure. Only three things can change the
system pressure where the tank joins the system. First, the pressure will change if
water is added to or removed from the system. Second, the system pressure will
change if air is removed from or added to the expansion tank. And third, the
pressure will change when the water is heated due to its expanding volume. The
circulator cant do any of these it cant add or remove water or air from the tank,
and it cant heat the water up to make it expand. The circulator has only one job,
and thats to create a pressure differential within the system in order to promote
flow. And it can only create a pressure differential if it has a reference point the
circulator uses the expansion tank and the point of no pressure as that reference
point.
15
So where should the circulator be in relation to the point of no pressure change?
Well, lets examine what will happen when you pump toward the expansion tank.
Remember that the circulator must create a pressure differential positive or
negative in order to move water. If the circulator is pumping into the expansion
tank, it cant raise the system pressure any higher than it already is, which is 12
PSI. So no matter how power the circulator is, the outlet pressure on the other side
of the expansion tank will never be any higher than 12 PSI. If thats the case, and if
the circulator MUST create a pressure differential whats the only thing the
circulator can do? Lower the suction side pressure and create the differential that
way. That will create flow, but will also create a host of other issues.
16
A: when system is filled with cold water, the pre-charged pressure is equal to
system fill pressure and diaphragm is flush against tank.
B: As water temp increases, the expanded water is absorbed by the tank.
C: As system water temp reaches max, the diaphragm flexes against the air
cushion to allow for the increased water expansion
17
Here we show the circulator pumping into the expansion tank connection
the point of no pressure change. The circulator is off the gauges read 12
psi at the tank, and at both the suction and discharge side of the circulator.
The system is 18.5 feet high, so the static pressure drops roughly 8 psi
down to 4 psi at the peak of the system. The weight of the water coming
back down the return side is what brings the pressure back to 12 psi at the
suction side. What happens when the circulator is turned on?
18
Now that the circulator is on, its creating a 4 psi pressure differential to
create flow. Since the circulator cant change the pressure at the tank or
point of no pressure change the pressure there will remain 12 psi. The
circulators differential will show itself as a pressure DROP on the suction
side. A gauge on the outlet side will still read 12 psi, but the gauge on the
suction side will drop to 8 psi. Since the system will lose 8 psi on its way to
the peak, and add 8 psi back down to the suction side of the circulator, the
pressure at the peak of the system will be zero, or close to it. This can
create a system with air noise, or worse if there are manual air vents
installed in the line if the pressure in the system ever pulls negative, the air
vents become air intake valves and can cause the system to get air bound.
19
Here we move the circulator so that it pumps away from the point of no pressure
change. When the circulator is off, we have the same scenario as before, with the
pressure reading 12 psi on either side of the circulator, and 4 psi at the highest point
of the system.
20
When the circulator is turn on, since the system pressure on the suction side of the
circulator cant drop below 12 psi, the circulator will ADD its pressure differential to
the system. The pressure reading on the outlet side of the system is now 16 psi.
The system will lose 8 psi on its trip to the highest point the pressure there will
now be no lower than 8 psi from that point back the weight of the water will
increase the pressure back to the 12 psi at the expansion tank.
This will keep air dissolved in the water solution and prevent the system from ever
getting air bound or experiencing air related noise issues such as a babbling
brook sound. Keeping the air dissolved will also enhance system performance and
circulator life.
21
22
What we call a pump in hydronics is a bit of a misnomer. Its not really a pump
its a centrifugal pump, or a circulator. It doesnt lift water the way a well pump lifts
water it circulates water in a closed loop system by creating a pressure
differential, meaning it takes the fluid that comes into it at a lower pressure and
sends it back out at a higher pressure. When the circulator creates a pressure
differential, mother nature takes over because high pressure will always go to low
pressure, thus creating flow through the system. The trick for the circulator is to
create enough of a pressure differential to produce adequate flow through the
system.
How does the circulator create a pressure differential? Simple by using
centrifugal force.
23
Heres a line drawing of the guts of a Taco 007 circulator. You see flow entering at
the bottom of the circulator. Theres a cast iron or bronze casing for the circulator
known as the volute. You also see the impeller which is part of the circulator
cartridge which houses all the moving parts of the 007. The cartridge fits into the
steel motor housing and the motor itself, which makes the impeller go round and
round.
24
Heres a closer look at the cartridge. In the picture, you see the open faced impeller
--With the 00 series, its a water lubricated cartridge, meaning theres always water
in the cartridge. Youll also hear this type of circulator referred to as a wet-rotor
circulator.
As the system is filled and pressurized during initial start-up, system water is forced
into the empty cartridge through the hollow ceramic shaft. In turn, the air in the
cartridge is forced out, also through the ceramic shaft. Once the system is filled
and pressurized, small amounts of air may remain in the cartridge. This remaining
air will be purged from the cartridge as soon as the pump is turned on. The
spinning of the shaft and rotor assembly creates a centrifugal suction that replaces
the air with water. Once the cartridge is full of water the hollow ceramic shaft acts
as a mini expansion tank. It provides the exact amount of space so the water in the
cartridge can expand and contract, as the water heats and cools, without bringing
new system water into the cartridge.
25
Heres a closer look at the impeller itself. When the circulator is in operation, water flows into the
suction side of the volute which is always wider and larger than the discharge side -- and then into
the eye of the impeller. As the impeller rotates, the vanes slap the water from the inside of the
impeller to the outside of the impeller adding velocity to the fluid. The fluid then moves to the
discharge side of the volute which is smaller and narrower. The collection chamber on the
discharge side turns the kinetic energy of the fluid energy due to velocity, into pressure. So the
water comes into the circulator at a low pressure, and due to centrifugal force and the design of the
circulator, leaves at a higher pressure.
Some things to know about impellers the thickness, diameter and construction all play a role in the
performance of the circulator just as much as motor horsepower. First, different circulators will
have thicker or thinner impellers the thickness of the impeller determines its flow capacity the
thicker the impeller, the more flow the circulator will be able to produce. The diameter of the impeller
is also important. The larger the diameter meaning the bigger around the impeller is, the more
velocity the circulator can impart of the fluid. The more velocity, the more pressure the circulator can
produce. Horsepower also plays a role with any type of impeller the faster the impeller spins, the
more flow AND pressure the circulator can produce.
Also not the drawing in the center represents a closed vane impeller. The picture on the side shows
an open vane impeller. Open vane impellers are used in circulators designed to provide high flow
and relatively low head. These types of circulators are called flat curve circulators as you will see
when we look at performance curves. The Taco 007 and 0010 are considered flat curve circulators
and are used in radiator and baseboard applications which require higher flow rates but have lower
overall head losses. Close vane impellers are used for higher head and medium to high flow
circulators, such as the Taco 008 and 00R. These are designed for lower flow systems that produce
higher head losses, which are typically found in most radiant applications.
26
27
28
29
30
31
32
33
To size a circulator properly, you gotta do the math. By that we mean a heat loss
analysis of the structure so you know what the job really needs. The flow rate
needed for a particular job or a particular zone is based solely on the heat loss. Any
heat loss analysis should be conducted on a room by room basis, since each room
will have its own unique heating requirements and will need baseboard or a radiant
sized for its unique needs. When you have each room figured out, then you can
group rooms together into zones, and determine what the zone heat loss would be.
This is important when zoning by circulator, since you will select each circulator
based on the zone flow requirement. When zoning with zone valves, it will be
important to know the flow rate for the entire job so the circulator will be big enough.
Once we know the BTUH load of the zone or of the entire job, depending on
whether were zoning with zone valves or circulators, we then need to calculate the
actual flow rate using the Universal Hydronics formula: GPM (or gallons per
minute) =BTUH divided by Delta T times 500. The BTUH is, of course, the heating
load. To determine the flow rate, well divide that load by the Delta T ( or
temperature drop) times 500. The Delta T is the temperature drop across the piping
circuit typically with baseboard or radiators the Delta T is 20 (meaning the water
goes out to the zone at 180 and returns to the boiler at 160). 500 is a constant, and
represents the weight of one gallon of water (8.33 lbs) times the number of minutes
in an hour (60) times the specific heat characteristic of the fluid used in this case
water (it takes one BTU to raise the temperature of one gallon of water one degree
in one hour).
34
So lets do one.
Lets say were zoning with circulators, and we have a zone that has 27,000 BTUs
worth of baseboard, or roughly 45 feet. Its a good sized zone. Since its
baseboard, were using a 20 degree Delta T, and were also using 100% water no
glycol. To determine the flow rate, we simply divide the load 27,000 by the Delta
T of 20 times 500. If we math it out, we will divide 27,000 by 10,000 (20 x 500) to
determine an actual flow rate for the zone of 2.7 gallons per minute.
What size pipe should we use for this zone? Well, the guidelines for pipe sizing are
as follows: 2 to 4 gallons per minute of flow, use M copper; 4-9 GPM, use 1
inch; 8 to 14 GPM, use inch and a quarter; 14 to 22 GPM, use inch and a half.
These all fall within hydronics guidelines for pipe sizing and keeping flow velocities
at no less than 2 feet per second and no more than 4 feet per second. At velocities
greater than 4 feet per second, the system will produce velocity noise and customer
complaints. At velocities lower than 2 feet per second, dissolved oxygen will tend to
come out of solution and cause air problems within the system.
35
To determine the head loss of a zone, start by measuring the total length of the
zone, including the element. Once that is done, multiply the total by 1.5 to allow for
fittings, valves, etc. Fittings and valves produce pressure drop in a system that are
the equivalent of a few feet of pipe each, so multiplying by 1.5 accounts for most
basic fittings and valves. We may need to add later for items such as flowchecks, 3
way valves (if used) and other high head loss items, but the .5 multiplier will take
care of fittings and isolation valves. That multiplication will give you the total
developed length of the circuit. Next, take that number and multiply by .04 this
number represents 4 feet of head per 100 feet of copper pipe. That head number
applies as long as the pipe has been sized according to the velocity guidelines
shown in the previous slide. The end product is the head loss for the zone.
Lets do an example. We measure out zone to be a total of 80, including all the
element and the supply and return piping to the boiler. If we multiply 80 times 1.5,
we get a total developed length of 120 feet. Lets multiply that times .04, and we get
a head loss for the zone of 4.8 of head. To size the circulator, well need one that
can provide a total of 2.7 gallons per minute and overcome 4.8 feet of head.
36
If we take a look at the Taco 00 series performance curve chart we can
determine which circulator we should use for this zone. First, on the bottom axis,
we find the flow rate in this example, its 2.7 gallons per minute. On the vertical
axis we have head loss in this example its just under 5 feet of head. We follow
the two lines until they intersect to find our operating point of 2.7 GPM at 4.8 feet of
head. Next, we look at the performance curves to find out which circulator would
make the best selection. In this example, a 005, 005 or a 007 would be good
choices with the most likely choice being the 007, since its the most common and
most readily available.
37
We spoke earlier about open vaned impellers and closed vaned impellers.
Circulators such as the 007 and the 0010 have open vaned impellers producing
high flow rates but a relatively flat performance curve. Pumps such as this can
handle a wide range of flow rates in systems with relatively low head losses, such
as baseboard and radiator systems. Flat curve circulators are also preferable in
zone valve jobs. The amount of flow needed will depend on how many zone valves
may be calling at a particular time. As you can see with the flat curve circulators
big changes in flow will result in very small changes in head produced which will
help keep the system quiet. Steeper curve circulators, such as the 008 and some of
the European models, will require pressure differential bypass valves to prevent
velocity noise in zone valve applications. Another option, of course, would be the
Taco 00-VS variable speed setpoint circulator set to a Delta T operating mode.
Steeper curve circulators, such as the 008, its close cousin the 00R and the 0011
and 0013, are better for higher head applications, including radiant floor heating
applications, as well as high head loss fan coils, air handlers and heat exchangers.
38
39
40
Sizing expansion tanks involves calculating water volume within a system as well as
the temperature increase, etc. This simple rule can help you move tank sizing
along. Tank manufacturers offer what they call 15 gallon, 30 gallon and 60 gallon
tanks, based on how much water is in the system. This can also relate to BTUH
requirement. For the most part, if the system requirement/output is less than or
equal to 50,000 BTUH, a 15 gallon tank will suffice. From 50 to 150,000 BTUH, use
a 30 gallon tank, and 150 up to 200,000 BTUH, use a 60 gallon tank. This will
handle most residential applications.
41
The next step is to size the primary boiler loop. In hydronics, all pipe sizing is done based on flow, or
Gallons per minute. To find the flow, we use the universal hydronics formula GPM =BTUH divided
by Delta T times 500. BTUH is the total heating load. Delta T is the temperature drop across the
piping circuit in this case well use a 20 degree temperature drop across the primary, and 500 is a
constant representing the weight of 1 gallon of water (8.33 pounds) times 60 (the number of minutes
in an hour) times the specific gravity of the fluid used (water has a specific gravity of 1) times the
specific heat of the fluid (water has a specific heat of 1). 8.33 times 60 times 1 times 1 equals 499
and change, well call it 500.
If we calculate out our flow rate, well divide 75,421 BTUH by 10,000 (20x500) to determine a primary
flow rate of 7.54 gallons per minute.
The pipe is always sized to handle the required flow. Standard hydronics guidelines tell us that flow
between 2 and 4 gallons per minute will require copper pipe. 4 to 9 GPM requires 1. 8 to 14 is
1 and 14 to 22 GPM is 1 pipe. This pipe sizing keeps systems within the velocity guidelines of
hydronics which require a velocity of at least 2 feet per second and no more than 4 feet per second
when using copper pipe. At velocities less than 2 feet per second the fluid wont be able to keep air
in solution and will sound like a babbling brook. At velocities greater than 4 feet per second the water
will create velocity noise and sound like a freight train in the mechanical room.
With a calculated flow rate of 7.54, rounded up to 7.6 GPM, the guidelines tell us well need to use 1
pipe.
42
Heres your basic cast iron Taco air scoop. Its been around forever its a one
piece air separator with no moving parts. Theres an 1/8 tapping on top for a Hy-
vent and a tapping at the bottom for the expansion tank and cold water fill
connections.
43
How does an air scoop work? When water enters the scoop, it enters a larger area,
so its velocity slows down and the pressure decreases slightly. As the velocity
slows down and the pressure decreases, the air bubbles will separate from the
water. There are turning vanes inside the scoop that will scoop the bubbles into the
upper chamber, where they will vent out through the hy-vent at the top of the scoop.
Its a simple process with no moving parts.
The scoop will only work, however, if there is a minimum of 18 inches of straight
pipe on the inlet side. The air bubbles need to be on the top of the flow as the water
enters the scoop, otherwise the vanes wont catch the bubbles and the scoop wont
remove the air. The 18 inches is needed to create laminar flow - meaning the flow
will smooth out and air will be allowed to float to the top. If the scoop is installed
right after an elbow, the flow will be turbulent and the air will be mixed with the water
and the scoop will be unable to remove the air.
44
Taco offers three levels of air eliminators that fall under the good-better-best
categories. First the traditional Taco air scoop with a Taco Hy-Vent. A better
alternative one capable of removing lots of air rapidly from the system is the
Taco VorTech. And the best option of all one that removes more air and smaller
microbubbles than any other eliminator on the market, is the Taco 4900. Well
discuss each of these indivudually.
45
The next step up in air removal is the Taco 4900 air separator. The 4900 is a high
performance air separator, removing 3x times more air than the Spirovent according
to independent studies. In addition, unlike the Sprirovent, the 4900 can be used
with glycol in the system. No minimum pipe run is required with the 4900. The
4900 uses Pall rings to remove the air from the system. Like the air scoop, the
4900 is a large chamber. With will slow the velocity down and lower the pressure
slightly. This allows disolved air to come out of solution these microbubbles cling
to the pall rings. There are dozens of pall rings in the 4900, representing a huge
amount of area for the bubbles to cling to. Bubbles will continue to grab onto the
pall rings and, over time, the bubbles will grow to a point where they will rise
through the 4900 the float mechanism will go up, opening the air vent to let the air
out.

You might also like