THE MILESTONE OF GREEN DATA CENTER COOLING TECHNOLOGY

2 l 3
THE FUTURE OF DATA CENTERS
BRINGS BOTH ADVANCED
TECHNOLOGIES AND
EXPONENTIAL DATA
EXCHANGE THAT STRONGLY
INCREASE HEAT LOADS PER
SQUARE METER.
STRUCTURAL LIMITS RESULT
IN HIGHER AND HIGHER POWER
DENSITIES AFFECTING THE
DEVELOPMENT AND DESIGN
OF SERVER ROOMS.
Energy efficiency is crucial in Data Centers that require
the latest cooling technologies to ensure the reliability
and high performance of these critical applications.

Server usage in both upgraded and newly designed Data
Centers will, over time, lead to increasingly higher
performance that eventually will result in higher density
power loads.

The ambient of a Data Center is critical and requires a
guarantee of reliability, device safety and modularity.
Preparing for the evolution of modular infrastructure, with
more standards, classifications and certifications to
comply with.

The key factor that must be continuously improved is the
Energy Efficiency to cope with more demanding OPEX
requirements, and the global footprint, which greatly
affects CAPEX.

Virtualisation, Cloud Computing and Internal Redundancy
also greatly contribute to develop server rooms'
development with many powerful and concentrated
servers creating racks exceeding 40kW in less than one
square meter (or 10 square feet).

Cooling such loads is a serious challenge for the air
conditioning industry and only solid technological
innovations backed by R&D and experienced staff can
provide the right solutions.

The answers lie in the use and combination of the most
sophisticated technologies such as MAGNETIC
LEVITATION and FULL ELECTRONIC MODULATION
cooling equipment.

As a racing car needs an experienced driver, high tech
components require superb design capacities as well
as a deep understanding of the application's
requirements.
Climaveneta has a full range of cooling solutions that
include state of the art, efficient and reliable cooling
technologies for ICT environments.
H
e
a
t

l
o
a
d

p
e
r

e
q
u
i
p
m
e
n
t

f
o
o
t
p
r
i
n
t

-

w
a
t
t
s
/
f
t
2
H
e
a
t

l
o
a
d

p
e
r

e
q
u
i
p
m
e
n
t

f
o
o
t
p
r
i
n
t

-

w
a
t
t
s
/
m
2
10,000
8,000
6,000
4,000
2,000
1,000
800
600
400
200
100
80
60
100,000
80,000
60,000
40,000
20,000
10,000
8,000
6,000
4,000
2,000
1,000
800
1992 1994 1996 1998 2000 2002 2004 2006 2008 2010
Year of Product Announcement
Product Heat Density Trend Chart
Thermal Load Trend by ASHRAE
45
40
35
30
25
20
15
10
5
0
Computer Servers - Blade
Server
1994 1996 1998 2000 2002 2004 2006 2008 2010 2012 2014
Communication
equipment (frames)
Servers & disk
sterage systems
(1.8 - 2.2m tall)
Workstations
(standalone)
Tape storage
systems
Growth of microprocessors performances,
even though compensated by increased
efficiency, lead to the growth of power
generated density. The evidence is such that,
to represent the phenomenon, a logaritmic
scale is necessary.
(Source: Uptime Institute)
Progressive diffusion of incoming
virtualisation and BLADE SERVERS
characterized by increasing power in limited
volumes, leads to the unrelenting growth of
loads which consequently increases
thermal power per m
2
.
4 l 5
BASED ON ACTUAL DATA CENTER HEAT LOAD AND
INSTANTANEOUS WORKING CONDITION
< 5 kW/rack 10 - 20 kW/rack > 25 kW/rack
REDUCE OPERATING COSTS
The growing energy demand in modern Data Centers implies that every
energy
improvement allows for a significant reduction in OPEX (operating costs).
In infrastructures working 24 hours per day, 365 days per year, over an
average of 10 years, this accounts for the largest proportion of overall costs.
BEST USAGE OF AVAILABLE POWER CAPACITY
Many facilities, especially in crowded urban areas, cannot install more
servers because power feeds are at capacity. In these situations to improve
the energy performance of the whole structure, the key option is to grow
the Data Center.
OPTIMIZE AREAS
A green, energy efficient approach to Data Centers has positive implications
also for optimizing space. It allows for the more effective use of the Data
Center, concentrating cooling units along the walls, reducing waste due to
cooling dispersion and delaying the need of building new rooms.
INCREASE SUSTAINABILITY?
Growing digitalization and consequent energy consumption transform Data
Centers into a very critical application regarding TEWI. Intelligent energy
management is crucial not only for profitability but also for sustainability.
CLIMAVENETA CAN HELP YOU TO:
6 l 7
The awareness of the requirements of Data
Centers and the commitment to improve their
energy efficiency has led to the development
of dedicated indexes for these applications.
All Climaveneta solutions are developed
to optimize these metrics, allowing for a
transparent evaluation of the real benefits
offered by our approach to HD.
Power and cooling represent the lion's share
of the energy consumed in a Data Center,
although they are not directly linked with the
value adding operations of the Data Center.

Accurate measurements of heat loads are the
essential base for the design of highly efficient
Green Data Centers.
Power and
cooling
IT Load
50%
45%
40%
35%
30%
25%
20%
15%
10%
5%
0%
8%
6%
32% 30% 18%
5%
1% 1%
Chiller
IT equipment
Power distrib. units
CRAC
Humidification
UPS
Lighting
Switchgear/generator
Data Center cooling & power load consumption
Data Center power consumption by apparatus
1,2
1,7
1,5
2,3
3,1
2,8
1,9
33% 42%
66%
51%
CAPEX
Capital Expenditures
The Data Center is a valuable asset for a company. All expenses
relating to the infrastructure, especially high-tech solutions, remains
within the company by adding value and extending the life span of the
Data Center.
OPEX
Operating Expenditure
Running costs of a Data Center operating 24 hours a day, 365 days
a year for an average of 10 years, are crucial for those who must
manage it. Even a small saving becomes very significant over time.
This justifies even very high initial investments and justifies an
anticipated refurbishment of the systems, aimed to improve their
efficiency.
PUE
Percentage of effectiveness =
total facility power/ IT equipment power
It considers the overall energy efficiency of the Data Center, measured
as the ratio between total absorbed power and the power needed by
the servers. As only energy used to transfer data creates value for the
Data Center, a ratio close to 1 would represent the condition of
optimum efficiency. Most Data Centers have a PUE between 2 and 3,
excellent values are between 1,2 and 1,5.
DCiE = 1/PUE x 100
Reciprocal of PUE, DCiE shows the % of power absorbed by IT
infrastructure, compared to the overall Data Center consumption.
Values close to 33% are usual for traditional Data Centers. DCiE 66%
reflects a very high energy efficiency.
8 l 9
ALL SOLUTIONS ENHANCE THE
ADVANTAGES OF A GREEN DATA CENTER
DESIGN ENSURING:
FLEXIBILITY
Over the years Data Centers are
continuously changing the original
design features, in terms of:
< Shape & architecture
< Computing capacity
< New rack solutions
< Heat dissipation
SCALEABILITY
Data Centers require scalable design
to:
< Manage different heat loads for
different areas
< Allow increasing heat load over time
< Accomodate new areas to be cooled
GREEN DATA CENTERS ?
BEST PRACTICES
Extensive research in this application has developed
some best practices, which are a must for an
efficient Data Center.
Climaveneta solutions are designed to perfectly fit
with this approach.
OPTIMIZED AIR FLOW MANAGEMENT
Optimized air flow design, directing cold air
through the raised floor to form cold aisles in
front of the rack air intake
COLD AND HOT AISLES
Hot & Cold aisles layout address air-flow to
the servers to ensure a constant
temperature. Working conditions become
more stable and the efficiency of the whole
cooling system increases.
LOCALIZED ?COOLING
Dedicated localized cooling to target
hot spots directly, and integrating the
hot & cold aisle.
HIGHEST EFFICIENCY
WITH WATER COOLED SYSTEMS
Optimized hydronic solutions for HPAC
combine energy efficiency with flexible
performance and utmost reliability.
100.00%
99.95%
99.90%
99.85%
99.80%
99.75%
99.70%
99.65%
99.60%
I II III IV
A
v
a
i
l
a
b
i
l
i
t
y
TIER
Number of Delivery Paths
Redundancy
Aisle Containment
Concurrently Maintainable
Fault tolerance to Worst Event
TIER I TIER II TIER III TIER IV
Only 1
N
No
No
None
Only 1
N + 1
No
No
None
1 Active
1 Passive
N + 1
No
Yes
None
2 Active
S + S or
2 (N + 1)
Yes
Yes
Yes
RELIABILITY
PROPER DESIGN
RELIABILITY - TIER Classification
(by Uptime Institute) defines the
acceptable Downtime per Data Center.
< TIER I: 99.671%
(28.8 hours downtime)
< TIER II: 99.741%
(22.7 hours downtime)
< TIER III: 99.982%
(1.58 hours downtime)
< TIER IV: 99.995%
(0.44 hours downtime)
Redundancy is the typical way to increase
the Uptime. In facing the cooling problems
only smart solutions can avoid the disaster
of shut-down while limiting CAPEX and
OPEX. Reliability must look around at 360.
10 l 11
CLIMAVENETA HPAC SOLUTIONS ARE
ADAPTIVE COOLING SYSTEMS DESIGNED
ON ACTUAL DATA CENTER HEAT LOAD
REQUIREMENTS (kW/RACK)
HOT/ COLD AISLE

An easy, fast and long lasting solution;
the hot & cold aisle is the basic and
essential concept that drives the layout
of all Data Centers.
< Through raised floor air can be easily
delivered exactly where required (in
front of the rack) allowing easy
management of redundant cooling
units.
< Flexible, providing maximum freedom in
accommodating new racks distribution
or even major infrastructure changes.

< Lowest CAPEX allows more investment
on more productive equipment
C
O
L
D

A
I
S
L
E
C
O
L
D

A
I
S
L
E
C
O
L
D

A
I
S
L
E
R
A
C
K
R
A
C
K
R
A
C
K
R
A
C
K
AISLE CONTAINMENT
AISLE CONTAINMENT prevents the
HOT & COLD air mixing in the upper
section of the racks, guaranteeing
homogeneous air flow at the suction
of the server.
< No mixing between Hot & Cold air,
so no losses.
< Additional 15% energy saving
depending upon the Data Center
layout
< Easy solution to implement
following HOT&COLD aisles with
relatively low CAPEX
< Complete integration with existing
perimeter CRAC units
< Immediate energy benefits
AISLE CONTAINMENT + LOCAL
COOLING to manage HOT SPOTS
CCD (Climaveneta Cooling Door) & CRC
(Climaveneta Rack Cooler) guarantee ideal
integration to manage HOT SPOTS caused
by new BLADE SERVERS providing extra
local cooling exactly where it is needed.
< Extra cooling only where required
< Direct expansion inverter type or Chilled
water system for complete flexibility of the
cooling system
< Modulating Air flow thanks to EC high
efficiency fans. The fans adapt to the thermal
load detected by sensors positioned in the
hot and cold aisle. This increases efficiency
and reduces air stratification.
< Perfectly compatible with most racks and
ready for extension of the cooling system.
12 l 13
LOW
DENSITY ZONE
< 5 kW/rack
In the last decade the design of Data Centers
has dramatically changed. Years ago Data
Center design was not driven by heat. Loads,
so server distribution in the room was driven
by other needs leading to only one reference
room temperature. This used to be from 18C
to 24C and it was an accepted standard
throughout the world. As soon as server heat
generation increased, it became clear a more
rational distribution of heat was necessary;
this resulted in the Hot & Cold Aisle concept.

The arrangement of rack servers according to
this logic allows delivery of cold air-flow
exactly where it is needed - i.e. typically in
front of the racks, greatly reducing the
chances of cold and hot air mixing. This fact
increases the efficiency of the cooling system
by 20% if compared to traditional layouts.
On the other hand, this new concept requires
two levels of temperatures to be properly
defined.The optimisation of these
temperatures leads to greatly improved
working conditions.
The cold and hot aisle solution overcomes the limits of a
traditional approach where cooling aims to maintain stable
conditions of the room, and forgets to focus on the racks
requirements.
HOT/ COLD AISLE
The Data Center is designed in order to
create hot and cold aisles. Cold air is
delivered through the floor or ducts
exactly where it is needed and hot air
returns to the HPAC units, thus
improving the set point and the overall
Energy Efficiency of the system.
THIS SYSTEM ALLOWS:
< good efficiency,
< easy redundancy,
< easy expansion,
< minimal investment.
C
O
L
D

A
I
S
L
E
C
O
L
D

A
I
S
L
E
C
O
L
D

A
I
S
L
E
R
A
C
K
R
A
C
K
R
A
C
K
R
A
C
K
At the same time, the use of a raised floor has demostrated the
clear advantage of distributing air where needed with negligible
energy consumption. Those who designed very high raised
floors could ensure extended life of their fast changing Data
Center. But such growth includes an increase of racks, data
and power cabling and other ancillary services that almost
completely fill the raised floor void, resulting in unexpected
effects in air distribution. The best way, and sometimes the only
way, to cope with this is to keep constant pressure in the floor
void; this is fundamental to keep the required air distribution.

What appeared to be a complicated problem to solve is now
removed by the new Climaveneta pressure system.
All HPAC units can be connected to several pressure sensors
and the air control system automatically manages airflows in
order to keep steady ambient conditions for the servers.
The feature can be customised as Constant Air Pressure or
Constant Air-Flow.
CONSTANT AIR FLOW AND PRESSURE MANAGEMENT SYSTEMS
14 l 15
THIS SYSTEM ALLOWS:
< significant improvement in
efficiency
< tight control of conditioned
air feeding the servers
< adding more servers in less
volume.
AISLE CONTAINMENT
NO AISLE CONTAINMENT
WITH AISLE CONTAINMENT
This prevents the HOT & COLD air mixing in the
upper section of the racks, guaranteeing
homogeneous air flow at the
air-inlets of the servers.
MEDIUM
DENSITY ZONE
10-20 kW/rack
AISLE CONTAINMENT
In High Density applications the presence of
hot and cold aisles is not enough to prevent
the mix of supply and return air.
This mix results in air flow with a temperature
that reduces the performance of the Data
Center. If such air goes to servers it is warmer
than expected and servers may stop working
due to overheating.
If mixed air goes to the cooling system it is
colder than air coming out from servers,
therefore heat exchange is reduced and then
global efficiency is affected.
Therefore it is necessary to provide a physical
separation for the two airflows.
This is achieved by using aisle containment,
which is a simple and cost effective solution: it
guarantees the servers to be fed with the
design cold air and the cooling system to be
more efficient.
The image above shows an excellent example of the
advantages in terms of hot and cold flows separation
obtained through aisle containment.
TECHNOLOGICAL SOLUTIONS
The decision regarding usage of aisle containment
needs to be analyzed on a project basis as it is affected
by different factors such as: room dimensions, shape,
heat load and density, cooling technology, redundancy
provisions and more.
In practice Climaveneta provides two methods for aisle
containment:
1 Cold Corridor Aisle Containment, which provides
tight control to the cold air feeding the servers.
2 Hot Corridor Aisle Containment, which confines
hot discharge air from servers to a zone.
1
2
CRAC
Roof Panel
Baffle
Floor Brush
Seals
CRAC
Return Air Plenum
Baffle
Floor Brush
Seals
16 l 17
This solution must accomodate the most critical heat
load densities. Here hot-spots cannot be avoided
without aisle containment. Redundancy is a serious
and complicated issue to address and extra cooling
capacity must be added to traditional systems.
THIS SYSTEM ALLOWS TO:
< Maximize the internal capacity of the infrastructure.
< Eliminate hot spots.
< Allow minimum floorspace occupancy.
AISLE CONTAINMENT
+ COOLING DOOR
+ RACK COOLER
HIGH
DENSITY ZONE
> 25 kW/rack
CCD
Climaveneta Cooling Door
< ADDITIONAL COOLING CAPACITY
Thanks to chilled water coil available in both
single & double circuit.
< ZERO FOOTPRINT
< ADAPTABLE TO ALMOST ALL RACKS
< TOP ENERGY EFFICIENCY
With Electronic Controlled Fans modulated to
actual needs
< AIR STRATIFICATION MANAGEMENT
Tight control of the RACKs temperatures
thanks to 8 independent sensors
< FLEXIBLE CONNECTIONS
From top and from the bottom depending on
the customer's choice and on raised floor
availability
< READY TO OPERATE WITH LATEST
GENERATION CHILLERS
including MAGNETIC LEVITATION and
FREE-COOLING techonologies.
32-35C
45-50C
20-25C
CRC
Climaveneta Rack Cooler
<LARGE SAVING DUE TO THE LIMITED AIR
VOLUME TO SCALEABILITY & MODULARITY
<OPTIMAL SOLUTION FOR SINGLE RACK
<100% REDUNDANCY AVAILABLE.
A solution for each system
CRCX: Direct Expansion
<DC INVERTER COMPRESSOR
< NEW GENERATION EC BRUSHLESS FANS
< CAPACITY FROM 4,7 TO 33 kW
CRCC: Chilled Water
<NEW GENERATION EC BRUSHLESS FANS
<3-WAY MODULATING VALVE
<CAPACITY FROM 16 TO 31 kW
CRCD: Dual Fluid
<DC INVERTER COMPRESSOR
<100% BACK-UP
<CAPACITY FROM 4,5 TO 16 kW
CRCF: Free Cooling
<DC INVERTER COMPRESSOR
<NEW-GENERATION EC BRUSHLESS FANS
<CAPACITY FROM 4,6 TO 17,5 kW
<60% OF THE YEAR IN THE FREE COOLING MODE
18 l 19
DATA CENTER
THE MILESTONES OF DATA CENTER COOLING TECHNOLOGY
Unbeatable Efficiency, Silent Operation,
Reliability. Climaveneta can deliver the
Experience of the World's Latest
Technology in Refrigeration: centrifugal
compressors with Magnetic Levitation
of Electric Rotor that reaches 50'000
rpm. ESEER can touch the threshold of
15 kW of cooling capacity per each 1
kW of Electric Power.
Freecooling is a fundamental technology
to reduce energy consumption of data
centers. Available in direct and indirect
versions this solution uses external air
whenever the temperature is lower than
room or water temperature.
The advantage of this cooling is
mirrored by the inverter compressor that
improves efficiency particularly during
lower ambient conditioning.
Both R-410A and R-134a represent the most
advanced choice in refrigerant technology: they
clearly contribute in making the ICT GREEN
since they comply with environmentally friendly
policies and provide enhanced cooling
efficiency.
Smart management of water temperature
allows unprecedented increase of efficiency and
money saving in cooling of Data Centers when
coupled with Free-Cooling or Magnetic
Levitation technologies. Best performances
require decades of expertise to be developed.
MAGNETIC
LEVITATION
FREE
COOLING
ECOLOGICAL
REFRIGERANTS
ADAPTIVE
SET POINT?
1
2
3
1
2
3
4
4
5
6
7
9
10
11
Electronic Expansion Valve allows ultimate
compressors working conditions in order to
achieve the most efficient performances and
to avoid dangerous downtimes.
Modulating the cooling capacity results in a major increase of Energy
Efficiency: EER can rise from typical 2.7 to 5.2 and more! Redundant unit
shall not be a dead investment as it will be on duty at extremely partialised
loads thus granting cooling capacity with greater efficiency. ?i-ACCURATE
represents the ultimate MILESTONE in Data Center cooling, providing a
FULLY ELECTRONICALLY?CONTROLLED HPAC UNIT
ELECTRONIC EXPANSION VALVE?
ELECTRONIC
INVERTER DRIVEN COMPRESSOR
LOW NOISE
ENVIRONMENT ?
& ?ENERGY SAVING
ADDITIONAL FULL
SENSIBLE COOLING
CAPACITY
AISLE CONTAINMENT
FOR HIGHEST EFFICIENCY?
SHORT LOOP
AIR VOLUME,
SCALABLE AND
MODULAR?100%
NEW GENERATION EC FANS
The high efficiency EC fan reduces both noise levels as well as energy consumption,
and assures a variable air flow at part loads. Operational Costs reduce -15% if
compared to traditional EC-Fans, -25% if compared to plug fans.
EC FANS ALSO IN THE REMOTE CONDENSERS
The use of EC technology even on the remote condenser fan assures a further average
reduction of noise levels by 10%, together with a strong reduction of energy
consumption by 45% when compared with traditional condensers with AC technology.
ELECTRONIC
CONTROLLED FANS
5 6 7
8
8
9
10
11
20 l 21
REMOTE CONDENSERS
Remote condenser
with axial fans
BRE 7 - 187 kW i-BRE 13,4-187 kW
from 26,6 to 39 kW
Suitable for 600mm
wide racks.
CLIMAVENETA HPAC SOLUTIONS COMPRISE
OF A WIDE RANGE OF UNITS FROM 4,3 TO
225 kW, ALL INTEGRATING CUTTING EDGE
TECHNOLOGIES TO ACHIEVE COMPLETE
RELIABILITY AND HIGH EFFICIENCY
CCD COOLING DOOR CRC RACK COOLER
Side Cooling from 4,7 to 33 kW
CRCX:
Direct expansion version
CRCC:
Chilled water type
CRCD:
Dual Fluid version
CRCF:
Free cooling version
EC AXIAL
r HFC
R-410A
EC AXIAL AXIAL CENTRIFUGAL
r HFC
R-410A
BREC M1D-M4F_B 16,1-108 kW
Remote condenser with
centrifugal fans
INVERTER DRIVEN DIRECT EXPANSION
ACCURATE Full range Upflow - Downflow unit with R410A & inverter
driven scroll compressor from 4,3 to 159 kW, air/water cooled.
ACCURATE range unit with R410A scroll compressor
from 4,9 to 102 kW, air/water cooled.
ACCURATE CLOSE CONTROL AIR-CONDITIONERS
CHILLED WATER DIRECT EXPANSION - ON/OFF
r HFC
R-410A
SCROLL
COOLING RE-HEATING DEHUMIDIFICATION
COOLING RE-HEATING DEHUMIDIFICATION COOLING RE-HEATING DEHUMIDIFICATION
COOLING RE-HEATING DEHUMIDIFICATION
COOLING RE-HEATING DEHUMIDIFICATION
i-AX 4,3-151,8 kW
Air cooled
i-AW 4,7-159 kW
Water cooled
i-AD 6,7-124,4 kW
Dual Fluid, air cooled
i-AT 7,4-130,2 kW
Dual Fluid, water cooled
i-AF 7,4-130,2 kW
Free Cooling
COOLING
AC 4,6-225 kW
Chilled Water
AB 22,5-148 kW
Chilled Water
Double Circuit
COOLING
RE-HEATING DEHUMIDIFICATION
COOLING RE-HEATING DEHUMIDIFICATION
COOLING RE-HEATING DEHUMIDIFICATION
COOLING RE-HEATING DEHUMIDIFICATION
RE-HEATING DEHUMIDIFICATION
COOLING RE-HEATING DEHUMIDIFICATION
RE-HEATING DEHUMIDIFICATION
AX 4,9-95,4 kW
Air cooled
AW 5,2-99,3 kW
Water cooled
AD 23,7-98,8 kW
Dual fluid air cooled
AT 24,9-101,9 kW
Dual fluid water cooled
AF 24,9-101,9 kW
Free Cooling
Dry Cooler with
axial-type fan(s).
BDC 8-210 kW i-BDC 14-210 kW
DRY COOLER CLIMAVENETA INFRASTRUCTURES
High quality
cabinets for
protecting and
housing servers
Aisle Containment solution for
high density applications
CV RACK CV AISLE CONTAINMENT
EC AXIAL AXIAL
r HFC
R-410A
SCROLL
22 l 23
MANAGEMENT AND CONTROL SYSTEMS
A full range of controllers,
supervision and metering devices
complete the Climaveneta High
Density Data Center Cooling
solutions. They allow for enhanced
efficiency, synergies among all the
components and the reliability of
the system.
NECS-FC
Free-Cooling
chillers with scroll
compressors,
optimised for
Data Center
application.
SCROLL
NECS-FC
Acoustic versions
B base version
SL super-low noise version
40 400
0 100 200 300 400 500 600 700 800 kW 900 1000 1100 1200 1300
r
HFC
R-410A
FX-FC
Free cooling chiller
with screw
compressors:
robust, reliable and
highly energy
efficient.
r
HFC
R-134a
SCREW
0 100 kW
FX-FC
Acoustic versions
T Free cooling version
SL-T Super low noise version
with free cooling
200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400
332 1450
Control Devices
DATA CENTER
MANAGER
Group and
regulation device
Monitoring devices
FWS3000
Measurement &
Verification devices
DEMETRA
Dedicated monitoring
software for complex
cooling plants including
multiple redundancies.
0 100 200 300 400 500 600 700 800 kW 900 1000 1100 1200 1300
230 1200
TECS VISION 2.0
Air and water cooled chiller with
magnetic levitation compressors.
The World's Most Advanced
Technology in the refrigeration
industry.
Acoustic versions
SL-CA Super Low noise version,
Class A of efficiency
XL-CA Extra Low noise version,
Class A of efficiency
SL-CA-E Super Low noise version,
very high efficiency,
Class A enhanced
CENTRIFUGAL
Essential for
True PUE Metering
24 l 25
Sir Francis Bacon British Philosopher (1561 - 1626)
TMC - TRANSPORT MANAGEMENT CENTRE
South Africa - Cape Town
Installed Machines: 5 AD 070 Close Control Units,
1 AD 030 Close Control Units
BOUYGUES TELECOM
France - Bobigny
Data center
Total cooling capacity: 433,9 kW
Installed appliances: 2x i-AX Close
Control Units, 15x i-AX Close Control Units
ALCATEL
Italy - Bergamo
Data center
Total cooling capacity: 3570 kW
Installed appliances: 39x AC, 7x AX Close Control
Units
PARTIKELTHERAPIEZENTRUM
Germany - Kiel
Healthcare & Hospitals
Total cooling capacity: 900 kW
Installed appliances: Several HPAC units,
ACCURATE range
ALPHA BANK
Romania - Bucharest
Financial Institutions
Total cooling capacity: 548 kW
Installed Appliances: 4 AT 60 Close Control
Units, 4 AT 77 Close Control Units
NUOVO PIGNONE
Italy - Florence
Data center
Total cooling capacity: 400 kW
Installed appliances: 5x i-AX , 4x CRCX-I, 4x i-HCAT
CLIMAVENETA SOLUTIONS FOR DATA
CENTER COOLING, WITH THEIR
UNBEATABLE ADVANTAGES IN TERMS
OF EFFICIENCY, QUALITY AND
RELIABILITY, ARE ALREADY THE
PREFERRED CHOICE IN THE MOST
CHALLENGING AND PRESTIGIOUS
PROJECTS, ALL AROUND THE WORLD
AND WITH ALL THE MAJOR BRANDS.
LG CHEMICALS
South Korea - Seul
Chemical & pharmaceutical
Total cooling capacity: 120 kW
Installed appliances: 2x AX 60 Close Control Units
ENI
Congo - Pointe Noire
Office building
Total cooling capacity: 284 kW
Installed appliances: 4x AXU, 9x ACO,
Fan Coil Units, Air Handling Units
BRE BANK
Poland - Warsaw
Bank Offices
Installed appliances: 6x AX Close Control
Units, 1x BRE, 1x BRE, 1x BRE, 1x BRE,
2x HCAT
SHELTER TIM
Italy
Telecommunications
Total cooling capacity: 1125 kW
Installed Appliances: Several HPAC units,
ACCURATE range
Total cooling capacity: 1200 kW
Installed Appliances: 2 air cooled
chiller with EC-fans
VODAFONE CED
Italy - Padua
Data center
Total cooling capacity: 968 kW
Installed appliances: 2x NX, 6x AC Close
Control Units
26 l 27
9 PRODUCTION SITES ORGANIZED ACCORDING TO LEAN MANUFACTURING PRICIPLES
WITH 40 YEARS
LEADING EXPERIENCE
CLIMAVENETA IS A
MAJOR WORLD PLAYER
IN THE AIR
CONDITIONING, HEATING
AND PROCESS COOLING
INDUSTRY.
Based on 9 manufacturing facilities and present in over 100
countries around the world, Climaveneta has developed a full
range of high efficiency solutions for any kind of building and
cooling requirement.
Its systems are the preferred choice of the most demanding
customers for the most challenging projects all around the world.
These achievements are the result of an unbeatable know-how
and a strong focus on R&D, proven also by its many patents in
many different technologies and applications. With this
background Climaveneta has anticipated the high-technology
challenges for cooling of Data Centers, developing a complete
range of high efficiency leading edge solutions that has already set
a new technology milestone in this field.
Headquarters
Operational area:
12.500m
2
Production of:
< Chillers: air and water cooled, from 30
to 700kW
< Reversible units: air and water cooled,
up to 400kW
< Multipurpose up to 400KW
< Chillers with free-cooling up to 300kW
Operational area:
25.000 m
2
Production of:
< Chillers: air and water cooled, from 200
to 1700kW
< Heat pumps: air and water cooled, up to
2400KW
< Multipurpose units: up to 700KW
< Chillers with free-cooling up to 1250kW
< Shell & tube evaporators
< Roof-top units up to 500kW
Climaveneta Training centre
Operational area:
7.000 m
2
Production of:
< Air handling units
Operational area:
20.000m
2
Production of:
< Split and multisplit systems
< Chillers and heat pumps up to 150kW
< Hydronic fan coils from 1 to 30kW
< Close control units
< Telecommunications units
Climaveneta 1
Bassano del Grappa-Italy
Climaveneta 2
Belluno-Italy
Climaveneta 3
Belluno-Italy
Climaveneta 4
Treviso-Italy
Head offices and foreign branches
- Climaveneta SpA in Italy
- Climaveneta France
- Climaveneta UK
- Climaveneta Deutschland
- Climaveneta Espaa
- Climaveneta Poland
- Climaveneta Chat Union
Refrig. Equipment Co Ltd in China
- Climaveneta India
Climate Technologies (P) LTD
- Climaveneta UK LTD
Distributors
Over 55 distributors in more than 100 countries of the
world for a truly complete market coverage.
Service
Service is assured in all countries through the
assistance networks of our subsidiaries and distributors
with highest expertise, a wide range of after sales
service contracts for a truly complete support.
1EUROPEAN AND
5WORLD MANUFACTURER,
2 TO 2.400 KW
COOLING POWER RANGE
17 TEST LABORATORIES
OVER 70 PEOPLE IN R&D
40 YEARS EXPERIENCE
90.000 M
2
PRODUCTIVE AREA
1971 ESTABLISHED IN
BASSANO DEL GRAPPA (ITALY)
SINCE 2012 A DEL CLIMA COMPANY
245 MILLION TURNOVER 2013
SOMETIMES NUMBERS SAY MORE THAN A THOUSAND WORDS
Operational area:
2.500 m
2
Production of:
< Direct expansion units
< Compact units
< Rooftop units for small and
medium applications
Operational area:
15.000 m
2
Production of:
< Air cooled chillers & heat pumps
from 40 to 1700kW
< Water cooled chillers & heat
pumps from 10 to 3070kW
Operational area:
4.500 m
2
Production of:
< HPAC units for the Eastern
market
< Evaporators
< Condensers
Operational area:
8.500 m
2
Production of:
< AHU units
< Fan coils
Operational area:
2.500 m
2
Production of:
< HPAC units
CV Parets De Valles
Barcelona-Spain
CV Chat Union
Shanghai-China
CV Refrigeration
Shanghai-China
Climaveneta 8
Shanghai-China
Climaveneta 9
Bangalore-India
C
V
-
D
A
T
A

C
E
N
T
E
R
_
0
2
-
2
0
1
4
_
e
n
g
_
0
0