Water in Transformers

TVPPA E&O CONFERENCE AUGUST 79, 2013


SPX TRANSFORMER SOLUTIONS, INC.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Rich Simonelli
Territory General Manager Southeast
SPX Transformer Solutions, Inc.
Office 919-300-1522
Email Rich.Simonelli@spx.com


Water in Transformers
Rich joined SPX in January 2005, bringing with him
over 20 years of experience in the power systems
industry. As the national service manager, Rich was
responsible for leading the Waukesha

Service group
in providing and implementing creative field service
solutions on electrical equipment used in power
generation, transmission and distribution, mass transit
and industrial processes, while maintaining customer
satisfaction, quality, environmental and safety systems
and processes. In 2011, Rich was promoted to
Territory General Manager where he has complete
commercial responsibility for all products and services,
business development, sales strategies and customer
relationships in the southeast region.
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Agenda


Effects of water in
transformers
How does water get in?
How to estimate water
content in transformers
What can you do about it?


3
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Effects of Water in Transformers
4
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Water in Transformers is Bad
5
Cellulose is highly hygroscopic.
Influence of the temperature over water absorption of 3 mm
high-density pressboard at 50% relative humidity
Source: Water Absorption of Cellulosic Insulating Materials used in Power Transformers
HP. Gasser, Ch. Krause and T. Prevost, Weidmann Transformer Board Systems
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Water in Transformers is Bad (cont.)
6
Moisture lowers the dielectric strength of oil.
Source: ABB IL 48-500-11, 2002
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Water in Transformers is Bad (cont.)
7
Moisture lowers the dielectric strength of solid insulation.
Source: Tom Prevost, EHV Weidmann, 2006
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Water in Transformers is Bad (cont.)
8
Moisture raises the dielectric power factor and increases
the risk of thermal breakdown of solid insulation.
Source: Tom Prevost, EHV Weidmann, 2006
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Water in Transformers is Bad (cont.)
9
Moisture lowers the lowest hot-spot temperature range for
possible bubble formation.
Source: TV Oommen, EPRI Reports:
EL-6761, March 1990; EL-7291, March 1992
50
70
90
110
130
150
170
190
0 2 4 6 8 10
WCP % w/w
T
e
m
p
e
r
a
t
u
r
e
Kobayashi rapid heating
Kobayashi slow heating
Davydov
Oommen gas free
Oommen gas saturated
Comparison of critical bubble temperature vs.
water content in paper by three researchers
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013

10
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Water in Transformers is Bad (cont.)
11
Moisture accelerates thermal aging of paper insulation.
1
2
3
4
5
6
7
8
9
10
0.5 1.5 2.5 3.5 4.5 5.5
Moisture in Paper (%)

A
g
i
n
g

A
c
c
e
l
e
r
a
t
i
o
n

F
a
c
t
o
r


IEEE Std C57.91-1995 Source: Sam Mehta, Tom Golner, SPX Transformer
Solutions, 2000 TJH2B presentation
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Water in Transformers is Bad (cont.)
12
Moisture can be the root cause of a catastrophic failure.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
How Does Water Get In?
13
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Many Ways for Water to Enter Transformers
14
Inadequate dry-out at factory
Leaks gaskets and welds
Breathing in outside air during
oil temperature changes
Defective oil preservation
system

SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Water is Also Produced as a By-Product
15
Even if a transformer
is leak-free and the
oil preservation
system is performing
flawlessly, water is
PRODUCED as
a BY-PRODUCT of
the normal cellulose
aging process!

Degradation of Cellulose
O
H
O
H
O
H
OH
OH
O
H
H
CH
2
O
CH
2
OH
H
O
H
H
O
OH
H
Heating
Heating
C O
O C O
O
H H
Carbon Monoxide Carbon Dioxide
Water
Section of
Cellulose
Molecule
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Once Inside, Where Does It Go?
16
Once water is inside, the molecules are stored in various
parts of the insulation:
Oil
90%
Thick
5%
Thin
2%
Winding
3%
Insulation Weight Distribution
Thick
55%
Thin
22%
Winding
22%
Oil
1%
Water Distribution
Source: J. Aubin, 2005 Weidmann-ACTI Conference, San Antonio, TX
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
How Do We Measure / Estimate Water Content
in Transformers?
17
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Different methods can be used to assess water content
in transformers:
Karl Fischer Titration of Insulation Sample
Moisture Equilibrium Curves
Dew point
Vapor Pressure Curve
Recovery Voltage Method
Dielectric Frequency Response
Power Factor
Cold Trap
IEEE C57.106 Limits
Variety of Assessment Methods Available
18
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Moisture Equilibrium Curves
19

T
e
m
p
e
r
a
t
u
r
e

(

C

)

Moisture in Oil (ppm)
M
o
i
s
t
u
r
e

i
n

P
a
p
e
r


(

%
)

Source: Oommen 1983/2003
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Moisture Equilibrium Curves (cont.)
Source: IEEE C57.106-2008
20
Challenges with Moisture Equilibrium Curves
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Dew Point
21
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Challenges with dew point to moisture content conversion:
At best, calculation is only an average surface moisture
content measurement
Difficult to achieve equilibrium due to temperature changes;
conversion is temperature and pressure sensitive
Difficult to measure/estimate insulation temperature
Moisture distribution is not uniform in insulation
Transformer must be without oil to get measurement
Despite these issues, dew point to moisture content
conversion is widely used as an acceptance test because
calculations are done without having to open the transformer.

Dew Point (cont.)
22
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Vapor Pressure Rise/
Vacuum Drop Loss Method

Vapor Pressure Curve
Developed to monitor progress during
vacuum dry out operations.
Equilibrium vapor pressure from the absolute
pressure in the transformer tank can be obtained
during the time condensed moisture is being
removed from the vapor trap. The transformer is
isolated from the vacuum pump and vapor trap.
A pressure rise (vacuum loss) test is then
conducted:
1. Leak rate of the transformer tank.
2. Outgassing rate for insulation and solid
components inside transformer (from change
in slope of pressure rise curve).
3. Pressure rise during the first minute after the
isolation valve is shut (rate of moisture
evaporation).
4. Intercept of the pressure rise curve with zero
time axis (equilibrium vapor pressure).
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Vapor Pressure Curve (cont.)
Challenges with Vapor Pressure Rise / Vacuum Drop Loss
Problems/Factors directly
effect equilibrium of the vapor
pressure measurement:
Atmospheric air leaking into
transformer tank
Dissolved gas (air) released
from residual oil on the tank
bottom and/or oil-
impregnated insulation,
causing a rise in absolute
pressure (outgassing)
Moisture evaporating out of
the insulation
Application and calibration
errors in pressure and temp
measuring sensors
Temperature variations
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Recovery Voltage Method (RVM)
Testing the dielectric properties of the
oilpaper insulation.
DC voltage (usually 2000V) is applied
across the insulation for a period of time
(charge time)
This DC voltage causes polarization of
the molecules in the insulation material
Test piece is then discharged via short
circuit for a period equal to half the
charge time
Polarized insulation material then tries to
revert to the original state which gives
a characteristic response, known as the
recovery voltage
Recovery voltage is measured and key
points are notedvoltage, time and slope
Specimen is then discharged, ready for the next test cycle

RVM / DFR Tests
25
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Recovery Voltage Method (cont.)
Tests are repeated for charge times
ranging from 20 ms up to
10,000 seconds
These points can then be plotted on
a series of graphs with varying
charge times
The most important of these graphs
is called the polarization spectrum,
which is obtained by plotting peak
recovery voltage vs. charge time
The time at which this peak occurs is known as a dominant time
constant and is dependent on properties of the insulating materials
This value directly reflects the moisture content of the oil-paper
insulation system


RVM / DFR Tests (cont.)
26
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Dielectric Frequency Response test
Used to assess the integrity of a transformers
insulation system. The test attempts to determine the
volume of moisture and presence of contaminants in the
solid insulation as well as the conductivity and power
factor of the oil
With the support of Omicron, DFR test have gained popularity
in recent years as a diagnostic tool for transformer insulation
system testing. The DIRANA uses a combination of the time
and frequency range method (Polarization Depolarization
Current [PDC] and Frequency Domain Spectroscopy [FDS]).


RVM / DFR Tests (cont.)
27
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Challenges with RVM and DFR:
Difficult to achieve equilibrium due to temperature changes
Difficult to get accurate insulation temperature
Oil permittivity and conductivity change with aging of
insulation system
Moisture distribution is not uniform in insulation
Construction details are not always available
Transformer must be de-energized for a long time before
reaching equilibrium, making for a long test time duration

RVM / DFR Tests (cont.)
28
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Power Factor has been used for many decades to assess the
drying process of transformers using a low voltage test or by the
use of probes and models to assess the condition of the solid
insulation.
Pros and Cons
Can be used for acceptance testing and at completion
of field drying after oil filling to ensure a dry unit
Can be used to detect pockets of water that may be deeply
imbedded and missed by other methods that
rely on equilibrium conditions to be accurate
No direct correlation between power factor and
moisture content
Transformer Power Factor
29
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
The Cold Trap method involves measuring the amount of water
collected in a trap over a four to six hour period and then calculating
the amount of water collected per hour. If the amount of insulation
and its initial moisture content are known, the
amount of water removed can provide
a sense of the insulation dryness.
Pros and Cons
Collecting the water in a trap prevents
it from collecting in the vacuum pump
Sometimes initial dryness and mass of insulation is difficult
to ascertain
Must have a cold trap available that efficiently catches the
majority of the water so it can be measured
Cold Trap Method
30
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013



Classification of Service Aged Oils
Test Standard Unit Voltage Group 1 Group 2 Group 3 Group 4
< 69 kV 23 <23 - -
69 - 288 kV 28 <28 - -
> 345 kV 30 <30 - -
< 69 kV 0.2 - >0.2 >0.5
69 - 288 kV 0.15 - >0.15 >0.5
> 345 kV 0.1 - >0.10 >0.5
< 69 kV 25 - <25 <18
69 - 288 kV 30 - <30 <18
> 345 kV 32 - <32 <18
< 69 kV 35 >35 - -
69 - 288 kV 20 >20 - -
> 345 kV 12 >12 - -
< 69 kV 0.5 - >0.5 >1.0
69 - 288 kV 0.5 - >0.5 >1.0
> 345 kV 0.5 - >0.5 >1.0
Dielectric
Breakdown
ASTM-D1816
w/ 1mm gap
min, kV
Neutralization
Number
ASTM-D974
max, mg
KOH/g
Power Factor ASTM-D921 max, %
Interfacial
Tension
ASTM-D971
min,
Dynes/cm
Moisture
Content
ASTM-D1533
max, PPM
@60C Avg.
Oil Temp.
31
Source: IEEE C57.106-2006
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013 32
Current measurement practices assume a state of equilibrium.
Why is Moisture Content So Difficult to Measure?
Varying Temperatures:
Top oil temp
Bottom oil temp
Winding temp

Does Equilibrium
Ever Occur?
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013 33
Does Equilibrium Ever Occur? (cont.)
Source : Transformer Moisture Content/Cold Weather Dew Point Measurement,
Doble Client Conference 2009; Rich Simonelli, SPX / Phil Prout, NGRID / Lance
Lewand, Doble / Brian Anderson, CSU
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013 34
Does Equilibrium Ever Occur?
Factors Directly Affecting Equilibrium
Equilibrium, by definition, is a state of balance between opposing forces or
actions that is either static (as in a body acted on by forces whose resultant is
zero) or dynamic (as in a reversible chemical reaction when the rates of reaction
in both directions are equal).

Where continuously varying conditions exist (internal and external), the
equilibrium curves cannot be applied directly.

In a Transformer:
Temperature stratification/unstable thermal environment
Non-uniform moisture distribution in the insulation
Only an average surface moisture content measurement
achievable with any method (best case scenario)
Varying thicknesses of insulation structures directly affecting
the rates of diffusion and adsorption
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013 35
Does Equilibrium Ever Occur? (cont.)
Factors Directly Affecting Equilibrium in a Transformer (cont.)

Under Ideal Conditions:
Vapor Diffusion is already impeded because water
molecules are physically deterred from moving rapidly by
the labyrinth of micro capillaries
De-sorption of water molecules from the surface of active
sites on the cellulose surface occurs more slowly
because energy is required to break the bond
The film of oil coating the surfaces of the insulation adds
another diffusion process
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
What Can Be Done About Water in
Transformers?
36
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Select the most suitable measurement method that
allows you to minimize error-producing variables,
continue using the same method over a long period of
time and monitor changes
Support industry-wide R&D initiatives to develop ways
to measure moisture content of working transformers
accurately and reliably
What Should You Do About the Moisture?
37
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
For a new unit:
Specify maximum
allowable moisture
content at delivery
and determination
method
Specify proper oil
preservation system
Specify raised
flange for
all openings
Specify gasket material and suitable seal design
Consider specifying optional accessories that help maintain integrity
of the unit


What Can Be Done to Limit Water Ingress?
38
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
What Can Be Done to Limit Water Ingress? (cont.)
39
For an existing unit:
Maintain the integrity of the unit keep it sealed
Standardize on methods to monitor moisture content monitor,
observe, record
Implement loading policy to minimize
the aging process
Consider adding accessories that
help maintain integrity of the unit
Corrective Actions:
If it tests wet for your application,
dry it out
Off-line field drying: Fast, but costly
On-line field drying: Slow, but economical
Natural ester retrofill


SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Vapor Pressure
At atmospheric
pressure, you must
heat water in a
transformer to higher
than 212F (100C)
for water to boil off
When lowering the
pressure by pulling
vacuum, we can boil
water off without
heating (as long as
the temperature is
above freezing)
Transformer Drying Theory
40
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Why Add Heat?
Heat required for a phase change
comes from the surrounding
oil and transformer parts
As heat moves from the
insulation into the water, the
temperature of the insulation
and transformer drops
Therefore, replacement heat is
added by continuously reheating
the oil and pumping it into the
transformer
If the heat is not replaced,
freezing can eventually occur
Transformer Drying Theory (cont.)

41
VIDEO
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Off-Line Field Dry Out Methods
Multiple methods exist for field drying a transformer if the
moisture content is found to be above acceptable limits:
Vacuum
Vacuum with hot air
Short circuit and vacuum
High vacuum with hot oil
42
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Off-Line Field Dry Out Methods (cont.)
Vacuum
Good method for
removing small amounts
of residual moisture
Transformer is subjected
to high vacuum and held
for a period of time
Efficiency of method is
increased at higher temperatures
Cold traps can be used in vacuum line to measure
moisture extraction

43
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Off-Line Field Dry Out Methods (cont.)
44
High vacuum and hot oil
Evacuate tank
Introduce oil to heat core/coil
assembly
If capable, limit oil volume to
10% of total or enough to
establish oil circulation
Otherwise, cover core/coil
assembly
Circulate oil under vacuum until
outlet oil temperature reaches
desired temperature
Drain oil from transformer
Continue to pull vacuum and monitor moisture through cold trap,
if desired

SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
On-Line Field Dry Out Methods
45
Dry out process is slow
due to the diffusion rate of
water from cellulose to oil
Moisture content of oil
will decrease quickly
Higher operating
temperatures make
process more effective
Safety concerns should
be considered



SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Natural Ester Fluid Retrofill
46
Water Absorption of Dielectric Fluids
Exposed to Ambient Air (1 of 2)
Exposure Time (hrs)
0 500 1000 1500 2000 2500 3000 3500
A
b
s
o
l
u
t
e

W
a
t
e
r

C
o
n
t
e
n
t

(
p
p
m
)
0
100
200
300
400
500
600
conventional transformer oil
Envirotemp FR3 fluid
Source: Cooper Power Systems (prior to FR3 product line purchase by Cargill)
Natural ester fluid holds
more water in solution,
enhancing moisture
migration into the fluid
Hydrolysis converts
moisture and natural
ester fluid into long
chain free fatty acids
Trans-esterification
combines some of these
fatty acids with the OH group
in cellulose, strengthening the cellulose chain and making it
less likely to break

SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Natural Ester Fluid Retrofill (cont.)
47
Temperature (
o
C)
20 40 60 80 100 120
W
a
t
e
r

S
a
t
u
r
a
t
i
o
n

P
o
i
n
t

(
m
g
/
k
g
)
0
1000
2000
3000
4000
5000
Envirotemp FR3 fluid: A = 5.3318, B = 684
from Doble Engineering
mineral oil: A = 7.0895, B = 1567
from IEEE C57.106
|
.
|

\
|
+

=
T
B
A
T Saturation
273
10 ) (

Water Saturation
Dielectric Strength
Water Content (mg/kg)
0 100 200 300 400 500 600 700
D
1
8
1
6

D
i
e
l
e
c
t
r
i
c

B
r
e
a
k
d
o
w
n

S
t
r
e
n
g
t
h

(
k
V
)
0
10
20
30
40
50
60
70
80
FR3 Fluid
Mineral Oil
Source: Cooper Power Systems (prior to FR3 product line purchase by Cargill)
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Natural Ester Fluid Retrofill (cont.)
Source: Steve Moore, Transformer Insulation Dry Out By Retrofilling With Natural Ester
Dielectric Coolant, IEEE 2012
48
Aged Paper at 3% Water Content
(aged at 85
o
C)
Aging Time at 85
o
C (hrs)
0 500 1000 1500 2000
%

W
a
t
e
r

i
n

P
a
p
e
r
0
1
2
3
4
5
D
i
s
s
o
l
v
e
d

W
a
t
e
r

i
n

F
l
u
i
d

(
p
p
m
)
0
200
400
600
800
Paper in FR3 Fluid
Water in FR3 Fluid
Water in Mineral Oil
Paper in Mineral Oil
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Natural Ester Fluid Retrofill (cont.)
Source: Steve Moore, Transformer Insulation Dry Out By Retrofilling With Natural Ester
Dielectric Coolant, IEEE 2012
49
Time at 85
o
C (hr)
0 500 1000 1500 2000 2500 3000
W
a
t
e
r

i
n

P
a
p
e
r

(
w
t
%
)
0
2
4
6
W
a
t
e
r

i
n

F
l
u
i
d

(
m
g
/
k
g
)
0
200
400
600
A
c
i
d

N
u
m
b
e
r

(
m
g

K
O
H
/
g
)
0
1
2
3
4
5
6
7
Envirotemp FR3 fluid - water content
water in paper
Envirotemp FR3 fluid - acid number
SPX Transformer Solutions, Inc.
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Natural Ester Fluid Retrofill (cont.)
Sealed Tube Test - ML 152-2000
Upgraded Paper 2000 hr @ 170C
Sealed Tube Test - ML 152-2000
Upgraded Paper 4000 hr @ 170C
Sealed Tube Test - ML 152-2000
Upgraded Paper 500 hr @ 170C
Sealed Tube Test - ML 152-2000
Upgraded Paper 1000 hr @ 170C
Natural Ester Mineral Oil Natural Ester Mineral Oil Natural Ester Mineral Oil Natural Ester Mineral Oil
Source: Cooper Power Systems (prior to FR3 product line purchase by Cargill)
50
Life Extension Potential with Natural Ester Fluids
TRANSFORMERS | SERVICE | TRAINING | COMPONENTS
Water in Transformers August 2013
Questions?