Sound Power by Octave Band

Sound
Data
62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones
Inlet 87 92 86 79 78 75 69 67 84 73 24
Radiated 90 93 82 73 70 60 51 51 80 69 19.2
BLOWER
HOUSING
Inlet
Inline
Discharge
ELEVATION VIEW
Inlet
END VIEW
Inlet
Inline
Discharge
PLAN VIEW
1.5
41.875
1.5
38 46
46
18
Model: BSQ-300-50
Belt Drive Centrifugal Inline Fan
Dimensional
Quantity 1
Weight w/o Acc's (lb) 523
Weight w/ Acc's (lb) 527
Max T Motor Frame Size 215
Performance
Requested Volume (CFM) 12,000
Actual Volume (CFM) 12,000
External SP (in. wg) 0.5
Total SP (in. wg) 0.5
Fan RPM 736
Operating Power (hp) 3.37
Elevation (ft) 1,129
Airstream Temp.(F) 70
Air Density (ft3) 0.072
Drive Loss (%) 4.2
Tip Speed (ft/min) 5,878
Static Eff. (%) 29
Motor
Motor Mounted Yes
Size (hp) 5
V/C/P 460/60/3
Enclosure ODP
Motor RPM 1725
Windings 1
NEC FLA* (Amps) 7.6
Notes:
All dimensions shown are in units of in..
*FLA - based on tables 150 or 148 of National Electrical
Code 2002. Actual motor FLA may vary, for sizing thermal
overload, consult factory.
LwA - A weighted sound power level, based on ANSI S1.4
dBA - A weighted sound pressure level, based on 11.5 dB
attenuation per Octave band at 5 ft - dBA levels are not
licensed by AMCA International
Sones - calculated using AMCA 301 at 5 ft
02/07/2014 Printed Date:
CHROMA OFICINAS Job:
CHROMA PLAZA - CENTRIFUGOS Mark:
CAPS 4.14.1334 C:\Users\Ingenieria4\Documents\PRY_ERN\CHROMA\REDISEO EN SOTANOS\CHROMA- STANOS - NUEVO DISEO\CHROMA.gfcj Page 1 of 6
Model: BSQ-300-50
Belt Drive Centrifugal Inline Fan
Standard Construction Features:
- Galvanized steel housing - Backward inclined aluminum wheel - Two bolted
access panels - Integral duct connection flanges - Ball bearing motors -
Adjustable motor pulley - Adjustable motor plate - Fan shaft mounted in ball
bearing pillow blocks - Static free belts - Corrosion resistant fasteners
Options & Accessories:
NEMA Premium Efficient Motor - meets NEMA Table 12-12
Switch, NEMA-1, Toggle, J unction Box Mounted & Wired
Bearings with Grease Fittings, L10 life of 100,000 hrs (L50 avg. life 500,000 hrs)
Unit Warranty: 1 Yr (Standard)
02/07/2014 Printed Date:
CHROMA OFICINAS Job:
CHROMA PLAZA - CENTRIFUGOS Mark:
CAPS 4.14.1334 C:\Users\Ingenieria4\Documents\PRY_ERN\CHROMA\REDISEO EN SOTANOS\CHROMA- STANOS - NUEVO DISEO\CHROMA.gfcj Page 2 of 6
Disconnect Switch
Enclosure Rating: NEMA-1
Standard Construction Features:
Enclosure constructed for indoor use to provide a degree of protection to personnel against incidental contact with the enclosed
equipment and to provide a degree of protection against falling dust. This enclosure meets the rod entry and the indoor
corrosion protection design tests. The rod entry test is intended to simulate incidental contact with enclosure equipment.
Enclosure is equipped with provision to lockout in the off position with customer supplied lock.
Notes: All dimensions shown are in units of in.
OFF
Electrical Drawing Details
Wiring
Schematic
2.75
2.88
3.00
0.56
2.44
0.41
1.63
4.25
Disconnect Switch Configuration
Type: Toggle Motor Size: 5 hp Voltage: 460 UL Listed: Yes
Manufacturer: Square D Cycle: 60 Amperage: 30 CSA Approved: Yes
Overload Protection: None Phase: 3 Switch Pole(s): 3 Rating: 10 hp
Mounting: Mounted and Wired RPM: 1725 Wiring (Exp. Resist.): None
02/07/2014 Printed Date:
CHROMA OFICINAS Job:
CHROMA PLAZA - CENTRIFUGOS Mark:
CAPS 4.14.1334 C:\Users\Ingenieria4\Documents\PRY_ERN\CHROMA\REDISEO EN SOTANOS\CHROMA- STANOS - NUEVO DISEO\CHROMA.gfcj Page 3 of 6
Assembly Drawing
Type: Belt Drive Centrifugal Inline Fan
BLOWER
HOUSING
Inlet
Inline
Discharge
ELEVATION VIEW
Inlet
END VIEW
Inlet
Inline
Discharge
PLAN VIEW
1.5
41.9
SQ.
1.5
38.0 46.0
46.0
18.0
Max
64.0
Notes: All dimensions shown are in units of in..
02/07/2014 Printed Date:
CHROMA OFICINAS Job:
CHROMA PLAZA - CENTRIFUGOS Mark:
CAPS 4.14.1334 C:\Users\Ingenieria4\Documents\PRY_ERN\CHROMA\REDISEO EN SOTANOS\CHROMA- STANOS - NUEVO DISEO\CHROMA.gfcj Page 4 of 6
BSQ-300-50 Min/Max Fan Curve
Performance
Requested
Volume
(CFM)
Actual
Volume
(CFM)
External
SP
(in. wg)
Total
SP
(in. wg)
Fan
RPM
Operating
Power
(hp)
12,000 12,000 0.5 0.5 736 3.37
02/07/2014 Printed Date:
CHROMA OFICINAS Job:
CHROMA PLAZA - CENTRIFUGOS Mark:
CAPS 4.14.1334 C:\Users\Ingenieria4\Documents\PRY_ERN\CHROMA\REDISEO EN SOTANOS\CHROMA- STANOS - NUEVO DISEO\CHROMA.gfcj Page 5 of 6
AMCA Licensed for Sound and Air Performance. Power rating (BHP/kW) includes transmission losses.
Greenheck Fan Corporation certifies that the model shown herein is licensed to bear the AMCA Seal. The ratings shown
are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and
comply with the requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B:
Free inlet, Ducted outlet. Power rating (BHP/kW) includes transmission losses. Performance ratings do not include the
effects of appurtenances (accessories). The inlet sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in
a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type B: free inlet
hemispherical sone levels. dBA levels are not licensed by AMCA International. The AMCA Certified Ratings Seal applies
to inlet sone ratings only. Radiated (casing) sound data is the sound generated through the fan housing when the fan is
ducted on both the inlet and outlet.
AMCA
02/07/2014 Printed Date:
CHROMA OFICINAS Job:
CHROMA PLAZA - CENTRIFUGOS Mark:
CAPS 4.14.1334 C:\Users\Ingenieria4\Documents\PRY_ERN\CHROMA\REDISEO EN SOTANOS\CHROMA- STANOS - NUEVO DISEO\CHROMA.gfcj Page 6 of 6