You are on page 1of 24

THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY

Sea Water System



System Preparation and Putting in Operation

1. Open the upper sea chest (when in port) UPPER CHEST.

2. Check that the overboard valve is open.

3. Start the pump (PUMP 1 or PUMP 2 button in MANUAL mode).

4. Open the FW COOLER water cooler valve, the LO COOLER oil cooler
valve of ME.

5. Open the COMPR. COOLER, CPP Servo and REDUCTION GEAR
cooler valves.

6. Check water pressure in the system.

7. Switch the pump control mode to AUTO.

8. Switch the recirculation valve control mode AUTO.

9. Specify SET POINT for the temperature controller.

10. Check that there is no alarm signal in the system.

Control Over System Operation

1.When putting to sea, switch over to the lower sea chest LOWER
CHEST.

2. Check water pressure in the system.

3. Check water temperature after/before the coolers.

4. Check for correctness of temperature controller operation maintaining
the proper temperature value.

5. Adjust the rate of flow through the air cooler using the SCAV. AIR
COOLER FLOW valve to maintain scavenge air temperature within the
working range.

6. Check that there is no alarm signal in the system.

Switching Over to In-Port Mode

1. When in port, switch over to the upper chest UPPER CHEST.

2. Switch the pump control mode to MANUAL.

3. Stop the pump (PUMP 1, PUMP 2 in MANUAL mode).

4. Start the auxiliary (port) pump AUX. PUMP.

5. Shut the valves of the unused coolers.

Fresh Water System

System Preparation and Putting in Operation

1. Check if there is water in the both expansion tanks. Add, if necessary
(TANK MAKE UP button and MAKE UP button).

2. Start the pump (PUMP 1 or PUMP 2 button in MANUAL mode).

3. Adjust pressure before diesel using the valve ME FLOW, check if there
is water flow through the diesel.

4. Switch the pump control mode to AUTO.

THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY
5. Switch the thermostatic valve control mode to AUTO.

6. Specify SET POINT for the temperature controller.

7. Open valve of a coolers - COOLER 1 or COOLER 2 and INJECTORS
COOLER (FW side and Injectors water side).

8. Start the Injectors cooling system pump (PUMP 1 or PUMP 2 button
in MANUAL mode).

9. Switch the injectors pump control mode to AUTO.

10. Check that there is no alarm signal in the system.

Control Over System Operation

1. Check water pressures before diesel, after injectors cooling system
pump, before injectors.

2. Check that there is water flow through the diesel.

3. Check that there is water flow through the each injector.

4. Check water temperatures before and after diesel.

5. Check water temperatures before and after injectors.

6. Check for correctness of temperature controller operation maintaining
the proper temperature value.

7. Check level in the both expansion tanks.

8. Check for alarm signals in the system.

Switching Over to In-Port Mode

1. Retain the system running mode for 40 60 min. after ME stop.

2. Switch the pumps control mode to MANUAL.

3. Stop the pumps.

4. Use the PORT MODE button to switch ME to heating from the running
Diesel Generator(s).

5. Open valve of a engine Oil Heater.

6. Check that there is water flow through system.

Fuel System

System Operation

System Preparation and Putting in Operation

1. Check the level in the DO service tank. Drain sludge (the DO DRAIN
button). Fill up the tank, if necessary (the DO TRANSFER PUMP in the
FOT system the START/STOP button).

2. Check the level in the HFO service tank. Drain sludge (the DRAIN
button). Fill up the tank, if necessary (SEPARATOR in the FOT system
the START/STOP button).

3. Check temperature in the heavy fuel service tank HFO TANK. Turn
ON HFO TANK HEATING, if necessary.

4. Set switches of fuel type selection for ME and DGs to the required
position: HFO-OFF-DO and AE1-AE2, respectively.

5. When running on heavy fuel oil turn ON the heating of the fuel
pipelines by the TRACING button.
THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY

6. Start the supply pump (the PUMP 1 or PUMP 2 button of the
SUPPLY PUMPS module, in MANUAL mode). Check its operation on the
pressure gauge.
7. Switch the pump control mode to AUTO.

8. When running on heavy fuel oil, open the preheater valves (the
PREHEATER ON button); if operating on diesel oil, open the bypass
valve (the PREHEATER BYPASS button).

9. Check fuel pressure before diesel (the ENGINE INLET pressure gauge).

10. Check filter pressure drop (the FILTER DROP pressure gauge);
change over to the filter stand-by section, if necessary.

11. Switch to the MANUAL mode of thermostatic valve control.

12. Use the HEATING controller to adjust fuel temperature before diesel
(PREHEATER OUTLET).

13. Check that there is no alarm signal in the system.

Control Over System Operation

1. After starting the diesel, switch to the AUTO mode of thermostatic valve
control.

2. Specify SET POINT for the temperature controller.

3. Check fuel temperature before diesel.

4. Check for correctness of temperature controller operation maintaining
the proper temperature value.

5. Check fuel pressure before diesel.

6. Check pressure drop through the filter; change over to the stand-by
section of the fuel, if necessary.

7. Check the flow rate for the fuel from the service tanks.
8. Check the level in the DO service tank. Drain sludge (the DO DRAIN
button). Fill up the tank, if necessary (the DO TRANSFER PUMP in the
FOT system the START/STOP button).

9. Check the level in the HFO service tank. Drain the sludge (the DRAIN
button). Fill up the tank, if necessary (SEPARATOR in the FOT system
the START/STOP button).

10. Check temperature in the heavy fuel service tank HFO TANK. Turn
ON HFO TANK HEATING, if necessary.

11. Check that there is no alarm signal in the system.

Switching Over to In-Port Mode

1. If your stay in port is of short duration, you can continue to use the
running mode of the FOS system for the purpose of being ready for
operation on heavy fuel oil.

2. Before a long-duration stay, change the system in due time to DO
before manoeuvring.

3. Switch to the MANUAL mode of thermostatic valve control.

4. Set the fuel type selection switch HFOOFFDO of the main engine to
the DO position.

5. Use the HEATING controller to gradually reduce fuel temperature
before diesel (PREHEATER OUTLET).

6. Check fuel pressure before diesel (the ENGINE INLET pressure gauge).

THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY
7. Open the preheater bypass valve (the PREHEATER BYPASS button),
close the preheater valves (the PREHEATER ON button).

8. Turn ON the fuel pipeline heating using the TRACING button.
9. After stopping the diesel, change control of the fuel-supply pumps to the
MANUAL mode; stop the pumps.

Fuel Oil Transfer System

System Operation

DO Service Tank Replenishment

1. Start the DO TRANSFER PUMP to transfer diesel oil from the DO
bunker to the DO service tank (the START/STOP button).
2. Check pump operation using the pressure gauges on the suction side
(SUCTION) and the discharge side (DISCHARGE).

3. Check the fuel level in the DO service tank.

4. Stop the pump in time to prevent overflow.

HFO Settling Tank Replenishment

1. Turn ON the heating of the HFO bunker in due time to provide for its
normal transfer.

2. Turn ON the heating of the fuel pipelines by the TRACING button.

3. Set the HFO TRANSFER PUMP suction switch to the required position
i.e From Bunker or From Spill Tank.

4. Start the HFO TRANSFER PUMP (the START/STOP button).

5. Check pump operation using the pressure gauges on the suction side
(SUCTION) and the discharge side (DISCHARGE).

6. Check the level in the HFO settling tank.

7. Stop the pump in time to prevent overflow.

8. Turn ON the fuel pipeline heating using the TRACING button.

HFO Service Tank Replenishment

1. Turn ON the heating of the HFO settling tank in due time to provide for
its normal transfer.

2. Drain sludge.

3. Set the separator suction switch (SUCTION) to the FROM SETTLE
position.

4. Set the separator discharge switch (DISCHARGE) to the TO SERVICE
position.

5. Turn ON the heating of the fuel to be treated.

6. Start the separator(s) please see the page OFS.

7. Check the fuel level in the HFO service tank and stop the separator in
time to prevent overflow.

8. Turn OFF the heating of the separated fuel.



THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY
Lube Oil Separators

System Operation

Separators 1 and 2 in the simulator are intended for the fuel purification
or clarification, if necessary. Separator 3 in the simulator is intended for
the clarification of the lubricating oil. Separators 1 and 2 can operate:

In parallel in this case both separators operate separately;

In series in this case, e.g. separator 1 operates in the
purification mode, whereas separator 2 operates in clarification
mode (for example). Serial or parallel operation of separators is
enabled by the pipeline valve which opens the supply of non-
purified fuel oil in separator 2 (TO SEP. 2 button) and three-way
valve at the outlet from separator 1 (PARALLEL IN SERIES
switch). Before starting the separator(s), it is necessary to supply
operating water in the system (WATER ON) and open supply of
opening and closing water in the separators (OPEN WATER and
CLOSING WATER buttons).

Starting the Separator

1. In the simulator, the separator is started in the manual control mode:
AUTO-MANUAL switch is in MANUAL position.

2. Select the separator operating mode: Purification or Clarification
buttons.

3. Check the separator Brake BRAKE button must be off.

4. Open WATER ON valve.

5. Lock the bowl. Feed the closing water CLOSE button. Check the
status of the OPEN button (must be off).

6. Start the separator drive electric motor (START button). Check that the
separator bowl develops its rated revolutions (about 10000 rpm). As this is
done, the bowl is opened, and the remains of water, product and sludge
are removed from it.

7. Open FUEL INLET valve.

8. Turn on the pump for supplying the product to the separator (FEED
PUMP button is on). As this is done, FLOW valve feeding fuel to the
separator is closed.

9. Turn on the heating (HEATING button) and set the required product
temperature (SET POINT, oC controller).

10. Supply the operating water for water lock OPER. WATER button
and the bowl is filled with water until the water appears in the indicator
(peep-hole) in the water drain line.

11. The separator bowl is filled with fuel - FLOW valve opens slowly to
supply the product to the separator (check the required fuel temperature
before). The product pressure at the separator outlet (BACK RESSURE)
is controlled with the aid of SET POINT, bar controller. If the waterlock is
broken because of the high back pressure, it is necessary to reduce the
back pressure by 0,5-1 bars and/or to decrease the fuel feed. Safety
solenoid valve is opened if back pressure more than 1 bar and closed if
back pressure less then 0,8 bar or in emergency, if sludge or water will
appeared in separator outlet (product discharge line). Back pressure
regulator especially significant in manual mode. In automatic mode,
WATER DRAIN valve is closed, if water level in bowl is reduced. Use
AUTO-MANUAL switch to switch the separator to AUTO mode.

12. Set the time of removing the sludge from the separator bowl the time
is set by using TIME, min controller (in AUTO mode).
THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY
13. Check the separation quality water content in the product
before/after the separator or the content of solid particles. Its simulated by
WATER CONTENTS, % INLET/OUTLET and IMPURITY, ppm
INLET/OUTLET displays.

14. Check the separator operating parameters by using the indicators on
the control panels.

Separator Washing

1. The separator operates in AUTO mode.

2. Empty the bowl (DISCHARGE button).

3. Switch the separator to MANUAL mode.

4. Supply closing water CLOSE button.

5. Supply operating water OPER. WATER button. The bowl is filled
with water and is washed.

6. Empty the bowl. Operations can be repeated several times depending
on how dirty the separator is.

Stopping the Separator

1. The separator operates in AUTO mode.

2. Empty the bowl (DISCHARGE button).

3. Switch the separator to MANUAL mode.

4. Cut the water supply to the separator.

5. Stop the separator drive electric motor (STOP button).

6. Brake the separator (BRAKE button).

7. In emergencies, use EMERGENCY STOP button.

Specific Features of Separator Operation in Clarification Mode

In the case of product clarification, the sludge and remains of water are
removed at regular intervals rather than constantly. The sludge is removed
either when some amount of it is accumulated in the bowl (by level) or
over a certain time interval (by timer). In the separation of lubricating oil,
hot operating water used for clarifying the lub.

Oil it is deoxidation in MANUAL control mode.

Lubricating Oil Systems

System Operation

System Preparation and Putting in Operation

1. Check the level of lube oil in the both oil tanks. If replenishment is
required, use the MAKE UP valves.

2. Open the valve of an oil heater (HEATER button).

3. Start Pump 3 for engine pre-lubricating and preheating (PUMP 3
button). Make sure there is pressure in the system. Stop Pump 3 after
engine pre-lubricating and preheating.

4. Set the PRESSURE LIMIT valve of pressure adjustment to the position
that ensures the minimum pressure in the system.

5. Switch the thermostatic valve control mode to AUTO.

THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY
6. Specify SET POINT for the temperature controller.

7. Open the valve of a cooler: COOLER 1 or COOLER 2.

8. Select the MANUAL mode for the main circulation oil pumps and start of
them (the PUMP 1 or PUMP 2 button). Make sure there is pressure in
the system.

9. Adjust pressure before diesel using the PRESSURE LIMIT valve.

10. Set the circulation oil pump control to the AUTO mode.

11. Select the MANUAL mode for the valve rockers oil pumps and start of
them (the PUMP 1 or PUMP 2 button). Make sure there is pressure in
the system.

12. Set the valve rockers oil pump control to the AUTO mode.

13. Make sure there is no alarm signals in the LO system.

Control Over System Operation

1. Check the pressure of oil before diesel (engine inlet).

2. Check the level of oil in the both collecting tanks. If replenishment is
required, use the MAKE UP valves.

3. Check pressure drop through the filters (of both systems); change over
to the stand-by section of the fuel, if necessary.

4. Check the temperature oil before diesel (engine inlet).

5. Check flow and temperature of oil at its exit after piston cooling, for each
cylinder.

6. Check for correctness of temperature controller operation maintaining
the proper temperature value.

7. Check for alarm signals in the LO system.

Setting the System to the In-Port Mode

1. Maintain the system running mode for 60 to 80 min. after stopping ME.

2. Switch over to the MANUAL mode of oil pump control (both sub-
systems).

3. Set the PRESSURE LIMIT valve of pressure adjustment for minimum
pressure.

4. Stop the running oil pumps.

Compressed Air System

System Operation

System Preparation and Putting in Operation

1.Blow down the RECEIVER 1, RECEIVER 2 bottles (the BLOW DOWN
module).

2. Open the bottle 1 valves (the RECEIVER 1 module) FROM
COMPRESSOR.

3. Open the bottle 2 valves (the RECEIVER 2 module) FROM
COMPRESSOR.

4. Make sure the cooling of components is ON in the SW system.

THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY
5. Start the compressor (the STOP/START buttons for COMPRESSOR
1 and COMPRESSOR 2 in MANUAL mode), fill up both bottles up to 30
bar.

6. Set compressor control to the AUTO mode.

7. Open the bottle 1 valves (the RECEIVER 1 module) START AIR,
CNTRL. AIR.

8. Check that there is no alarm signal in the system.

Control Over System Operation

1. Check and maintain proper pressure in bottle 1.

2. In emergency, if short of compressed air supply, open the valves of
bottle 2 (the RECEIVER 2 module) START AIR, CNTRL. AIR.

3. Regularly blow down the RECEIV. 1, RECEIV. 2 bottles (the BLOW
DOWN
module).

4. When starting the compressor, check operation of the SEPARATOR
valve designed for automatic blow-down of the water separator (the
BLOW DOWN module).

5. Control over the reducing station on the CONTROL AIR pressure
gauge.

6. Check that there is no alarm signal in the system.




Controllable Pitch Propeller

System Preparation and Putting in Operation

CPP pitch setter:

1. Check oil level in the CPP hydraulic drive oil tank. Replenish the tank
using the MAKE UP valve, if necessary.

2. Start the pump; make sure it creates the working pressure (about 40 bar
for maintaining a specified pitch, and about 70 bar for changing it).

3. Set the pump control mode switch to AUTO the stand-by pump will
start automatically in case of pressure drop in the system.

4. Check filter pressure drop, if the filter is fouled, switch over to the
second one.

5. In the SW system, open the valve that supplies water to the CPP oil
cooler; oil temperature is maintained automatically by the three-way
thermostatic valve. Clutch, reduction gear:

Clutch, reduction gear:

1. Before starting the diesel, check oil level in the reduction gear splash
pan; replenish it, if necessary.

2. Start the stand-by electric pump to circulate oil through the reduction
gear bearings (the PRIMING button).

3. Check pressure on the LUB. PRESSURE gauge of the REDUCTION
GEAR module on the CPP page.

4. Check filter pressure drop on the PRESSURE DROP pressure gauge, if
the filter is fouled, switch over to the second one.
THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY

5. In the SW system, open the valve that supplies water to the reduction
gear oil cooler; the oil temperature being maintained automatically by the
three-way thermostatic valve.

6. After starting the diesel, turn the electric pump off and check oil
pressure on the CLUTCH PRESSURE and LUB. PRESSURE gauges in
the REDUCTION GEAR module on CPP page.

7. To engage the clutch, press the ON button in the CLUTCH module
on the ME page, when the READY indicator is highlighted. When the
clutch engages, the ENGAGED indicator will be highlighted. The
PROPELLER RPM indicator on the ME page shows the current propeller
shaft revolution speed.

8. To avoid clutch overheating, do the engagement at a maximum diesel
revolution of 380 RPM.

9. To avoid diesel overloading, do the clutch engagement at the zero
propeller pitch. Stern tube check oil level in the header tanks, make use
of the MAKE UP button, if needed.

Control Over System Operation

CPP pitch setter:

1. All system faults are reported by the alarm indicators on the CPP page.

2. Pressure, oil temperature, and oil filter pressure drop are monitored by
the corresponding instruments (PRESSURE, OIL TEMP, and FILTER
DROP respectively). The oil level in the tank should be also checked.

3. The current position of propeller blades can be checked on the
PROPELLER PITCH instrument. Clutch, reduction gear:


1. All system faults are reported by the alarm indicators on the CPP page.

2. Pressure, oil temperature in the system, thrust bearing temperature, and
oil filter pressure drop are maintained by the corresponding instruments.
The oil level in the reduction gear splash pan should be also checked.

3. Clutch slipping can be identified by reduction of propeller shaft
revolutions as compared with a constant diesel revolution speed.
Stern tube:

1. Check oil level in the header tanks.

2. Condition of stern tube bearings should be checked on the temperature
of oil in the stern tube.

Setting the System to the In-Port Mode

CPP pitch setter:

1. Set the pump control mode switch to MANUAL.

2. Stop the operating pump.

3. Turn off the valve that supplies water to the CPP oil cooler on the
SOFTWARE page. Clutch, reduction gear:

1. To avoid a dramatic increase of diesel revolutions, the clutch should be
disengaged at the zero propeller pitch.

2. To disengage the clutch, press the OFF button in the CLUTCH
module on the ME page. When the clutch disengages, the DISENG.
indicator will be highlighted.

3. After stopping the diesel, start the electric oil pump to circulate oil
through the reduction gear bearings to cool them gradually down.
THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY

Main Engine Start

System Preparation and Putting in Operation

Turn ON the ARC system by the CNTRL ON button. In case of joint
work with the NTPro navigation simulator, select in cooperation with
the bridge a control station (BRIDGE or ECR).

In case of the simulators stand-alone mode, select ECR as the control
station.
Check for readiness of the other systems.

Open the main start valve, check start air pressure using the START AIR
PRESSURE indicator.

If necessary, set the maximum limit for CPP pitch using the Pitch Limit
controller.

Select a control mode: Fixed R.P.M. Combined Mode. If the Fixed
R.P.M. is selected, engage the reduction gear clutch using the On
button. The ET lever should be in the STOP position, which corresponds
to the zero CPP pitch.

Start ME using the Start button. The engine will run up the rated
revolution.

In case of the Combined Mode mode selected, start ME using the
START button. The ET lever should be in the STOP position, which
corresponds to the zero CPP pitch and ME idle revolutions. Then engage
the clutch by the On button.

Diesel Control
Diesel operation mode setting comes to the ARC system:

In the BRIDGE CONTROL model from the engine telegraph
located on the bridge;

In the ECR CONTROL mode from the engine telegraph
located in ECR, being monitored by SPEED SETPOINT digital
indicator.

The current mode of diesel operation is monitored using:

LOAD DIAGRAM;
ME RPM meter, CPP revolution indicator CPP pitch indicator;
Digital POWER indicator;
FUEL INDEX analog/digital indicator of FUEL INDEX fuel lever
position.

2. The SPEED digital indicator monitors ships speed.

3. The Slow Down and Shut Down indicators register actuation of the
safety diesel protection system. The safety system can be unlocked using
the SAFETY RESET button. To turn OFF the safety system, press the
EMERGENCY RUN button.

4. To stop diesel in emergency, use the EMERGENCY STOP button.

5. Emergency CPP control is performed using the Astern/Ahead
buttons with a depressed ON button.








THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY
ELECTRICAL SYSTEM

Electrical System Operating Instructions

This section provides recommendations for SEPS preparation for
operation, setting to work and operation.

SEPS Control

SEPS Manual Control Mode

Turn the CONTROL MODE switch to the MANUAL position;
Control of generators and consumers on the switchboards 24VDC,
220VAC and
380VAC should be performed in the manual mode.

SEPS Control in the Automatic Mode

Turn the CONTROL MODE switch to the AUTOMATION position;
Apply power to the diesel generator GBCs (turn the CIRCUIT BREAKER
SUPPLY switch to position 1);
Select an automatic control mode for SEPS (EQUAL, CYCLIC,
OPTIMAL
or CONST FREQ.);
Control of consumers on the switchboards 24VDC, 220VAC and
380VAC should
be performed in the manual mode.































THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY

Auxiliary Diesel Engine Control

Startup Preparation

Turn on the oil priming pump (set the PRE-LUBRICATION
switch to RUN);

TURN ON ENGINE preheating (open the cut-off valve in the
freshwater system)m (depress the PREHEATING ON button).

Standard Start

Depress the START button. At this moment, if pressure in the lubrication
system is below 2.0 bar, the electric oil-priming pump will be switched on
prior to air supply. When the pressure reaches the specified value, the
diesel engine will be started. The engine is brought down to 80% of its
rated RPM and is maintained at this RPM for 35 seconds for heating the
cooling water and lubrication oil. Then the RPM is brought to the rated
value, and the engine is ready to accept 50% of load. After another 2
minutes the engine is ready for 100% load.

Emergency Start

Press the EMCY START button. In this case, the engine will be started
without checking the initial oil pressure, and come to its rated RPM in
minimum time.

Standard Shut Down

Remove the generator from MSB buses using the
DISCONNECT button of the GCB;

Depress the STOP button, In case of a standard stop, the
engine is brought down to 80% of its rated RPM and is maintained
at this RPM for 1 minute. The engine is then stopped by cutting
off the fuel supply. SEPS Operation Instructions

Emergency Stop

Press the EMCY STOP button, which will result in automatic
disconnection of the generator circuit breaker and fuel supply cutting off.
The EMCY START, EMCY STOP buttons are of higher priority. If the
engine is started by using first the START button and then the EMCY
START, it will be started according to the emergency start procedure from
the moment of pressing the EMCY START button. In this case no return
to the standard start program is possible. The STOP and EMCY STOP
button have a similar way of operation.

Coupling the Auxiliary Diesel Generator

Closing to Dead MSB Buses

Start the engine;

Check that generator frequency has reached 50 Hz (engine
preheated and
reached 100% of its rate RPM), and generator voltage has
reached 400V;

Supply power to GCB (CIRCUIT BREAKER SUPPLY in position
1);

Arm GCB, if applicable (move the HAND DRIVE handle to the
upper position);

Press the CONNECT button.
THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY

Switching to the Parallel Operation (MSB Energized)

Start the diesel engine;

Check that generator frequency has reached 50 Hz (engine
preheated and reached 100% of its rate RPM), and generator
voltage has reached 400V;

Supply power to GCB (CIRCUIT BREAKER SUPPLY in position
1);

Arm GCB, if applicable (move the HAND DRIVE handle to the
upper position);

Synchronize the generator to be connected to MSB buses
manually or automatically.

Manual synchronization:

use the More/Less buttons of the DG frequency regulation system

(GOVERNOR CONTROL 2) to adjust the frequency of the generator to be
closed to the MSB frequency. The frequency of the generator to be closed
should slightly exceed the MSB frequency. Monitoring is performed using
the
frequency meters on the synchronization section;
use the More/Less buttons of the DG frequency regulation system

(GOVERNOR CONTROL) to reduce the phase difference (phase
displacement) between the generator voltage and the MSB voltage.
Monitoring is performed using the synchronoscope;

at the moment of the zero phase difference (the (12 oclock
indicator illuminates at the synchronoscope) or a minimum phase
difference, press the CONNECT GCB button for the generator to
be synchronized.

Automatic synchronization:

press the selection button for the generator to be synchronized
at the synchronization section (DG1, DG2);

move the synchronization mode switch to the AUTO position.
The moment of moving the synchronization mode switch to the
AUTO position is the synchronization process starting moment.
On completion of the synchronization process, the synchronized
generator will be closed to the MSB buses. Then the
synchronization mode selection switch will automatically return
from the AUTO position to the MANUAL position.

Active Power Distribution in Parallel Operation

Use the More/Less buttons of the DG frequency regulation system
(GOVERNOR CONTROL) to change the generator active power. The
active load increases with frequency. Monitoring of the active load is
performed using the wattmeter on the MSB generator section.

Reactive Power Distribution in Parallel Operation

Adjust generator voltage using the handle of the automatic voltage
regulator controller (VOLTAGE). The reactive load increases with voltage.
Monitoring of the reactive load is performed using the reactive-power
meter on the MSB generator section.

Taking Generator out of Parallel Operation

Use the More/Less buttons of the DG frequency regulation
system (GOVERNOR CONTROL) do decrease generator load
down to 50kW to 100 kW. The active load decreases with
THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY
frequency. Monitoring of the active load is performed using the
wattmeter on the MSB generator section;

Press the GCB DISCONNECT button.

Shaft Generator Drive Control

Standard Coupling Engagement

The clutch can be switched on, if the READY TO CLUTCH
TURN indicator illuminates (when oil pressure in the gearbox is
above 2 bar; the temperature being above 30C);

Press the CLUTCH ON button before the gearbox speed
doesnt exceed 400 RPM.

Emergency Coupling Engagement

Press the CLUTCH ON button.

Coupling Disengagement

Press the CLUTCH OFF button.

Coupling the Shaft Generator

Closing to Dead MSB Buses

Switch on the ShG drive clutch;

When ShG speed frequency reaches 47.5 Hz to 50 Hz, press the
GENERATOR
EXCITATION ON button, i.e. supply power to the generator excitation
winding;

Check that generator voltage has reached 400V;

Energize GCB (CIRCUIT BREAKER SUPPLY);

Wind the GCB springs (HAND DRIVE), if necessary;

Press the CONNECT button.

Setting to the Parallel Operation (MSB Energized)

Switch on the ShG drive clutch;

When ShG speed frequency reaches 47.5 Hz to 50 Hz, supply
power to the generator excitation winding (press the
GENERATOR EXCITATION ON button);

Check that generator voltage has reached 400V;

Energize GCB (CIRCUIT BREAKER SUPPLY);

Wind GCB, if necessary (HAND DRIVE);

Synchronize the shaft generator with the MSB buses (manually
or automatically).

Manual synchronization:

use the More/Less buttons of the frequency regulation system
of one or both diesel generators (GOVERNOR CONTROL) to
adjust MSB bus voltage frequency to the shaft generator voltage.
Voltage frequency of the ShG to be closed should slightly exceed
THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY
the MSB voltage frequency. Monitoring is performed using the
frequency meters on the synchronization section;

use the More/Less buttons of the DG/DGs frequency
regulation system

(GOVERNOR CONTROL) to reduce the phase difference (phase
displacement) between the shaft generator voltage and the MSB voltage;
at the moment of the zero phase difference (the 12 oclock indicator
illuminates at the synchronoscope) or a minimum phase difference, press
the CONNECT GCB button for the shaft generator.

Automatic synchronization:

press the selection button for the generator\shaft generator to be
synchronized at the synchronization section; move the synchronization
mode switch to the AUTO position. The moment of moving the
synchronization mode switch to the AUTO position is the synchronization
process starting moment. On completion of the synchronization process,
the synchronized generator will be closed to the MSB buses. Then the
synchronization mode selection switch will automatically return from the
AUTO position to the MANUAL position:

Use the buttons for changing specified frequency values to
reduce the DG/DGs load down to 50kw to 100 kW;

Switch off the diesel generator GCB(s).

Taking out of Operation

Set the diesel generator(s) to the parallel operation with ShG;

Use the buttons for changing diesel generator(s) frequency to
increase its/their load for the purpose of reducing the shaft
generator load down to 50kw to 100 kW;

Press the DISCONNECT button of the shaft generator circuit
breaker.

























THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY
Auxiliary Systems

Boiler fuel System

System Operation

Pre requisites:

Check the boiler water level is half a glass. Drain down or make up level
as required.

1. Check if there are alarm signals in the system. Acknowledge active
alarms and sort out the situation: determine what caused the alarm to
trigger off. Check if the boiler system safety system is activated (RESET
button) (see Steam Plant system).

2. Check if there is fuel in heavy and diesel fuel oil tanks. Replenish the
fuel store as required by opening HFO MAKE UP or DO MAKE UP
valve and checking the tank refilling by the level indicators. Tank overflow
is not permitted.

3. Check the heavy fuel oil temperature in the tank (HFO TANK pressure
gauge). If the temperature is low, turn on the heating of fuel in the tank
(HFO HEATING button). Do not allow the Fuel Low/High Temperature
alarm to be generated.

4. Select the type of fuel to be used by using HFO-OFF-DO switch.

5. With the use of the heavy fuel oil, turn on the heating or pipelines:
TRACING button.

6. With the use of heavy fuel oil, supply steam to the fuel oil heater by
pressing PREHEATER ON button. Select the steam heater operating
mode: MANUAL or AUTO. In MANUAL mode, control the steam
supply to the fuel oil heater by using HEATING controller. In AUTO
mode, set the required fuel oil temperature by using SET POINT,
rotating knob.

7. If diesel oil is used, turn on the fuel oil heater bypassing by using
PREHEATER BYPASS button.

8. Select the hot filter section by using FILTER 1-2 switch.

9. Select MANUAL fuel pump operation mode by using MANUAL-AUTO
switch. Start the required pump by using PUMP 1 or PUMP 2 button.
The fuel will start circulating in the system.

10. Control the pressure at the burner unit inlet by using PRESSURE SET
POINT, Bar controller. Check the parameters by using the available
pressure and temperature
gauges.

11. To enable of operation of burners in Steam Plant system and operation
of the boiler, open the supply of fuel oil to the boiler burners by using
BURNER 1 ON or BURNER 2 ON button.

12. Put the extraction and feed system into operation

Warning

In the event of a flameout ensure that the boiler is purged before
attempting to restart a burner.








THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY
Boiler

System Operation

1. Check if there are alarm signals in the system. Acknowledge active
alarms and sort out the situation: determine what caused the alarm to
trigger off. Check if the boiler system safety system is activated (RESET
button) (see Steam Plant system).

2. Check if there is fuel in heavy and diesel fuel oil tanks. Replenish the
fuel store as required by opening HFO MAKE UP or DO MAKE UP
valve and checking the tank refilling by the level indicators. Tank overflow
is not permitted.

3. Check the heavy fuel oil temperature in the tank (HFO TANK pressure
gauge). If the temperature is low, turn on the heating of fuel in the tank
(HFO HEATING button). Do not allow the Fuel Low/High Temperature
alarm to be generated.

4. Select the type of fuel to be used by using HFO-OFF-DO switch.
5. With the use of the heavy fuel oil, turn on the heating or pipelines:
TRACING button.

6. With the use of heavy fuel oil, supply steam to the fuel oil heater by
pressing PREHEATER ON button. Select the steam heater operating
mode: MANUAL or AUTO. In MANUAL mode, control the steam
supply to the fuel oil heater by using HEATING controller. In AUTO
mode, set the required fuel oil temperature by using SET POINT,
rotating knob.

7. If diesel oil is used, turn on the fuel oil heater bypassing by using
PREHEATER BYPASS button.

8. Select the hot filter section by using FILTER 1-2 switch.
9. Select MANUAL fuel pump operation mode by using MANUAL-AUTO
switch. Start the required pump by using PUMP 1 or PUMP 2 button.
The fuel will start circulating in the system.

10. Control the pressure at the burner unit inlet by using PRESSURE SET
POINT, Bar controller. Check the parameters by using the available
pressure and temperature gauges.

11. To enable of operation of burners in Steam Plant system and operation
of the boiler, open the supply of fuel oil to the boiler burners by using
BURNER 1 ON or BURNER 2 ON button.

Water Making Plant

Procedure to Put the Plant into Operation
1. Switch on SEA WATER pump.

2. Open the ejectors cut-off valve.

3. Open the condenser cooling water supply valve, which controls the
cooling water flow.

4. Open the feed water supply valve as appropriate for the required plant
capacity.

5. Open the evaporator heating water valve as appropriate for the heating
water temperature and desired plant capacity.

6. Set the solenoid valve control switch in Salinity Control group to AUTO
mode.

7. Set SET POINT distillate salinity control to the required position (at 2.5
PPM for obtaining the boiler feed water, at 200 PPM for the drinking and
domestic water).
THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY
8. Set the distillate pump control switch to the AUTO mode.

9. Check the plant operation parameters maintaining their values within
the rated value range.

Provisions Cooling

Procedure for Starting the Plant in Manual Mode

1. Turn on the sea water pump. Monitor its operation by the pressure
gauge.

2. Set the compressor operating mode switch to MANUAL position.

3. Open the shut-off valves on the liquid refrigerant circulation lines.

4. If the refrigeration plant is expected to operate for its own group
of storerooms only, shut-off valves on the connecting steam and
liquid pipelines are closed. If one of the refrigeration plants operates
for both groups of consumers (the second plant is not turned on),
the shut-off valves should be closed.

5. Adjust the low pressure switch.
On OFF scale, set the pressure value whereby the compressor is turned
off.
By the moment of the compressor stop, the temperature in all the cooled
storerooms should achieve the set value. On ON scale, set the pressure
value whereby the compressor is turned on. By this moment, temperature
in at least one room has grown to more than the set value.

6. Adjust thermoswitches for each storeroom.

7. For Butter and Dry. Prov. storerooms. Adjust the evaporation
pressure control.

8. Open the master solenoid valve.

9. Start the compressor.

10. Set the operating mode switch of the equipment defrosting system to
AUTO position.

11. Set the time interval (in hours) at which the defrosting of refrigeration
equipment will be performed in each cooling space.

12. Set the defrosting system control switch to AUTO position.

13. Monitor the plant operation parameters maintaining their values within
the standard range. You will be advised about all the faults by the alarm
system. As a monitored parameter reaches the maximum permissible
value, the safety system is actuated: an appropriate alarm is turned on in
the bottom part of the screen.

14. Load (unload) as necessary the set mass of goods (products) into/from
the storerooms.

Defrosting of Refrigeration Equipment in Manual Mode

This is used in case of excessive growth of hoar frost on the surface of
refrigerating units:

1. If the thickness of the hoar frost layer is 5 mm or more, and the
equipment defrosting process has not been started automatically, then it is
necessary to: Set the defrosting system control switch to MANUAL
position.

2. Press ON button under the switch.




THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY
Replenishment of Liquid Refrigerant

This is performed if the refrigerating plant operating mode indicates the
insufficiency of liquid refrigerant in the system (low level of liquid
refrigerant in the condenser receiver part, gas bubbles in the sight glass,
low suction pressure, extensive overheating on the suction line and high
charging temperature):

1. Set the compressor operating mode switch to MANUAL position.

2. Close the shut-off valve on the liquid line after the condenser.

3. Open the make-up valve.

4. Monitor the liquid refrigerant level by using the sight glass on the
receiver part of the condenser.

5. After the end of the process, close the make-up valve (the liquid
refrigerant level on the condenser sight glass is 0.40.5 ).

6. Open the shut-off valve after the condenser.

7. Turn the compressor on.

8. Set the operating mode switch to AUTO.

9. Monitor the refrigerating plant operation parameters. In case of the
system overfilling with liquid refrigerant, there may be damp
compressor operation.

Compressor Replenishment with Oil

This is performed if the oil level in the sight glass on the compressor sump
has dropped to below mark. The oil should best be added with the
compressor not running (the oil level is clearly visible in the sight glass):

1. Set the compressor operating mode switch to MANUAL position.

2. Close the compressor suction valve.

3. After the suction pressure (in the sump) has dropped to a value
below the atmospheric pressure ( -0.5 bars), stop the compressor.

4. Open the oil make-up valve.

5. After the end of the process (oil level is not higher than 2/3
of the sight glass), close the valve.

6. Turn the compressor on.

7. Set the operating mode switch to AUTO position.

8. Monitor the refrigerating plant operating parameters. Where the
compressor cannot be stopped (e.g. loading of a considerable
amount of goods with rather high temperature) at the moment of oil
replenishment, it is necessary:

9. To re-adjust the low pressure switch on OFF scale make -0.5 -
0.3 setting.

10. After the pressure has dropped below the atmospheric pressure, open
the oil make-up valve.

11. After the end of the process, close the valve.

12. Re-adjust the low pressure switch to the operating mode.

13. Monitor the refrigerating plant operating parameters. If oil is added to
the operating compressor, the replenishment will be either
excessive or incomplete.


THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY
Air Discharge

This is performed if the pressure gauge needle on the charging line makes
jerking oscillatory motions, and the charging pressure exceeds the
optimum value by 0.2 MPa and more:

1. Set the compressor operating mode switch to MANUAL position.

2. Turn the compressor off.

3. Turn the compressor off (on the right in Fig).

4. After the water temperature drops at the condenser outlet
(OUTLET temperature gauge) down to the sea water temperature
(INLET temperature gauge), open the valve for the discharge of air
from the system.

5. As the charging pressure drops to the value corresponding to the
optimum condensation temperature, i.e. as the temperature readings in
DISCHARGE pressure gauge and DISCHARGE temperature gauge are
equalised, close the air discharge valve.

6. Monitor the level of liquid refrigerant by using the sight glass on the
condenser (there should be no lowering of the level).

7. Adjust the condensation pressure control for the maintaining of the set
pressure value (0.6 0.7 MPa).

8. Turn the compressor on.

9. Set the operating mode switch to AUTO position.

Replacement of Filter Drain

This is done when the colour of the sight glass indicator changes. The
indicator
colour changes from green to yellow as the moisture penetrates in the
liquid refrigerant system:

1. Close the shut-off valves of the filter drain.

2. Open the bypass valve of the filter drain.
As this is done, the indicator colour will change from the yellow colour to
green, i.e. there will be an imitation of the filter drain replacement.

3. Open the shut-off valves of the filter drain.

4. Close the bypass valves of the filter drain.

Compressor Breakdown

In case of failure of one of the compressors, the other compressor will
maintain the required temperature in all the six provision storerooms:

1. Re-adjust the low pressure switch of the operating compressor (N2) as
required (in case of breakdown of compressor N1).

2. Set the operating mode switch of the stopped (broken) compressor to
MANUAL position.

3. Close the master solenoid valve on the refrigerating plant which is
not operating.

4. Open the shut-off valves on the steam and liquid connecting lines.






THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY
Air Conditioning Plant Operation and
Maintenance

Procedure to Bring the Air Conditioning System into Operation in
Summer Mode

The air conditioning system is switched to the summer more as the
ambient
temperature grows to +25:

1. Set the conditioner operating mode switch to SUMMER position.

2. Open the valve for feeding water to the compressors cooling.

3. Turn on the sea water pump.

4. Open the shut-off valves on the liquid refrigerant circulation lines.

5. Adjust temperature switches.

6. Set the compressors operating mode switch to MANUAL position.
Simulator Module Systems

7. Adjust the low pressure switch. On OFF scale, set the suction
pressure value whereupon, with some delay, the compressor cylinders will
start to turn off. On ON scale, set the pressure value whereupon the
compressor cylinders will start to turn on, by the timer, too.

8. Open the master solenoid valve.

9. Check if the compressor suction valve is closed.

10. Run the compressor.
As this is done, the electromagnetic actuators which raise the suction
valve plates are ON, taking the cylinders out of operation and thus creating
the compressors idle running. After the compressor has been run, the
pushing devices are turned off in several seconds, and its cylinders start
operating:

1. Partly open (to 5-10%) the compressor suction valve.

2. Check pressure in the compressor lubricating system.

3. With normal oil pressure value, continue opening the suction valve
observing
safety precautions.

4. Set the compressor operating mode switch to AUTO position.
Simulator Module Systems

5. Use manual switches to set the desired air temperature in the cabins.

6. Use manual switches to set the desired air temperature in the cabins.
Values of temperature and humidity in the cabin are shown on indicators.

7. Monitor the plant operating parameters maintaining their values within a
standard range. The alarm system will signal about all the possible faults.
As a monitored parameters reaches its limit value, and appropriate alarm
lights up in the bottom part of the screen. Where no steps are made to
normalise the compressor operation, SHUT DOWN protection is actuated,
and the compressor is stopped, where after it can be brought back into
operation in MANUAL mode only.

Procedure to Bring the Air Conditioning System into Operation
in Transient Mode

The air conditioning system is switched to the transient mode at the
ambient temperature of +15 to +25.
THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY
Set the conditioner operating mode switch to WINTER position, turn off the
heaters and humidifier: the fan only will remain operating.

Procedure to Bring the Air Conditioning System into Operation in
Winter Mode

The air conditioning system is switched to the winter operating mode when
the ambient temperature drops to +15:

1. Set the conditioner operating mode switch to WINTER position.

2. Depending on the ambient temperature (t), tune on the first and second
stage heaters. Ambient temperature after the first and second stage
heaters, as well as relative humidity of the treated air is maintained
automatically by using the direct-acting temperature controls (steam
control valves). In this case, the first stage control maintains constant
temperature at the first duct outlet, whereas the second stage control
maintains temperature at the second duct outlet in accordance
with its setting changed automatically with the ambient temperature.
Simulator Module Systems

3. To control the air humidity, it is first necessary to turn on H2O valve
manually monitoring the air humidity values in the first and second ducts.
After it has been set, humidity is controlled automatically in accordance
with the ambient temperature by the first duct temperature control.

4. Use manual switches in the cabin to set the desired temperature
in the cabin.

5. Monitor the air conditioned operation parameters maintaining their
values within the standard range.





Refrigerant Replenishment

The operation is performed if the refrigeration plant operating mode
indicates insufficient refrigerant in the system (low refrigerant level in the
receiver, gas bubbles in the sight glass, low suction pressure, excessive
heating in the suction line and high temperature on the charging line):

1. Set the compressor operating mode switch to MANUAL position.

2. Close the shut-off valve on the liquid line after the receiver.

3. Open the make-up valve.

4. Monitor the refrigerant level by the sight glass on the receiver.
5. After the end of the process, close the make-up valve (the refrigerant
level on the receiver sight glass is 50%).

6. Open the shut-off valve after the receiver.

7. Set the operating mode switch to AUTO position.

8. Monitor the refrigerating plant operation parameters.

9. In case of the system overfilling with liquid refrigerant, there may be
damp compressor operation.

Compressor Replenishment with Oil

This is performed if the oil level in the sight glass on the compressor sump
has dropped to below height mark. The oil should best be added with
the compressor not running (oil level is clearly visible in the sight glass):

1. Set the compressor operating mode switch to MANUAL position.

2. Close the compressor suction valve.

THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY
3. After the suction pressure (in the sump) has dropped to a value
below the atmospheric pressure (-0.5 bars), stop the compressor.

4. Open the oil make-up valve.

5. After the end of the process (oil level is not higher than 2/3 of the sight
glass), close the valve.

6. Turn the compressor on.

7. Open the compressor suction valve.

8. Set the operating mode switch to AUTO position.

9. Monitor the refrigerating plant operating parameters.

Air Discharge from the Refrigerant System

This is performed if the pressure gauge needle on the charging line makes
jerking oscillatory motions, and the charging pressure exceeds the
optimum value by 2 bars or more:

1. Set the compressor operating mode switch to MANUAL position.

2. Close the compressor suction valve.

3. Turn the compressor off.

4. Adjust the condensation pressure control to 100% opening (which
corresponds to the setters position 5).

5. After the water temperature drops at the condenser outlet
(OUTLET temperature gauge) down to the sea water temperature
(INLET temperature gauge), open the valve for the discharge of air
from the system.

6. As the charging pressure drops to the value corresponding to the
optimum condensation temperature, i.e. as the temperature readings in
DISCHARGE pressure gauge and DISCHARGE temperature gauge are
equalised, close the air discharge valve.

7. Monitor the level of refrigerant by using the sight glass on the condenser
(there should be no lowering of the level). 8. Adjust the condensation
pressure control for the maintaining of the set pressure value (9-10 bars).

9. Turn the compressor on.

10. Open the compressor suction valve.

11. Set the operating mode switch to AUTO position.
Simulator Module Systems

Replacement if Moisture Eliminator

This is done when the colour of the sight glass indicator changes. The
indicator colour changes from green to yellow as the moisture penetrates
in the refrigerant system:

1. Close the moisture eliminator shut-off valves.

2. Open the moisture eliminator bypass valve.

3. Open the valve for drawing off refrigerant from the moisture eliminator
for several minutes (1-2 minutes).

4. Close the valve for drawing off refrigerant from the moisture eliminator.

5. Open the moisture eliminator shut-off valves.

6. Close the moisture eliminator bypass valve. As this is done, the
indicator colour will change from the yellow colour to green, i.e.
there will be an imitation of the moisture eliminator replacement.
THIS OPERATING PROCEDURE IS FOR TRANSAS TRAINING SIMULATOR USE ONLY

Elimination of Compressor Damp Operation

This is performed if there is a sharp drop of temperature on the charging
line (down to +10-0), overheating decreases, the compressor noise
changes to dull, the cylinder walls and sump are covered with ice (if there
is considerable flooding with liquid refrigerant), rattling noise appears, and
the amperemeter needle goes beyond the red line:

1. Close the compressor suction valve leaving it 5-10% open.

2. After the indications of damp operation disappear, open the compressor
suction
valve slowly.

3. Check oil level in the sump replenish the compressor with oil as
required.

Breakage of Conditioner Fan

If a fan is broken, air is supplied to this conditioner by the fan of the
conditioner on the other board through the air flap. To do this, press the
air flap control button. You can act in much the same way in case of the
fan air filter fouling until it is replaced (the fault is eliminated from the
instructor workplace).

Breakage of Automatic Steam Control Valve

If the automatic steam control valve is broken:

1. Close the shut-off valves Bypass 1 and Bypass 2 of the
steam control (for the time of the repairs).

2. Open the manual control valve on the bypass line, adjusting its flow by
the
readings of temperature gauges at the outlets of the first and second
ducts.

You might also like