You are on page 1of 7

SOLUTION AIR HANDLING UNIT

PERFORMANCE SPECIFICATION
Unit Tag Qty Model Air Flow (CFM)
UMA-08 1 Solution Outdoor Air Handler 33 x 51 2825
Unit Sequence
Tier 1 FS <<< CC <<< FM
Basic Unit Options
Insulation Type: (Refer to Each Segment) Exterior Casing Paint
Base Rail Height: None
Performance: High Performance
Unit Special Quotes
None
*Note:Component locations are listed as Segment Hand (Unit Hand) : ex. Left (Right)
See Submittal Drawing for additional details
Segments Listed Starting At Air Inlet
Project Name: Idsaa-CentroMedicoMorelos York Contract No.:
Printed: 11/28/2012 17:31:58 UMA-08Performance
Unit Folder: UMA-08 10/03/2012 11:54:23 AM Page 1 of 7
SOLUTION AIR HANDLING UNIT
PERFORMANCE SPECIFICATION
Unit Tag Qty Model Air Flow (CFM)
UMA-08 1 Solution Outdoor Air Handler 33 x 51 2825
FM Filter/Mixing Box Segment
Segment Detail
Segment Air Pressure Drop (in. w.g.): 0.85
Outside Air (OA) Return/Mixed Air
(RA/MA)
AirFlow (CFM) 2825 2825
Opening (QTY) Size 9.50Hx37.00W 9.50Hx37.00W
Area per Opening (ft) 2.44 2.44
Location Front-High(Front) Bottom
Damper (QTY) Size (1)9.50x37 (1)9.50x37
Damper Type Control Control
Configuration 100% 100%
Damper Model CD60 CD60
Damper Material Galvanized Galvanized
Blade Orientation Parallel Parallel
Min. Allowed CFM N/A N/A
Damper Linkage Linked Linked
Filter Media Detail
Filter Type 2"Pleated 30% (MERV 7)
Filter Area (ft) 8.89
Filter QTY/Size (4)20x16
Load Option Side
Filter APD (in. w.g.) 0.15
Dirty Filter Allowance 0.00
Spare Filter Type None
Spare Filter QTY 0
Filter/Mixing Box Segment Options
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 27H x 29W
Standard Door Latch, No Lock, Outward
Opening
Dampers Selected are ASHRAE 90.1 Compliant
Project Name: Idsaa-CentroMedicoMorelos York Contract No.:
Printed: 11/28/2012 17:31:58 UMA-08Performance
Unit Folder: UMA-08 10/03/2012 11:54:23 AM Page 2 of 7
SOLUTION AIR HANDLING UNIT
PERFORMANCE SPECIFICATION
Unit Tag Qty Model Air Flow (CFM)
UMA-08 1 Solution Outdoor Air Handler 33 x 51 2825
CC Cooling Coil Segment
Coil Segment Details Coil Segment Options
Coil Space: 13" Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
22" IAQ Coil Drain Pan Left (Left)
Stainless Steel
Bulkhead Material Galvanized
Coil Supports Galvanized
UV Surface Decontamination Detail
None
Project Name: Idsaa-CentroMedicoMorelos York Contract No.:
Printed: 11/28/2012 17:31:58 UMA-08Performance
Unit Folder: UMA-08 10/03/2012 11:54:23 AM Page 3 of 7
SOLUTION AIR HANDLING UNIT
PERFORMANCE SPECIFICATION
Unit Tag Qty Model Air Flow (CFM)
UMA-08 1 Solution Outdoor Air Handler 33 x 51 2825
FS - Supply Fan Segment
Segment Details Fan Segment Options
Segment Air Pressure Drop (in. w.g.): 0.00 1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 27H x 18W
Standard Door Latch, No Lock, Outward Opening
Air Flow (CFM): 2825
Altitude (ft.): 3000
TSP/ESP (in. w.g.): 2.62/ 1.00
Air Inlet: Front(Front)
Fan Discharge: Rear(Rear)
Fan Detail
Type: FC
Size: 10-10
Construction: S
Bearing Options: Permanent Seal
Fan RPM: 1554
BHP: 1.87
Fan BHP w/ Belt Loss: 2.01
Outlet Velocity (ft/min): 2346
Motor Detail
Motor Type: TECO ODP Premium Efficiency
HP 2.0
Voltage/Phase/Frequency: 230/3/60 Hz
Motor RPM: 1800
Frame Size: 145
Location: Left(Left)
Drive Type: Belt Drive
Belt Drive Type: Fixed
Full Load Amps (FLA): 5.22
Efficiency: 86.5%
Project Name: Idsaa-CentroMedicoMorelos York Contract No.:
Printed: 11/28/2012 17:31:58 UMA-08Performance
Unit Folder: UMA-08 10/03/2012 11:54:23 AM Page 4 of 7
SOLUTION AIR HANDLING UNIT
PERFORMANCE SPECIFICATION
Unit Tag Qty Model Air Flow (CFM)
UMA-08 1 Solution Outdoor Air Handler 33 x 51 2825
Coils & Spacers Listed Starting In Direction Of Air Flow
CC Coil - 01
Coil General/Physical Details Air Side Performance Fluid Side Performance
Location: 0 Rows: 8 Air Flow (CFM): 2825 Fluid Type:
Suct Tmp(F):
RPD (PSI):
Fluid Weight(lb):
Fluid Volume(ft):
R-410a
45.00
2.5
9.3
0.7
Tag: AirCoil Fins Per Inch: 13 Altitude (ft.): 3000
Application: Cooling Circuit: 8 EAT-DB (F): 75.9
Coil Type: DX Finned Height (in.): 22.50 EAT-WB (F): 60.9
Face Type: Full Finned Length (in.): 39 LAT-DB (F): 47.8
Tube Diameter: 1/2" BDX Coil Face Area (ft): 6.1 LAT-WB (F): 47.7
Tube Material: Copper Coil Conn. Loc.: Left(Left) FV (ft/min): 463
Tube Wall Thickness: .016" Suct Conn Size:
Liq Conn Size:
Distributor Data:
Distributors:
Pct. Cap
Split(Inter):
1-5/8
7/8
1
None
SMBH: 77.1
Fin Type: Corrugated TMBH: 95.2
Fin Thickness: .008" APD (in. w.g.): 0.77
Fin Material: Aluminum
Casing Material: Galvanized
Connection Material: Copper
Connection Type: Sweat
Coating: None
ARI Messages:
R410A coil - This coil is outside the scope of the AHRI certification, but is rated in accordance with AHRI Standard 410
NOTE: Auxiliary Side Connectors for hot gas bypass are provided for ONE circuit only.
Coil Dll Version: 5.4a
Static Pressure Summary
Segment Component Supply
(in.
w.g.)
Return
Fan
(in. w.g.)
FM Filter / Mixing Box
CC Variable Length Cooling Coil
FS-DWDI Supply Fan
Outside Air Moisture Eliminator
Standard Hood
Opening Pressure Drop
Control Galvanized (CD60)
2" Pleated 30% (MERV 7)
Cooling 8 rows 13 fins
External Static Pressure - User Entered Pressure Drop
0.32
0.06
0.23
0.09
0.15
0.77
1.00
Total 2.62 0.00
Air handling unit parameters vary depending on conditions. Parameters such as airflows, air pressure
drops, and coil capacities are shown for design conditions.
Project Name: Idsaa-CentroMedicoMorelos York Contract No.:
Printed: 11/28/2012 17:31:58 UMA-08Performance
Unit Folder: UMA-08 10/03/2012 11:54:23 AM Page 5 of 7
SOLUTION AIR HANDLING UNIT
PERFORMANCE SPECIFICATION
Unit Tag Qty Model Air Flow (CFM)
UMA-08 1 Solution Outdoor Air Handler 33 x 51 2825
Dimension & Weights Summary
Section
Length*
(in.)
Width**
(in.)
Height
(in.)
Weight
(lbs.)
FM Filter / Mixing Box Segment
CC Variable Length Cooling Coil Segment
FS-DWDI Supply Fan Segment
32
22
36
51
51
51
33
33
33
353
640
522
Overall:
90 51 33 1515
*The length includes bottom tier segments only.
**The width does not include coil connection extensions or door latches that extent beyond the unit casing.
The width does not include the depth of any pipe chases.
Shipping Skid Summary
Shipping Skid
Length*
(in.)
Width**
(in.)
Height***
(in.)
Weight
(lbs.)
(FS-DWDI CC FM)
Ship Loose:
None
109 63 39 1515
*The length includes any mounted rain-hoods, discharge flanges, tie-down brackets, shipping wood-blocks, front dampers, split
connectors, electrical/control components, out rigging HW supports, isolation dampers, inlet baskets
**The width includes any door handles, coil connections, drain connections, lifting lugs, mounted pipe-chases, electrical/control
components, tie-down brackets, side dampers
***The height includes any base-rails, shipping wood-blocks, roof peak, discharge flanges, mounted gas-furnace flue pipes
Shipping Skid Sequence
Tier 1
(FS < CC < FM)
Project Name: Idsaa-CentroMedicoMorelos York Contract No.:
Printed: 11/28/2012 17:31:58 UMA-08Performance
Unit Folder: UMA-08 10/03/2012 11:54:23 AM Page 6 of 7
SOLUTION AIR HANDLING UNIT
PERFORMANCE SPECIFICATION
Unit Tag Qty Model Air Flow (CFM)
UMA-08 1 Solution Outdoor Air Handler 33 x 51 2825
Sound Summary
Octave Band Sound Power Levels (dB Re. 1 picowatt)
63 125 250 500 1000 2000 4000 8000 dBA
Ducted Discharge Rear-1, FS 92 87 87 88 88 84 79 74
Return Air Bottom-1, FM 77 77 72 68 73 71 64 57
Outside Air Front-1, FM 71 70 66 64 69 67 60 53 73
Sound data tested in accordance with AHRI-260 (2001), Standard for Sound
Rating of Ducted Air Moving and Conditioning Equipment.
Notes:
1. The overall A-weighted sound power level is only applicable to sound radiation outdoors and casing radiated
sound. This metric does not apply to ducted components
2. Return air sound powers are estimated using 85% of unit flow. Outside air sound powers are estimated using
15% of unit flow.
Project Name: Idsaa-CentroMedicoMorelos York Contract No.:
Printed: 11/28/2012 17:31:58 UMA-08Performance
Unit Folder: UMA-08 10/03/2012 11:54:23 AM Page 7 of 7

You might also like