You are on page 1of 9

Solid-state tap-changer of transformers: Design, control and implementation

Jawad Faiz

, Behzad Siahkolah
Center of Excellence on Applied Electromagnetic Systems, School of Electrical and Computer Engineering, University of Tehran, Tehran 1439957131, Iran
a r t i c l e i n f o
Article history:
Received 28 April 2009
Received in revised form 5 July 2010
Accepted 13 August 2010
Keywords:
Transformer
Electronic tap-changer
Hardware
a b s t r a c t
This paper presents the implementation of a prototype electronic tap-changer of transformer. Mechanical
tap-changer has many problems such as low operating speed, short lifetime and heavy size. In order to
solve these problems a fully solid-state tap-changer with a new control strategy and optimal congura-
tion is proposed. The design of tap-changer is discussed and bi-directional solid-state power electronics
switches are implemented. Following the realization of the tap-changer controller, developed software
for such precise control is introduced. To verify the design procedure and optimal conguration and apply
the developed software, a prototype low-power tap-changer has been built and tested.
2010 Elsevier Ltd. All rights reserved.
1. Introduction
Normally the main objective of a tap-changer is to regulate and
adjust the output voltage of transformer [1]. The voltage uctua-
tion springs from the load changes. Sometimes tap-changer in
power transformer is used to shift the phase angle [2,3]. An on-load
tap-changer (OLTC) enables to change the taps under load and it is
utilized where a short period of time is required for such changes.
In an OLTC impedance is added to circuit in order to prevent the
short circuit during the tap-changing process while the load cur-
rent passes the load when tap-changer operates.
The main advantage of a reactive OLTC is that the reactor stands
continuous load current. However, this type of tap-changer has
some disadvantages including low operating speed, large arcs,
shorter lifetime and heavy size [4]. Therefore, it is obsolete now.
Due to the above-mentioned drawbacks, reactive tap-changers
are almost replaced by resistive tap-changers. In spite of progress
made in the structure of mechanical OLTC, they have some limita-
tions and considerable drawbacks, as such that major fault in
power transformers springs from the tap-changer fault [5]. Some
limitations and drawbacks of mechanical OLTC include arc in con-
tacts, high cost of maintenance, low speed of operation and high
losses [6]. The main function of the controller in the tap-changer
system is to minimize the uctuations (rising and falling) of the
voltage amplitude in comparison with the reference voltage at
the point called the regulation bus. The regulation bus may be
far from the secondary of transformer. In the other words, the main
objective of the controller is to keep the amplitude of the bus volt-
age within a dened range [7]. Of course, in addition to the main
function, the tap-changer controller may control the tap-changer
during critical cases such as over-loads, output short-circuits, tran-
sient over-voltages of input and tap-changer damage. In order to
preserve power system integrity in emergency conditions, the taps
of transformer can be moved and locked to predetermined position
or voltage set-point [8]. The controller may also make the neces-
sary decision to protect the tap-changer system and its loads. To
remove these limitations and drawbacks, new circuits and struc-
tures for OLTC have been so far suggested [16]. They are catego-
rized into two main groups:
1. Electronically assisted OLTC [912].
2. Solid-state OLTC [1322].
In the 1st group, solid-state power switches have been em-
ployed beside mechanical switches in order to reduce the arc. In
the 2nd group, there are no mechanical parts and they have been
totally built by solid-state power switches. The advantages of the
latter group of OLTC are very low maintenance cost, high operating
speed, and possibility of tap jumping and high performance.
Although several ideas have been so far introduced to realize the
totally solid-state tap-changer, there is no any versatility in these
ideas. It is not clear that which ideas is suitable for a dene applica-
tion. Basically which structures are optimal or what is an optimal
conguration. The above-mentioned functions for the tap-changer
controller are expected for any mechanical and electronic tap-chan-
ger. However, it is noted that there are fundamental differences be-
tween the capabilities and characteristics of mechanical and
electronics tap-changers [23,24]. So, if the same conventional con-
troller of a mechanical tap-changer is used for an electronic tap-
changer system, many capabilities and features of the electronic
tap-changer will not be realized.
0142-0615/$ - see front matter 2010 Elsevier Ltd. All rights reserved.
doi:10.1016/j.ijepes.2010.08.016

Corresponding author. Tel.: +98 21 88003330; fax: +98 21 88633029.


E-mail address: jfaiz@ut.ac.ir (J. Faiz).
Electrical Power and Energy Systems 33 (2011) 210218
Contents lists available at ScienceDirect
Electrical Power and Energy Systems
j our nal homepage: www. el sevi er . com/ l ocat e/ i j epes
The authors have reviewed the differences between the tap-
changing processes in both types of the tap-changers, and de-
scribed the differences. Some modications in the conventional
controllers used in the mechanical tap-changers structure have
then been applied and a general structure for electronic tap-chang-
ers is suggested [2527]. Fig. 1 shows such a modied controller.
In a series of papers an attempt has been made to classify the
introduced ideas in OLTC in a logical manner. Then the cost of
tap-changer has been taken as an objective in order to introduce
an optimal structure. Following this selection, other requirements
such as switching technique for a proper commutation, controlling
and detecting fall and rise of voltage have been applied and nally
it has been built and tested [2834]. In [30] criteria for optimal
conguration of transformer windings as well as power electronic
switches are proposed for design and implementation of low-
power electronic tap-changer. The aims in this optimization in-
clude minimization of: (1) number of switches and their voltages
and currents, (2) number of taps in transformer, (3) number of
voltage steps and (4) deviation of amplitude of voltage compared
with the reference voltage in the regulation bus. Present paper de-
scribes the developed software for realization of the electronic tap-
changer. The hardware and software are then used to build a sin-
gle-phase low-power prototype 5 kVA electronic tap-changer.
The test results for this prototype are also presented and compared
with the simulated results and good agreements are achieved. This
shows the advantages of the proposed electronic tap-changer over
mechanical tap-changer.
Although a single-phase tap-changer is investigated in this pa-
per, it can be extended into three-phase version taking into ac-
count the structure of the transformer. If tap-changer is xed in
the star-connected side of the three-phase transformer, this exten-
sion can be easily implemented, because the phase voltage is easily
measured. However, this can be also implemented in the D-con-
nected case with some modications. However some design con-
siderations such as bi-directional switches conguration, current
commutation between them and control loop in any phase can
be exactly applied. Of course, algorithm of amplitude and phase
angle measurements must be largely changed compared with the
single-phase version
Section 2 points out the design of taps winding structure and
switches arrangements. Bi-directional solid-state switches used
in OLTC are described in this section. In Section 3, more explana-
tion of each block shown in Fig. 1 is given and their design proce-
dures are discussed. In Section 4, the developed software for
controlling an electronic tap-changer is introduced and a method
for converting the difference between the output voltage of the
transformer and the reference voltage (DV) into the tap-number
and switch commands. Section 5 presents the experimental re-
sults. Finally, Section 6 concludes the paper. It is noted that up to
now the required software in the microprocessor board has not
been proposed in the literature and this paper is mainly focused
on the detailed requirement of such software.
2. Designing taps winding structure and solid-state switches
arrangement
There are two following major parameters that determine the
cost of an OLTC: (1) number of solid-state power switches and
their voltages and currents and (2) number of taps because any
tap needs insulating and special insulator. The main objectives of
OLTC design consists of:
1. Minimizing number of solid-state switches and their currents
and voltages.
2. Minimizing the taps number.
3. Maximizing voltage steps over output voltage regulation range
for precise regulating.
Of course, there are some other objectives beside the above-
mentioned objects such as lower losses, higher reliability, lower
short circuit current and over-voltage. Design of taps winding
structure was proposed in [23]. Selecting voltage of any section
of windings in the taped-winding was given in [24]. The switches
arrangement leading to the maximum achievable number of volt-
ages was discussed in [27]. The optimal topology without and with
taking into account the voltage and current of the switches was
proposed in [23].
Solid-state switches are the most important element of an elec-
tronic OLTC which are bi-directional switches due to their ac volt-
age and current [34]. The bi-directional switches used are two
common emitter IGBTs in series with reversed diodes. Strategy of
switches control is based on the current direction [24,28]. A com-
bination of solid-state switches is employed in order to realize a bi-
directional switch. Switch-on losses in the bi-directional switches,
current commutation between these switches based on the voltage
and current direction, design of terminals snubber capacitor of
OLTC, different switches modulation in tap-changer and no-modu-
lation case are the major problems that are proposed in [2834]. To
realize the proposed electronic tap-changer a single-phase proto-
type low-power tap-changer was designed, built and tested as de-
scribed in [30].
3. Electronic tap-changer controller
The main blocks of Fig. 1 are described in this section.
3.1. Measurement and calculation block for rms value
In a mechanical tap-changer, the method shown in Fig. 2 is used
for measuring the rms voltage of the regulation bus, where the
Fig. 1. Schematic of the proposed electronic tap-changer based on a modied conventional controller used in a mechanical tap-changer.
J. Faiz, B. Siahkolah/ Electrical Power and Energy Systems 33 (2011) 210218 211
minimum delay of the low-pass lter is equivalent to 0.45 s or 20
cycles of the operating frequency. The process of tap-changing in a
mechanical tap-changer system is a slow process, but the delay
introduced does not produce a serious problem. However, an
electronic tap-changer operates fast and a real-time measurement
of the rms value of the regulation bus is expected. This is the rea-
son that the averaging concept of rms voltage cannot be used. One
of the best substitutions for the rms value of the voltage is the
instantaneous rms value of the voltage. Fig. 3 shows the block dia-
gram of this method.
Referring to Fig. 3, the rms value of instantaneous voltage can
be expressed as follows:
V
2mrms
t

1
T
Z
t
0
V
2
2m
t
0
V
2
2m
t
0
Tdt
0

s
1
T
Z
t
0
V
2
2m
t
0
dt
0
s
1
where T is the period of signal V
2m
(t), which is half of supply fre-
quency (10 ms). The response of the rms voltage detecting block
(for a = 10) and rms detecting with a low-pass lter (the conven-
tional method) for a step change of the sinusoidal function has been
shown in Fig. 4. The rms value of the instantaneous voltage is a very
useful value for the controller of the electronic tap-changer. This va-
lue contains the data of a half cycle of the waveform and measures
the variations of the output voltage amplitude over a maximum
period of 10 ms. For 50 Hz supply the full period is 20 ms and the
period of the rectied V
2m
(t) will be 10 ms (20 ms divided by 2). If
the supply frequency is slightly changed, by measuring the time be-
tween the voltages of zero-crossing in hardware system, this
change is measured and the measured time is used in the software.
Obviously transformer and tap-changer is designed for 50 Hz and
large change of the frequency not only affects the tap-changer but
also can seriously damage the transformer.
) (
1
10 ) ( ) (
1
2
2
X
ST
ms T X t V
m
=

Fig. 3. Block diagram of system for measuring rms value of instantaneous voltage of regulation bus in an electronic tap-changer.
Fig. 4. (a) Main signal, (b) response of rms detecting block (for a = 10) and (c) rms response of detecting with low-pass lter (conventional method) for step change of
sinusoidal function.
2 1 2
2
2
) (
/ 1
1
) ( ) ( X
a s
X t V
m
+
Fig. 2. Block diagram of system for measuring rms voltage of regulation bus in a mechanical tap-changer.
212 J. Faiz, B. Siahkolah/ Electrical Power and Energy Systems 33 (2011) 210218
3.2. Dead-band block
A dead-band (DB) is inserted after the DV calculation due to the
intrinsic limit of the tap-changer system and the discontinuity of
the system. This dead-band is always necessary. In the mechanical
tap-changer, DV reaches the saturation values of +1 and 1 after
passing from the dead-band block to the saturation block, because
it is only possible to change any tap to a higher or lower tap. How-
ever, in the electronic tap-changer, it is possible to jump from one
tap to another and there is no need for a saturation block.
It has been shown [7] that if the controller system is designed
such that DB is a xed parameter, then it must satisfy the following
condition:
2DB > V
2stepMax
2
where V
2StepMax
is obtained as follows:
V
2StepMax

V
2Max
a
0

Da
a
0
1 2n
max
1
Da
a
0
3
where n
max
is the maximum tap number, a
0
is the turn ratio of the
transformer and Da is the step variations of a with varying one
number in the tap. V
2Max
is the maximum voltage of the secondary.
It is noted that if condition (2) is not satised in determining DB,
oscillations will occur in the control loop.
3.3. Compensating block
On the contrary to a mechanical tap-changer, an electronic tap-
changer is a rapid system. Therefore, the compensator used in the
electronic tap-changer must be designed more carefully such that
it satises the control loop requirements and at the same time does
not slow down the system. So, a general compensating block is
used instead of a delay block, which is a special type of
compensator.
In [7], it has been shown that the use of an integrator in the
compensating block of an electronic tap-changer seems interesting
from a quality point of view. The integrator produces typically the
delay proportional with DV and it also has memory. Meanwhile,
the integrator extends the steady-state error to the minimum pos-
sible value. The integrator gain inuences the stability and also the
speed of the system. If the gain factor of this block is large, it causes
the oscillation of the control loop, and if the gain is too small, it
slows down the loop operation.
3.4. Quantizer, sampler, keeper and detector of zero-crossing and look-
up table
Since the row number of tap is an integer, a quantizer block
must be included. The range of the quantizer block output is be-
tween the maximum (+n
max
) and the minimum (n
max
) row num-
ber of tap. The reason for using the sample and hold block and also
the zero-crossing detector is that the tap position is allowed to be
changed only during the instants of the zero-crossing of current.
The reason for adding the look-up table is that any row of the num-
ber corresponds to a particular position of the switches, and the
position of the switches has already been stored in the memory
of the look-up table for later use.
The inputoutput characteristic block is shown in Fig. 5. The
output of the quantizer block is the row number of the tap. It is
clear from Fig. 5 that the system is non-continuous.
4. Software development
This section presents the developed software used in the micro-
processor briey.
4.1. General strategy for software design
Fig. 6 shows the block diagram of the electronic tap-changer
from a control point of view. The designed software in the micro-
processor is fully realized in the control part of the block diagram.
Output
1 2 3 -1
n
Max
-2 -3
1
2
1-
2-
n
Max
input
-n
Max
-n
Max
Fig. 5. Inputoutput characteristic of quantizer block.
Tapped transformer
and
switches connected
to taps
Detecting zero
crossing load
current
Converting
V
to tap number
Switches positions
considering V
Tap-changer
switches
command
Input
voltage
l
o
a
d

v
o
l
t
a
g
e
l
o
a
d

c
u
r
r
e
n
t
Output
voltage
V
Vrem
+

V
ref
=220 V
Sampling load
voltage and
computation of
rms value
c
o
n
t
r
o
l

s
e
c
t
i
o
n
Fig. 6. Block diagram of the electronic tap-changer from control point of view.
J. Faiz, B. Siahkolah/ Electrical Power and Energy Systems 33 (2011) 210218 213
It is noted that the controller block in Fig. 6 is the block converting
DV to tap number.
In order to convert the voltage and load current signals into
desired signals for the control system, three rectied full-wave
voltages in-phase with the load voltage, three rectied full-waves
in-phase with the load current, a square wave voltage in-phase
with the load voltage and a square wave voltage in-phase with
the load current are produced using an analogue processor board
(Fig. 7). Relation of load voltage and load current with the afore-
mentioned signals are presented in Fig. 8.
The reason for generating the three rectied signals from volt-
age (or current) covers a wider range of voltage with suitable accu-
racy. In the present paper, a single-phase prototype 220 V/220 V
transformer equipped with an electronic tap-changer has been dis-
cussed. If a load voltage signal of peak amplitude up to 350
p
2 is
covered, the ratio 350
p
2/5 = 99 must be used, while the load volt-
age peak is frequently around a rated value of 220
p
2 V. So by the
above ratio, the input signal A/D has an amplitude equal to 220
p
2/
99 = 3.14, while the amplitude of the input voltage of the A/D con-
verter of up to 5 V is permissible. This is the reason for using three
ratios, where one converts peak amplitude of 250
p
2 V into 4.5 V,
another 300
p
2 V into 4.5 V and the last one 350
p
2 V into 4.5 V.
Therefore, if in reading a channel of the A/D, the amplitude of
the voltage of one channel exceeds 4.5 V, sampling will be carried
out from another channel in order to keep the accuracy and read
the larger voltage. This is also true for current. The reason to pro-
duce digital signals in-phase with voltage and current is that when
rectifying full-wave voltage and current, the zero-crossing infor-
mation of these signals is eliminated (crossing from negative val-
ues to positive or vice-versa). This information exists in the
digital voltage and current signals and they are entered into the
micro-controller. The major feature of voltage and current digital
signals is that the edges of two signals determine the location of
zero-crossing voltage and load current. This is useful information
and may be more important than the rst feature. In particular,
the zero-crossing of current is required for switching at zero cur-
rent. Thus, digital voltage and load current signals contain informa-
tion about the time of zero-crossing of the voltage and load
current.
The general strategy for designing the software is based on the
following:
(1) Using the edge of the digital voltage for:
(a) Calculating the length of half the period of the load voltage
and consequently evaluating load voltage frequency (f);
(b) Measuring the frequency;
Fig. 7. Inputs and outputs of analogue processor board.
Load
voltage
t
Load
current
t
rectified
voltages
t
+5 v
Digital
voltage
+5V
t
Rectified
currents
t
+6 V
Digital
Current
5V
t
+5V
2 220
Fig. 8. Typical waveforms of input and output of analogue processor board.
214 J. Faiz, B. Siahkolah/ Electrical Power and Energy Systems 33 (2011) 210218
(c) Starting regular sampling of the voltage and current dur-
ing a half-period over the following time intervals:
t
samp

T
2
nsamp
2
4
where T/2 is the interval between two successive crossings of zero
voltage, t
samp
is the time between two successive samples of the
analogue signals and n
samp
is the sample number during a complete
cycle of the input voltage.
(d) Calculating the load power factor.
(2) Use the edge of digital current for:
(a) Calculating the load power factor;
(b) Applying switch commands to achieve zero current
switching.
The control system is implemented by taking all the above-
mentioned points into account. Using every edge, the half-period
time, which is now ended, is computed. This block does the sam-
pling, calculates the rms value edge, the time of the half-period
that has just ended is evaluated and t
samp
is then obtained by (4).
Now the block responsible for regular sampling of voltage and cur-
rent, evaluates DV and then converts it into a tap number.
Having the current edge, the load power factor is calculated and
the switch commands are applied. The high speed input (HSI) block
detects the edges of digital voltage and current, while the high
speed output (HSO) block programs the sampling interval (starting
the A/D at regular time intervals). Calculation of the rms value and
the conversion of DV into the tap number is carried out at the in-
stant of every voltage sample and pause routine the A/D. The dig-
ital voltage signal synchronizes the operation of the system. Every
edge of this signal indicates the end of a half cycle of voltage and
the start of the next half cycle. The necessary calculations, sam-
pling and evaluating required over the new half cycle is carried
out and programmed. So, in practice the HIS routine undertakes
the control programming. The HSO starts the A/D over a half cycle
in suitable time intervals and does this in parallel with the pro-
gram. The A/D pauses at the end of a conversion, after any sample
is taken by the A/D. The pause routine of the A/D then calculates
the rms value and DV and converts DV into the tap number. The
HSI block applies the switch commands corresponding with the
calculated tap number in A/D routine to the switch drivers at the
instant of detecting the current edge.
Based on the above, it is clear that the system is controlled by
the HSI pause routine, HSO block and pause block A/D. Thus, all
jobs are carried out in parallel with the main software program.
4.2. Converting DV into a tap number and switch commands
A curve that converts the value of DV(=V
ref
V
rms
) into the tap
number is a step curve with the hysteresis shown in Fig. 8. In this
gure, the width of the steps is 2a and the value of each curve over
every range, (2k1)a, a, (2k + 1)a, is a constant value of the tap
number k. The range of variation for k is: 24, 23, . . . , 0, . . . , 24.
As shown in Fig. 9, the hysteresis width is 2DV
offset
. Therefore:
For rising DV : T k; DV 2 2k 1a DV
offset
; 2k 1a DV
offset
5
For falling DV : T k; DV 2 2k 1a DV
offset
; 2k 1a DV
offset
6
For values of DV in the range of |DV| > (2k
max
+ 1)a, the curve va-
lue saturates and remains equal to its value at |k| = 24. Based on the
above explanation, in order to introduce the curve, it sufces that
the width of the step (DVSW = 2a) be the hysteresis value
(DVOFF = DV
offset
) and the maximum tap number (KMAX = k
max
) is
introduced to the program.
To prevent the use of the negative numbers, the curve is shifted
to the right by (2k
max
+ 1) on the horizontal axis and to the upper
side by k
max
on the vertical axis, so Fig. 10 is obtained. Therefore,
x is computed instead of DV and the value of SWPN is obtained
from this curve. In such a case the actual value of T is equal to
SWPN k
max
. Fig. 11 shows the block diagram of the process of
converting DV to the tap number. The low-pass lter is introduced
to the system with a cut-off frequency of A3 dB. To realize the low-
-a -3a -5a
2
-1
-2
-23
-24
1
2
2
49 47 45 5a 3a a
2 Voffset
Fig. 9. Hysteresis curve converting DV into tap number.
2 V
offset
2
1
4
4
8a 6a 4a 2a
(
2
k
m
a
x
-
1
)

2
a
(
2
k
m
a
x
)

2
a
(
2
k
m
a
x
+
1
)
2
a
3
Fig. 10. Shifted curve of Fig. 8 for preventing the use of negative numbers.
J. Faiz, B. Siahkolah/ Electrical Power and Energy Systems 33 (2011) 210218 215
pass lter, a trapezoidal model is used, which leads to a higher
accuracy. In this model, in addition to the input value at instant
t, an input and output at t 1 is also required. The spaces DV
and DV1 are assigned for this purpose.
Applying hysteresis is carried out such that the new SWPN is
compared with the old value, then:
1. If SWPN was not changed, hysteresis is not applied.
2. If SWPN was reduced, its value is modied using DVOFF.
3. If SWPN was increased, its value is modied using DVOFF.
Every tap number is equivalent with a specic on and off pat-
tern of the switches of the system. Table 2 shows the pattern cor-
responding with each number. This table is introduced as look-up
table to the micro-controller by the name of SEPO.
5. Experimental results
A prototype electronic tap-changer for a low-power transformer
have been constructed and tested. Specications of this tap-chan-
ger are summarized in Table 1. The test results for open-loop and
closed-loop cases will be presented below.
5.1. Open-loop control
The power circuit of the device and also command signals gen-
erated in the controller are tested and their performances are stud-
ied. For the open-loop case, a test software was developed, which
applies the tap number from the minimum value (24) and then
one number is added in every cycle (at the incident edge of digital
voltage signal) until the tap number becomes zero. At the zero tap
number, three cycles are paused and then the trend of re-increas-
ing the tap number continues from zero to the maximum value
(+24). If the tap approaches +24, the tap number jumps to 24.
Fig. 12 shows the output voltage waveform of the tap-changer
for the on-load case of the above-mentioned test software and
the load current equal to 5 A. According to this gure, 49 different
states for the output voltage are visualized. The linear steps of the
output voltage are also clear in the gure. The capability of jump-
ing from the highest tap number to lowest tap number has been
presented. A voltage drop of 1% can be visualized.
x=V+(2k
max
+1) a
A Applying
H Hysteresis
Tap No. = SWPN-k
max
Intermediate
SWPN
x
V
F Final
S SW WP PN N
t= Tap No.
Fig. 11. Block diagram of the process of transforming DV to the tap number.
Table 1
Specications of proposed electronic tap-
changer.
Number of phase 1
Regulated rms output voltage 220 V
Input rms voltage 220 V
No. of voltage steps 48
Step voltage for rated input 2 V
Maximum output current 20 A
Output power 5 kVA
Table 2
Position of one-by-one switches corresponding with every tape number.
No. Switches positions V
out
210
(V)
S
1
S

1
S
2
S

2
S
3
S

3
S
4
S

4
S
5
S

5
S
6
S

6
1 0 1 0 0 1 0 0 1 0 0 1 0 48
2 0 0 0 1 1 0 0 1 0 0 1 0 46
3 0 1 1 0 0 0 0 1 0 0 1 0 44
4 1 1 0 0 0 0 0 1 0 0 1 0 42
5 1 0 0 1 0 0 0 1 0 0 1 0 40
6 0 0 1 0 0 1 0 1 0 0 1 0 38
7 1 0 0 0 0 1 0 1 0 0 1 0 36
8 0 1 0 0 1 0 0 0 0 1 1 0 34
9 0 0 0 1 1 0 0 0 0 1 1 0 32
10 0 1 1 0 0 0 0 0 0 1 1 0 30
11 1 1 0 0 0 0 0 0 0 1 1 0 28
12 1 0 0 1 0 0 0 0 0 1 1 0 26
13 0 0 1 0 0 1 0 0 0 1 1 0 24
14 1 0 0 0 0 1 0 0 0 1 1 0 22
15 0 1 0 0 1 0 0 1 1 0 0 0 20
16 0 0 0 1 1 0 0 1 1 0 0 0 18
17 0 1 1 0 0 0 0 1 1 0 0 0 16
18 1 1 0 0 0 0 0 1 1 0 0 0 14
19 1 0 0 1 0 0 0 1 1 0 0 0 12
20 0 0 1 0 0 1 0 1 1 0 0 0 10
21 1 0 0 0 0 1 0 1 1 0 0 0 8
22 0 1 0 0 1 0 1 1 0 0 0 0 6
23 0 0 0 1 1 0 1 1 0 0 0 0 4
24 0 1 1 0 0 0 1 1 0 0 0 0 2
25 1 1 0 0 0 0 1 1 0 0 0 0 0
26 1 0 0 1 0 0 1 1 0 0 0 0 2
27 0 0 1 0 0 1 1 1 0 0 0 0 4
28 1 0 0 0 0 1 1 1 0 0 0 0 6
29 0 1 0 0 1 0 1 0 0 1 0 0 8
30 0 0 0 1 1 0 1 0 0 1 0 0 10
31 0 1 1 0 0 0 1 0 0 1 0 0 12
32 1 1 0 0 0 0 1 0 0 1 0 0 14
33 1 0 0 1 0 0 1 0 0 1 0 0 16
34 0 0 1 0 0 1 1 0 0 1 0 0 18
35 1 0 0 0 0 1 1 0 0 1 0 0 20
36 0 1 0 0 1 0 0 0 1 0 0 1 22
37 0 0 0 1 1 0 0 0 1 0 0 1 24
38 0 1 1 0 0 0 0 0 1 0 0 1 26
39 1 1 0 0 0 0 0 0 1 0 0 1 28
40 1 0 0 1 0 0 0 0 1 0 0 1 30
41 0 0 1 0 0 1 0 0 1 0 0 1 32
42 1 0 0 0 0 1 0 0 1 0 0 1 34
43 0 1 0 0 1 0 1 0 0 0 0 1 36
44 0 0 0 1 1 0 1 0 0 0 0 1 38
45 0 1 1 0 0 0 1 0 0 0 0 1 40
46 1 1 0 0 0 0 1 0 0 0 0 1 42
47 1 0 0 1 0 0 1 0 0 0 0 1 44
48 0 0 1 0 0 1 1 0 0 0 0 1 46
49 1 0 0 0 0 1 1 0 0 0 0 1 48
216 J. Faiz, B. Siahkolah/ Electrical Power and Energy Systems 33 (2011) 210218
5.2. Closed-loop test
The performance of the power circuit, switch drivers and the
generation of the command signals of the controller are veried
by the open-loop test. The capabilities of the control system for
output regulation are studied by means of the closed-loop test.
The closed-loop performance will be presented for line and load
voltage regulation.
5.2.1. Line regulation
The purpose of line regulation is to stabilize the output voltage
against input voltage uctuations. In this case, the load current is
xed. Fig. 13 shows the output voltage waveform of the tap-chan-
ger for the input voltage equal to 241 V and the no-load case. The
tap number in the gure is 24. It is clear from this input voltage,
the output voltage remains constant. Fig. 14 shows the tap-changer
output voltage for on-load current equal to 5 A and input voltage
241 V. The tap numbers in these cases are evident from the gures.
Thus far, the static line regulation has been studied. To investi-
gate the dynamic line regulation and transient states, the input
voltage is quickly varied by means of an auto-transformer. In all la-
ter tests the integrator factor is set to 10, unless another value is
mentioned. The output voltage waveform for quick input voltage
variations with the lter inserted has been obtained and shown
in Fig. 15. It is clear that inserting this lter leads to a second-order
closed-loop system and there is a small oscillation. Fig. 16 shows
the tap-changer output voltage waveform for integrator factor
equal to 50, as seen at the output voltage uctuates.
As shown in [30], the output voltage can be easily regulated
against sudden changes of the load at a xed input voltage. It
means that the scheme is stable and reliable under transient load
uctuations.
6. Conclusions
The design stages of a fully electronic tap-changer were pre-
sented in this paper. This included the design of the power circuit,
aspects relating to its control and software design. The simulation
results of a prototype low-power (5 kVA) electronic tap-changer
were also presented and a prototype built and tested. The experi-
mental results veried the design procedure in both hardware
and software parts. The prediction and simulation results agreed
well with the test results. If the cost of high voltage and high cur-
rent power electronics devices decrease considerably and the prop-
er protection equipment employed, the tap-changer with a similar
structure can be fully used in distribution systems as described in
[8].
Fig. 12. Tap-changer output voltage waveform for 5 A load and the test software:
vertical axis scale: 175 V and horizontal axis scale: 0.1 s [30].
Fig. 13. Tap-changer output voltage waveform for input voltage 241 V and no-load
case: vertical axis scale: 220 V and horizontal axis scale: 0.05 s [30].
Fig. 14. Tap-changer output voltage waveform for input voltage 241 V and 5 A load:
vertical axis scale: 220 V and horizontal axis scale: 0.05 s [30].
Fig. 15. No-load output waveform for sudden increase of input voltage from 170 V
to 220 V with low-pass software lter: vertical axis scale: 220 V and horizontal axis
scale: 0.1 s [30].
Fig. 16. Output voltage waveform for integrator factor equal to 50: vertical axis
scale: 220 V and horizontal axis scale: 0.1 s [30].
J. Faiz, B. Siahkolah/ Electrical Power and Energy Systems 33 (2011) 210218 217
References
[1] IEEE Standard Dictionary of Electrical and Electronics Terms. 3rd ed.; 1894. p.
9189.
[2] Gebert KL, Edwards KR. Transformers 1974:20721.
[3] Central Station Engineers of the Westinghouse Electric Corporation. Electrical
transmission and distribution reference book. p. 1214.
[4] Austen Stigant S, Franklin AC. The J & P Transformer Book. 10th ed.
Butterworth; 1976. p. 22767.
[5] Kang P, Birtwhistle D. Condition assessment of power transformer on-load tap-
changers using. IEEE Trans Power Deliv; 2003.
[6] Gao D, Lu Q, Luo J. A new scheme for on-load tap-changer of transformers. In:
International conf on power system technology, 2002, Power Con; 2002. p.
101620.
[7] Shuttleworth R, Tian X, Fan C, Power A. New tap changing scheme. IEE Proc
Electr Power Appl 1996;143(1):10812.
[8] Capitanescu F et al. Decentralized tap-changer blocking and load shedding
against voltage instability: prospective tests on the RTE system. Int J Electr
Power Energy Syst 2009;31:5706.
[9] Robert ME, Ashman WG. A thyristor assisted mechanical on-load tap-changer.
In: IEE Proc power thyristors and their applications; 1969. p. 18592.
[10] Cooke GH, Williams KT. Thyristor assisted on-load tap-changers for
transformers. In: Fourth international conf on power electronics and
variable-speed drives; 1990. p. 12731.
[11] Cooke GH, Williams KT. New thyristor assisted diverter switch for on-load
transformer tap-changers. IEE Proc Electr Power Appl 1992;139(6):
50711.
[12] Shuttleworth R, Power A, Tian X, Jiang H, Alzahawi BA. A novel thyristor-
assisted tap-changer scheme. In: IEE 14th international conf on electricity
distribution, vol. 1; 1997. p. 28/15.
[13] Musgrave G, OKelly D. Improvement of power system transmission by solid-
state techniques. In: IEE conf pub, vol. 123; 1974. p. 22833.
[14] OKelly ] D, Musagrave G. Improvement of power system transient stability
limits. Proc IEE 1973 1997;120(2):24753.
[15] Y-Zai FQ, QKelly D. Solid-state on-load transformer tap-changer. IEE Proc
Electr Power Appl 1996;143(6):48191.
[16] Larsson T, Innanen R, Norstrom G. Static electronic tap-changer for electric
machines and voltage control. In: IEEE fast phase and drives conf; 1997. p. TC3/
4.14.3.
[17] Degeneff RC. A new concept for a solid-state on-load tap-changer. In: IEE conf
pub no. 438, vol. 1; 1997. p. 7/14.
[18] Dernirci O, Torrey DA, Degeneff RC, Schaeffer FK, Frazer R. A new approach to
solid-state on-load tap-changing transformers. IEEE Trans Power Deliv
1998;13(3):95261.
[19] Bauer P, deHaan SWH. Electronic tap changer for 500 kVA/10 kV distribution
transformers: design, experimental results and impact in distribution
network. IEEE IAS 1998;2:15307.
[20] Bauer P, deHaan SWH, Paap GC. Solid-state control for transformer tap
changing, PEMC 1996, Budapest; 1996. p. 3944.
[21] Bauer P, deHaan SWH. Electronic tap-changer for 10 kV distribution
transformers. EPE 1997;97:3/10105.
[22] Bauer P, de Haan SWH. Protective device for electronic tap-changer for
distribution transformers. EPE 1997;97:4/2827.
[23] Faiz J, Siahkolah A. Optimal congurations for taps of windings and power
electronics switches in electronic tap-changers of power transformers. Proc
IEE, Pt. C. 2002;149(5):51724.
[24] Faiz J, Siahkolah B. New solid-state on-load tap-changers topology for
distribution transformers. IEEE Trans Power Deliv 2003;18(1):13641.
[25] Faiz J, Siahkolah B. Effect of solid-state on-load distribution tap-changer on
power quality enhancement. Int J Eng, IR Iran 2004;17:14356.
[26] Faiz J, Siahkolah B. Sag mitigation by an electronic tap-changer: specications
and comparisons with other custom power tools. IEE, Pt. C
2005;152(5):697704.
[27] Faiz J, Siahkolah B. Differences between conventional and electronic tap-
changers and modications of controller. IEEE Trans Power Deliv
2006;21(3):13429.
[28] Faiz J, Siahkolah B. New controller for an electronic tap-changer part I: design
procedure and simulation results. IEEE Trans Power Deliv 2007;22(1):2239.
[29] Faiz J, Siahkolah B. New controller for an electronic tap-changer part II:
measurement algorithm and test results. IEEE Trans Power Deliv
2007;22(1):2307.
[30] Faiz J, Siahkolah B. Implementation of a low power electronic tap-changer in
transformers. IET J Electr Power Appl 2008;2(6):36273.
[31] Bassett DL. Control of tap change under load transformers through the use of
programmable logic controllers. IEEE Trans Power Deliv 1993;8(8):175965.
[32] Wheeler P, Clare J, Empringham L, Apap M, Bland M. Matrix converters. Power
Eng J 2002:27382.
[33] Siahkolah B. Design and optimization of a full-electronic tap-changer for a
distribution transformer. Ph.D. Thesis, Department of Electrical and Computer
Engineering, University of Tehran; 2004.
[34] Bauer P, deHaan SWH. Electronic tap-changer for 500 kVA/10 kV distribution
transformers: design, experimental results and impact in distribution
network. IEEE IAS 1998;2:15307.
218 J. Faiz, B. Siahkolah/ Electrical Power and Energy Systems 33 (2011) 210218

You might also like