Professional Documents
Culture Documents
DESIGN PRACTICE
DESIGN PRACTICE
5-DP-001
DESIGN PRACTICE Pages 2 page 8
1.0 INTRODUCTION:-
5-DP-001
DESIGN PRACTICE Pages 3 page 8
Differential relays operates only for faults within their protected zone
they are inherently Selective and can operate much faster. Accordingly
they will provide better protection and in large generating systems
maintaining stability by fast clearing faulted generators.
5-DP-001
DESIGN PRACTICE Pages 4 page 8
The trip & alarm setting of this relay depends on the insulation class &
temperature rise of the generator. The generator manufacture should be
consulted during the setting of this relay.
Loss of excitation can occur when the generator is operating at only 20-
30% of rated power. In this case the machine runs as induction generator
executed from the others machines on the system. The generator quickly
over heats due to the system slip frequency currents induced in it ,
generator terminal voltage decreases and the stator currents starts to
increase.
The last might cause instability of the power system & over heating of the
other machines.
5-DP-001
DESIGN PRACTICE Pages 5 page 8
N.B. This relay should be used only with several generators connected
to isolated bus.
Over voltage may occur due to the transient surges on the network and
can also be caused from other reasons such as :
A typical setting for over voltage relay (59) is 107 % of rated stator
voltage with a time delay of 10 sec. to allow for transients due to load
switch off / rejection , over voltages resulting from recovery from
fault or motor starting
5-DP-001
DESIGN PRACTICE Pages 6 page 8
This protection is not required when the generator has large negative
phase sequence capacity.
5-DP-001
DESIGN PRACTICE Pages 7 page 8
5-DP-001
DESIGN PRACTICE Pages 8 page 8
REFERENCES:
5-DP-001