You are on page 1of 9

PAGE 1 OF 8

DESIGN PRACTICE

GENERATOR PROTECTION SCHEME

0 07/ 06 / 04 ISSUED FOR INFORMATION Tarek Hussein Hussein

REV. DATE REVISIONS BY CH'D APPR.


DESIGN PRACTICE Pages 1 page 8

DESIGN PRACTICE

GENERATOR PROTECTION SCHEME

5-DP-001
DESIGN PRACTICE Pages 2 page 8

1.0 INTRODUCTION:-

This document is concerned with generator protection aspects. It


describes various types of generator protection functions provide a basis
for applying proper generator protection schemes

2.0 TYPES OF FAULTS :-

The following problems required addressing & consideration from the


point of view of applying protection:-

• Short circuit protection


• Stator electrical faults
• Loss of excitation
• Over voltage
• Overload protection
• Unbalanced load protection
• Under /over frequency protection
• Mechanical Faults

2.1 SHORT CIRCUIT PROTECTION

2.1.1 PROTECTION AGAINST 3 PHASE , SHORT CIRCUIT (51 V)

Voltage restrained over current relay is one of the most commonly


used protection against generator external short circuit protection.

The reason of introducing a voltage signal into over current device


is to provide a relay that can ride through momentary overload
conditions such as motor starting and still provide proper short
circuit protection.

The voltage is said to restrain the current element. Typical voltage


setting of this relay is (80-90%) of nominal.

5-DP-001
DESIGN PRACTICE Pages 3 page 8

2.1.2 EARTH FAULT PROTECTION :-( 51 G )

A relay connected to a current transformer mounted on the Neutral-


Earth conductor can provide back up protection for all earth relays at
the generator voltage level, It provides protection against generator
internal earth faults, however not all the stator winding can be
protected against earth fault using this protection function.

The relay settings should be higher than the expected harmonic


current following the neutral during normal load condition and not
more than 33% of the maximum earth faults generator currents.

2.2 STATOR WINDING ELECTRICAL FAULTS:-

Failure of the stator winding or connection insulation can result in a


severe damage to the winding and stator core.
The extent of the damage depends on the magnitude and duration of the
fault current.

2.2.1 DIFFERENTIAL PROTECTION (87)

To respond quickly to a phase fault with damaging heavy currents, high


speed differential protection is normally applied to generator equal or
higher than 500 KVA.

Differential relays operates only for faults within their protected zone
they are inherently Selective and can operate much faster. Accordingly
they will provide better protection and in large generating systems
maintaining stability by fast clearing faulted generators.

The zone of protection of differential protection can be extended to


cover the connecting cabling.

Typical setting of the differential relay is 5- 10% difference in CT’s


current.

5-DP-001
DESIGN PRACTICE Pages 4 page 8

2.2.2 STATOR OVERHEATING PROTECTION (49Q):

Accidental over loading might occur through the combination of full


active load current governed by the primemover (KW) output and an
abnormally high reactive current component KVAR output, governed
by the level of rotor excitation.
Thermal relay (49 Q ) is normally connected to RTD’S resistance
temperature detectors imbedded in the stator winding of generators .It
Provides protection for the machine in the over load area but not fault
conditions

Each phase of the winding shall be connected to 2 RTD’S at the hot


spot defined by supplier

The trip & alarm setting of this relay depends on the insulation class &
temperature rise of the generator. The generator manufacture should be
consulted during the setting of this relay.

2.3 PROTECTION AGAINST LOSS OF EXCITATION:-

Loss of excitation can occur when the generator is operating at only 20-
30% of rated power. In this case the machine runs as induction generator
executed from the others machines on the system. The generator quickly
over heats due to the system slip frequency currents induced in it ,
generator terminal voltage decreases and the stator currents starts to
increase.

Rapid automatic disconnection is then required in order not only to


protect the generator but also to protect other machines from which the
faulted machine withdraw its excitation as an induction generator .

The last might cause instability of the power system & over heating of the
other machines.

Relay (40) loss of excitation is an impedance viewed from the generator


terminals. This relay must be used with a proper time delay to stabilize
the protection against maloperation in response to transient conditions.

5-DP-001
DESIGN PRACTICE Pages 5 page 8

N.B. This relay should be used only with several generators connected
to isolated bus.

2.4 PROTECTION AGAINST OVER VOLTAGES

Over voltage may occur due to the transient surges on the network and
can also be caused from other reasons such as :

a) Defective operation of AVR when the machine is running in


isolated operation.
b) Sudden loss of load (Due to the tripping of outgoing feeders
leaving the machine isolated or feeding over small load).
c) Operation under manual central of the voltage regulator. A sudden
change in load particularly reactive powered component will give
rise a substantial change in voltage.

A typical setting for over voltage relay (59) is 107 % of rated stator
voltage with a time delay of 10 sec. to allow for transients due to load
switch off / rejection , over voltages resulting from recovery from
fault or motor starting

2.5 UNDER VOLTAGE PROTECTION :-( 27)


(OVER LOAD PROTECTION )

Under voltage protection is used for generator feeding an isolated


system. It protects generators against prolonged over load or failure of
AVR.

Setting must be chosen to avoid maloperation during voltage dips


during power system fault clearance or associated with motor starting

5-DP-001
DESIGN PRACTICE Pages 6 page 8

2.6 PROTECTION AGAINST UNBALANCED CONDITIONS


RELAY FUNCTION (46)

Phase balanced load produces a reaction field that is constant and


rotates synchronously with the rotor field system. Any phase unbalance
can be resolved into positive and negative sequence component.

The positive sequence component is similar to the normal balanced


load. The zero sequence produces no main armature reaction.

The negative sequence component field reaction rotates in the opposite


direction to the DC field system, thereby producing double frequency
currents in the field system and in rotor body. The resulting eddy
currents are very large and cause severe heating of the rotor.

This protection is not required when the generator has large negative
phase sequence capacity.

N.B Enppi specification calls for 8 % negative phase sequence


capacity

2.7 UNDER / OVER FREQUENCY PROTECTION 81%


SEQUENCE CAPACITY :-

The governor fitted to the prime mover normally provides protection


against over frequency, however over frequency may occur in case
sudden removal loads. Under frequency as a result of over load of
generators operating in isolated systems. Prime mover & generator load
must be protected against excessively low Frequency by tripping of the
generators concerned.

Typical settings of under frequency is 49 HZ for 20 seconds & 48 HZ


for 0.5 seconds.

Over frequency setting 51 HZ for 10 seconds and 52 HZ for 1 second

5-DP-001
DESIGN PRACTICE Pages 7 page 8

2.8 MECHANICAL FAULTS:-

2.8.1 REVERSE POWER PROTECTION :(32)

Reverse power protection in its simple form means motoring of the


prim mover , if the prime mover has lost power for any reason and
start to be motored by the system. Diesel engine could catch fire or
suffer from damages to its gear box or shafts. Gas turbine could
suffers from gear box damage.

The manufacture value for motoring percentage of rated power


should be consulted.

The reverse power protection should be provided with time delay, on


operation to prevent operation of the relay with transient power
swings that may arise following synchronization

Typical protection settings is 50% of motoring power .This setting


must be checked during commissioning.

2.8.2 GENERATORS BEARING PROTECTION: -(38)

Failure of the generator lubrication system may cause over heating


of generator bearing. Consequently causing mechanical damage.

Resistance temperature detectors (RTD’s) embedded near the


driving & non driving end bearing to trip the generator breaker in
case of over heating of the bearing.

The generator manufacture should be consulted to provide this


setting.

5-DP-001
DESIGN PRACTICE Pages 8 page 8

REFERENCES:

• ALSTOM NETWORK PROTECTION & ALSTOM

• BROWN & ROOT DESIGN PRACTICE

• ENPPI SPECIFICATION 0000-000-510-06

5-DP-001

You might also like