Trane ZSM-11-1 is a human interface to be used in conjunction with the ZN523 Zone Controller. The ZSM-11-1 integrates a
convenient user interface with a complete function set. It offers user friendly comfort control through an LCD display and 3
control buttons.

Main features
Zone temperature measurement
Temperature setpoint and fan speed adjustment
Timed Override Pushbutton
Occupancy status and controller status indication
Multi icon LCD display

Physical presentation













Functions - Operation
Display icons



Temperature setpoint selection
Press the enter/validate key continuously for 1 second, then release it. If Icon is not blinking, press again the same
key for one second, then release, the icon is now blinking.
Within 5 seconds, use either the down or up key for adjusting a cooler or warmer setpoint.
The bar graph indicates the desired temperature setpoint:


To validate the choice, either press the enter/validate key or wait 2 seconds, until the icon is no longer blinking.

ZSM-11-1
80 mm
80 mm 32 mm
Occupancy status
Relati ve setpoint position
Unit alarm indication
Blinking: Fan speed adjustment mode
Blinking: Setpoint adjustment mode
Current temperature
(if option supported)
cooler
warmer
Connection to the ZN523
controller with RJ9 connector
Zone temperature sensor
Control buttons
Increase value
Enter / Validate
Decrease value
Occupancy Pushbutton
Controller status indication
BAS-SVX07A-E4 2




Fan speed adjustment
Press the enter/validate key continuously for 1 second, then release it. If icon is not blinking, press again the
same key for one second, then release, the icon is now blinking.
- The buttons and allow the user to select the desired ventilation mode


These are the available positions:






Timed override pushbutton / Controller status indication

Use key for switching from one mode to another.

If unoccupied the following icon appears:

- Push button once: Timed override activated, icon becomes and blinking.


- Push button again: timed override is canceled and the unit returns to unoccupied mode. Icon becomes

Note: After 120 minutes (typically) the controller reverts to unoccupied mode automatically. Should the user want to
extend the duration while already in timed override mode, he can press the push button for 5 seconds, and the timer
reverts to 120 minutes (typically).

Occupant call
By pressing the three push buttons simultaneously, for a duration of 5 seconds, a signal is sent
to the BMS (if any) for requesting help. This signal can be cleared only from the BMS after it has
been acknowledged. Whenever an occupant call is active the bell icon appears in the upper
left corner.


Unit fan speed

Fan Speed 3


Fan Speed 2


Fan Speed 1


Automatic Fan Speed


Ventilation Stopped
Displayed icons
ZSM-11-1
3 BAS-SVX07A-E4





Product specifications
Ambient Limits
Operating:
Temperature: 5C to 35C
Relative humidity: 5% to 95% non-condensing
Storage:
Temperature: -40C to 70C
Relative humidity: 5% to 95% non-condensing
Temperature setpoint adjustment
Setpoint offset is adjustable from -1K/+1K et -5K/+5K
(adjustable in the ZN523 controller) Step: 0,5 or 1 K
Power Supply
Thermostat is powered by the ZN523 controller
Enclosure
Material ABS UL94V0
Color: white (RAL 9010)
Dimensions: 80 mm x 80 mm x 32 mm
Degree of protection
IP 30
Standards
Product security:
EN 60730-2-9: Temperature sensing devices
Electromagnetic compliance
EN 50081-1: Emission
EN 50082-2: Immunity



Mounting recommendations

Location:
- Select a location, near the controlled equipment to reduce wiring costs, and EMC interference risks. Max distance is 12 m
- Device MUST not be directly exposed to sunlight nor mounted near heat/cool source
- Device should typically be installed at 1.5m above floor for correct temperature measurement performance.














Wiring diagram

Connector: RJ 9
Cable length: 12 m maximum
Recommended cable: FCC-68 flat cable, 4 wires, 26 AWG


Dimensions
typiques
80mm.
80mm. 60mm.
60mm.
RJ 9
32mm
Typical device
dimensions
Location
recommendations
4
2
1
3
1
3
4
2
RJ 9 RJ 9
to ZM terminal
on ZN523
Back of ZSM-11-1
ZSM-11-1

www.trane.com

For more information contact
your local sales office
or e-mail us at comfort@trane.com



Literature Order Number BAS-SVX07A-E4
Date 1006
New
LiteratureStocking Location Europe

Trane has a policy of continuous product and product data improvement and reserves the right to change