CBE - Active Chilled Beam
CBE
Active Chilled Beam
Combined cooling, heating, and supply air unit for
exposed installation
Ideal solution for applications where good indoor
environment, and individual room control are
appreciated
Typical applications: office rooms, landscape office, etc.
Enhanced life-cycle performance with low air and
water flow rates.
In-built flexibility for easy and fast adaptation of
operation during space layout and usage changes
Individually adjustable velocity conditions with
Halton Velocity Control (HVC)
In-built flexibility of partition wall relocations with
Halton Velocity Control
Rapid adjustment of operation in situations of
change without the need to change or plug nozzles.
Product Models & Accessories
Model with combined cooling and heating coil
Model with air flow adjustment damper
Different appearance options to suit the interior
Cable tray, duct cover, integrated control valves and
actuators as accessories
90 91
2
0
/
C
B
E
/
0
0
0
0
/
1
0
0
8
/
E
N
CBE - Active Chilled Beam
CBE
Active Chilled Beam
QUICK SELECTION
Pa 72 108 144 180 216 252 288
qv l/s 10 15 20 25 30 35 40
m
3
/h 36 54 72 90 108 126 144
Leff
1200 Pw 258 299 325
NZ/DPtot B/71 C/90 D/79
Lmin 2,2 5 5
Ld 2 3,2 3,2
1500 Pw 337 405 417 435
NZ/DPtot A/124 B/103 C/105 D/82
Lmin 3 3 5,8 5
Ld 2,2 2,4 3,4 3
1800 Pw 366 439 566 5
NZ/DPtot A/88 B/72 B/129 C/117
Lmin 2,2 2,2 3,8 4,6
Ld 1,8 1,8 2,4 3,4
2100 Pw 394 556 604 737 682 759
NZ/DPtot A/66 A/148 B/95 B/149 C/126 D/113
Lmin 2,2 3,4 4 4,2 6 5,6
Ld 1,8 2,4 2,2 2,4 3,4 3,0
2400 Pw 592 641 780 743 823 808
NZ/DPtot A/116 B/74 B/115 C/99 C/134 D/89
Lmin 2,2 2,2 3,4 2,2 4 5
Ld 2 1,8 2,2 3 3,4 3
2700 Pw 625 676 821 965 888 972
NZ/DPtot A/93 B/59 B/92 B/132 C/108 C/141
Lmin 2,2 1,8 2,6 3,8 5,4 6,2
Ld 1,8 1,8 2 2,4 3 3,4
3000 Pw 655 839 859 1008 1157 1039
NZ/DPtot A/76 A/136 B/75 B/108 B/147 C/117
Lmin 2,2 2,2 2,2 3 3,8 4,2
Ld 1,8 2 1,8 2,2 2,4 3,2
3300 Pw 686 876 898 927 1018 1108
NZ/DPtot A/64 A/114 B/63 C/55 C/75 C/98
Lmin 1,8 2,6 2,2 4 3,8 4,6
Ld 1,4 1,8 1,8 2,2 2,4 2,8
3600 Pw 912 995 1092 1082 1175
NZ/DPtot A/97 B/60 B/77 C/65 C/84
Lmin 2,2 1,8 2,2 2,4 3,8
Ld 1,8 1,8 1,8 2,4 2,6
3900 Pw 945 1145 1133 1145 1241
NZ/DPtot A/83 A/130 B/66 C/56 C/73
Lmin 1,8 3,8 2,2 2,6 3,4
Ld 1,8 2 1,8 2,2 2,4
Performance values are presented for operation with HVC in position 3.
If Lmin will be > 5 m then use HVC
The impact of HVC compared to presented values in average:
position 2: -21% of Pw and Position 1: -38 % of Pw
Leff Effective length, length of cooling coil, mm
Pa Supply air cooling capacity, W
Pw Coil capacity, W
NZ Nozzle type
DPtot Chilled beam chamber pressure, Pa
Lmin Minimum distance between central lines of two supply
units, m
Ld Distance from the supply unit, at which air jet detaches
from ceiling, m

Room temperature (Tr) = 24 C
Chilled water inlet temperature (Twin) = 15 C
Chilled water outlet temperature (Twout) = 18 C
Supply air temperature (Ta) = 18 C
A-weighted sound pressure level,
reduced by total equivalent absorption
surface of 10m
2
, dB(A) red 10m
2
sab < 35 dB(A)
92 93
2
0
/
C
B
E
/
0
0
0
0
/
1
0
0
8
/
E
N
CBE - Active Chilled Beam
Material and finishing
Cooling/heating water pipe connections are Cu15/
Cu10 with wall thickness of 1.0 mm fulfilling the
requirements of European Standard EN 1057:1996.
PART MATERIAL FINISHING NOTE
Front panel Pre-painted galvanised steel Polyester-painted White RAL 9010 /
20% gloss
Special colours available
Polyester-epoxy-painted
Duct cover Pre-painted galvanised steel Polyester-painted White RAL 9010 /
20% gloss
Special colours available
Polyester-epoxy-painted
Side plates Pre-painted galvanised steel Polyester-painted White RAL 9010 /
20% gloss
Special colours available
Polyester-epoxy-painted
End plates Galvanised steel Polyester-epoxy-painted White RAL
9010 / 20% gloss
Special colours available
Polyester-epoxy-painted
Cable tray Pre-painted galvanised steel Polyester-epoxy-painted White RAL
9010 / 20% gloss
Special colours available
Polyester-epoxy-painted
Supply air plenum Galvanised steel Special colours available
Brackets Galvanised steel
Coil pipes Copper
Coil fins Aluminium
The maximum operating pressure for chilled/hot water
pipework is 1.0 MPa. The supply air duct connection is
D125 mm.
PRODUCT MODELS AND ACCESSORIES
ACCESSORY MODEL CODE DESCRIPTION NOTE
Combined cooling and
heating coil
TC = H Coil with hot water circulation Cooling/heating copper water pipe
connections are 15/10 mm
Visual appearance VA = See product
code
For appearance options Selected options have the same
performance data and dimensions.
Control valve CV = See product
code
Valves with adjustable kvs value (Danfoss RA-C
dn15) or with max flow limit function (Danfoss
AB-QM dn 10 in heating and Danfoss AB-QM dn
15 in cooling)
Delivered factory fitted or loose. If
control valves are factory fitted,the
location of the pipe connections
cannot be changed on the site.
Valve actuator VM = See
product code
Thermal on/off actuators (230 VAC NC or 24 VAC
NC for both valve types.
Delivered factory fitted or loose
Cable length 1.2m.
Cable tray AC=KH Prepainted Length of the cable tray = Beam -
250 mm
Airflow adjustment
damper
FD = Y MSM damper Removable through access panel
Duct cover Subproduct, DC Self-supporting cover plate.
No need for installation brackets
Available in length 300, 400, 500,
600
92 93
2
0
/
C
B
E
/
0
0
0
0
/
1
0
0
8
/
E
N
CBE - Active Chilled Beam
Coil length 900,+100,..,4500
L 1200,+100,..,4800
kg/m 16
The front panel of the chilled beam is divided into two equal
sections in chilled beams longer than 2400 mm.
DIMENSIONS AND WEIGHT
Cable tray
Length of the cable tray = beam 250 mm
Valves
94 95
2
0
/
C
B
E
/
0
0
0
0
/
1
0
0
8
/
E
N
CBE - Active Chilled Beam
Appearance options
Appearance: B
Rounded, round perforation
Appearance: A
Rounded, oval perforation
Appearance: C
Angular, oval perforation
Appearance: D
Angular, round perforation
94 95
2
0
/
C
B
E
/
0
0
0
0
/
1
0
0
8
/
E
N
CBE - Active Chilled Beam
Function
The CBE unit is an active chilled beam for exposed
installation.
The primary supply air enters the plenum of the
active chilled beam, from which it is diffused into
the room through nozzles and supply slots on the
top of the beam. The supply air nozzle jets efficiently
induce ambient room air through the heat exchanger,
where it is either cooled or heated. The supply air jet
is directed horizontally along the ceiling surface. The
recommended minimum distance is 600 mm from the
wall and 100 mm from the ceiling.
Velocity control in the occupied zone
Halton Velocity Control (HVC) is used for adjusting
room air velocity conditions either when room layout
is changed (e.g., in cases where the chilled beam is
located near the partition wall) or when local, individual
velocity conditions need to be altered. Halton velocity
control adjustment has an impact on the induced room
air flow through the heat exchanger, and therefore it
either increases or decreases both the velocities in
the occupied zone and the cooling/heating capacity of
the chilled beam.
Position 1 = throttle position Position 2 = normal position
Position 3 = boost position
Halton Velocity Control involves manual velocity
adjustment with three different positions: 1 = throttle
position, 2 = normal position, and 3 = boost position.
The Halton velocity control system is divided into
sections to enable the adjustment of conditions in
different parts of the occupied zone.
It is recommended to design the chilled beam in the
normal position in order to allow both throttle and boost
functions during the buildings life cycle.
96 97
2
0
/
C
B
E
/
0
0
0
0
/
1
0
0
8
/
E
N
CBE - Active Chilled Beam
Temperature control
In heating mode, it is recommended for the temperature
difference between the jet outlet and room air to be no
more than 3 C. The temperature of the inlet water to
the heat exchanger should not be higher than 35 C.
Optimal heating performance requires operation using
the designed primary air flow rate. Thus, the air handling
unit shall be in operation during heating periods to
guarantee proper heating performance.
Cooling and heating capacity control
The chilled beam can be equipped in the factory
with either a standard control valve or a combination
control valve. Both control valves are operated by
a thermal actuator applying the on/off operation
principle.
The standard control valve has an adjustable kvs
value. The combination control valve has an adjustable
nominal water flow rate and there is a pressure
difference measurement across the control valve in
order to ensure that enough pressure difference (min.:
16 kPa) is available to achieve the adjusted water
flow rate and the automatic balancing in use. See
Document-section for more information.
It is also possible to locate the valves under the duct
cover at the building site.
96 97
2
0
/
C
B
E
/
0
0
0
0
/
1
0
0
8
/
E
N
CBE - Active Chilled Beam
Installation
The CBE unit is suitable for exposed installation in
the ceiling, typically lengthwise in the room. It is
recommended to position the beam no closer than
600 mm from the wall and 100 mm from the ceiling.
The chilled beam ceiling brackets can be fixed directly
to the ceiling surface or suspended using threaded
drop rods (8 mm). It is recommended that the bracket
be positioned one quarter of a unit length (L/4) away
from the end of the beam.
Install the main pipelines of the cooling and heating
water loops above the level of the chilled beams to
enable venting of the pipework.
Connection of motorised air quality control:
Power supply: 24 VAC.
Control signal: 0 ... 10 VDC.
Installation with installation brackets
Installation of the duct cover
98 99
q = k l p
v eff m

* *
2
0
/
C
B
E
/
0
0
0
0
/
1
0
0
8
/
E
N
CBE - Active Chilled Beam
Adjustment
Cooling
The recommended cooling water mass flow rate is
0.02 0.10 kg/s, resulting in a temperature rise of 1
4 C in the heat exchanger. To avoid condensation,
the recommended inlet water temperature of the heat
exchanger is 14 16 C.
Heating
The recommended heating water mass flow rate is
0.01 0.04 kg/s, resulting in a temperature drop of
5 15 C in the heat exchanger. The recommended
temperature of the inlet water for the heat exchanger
is 35 45 C.
Balancing and control of water flow rates
Balance the water flow rates of the chilled beam with
the standard control valve by selecting the designed
kv value in the valve body.
When using an automatically balancing combination
valve, set the designed water flow rate in the valve
body and verify the pressure difference (min.: 7.5 kPa)
between the measurement nipples of the valve. The
pressure difference over the valve must be 16 kPa, to
ensure proper operation.
The cooling and heating capacity of the chilled beam
are controlled by regulating the water mass flow rate.
Adjustment of supply airflow rate
Each chilled beam is equipped with a measurement
tap for static pressure measurement, which enables
fast and accurate measurement of the supply air flow
rate through the effective part of the beam. The air
flow rate is calculated using the formula below.
Nozzle jet airflow rate qv1
leff length of the coil
dpm measured static chamber pressure, Pa
Nozzle k (l/s) k (m
3
/h)
A 0,74 2,66
B 0,96 3,45
C 1,26 4,54
D 1,78 6,41
Adjustment of Halton Velocity Control
The Halton Velocity Control unit is adjusted by
manually turning the sections of the unit.
The HVC units have three different positions: 1 =
throttle position, 2 = normal position, and 3 = boost
position.
98 99
2
0
/
C
B
E
/
0
0
0
0
/
1
0
0
8
/
E
N
CBE - Active Chilled Beam
Cooling: nozzle A
qv l/s 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Leff m
3
/h 29 32 36 40 43 47 50 54 58 61 65 68 72 76 79 83 86
1800 DPtot 56 71 88 106 127 149
Pw 289 319 348 378 407 437
Pt 347 383 420 457 493 530
LpA 12 13 15 16 18 19
Lmin 1,6 1,6 1,6 1,6 1,6 1,6
Ld 1,2 1,4 1,6 1,6 1,8 2
2400 DPtot 62 74 87 101 116 131 148
Pw 439 470 503 537 570 602 635
Pt 517 556 597 637 678 716 757
LpA 13 14 15 16 17 18 20
Lmin 1,6 1,6 1,6 1,6 1,6 1,6 1,6
Ld 1,2 1,4 1,4 1,6 1,6 1,6 1,8
3000 DPtot 66 76 87 98 110 122 136 150
Pw 600 637 672 708 743 778 814 849
Pt 700 744 787 829 872 914 957 999
LpA 14 15 16 17 18 19 20 21
Lmin 1,6 1,6 1,6 1,6 1,6 1,6 1,6 1,6
Ld 1 1,4 1,4 1,6 1,6 1,6 1,6 1,8
3600 DPtot 62 70 78 87 97 107 117 128 139
Pw 737 774 814 851 888 927 965 1002 1039
Pt 852 896 943 987 1031 1078 1122 1167 1211
LpA 16 17 18 19 20 21 22 23 24
Lmin 1,6 1,6 1,6 1,6 1,6 1,6 1,6 1,6 1,6
Ld 1 1 1,4 1,4 1,4 1,6 1,6 1,6 1,6
Cooling: nozzle B
qv l/s 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 32 34 36
Leff m
3
/h 50 54 58 61 65 68 72 76 79 83 86 90 94 97 101 104 108 115 122 130
1800 DPtot 63 72 82 93 104 116 129 142
Pw 401 425 450 474 499 523 547 572
Pt 502 532 565 596 628 659 690 723
LpA 9 10 12 14 15 17 19 20
Lmin 1,6 1,6 1,6 1,6 1,6 2,6 2,6 1,5
Ld 1,6 1,8 2,0 2,0 2,0 2,2 2,4 2,4
2400 DPtot 60 67 74 81 89 98 106 115 125 134 145
Pw 572 600 625 653 680 708 735 761 788 815 841
Pt 701 736 768 803 838 872 907 940 974 1009 1042
LpA 10 11 12 13 14 15 16 17 18 19 20
Lmin 1,6 1,6 1,6 1,6 1,6 1,6 1,6 2,6 2,6 3,6 3,6
Ld 1,6 1,6 1,8 2,0 2,0 2,0 2,0 2,0 2,2 2,4 2,4
3000 DPtot 64 69 75 81 88 94 101 108 123 139
Pw 784 814 843 872 902 931 961 990 1047 1106
Pt 949 986 1022 1059 1095 1132 1169 1205 1276 1350
LpA 12 13 14 15 16 17 18 19 21 23
Lmin 1,6 1,6 1,6 1,6 1,6 1,6 1,6 1,6 2,6 3,6
Ld 1,6 1,6 1,6 1,8 2,0 2,0 2,0 2,0 2,0 2,2
3600 DPtot 62 67 72 77 87 99 111
Pw 982 1014 1045 1077 1137 1200 1255
Pt 1176 1214 1253 1292 1367 1444 1513
LpA 20 21 22 23 25 27 29
Lmin 1,6 1,6 1,6 1,6 1,6 1,6 1,6
Ld 1,6 1,6 1,6 1,6 1,8 2,0 2,0
CBE selection tables
Heating: nozzle A
Recommended maximum linear meter heating capacity in 80-120 Pa pressure level is 160 W/m.
Heating: nozzle B
Recommended maximum linear meter heating capacity in 80-120 Pa pressure level is 250 W/m.
100 101
2
0
/
C
B
E
/
0
0
0
0
/
1
0
0
8
/
E
N
CBE - Active Chilled Beam
Cooling: nozzle C
qv l/s 18 19 20 21 22 23 24 25 26 27 28 29 30 32 34 36 38 40 42 44 46
Leff m
3
/h 65 68 72 76 79 83 86 90 94 97 101 104 108 115 122 130 137 144 151 158 166
1800 DPtot 60 67 75 82 90 99 108 117 126 136 146
Pw 435 448 464 478 494 507 521 537 551 564 578
Pt 564 585 608 628 651 672 693 716 737 758 779
LpA 13 14 15 16 17 18 19 20 21 22 23
Lmin 1,6 1,6 2,6 2,6 2,6 3,6 4,6 4,6 5,6 6,6 5,6
Ld 2,2 2,4 2,4 2,4 2,6 2,6 2,8 3 3 3,2 3,2
2400 DPtot 63 68 74 80 86 92 99 112 127 142
Pw 637 653 670 686 702 717 733 764 796 827
Pt 809 832 857 879 902 925 948 994 1040 1085
LpA 14 15 16 17 17 18 19 21 22 24
Lmin 1,6 1,6 1,6 2,6 2,6 2,6 3,6 4,6 5,6 6,6
Ld 2 2,2 2,2 2,4 2,4 2,4 2,6 2,6 3 3
3000 DPtot 61 66 75 84 95 105 117 129 141
Pw 839 857 892 925 961 994 1029 1063 1096
Pt 1047 1072 1121 1169 1219 1266 1316 1364 1411
LpA 15 16 18 19 21 22 24 25 27
Lmin 1,6 1,6 1,6 2,6 2,6 3,6 4,6 5,6 5,6
Ld 2 2 2,2 2,4 2,4 2,6 2,6 2,6 3
3600 DPtot 61 68 76 84 93 102 112
Pw 1055 1090 1128 1165 1200 1237 1255
Pt 1299 1348 1400 1452 1501 1553 1585
LpA 17 19 21 22 24 25 27
Lmin 1,6 1,6 1,6 2,6 2,6 2,6 3,6
Ld 2 2 2 2,2 2,4 2,4 2,6
Cooling: nozzle D
qv l/s 26 27 28 29 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58
Leff m
3
/h 94 97 101 104 108 115 122 130 137 144 151 158 166 173 180 187 194 202 209
1800 DPtot 63 68 73 79 84 96 108 121 135
Pw 482 498 513 529 545 574 605 635 666
Pt 668 691 714 737 760 803 849 893 939
LpA 20 21 22 23 24 27 29 31 33
Lmin 3,6 4,6 4,6 5,6 5,6 5,6 6,6 5,6 6,6
Ld 2,6 2,6 2,6 2,8 3 3 3,2 3,6 3,6
2400 DPtot 65 72 81 89 99 108 118 129 140
Pw 696 729 762 798 831 865 898 931 965
Pt 939 987 1035 1084 1132 1180 1228 1275 1323
LpA 19 21 22 24 25 27 28 30 31
Lmin 3,6 4,6 4,6 5,6 5,6 5,6 6,6 5,6 6,6
Ld 2,4 2,6 2,6 2,8 3 3 3,2 3,2 3,6
3000 DPtot 61 67 74 80 87 95 103 111 119 128
Pw 890 925 963 1000 1035 1073 1108 1145 1181 1216
Pt 1177 1226 1278 1330 1379 1431 1481 1532 1582 1632
LpA 22 23 25 27 28 30 31 33 34 35
Lmin 2,6 2,6 4,6 4,6 5,6 5,6 5,6 5,6 6,6 6,6
Ld 2,2 2,4 2,4 2,6 2,6 2,6 3 3 3 3,2
3600 DPtot 59 65
Pw 1094 1133
Pt 1424 1477
LpA 33 35
Lmin 2,6 2,6
Ld 2 2,2
Heating: nozzle D
Recommended maximum linear meter heating capacity in 80-120 Pa pressure level is 300 W/m.
Heating: nozzle C
Recommended maximum linear meter heating capacity in 80-120 Pa pressure level is 300 W/m.
CBE selection tables
100 101
2
0
/
C
B
E
/
0
0
0
0
/
1
0
0
8
/
E
N
CBE - Active Chilled Beam
Notations of the selection tables
LpA values presented with room attenuation 4 dB (red 10m
2
- sab).
When using room attenuation 8 dB (red 25m
2
- sab): LpA - 4dB.
Performance values are presented for operation with HVC in position 3.
If Lmin > 5 m then use HVC
The impact of HVC compared to presented values in average:
position 2: -20% of Pw and Position 1: -38 % of Pw
Leff Effective length, length of cooling coil, mm
DPtot Chilled beam chamber pressure, Pa
Pw Coil capacity, W
Pt Total capasity, W
Water pressure drop
p
w
= k
coil
* q
mw
z
k
coil
= a + b * L
eff
LpA A-weighted sound pressure level, reduced by total
equivalent absorption surface of 10m
2
, dB(A) red
10m
2
- sab
Lmin Minimum distance between central lines of two
supply units, m
Ld Distance from the supply unit, at which air jet
detaches from ceiling, m

Room temperature (Tr) = 24 C
Chilled water inlet temperature (Twin) = 15 C
Chilled water outlet temperature (Twout) = 18 C
Supply air temperature (Ta) = 18 C
Factor Unit Description
Dp
w
[kPa] Pressure drop of water flow
q
mw
[kg/s] Water flow rate
L
eff
[mm] Effective length of the chilled
beam
k
coil
[ ] k value
a,b [ ] Parameters for the selected beam
Water flow range
Beam Cooling Heating
CBE 0.020 0.100 kg/s 0.010 0.040 kg/s
Beam Cooling b Cooling a Z Heating b Heating a Z
CBE 0.2297 86.60 1.87 0.9252 35.59 1.87
102 103
2
0
/
C
B
E
/
0
0
0
0
/
1
0
0
8
/
E
N
CBE - Active Chilled Beam
Servicing
CODE DESCRIPTION
1 Front panel
2 Supply air connection
3 Chilled water pipe connections
4 Heating water pipe connections
5 Access panel
6 Control valves and actuators
7 HVC
8 Cable tray
Open the front panel of the chilled beam. In beams
longer than 2400 mm, the front panel can be opened
in two sections.
Clean the supply air plenum, duct, and finned coils
of the heat exchanger using a vacuum cleaner, taking
care not to damage the finned coils. Clean the front
panel and, if necessary, the side plates with a damp
cloth.
Open the access panel, and check at regular intervals
that the air flow adjustment damper (if applicable) and
water flow control valves are working.
Suggested specifications
The unit is an active chilled beam for exposed
installation with bi-directional air supply.
The front panel shall be openable and detachable from
either side without the use of any special tools.
The active chilled beam shall be 382 mm wide and
183 mm high, with an inlet duct diameter of 125 mm.
The chilled beam shall have a duct cover extension
to cover the connection duct and pipe installations
(optional).
The front panel and side panels shall be made of pre-
painted galvanised steel plate.
All visible parts shall be white RAL 9010, 20% gloss.
The chilled beam shall be equipped with a cable tray
(optional).
All pipes shall be manufactured from copper,
connection pipes with a wall thickness of 1.0 mm.
The cooling heat exchanger shall consist of six
15-mm pipes connected in series. The fins of the heat
exchanger shall be manufactured from aluminium.
Heating shall be incorporated within the heat
exchanger via two 10-mm pipes connected in series.
All joints shall be factory pressure-tested.
The maximum operating pressure of pipework shall be
1.0 MPa.
Each active chilled beam shall be protected by a
removable plastic coating and individually packed in a
plastic. Duct connection and pipe ends shall be sealed
for transit.
Each chilled beam shall be identifiable by on a label
attached to the active chilled beam.
102 103
2
0
/
C
B
E
/
0
0
0
0
/
1
0
0
8
/
E
N
CBE - Active Chilled Beam
Product code
CBE/S-L-C
S = Direction of supply patterns & nozzle type
A Bi-directional / Nozzle 1
B Bi-directional / Nozzle 2
C Bi-directional / Nozzle 3
D Bi-directional / Nozzle 4
L = Total length
1200,+100, , 4800
C = Effective length (cooling coil length)
900, +100, ..., 4500

Specifics and accessories
TC = Cooling/heating functions (coil type)
C Cooling
H Cooling and Heating
D Cooling only,venting valves
F Cooling+Heating,venting valves
FD = Flow damper
N No
Y Yes

VA = Visual appearance
A Rounded, oval perforation
B Rounded, round perforation
C Angular, oval perforation
D Angular, round perforation
CO = Colour
W White
X Special colour

CV = Control valves & actuators
N No
A1 Adjust. kv value, factory mounted, no
actuator
A3 Adjust. kv value, factory mounted,
24-V act.
A5 Adjust. kv value, factory mounted,
240-V act.
A7 Constant-flow-mounted
Sub-products
DC Duct cover (exposed chilled beam)
AC = Accessories
KH Cable tray
Code example
CBE/B-1200-900, TC=C, CO=W, FD=N, VA=B,
CV=A5,AC=KH