Single-Duct

Table of
Contents

Service Model Number Description

SD 2 3

Selection Procedure

SD 4 5

General Data Valve/Controller Airflow Guidelines


Performance Data Air Pressure Requirements

VAV-PRC008-EN

SD 6
SD 7 9

Performance Data Hot Water Coil

SD 10 15

Performance Data Electric Data

SD 16 17

Performance Data Acoustics

SD 18 21

Dimensional Data

SD 22 27

Mechanical Specifications

SD 28 30

SD 1

Single-Duct

Single-Duct VAV
Terminal Units
The features of the single-duct VAV
terminal units are described by the
product categories shown in bold.
Within each category the available
options are listed.

Digit 1, 2Unit Type


VC
VariTrane single-duct
Digit 3Reheat
C
Cooling Only
E
Electric Heat
W
Hot Water Heat
Digit 4Development Sequence
F
Sixth
Digit 5, 6Primary Air Valve
04
4" inlet (225 cfm)
05
5" inlet (350 cfm)
06
6" inlet (500 cfm)
08
8" inlet (900 cfm)
10
10" inlet (1400 cfm)
12
12" inlet (2000 cfm)
14
14" inlet (3000 cfm)
16
16" inlet (4000 cfm)
24
24" x 16" inlet (8000 cfm)

VCCF

VCWF

VCEF

SD 2

Digit 7, 8Not Used


00
N/A

Service
Model Number
Description
DD15
DD17
AT08
AT10
FM00
FM01
HNY2
INV3
PWR1
PWR2
PW12
PW13
VMA2
EI05

Digit 9Not Used


0
N/A

EI28

Digit 10, 11Design Sequence


C0
Third (factory assigned)

EI29

Digit 12, 13, 14, 15Controls


ENON No controls, field-installed DDC/
electric
PNON No controls, field-installed
pneumatic
DD00 Trane elec actuator only
DD01 DDC Cooling only
DD02 DDC N.C. on/off water valve
control
DD03 DDC Prop hot water valve
control
DD04 DDC On/off electric heat
DD05 DDC Pulse-width modulation
electric heat
DD07 DDC N.O. on/off water valve
control
DD11 LonTalk DDC Controller
Cooling only
DD12 LonTalk DDC Controller w/ N.C.
on/off hot water control
DD13 LonTalk DDC Controller w/
proportional hot water control
DD14 LonTalk DDC Controlleron/off
electric heat control

PC00
PC04
PC05
PN00
PN04
PN05
PN11
PN32
PN34

LonTalk DDC Controller w/


pulse-width modulation electric
heat control
LonTalk DDC Controller w/ N.O.
on/off hot water control
FM Automated Logic ZN341v+
FM Automated Logic ZN141v+
FM Customer-supplied
actuator & controller
FM Trane actuator w/
customer-supplied control
FM Honeywell W7751H
FM Invensys MNL-V2R
FM Siemens 540-100 w/
GDE131.1 actuator
FM Siemens 540-103 w/
GDE131.1 actuator
FM Siemens 550-065
FM Siemens 550-067
FM Johnson VMA-1420
Analog With optional on/off
reheat
Analog With optional on/off
reheat with dual-minimum cfm
Analog With optional on/off
reheat with constant-volume cfm
PN N.C. Trane pneumatic
actuator
PN N.C. with optional on/off HW,
DA Stat
PN N.C. with optional on/off
electric, RA Stat
PN N.O. Trane pneumatic
actuator, RA Stat
PN N.O. PVR, DA Stat
PN N.O. PVR, RA Stat
PN N.O. dual-minimum cfm,
DA Stat
PN Water Valve, N.O. constant
volume, DA Stat
PN Electric heat, N.O. constant
volume, DA Stat

Notes:
N.C. =
Normally-closed
N.O. =
Normally-opened
DA Stat = Direct-acting pneumatic t-stat (by
others)
RA Stat = Reverse-acting pneumatic
t-stat (by others)
PN =
Pneumatic
FM =
Factory installation of customersupplied controller
PVR =
Pneumatic Volume Regulator

VAV-PRC008-EN

Single-Duct

Digit 16Insulation
A
1/2" Matte-faced
B
1" Matte-faced
C
1/2" Foil-faced
D
1" Foil-faced
F
1" Double-wall
G
3/8" Closed-cell
Digit 17Not Used
0
N/A
Digit 18Not Used
0
N/A
Digit 19Outlet Plenum (Connection
is Slip & Drive)
0
None
A
1 Outlet RH
B
1 Outlet END
C
1 Outlet LH
D
2 Outlets, 1 RH, 1 END
E
2 Outlets, 1 LH, 1 END
F
2 Outlets, 1 RH, 1 LH
H
3 Outlets, 1 LH, 1 RH, 1 END
J
4 Outlets, 1 LH, 1 RH, 2 END
Note: See unit drawings for outlet sizes/
damper information.
Digit 20Not Used
0
N/A
Digit 21Water Coil
0
None
1
1-Row
2
2-Row
Digit 22Electrical Connections (VCCF,
VCWF can be flipped in the field to
achieve opposite-hand connection)
L
Left (Airflow hitting you in the
face)
R
Right (Airflow hitting you in the
face)
0
Opposite side connection coil
and control

VAV-PRC008-EN

Digit 23Transformer
0
None
1
120/24 volt (50 VA)
2
208/24 volt (50 VA)
3
240/24 volt (50 VA)
4
277/24 volt (50 VA)
5
480/24 volt (50 VA)
6
347/24 Volt (50 VA)
7
575/24 Volt (50 VA)
8
380/24 Volt (50 VA)
Note: For VCEF units with transformers
the VA depends on the staging, control,
and contactor type (ranges are 40 VA
to 75 VA)
Digit 24Disconnect Switch
0
None
W
With

Note: VCCF, VCWF Toggle Disconnect


VCEF Door Interlocking Power
Disconnect
Digit 25Power Fuse
0
None
W
With
Digit 26Electric Heat Voltage
0
None
A
208/60/1
B
208/60/3
C
240/60/1
D
277/60/1
E
480/60/1
F
480/60/3
G
347/60/1
H
575/60/3
J
380/50/3
K
120/60/1

Service
Model Number
Description
Digit 27, 28, 29Electric Heat kW
000 None
050 0.5 kW
010 1.0 kW
015 1.5 kW
460

46.0 kW

Notes:
0.5 to 8.0 kW kW increments
8.0 to 18.0 kW 1 kW increments
18.0 to 46.0 kW 2 kW increments
Digit 30Electric Heat Stages
0
None
1
1 Stage
2
2 Stages Equal
3
3 Stages Equal
Digit 31Contactors
0
None
1
24-volt magnetic
2
24-volt mercury
3
PE with magnetic
4
PE with mercury
Digit 32Not Used
0
N/A
Digit 33Not Used
0
N/A
Digit 34Actuator
0
Standard
A
Spring Return (Normally Open)
B
Spring Return (Normally
Closed)
Digit 35Sensor Options
0
Standard (Wired)
1
Factory Mounted Wireless
Receiver (Sensor Accessory)

SD 3

Single-Duct

This section describes the catalog


selection of single-duct VAV terminal
units with specific examples. A
computer selection program is also
available to aid in selection of VAV
terminal units.
Selection of single-duct VAV terminal
units can involve three elements:

Air valve selection


Heating coil selection (if required)
Acoustics

Air Valve Selection


The wide-open static pressure and
airflows are found in the performance
data section of the catalog.To select an
air valve, locate the required design
cooling airflow for your terminal unit
type and find the smallest air valve size
that has a pressure drop equal to or
lower than the maximum wide-open
static pressure requirement.

Selection Example
Cooling Only VCCF Terminal Unit
Design cooling airflow:
1700 cfm
Maximum wide open
Air pressure drop:
0.25 in. wg
Minimum cooling airflow: 850 cfm
From the performance data charts,
select a valve size 12, which has a wideopen static pressure drop of 0.01 in. wg
Check the minimum and maximum cfm
desired with the minimum and
maximum cfm allowed in the table in
the general data section. The maximum
setting of 1700 cfm is within the
acceptable range. The desired minimum
setting of 850 cfm is acceptable for the
cooling only box desired. Note that if an
electric reheat box was selected, the
minimum cfm would be dependent
upon the kW of the electric heater. (See
Electric Heat Unit Selection.)

Heating Coil Selection (If


required)

Selection
Procedure

Select hot water coil from the coil


performance table in the Performance
Data section of the catalog.
Selection:
A one-row coil is sufficient to meet
design conditions. From the Hot Water
Coil Capacity Data of the Performance
Data Section, a one-row coil for a size
12 air valve will operate at the above
conditions as follows:
Coil Capacity:
Water pressure drop:

25.17 MBh
0.72 ft WPD

Air pressure drop (APD) of the hot


water coil is included in the chart
preceding the hot water coil
performance data section.
APD = 0.35 in. wg
Electric Heat
Determine the kW required to meet
zone design heat loss.
kW = MBh / 3.414
MBh = Design Heat Loss
Select the nearest available kW with
voltage and steps desired from the
electric heater kW guideline table in the
Performance Data section of the
catalog.
Example:
VCEF, Electric Unit Heat, Size 12
(See Air Valve Selection)
Heating airflow:
850 cfm
Voltage:
277/60/1 VAC
Design Heat Loss:
Q = 25 MBh
kW = Q/3.414
kW = 25/3.414
kW = 7.3
Selection:
Select 7.5 kW from the electric heat
table in the voltage and stages
required. The table shows the
minimum cfm allowable for the kW
selected. The static pressure
requirement is shown as 0.06 in. wg
for this example with a design cooling
flow of 1700 cfm.

First, determine the amount of heat


required to meet space and
downstream duct heat losses from a
load calculation.

Check Leaving Air Temperature:

Hot Water Heat


Select a hot water coil sufficient to meet
the design heat loss.

T is the primary entering air


temperature 55F for this example.

Example:
VCWF, Hot Water Unit Heat, Size 12
(See air Valve Selection)
Heating airflow:
850 cfm
Hot water flow:
1.0 gpm
Design Heat Loss:
Q =25 MBh
SD 4

LAT =

LAT =

Q
1.085 x CFM

3414 x 7.5
1.085 x 850

+T

+ 55 = 82.8

Decide if leaving air temperature of


82.8F is satisfactory for your
application.

Acoustics
The acoustical data found in the
"Performance Data" section of the VAV
catalog is used to make a
determination of the amount of noise
the terminal unit will generate. Locate
the table for the VAV terminal unit of
interest. Sound power data and an
equivalent NC level for an ARI 885-98
transfer function is listed.
Example:
VCCF, Cooling-OnlyTerminal Unit, Size
10 (See air Valve Selection)
Cooling Airflow:
1100 cfm
Maximum inlet static
pressure:

1.5 in. wg

Interpolation gives sound power


data of:
Octave
Band
Disch.
Sound
Power
Rad.
Sound
Power

NC

68

68

65

65

60

57

28

63

58

54

47

39

32

29

The NC level above is determined by


using either the catalogs ARI 885-98
(mineral fiber for radiated sound)
transfer function for the conditions
shown in the acoustics table. A
different transfer function could be
applied as conditions dictate.
The maximum NC level is NC-37. If the
maximum NC level was exceeded, it
would have been necessary to reselect
the next larger unit size.
Computer Selection
The advent of personal computers has
served to automate many processes
that were previously repetitive and
time-consuming. One of those tasks is
the proper scheduling, sizing, and
selection of VAV terminal units. Trane
has developed a computer program to
perform these tasks. The software is
called the Trane Official Product
Selection System (TOPSS).
The TOPSS program will take the input
specifications and output the properly
sized VariTrane VAV terminal unit along
with the specific performance for that
size unit.
The program has several required
fields, denoted by red shading in the
TOPSS screen, and many other
optional fields to meet the criteria you
have. Required values include
maximum and minimum airflows,
control type, and model. If selecting
models with reheat, you will be
required to enter information to make
VAV-PRC008-EN

Single-Duct

that selection also. The user is given


the option to look at all the information
for one selection on one screen or as a
schedule with the other VAV units on
the job.
The user can select single-duct, dualduct, and fan-powered VAV boxes with
the program, as well as most other
Trane products, allowing you to select
all your Trane equipment with one
software program.

Selection
Procedure

Schedule View
The program has many time-saving features such as:
Copy/Paste from spreadsheets like Microsoft Excel
Easily arranged fields to match your schedule
Time-saving templates to store default settings
The user can also export the Schedule View to Excel to modify and put into a CAD
drawing as a schedule.
Specific details regarding the program, its operation, and how to obtain a copy of it
are available from your local Trane sales office.

The program will also calculate sound


power data for the selected terminal
unit. The user can enter a maximum
individual sound level for each octave
band or a maximum NC value. The
program will calculate acoustical data
subject to default or user supplied
sound attenuation data.

Required entry fields (in Red


onTOPSS screen).

Rearrange what fields you see


and in what order with a few
clicks of a button.

VAV-PRC008-EN

SD 5

Single-Duct

General Data
Valve/Controller
Airflow Guidelines

Primary Airflow Control Factory Settings I-P


Control
Type

Direct Digital Control/


UCM

Pneumatic with
Volume Regulator

Analog Electronic

Air Valve
Size (in.)

Maximum Valve
Cfm

Maximum Controller
Cfm

Minimum Controller
Cfm

Constant Volume
Cfm

4
5
6
8
10
12
14
16
24 x 16
4
5
6
8
10
12
14
16
24 x 16
4
5
6
8
10
12
14
16
24 x 16

225
350
500
900
1400
2000
3000
4000
8000
225
350
500
900
1400
2000
2887
3789
7745
225
350
500
900
1400
2000
3000
4000
8000

25225
40350
60500
105900
1651400
2402000
3203000
4204000
8008000
38225
63350
73500
134900
2151400
3002000
4082887
5363789
10967745
52225
82350
120500
210900
3281400
4702000
6403000
840-4000
1600-8000

0,25225
0,40350
0,60500
0,105900
0,1651400
0,2402000
0,3203000
0,4204000
0,8008000
0,38225
0,63350
0,73500
0,134900
0,2151400
0,3002000
0,4082887
0,5363789
0,10967745
0,52225
0,82350
0,120500
0,210900
0,3281400
0,4702000
0,6403000
0,8404000
0,16008000

25225
40350
60500
105900
1651400
2402000
3203000
4204000
8008000
38225
63350
73500
134900
2151400
3002000
4082887
5363789
10967745
52225
82350
120500
210900
3281400
4702000
6403000
8404000
16008000

Minimum Controller
L/s

Constant Volume
L/s

0,12106
0,19165
0,28236
0,50425
0,77661
0,111944
0,1511416
0,1981888
0,3783776
0,18106
0,30165
0,35236
0,63425
0,102661
0,141944
0,1931363
0,2531788
0,5173656
0,25106
0,39165
0,57236
0,100425
0,155661
0,222944
0,3031416
0,3971888
0,7563776

12106
19165
28236
50425
77661
111944
1511416
1981888
3783776
18106
30165
35236
63425
102661
141944
1931363
2531788
5173656
25106
39165
57236
100425
155661
222944
3031416
3971888
7563776

Primary Airflow Control Factory Settings SI


Control
Type

Air Valve
Size (in.)

Maximum Valve
L/s

Maximum Controller
L/s

4
106
12106
5
165
19165
6
236
28236
Direct Digital Control/
8
425
50425
UCM
10
661
77661
12
944
111944
14
1416
1511416
16
1888
1981888
24 x 16
3776
3783776
4
106
18106
5
165
30165
6
236
35236
Pneumatic with
8
425
63425
Volume Regulator
10
661
102661
12
944
141944
14
1363
1931363
16
1788
2531788
24 x 16
3656
5173656
4
106
25106
5
165
39165
6
236
57236
Analog Electronic
8
425
100425
10
661
155661
12
944
222944
14
1416
3031416
16
1888
3971888
24 x 16
3776
7563776
Note: Maximum airflow must be greater than or equal to minimum airflow.

SD 6

VAV-PRC008-EN

Single-Duct

Air Pressure Drop in. wg (I-P)


Inlet
Size
04

05

06

08

10

12

14

16

24 x 16

Airflow Cooling
Cfm
Only
50
100
150
225
100
200
300
350
100
250
350
500
200
400
600
900
500
800
1100
1400
800
1200
1600
2000
1500
2000
2500
3000
2000
2500
3000
4000
4000
5500
6500
8000

0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.02
0.01
0.05
0.10
0.22
0.01
0.02
0.04
0.08
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01

Hot Water
1-row coil 2-row coil
0.01
0.02
0.03
0.06
0.01
0.05
0.09
0.12
0.02
0.11
0.22
0.45
0.03
0.10
0.20
0.40
0.07
0.15
0.27
0.42
0.10
0.19
0.31
0.45
0.10
0.16
0.22
0.30
0.11
0.16
0.22
0.35
0.40
0.70
0.95
1.37

0.01
0.02
0.03
0.06
0.03
0.08
0.17
0.22
0.03
0.17
0.32
0.63
0.05
0.17
0.34
0.69
0.12
0.26
0.44
0.66
0.19
0.35
0.55
0.79
0.23
0.36
0.51
0.69
0.30
0.46
0.65
1.14
0.66
1.12
1.47
2.06

Performance
DataAir Pressure
Requirements
Air Pressure Drop Pa (SI)

Electric
Heat

Inlet
Size

Airflow
L/s

Cooling
Only

0.01
0.01
0.01
0.02
0.01
0.01
0.02
0.02
0.01
0.05
0.11
0.23
0.01
0.02
0.05
0.11
0.01
0.02
0.03
0.05
0.01
0.03
0.05
0.08
0.01
0.01
0.01
0.01
0.01
0.02
0.02
0.03
0.15
0.30
0.44
0.69

04

25
50
70
105
45
95
140
165
45
120
165
235
95
190
280
420
235
375
520
660
375
565
755
940
700
945
1180
1415
940
1180
1415
1885
1885
2600
3070
3775

3
3
3
3
3
3
3
4
3
13
26
55
3
4
9
21
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3

05

06

08

10

12

14

16

24 x 16

Hot Water
1-row coil 2-row coil
3
4
7
15
3
12
22
29
4
29
55
112
8
25
49
99
16
37
67
104
24
47
76
111
26
40
56
74
28
40
54
87
100
176
236
341

3
4
7
15
6
21
41
54
7
43
79
155
13
43
83
169
29
63
110
165
47
88
138
195
55
89
127
171
73
114
162
284
165
279
366
513

Electric
Heat
3
3
3
3
3
3
5
6
3
14
27
57
3
6
12
28
3
5
9
13
3
7
13
19
3
3
3
3
3
4
5
8
38
76
110
172

Note: Hot water pressure drops are for the entire unit, not just the coil. To calculate the hot water coil only pressure drop, subtract the cooling only pressure drop from the
other pressure drop.

VAV-PRC008-EN

SD 7

Single-Duct

Performance
DataAir Pressure
Requirements (I-P)

Integral Outlet Plenum Air Pressure Drop in. wg (I-P)


Inlet
Size

Outlet
Configuration

4,5,6
4,5,6
8,10
10
12
4,5,6
4,5,6
8
10
10
12
4,5,6
4,5,6
8
8
8
10
10
10
12
12
4,5,6
4,5,6,8
8,10
8,10
10
12
12
4,5,6
4
5
6
8
8
8
10
10
10
12
12
10
12
12

A,C

Outlet
Diameter
(in.)
5
6
8
10
10
5
6
8
8
10
10
5
6
5
6
8
6
8
10
8
10
6
5
6
8
10
8
10
5
6
6
6
5
6
8
6
8
10
8
10
5
5
6

AC

D,E
D, E

D, E

D, E
F
F
F

H
J

100

150

200

250

350

400

0.02
0.01

0.07
0.03

0.15
0.07

0.26
0.13
0.04
0.01

0.41
0.20
0.06
0.02
0.03
0.23
0.04
0.01
0.04
0.01
0.02
0.05
0.01
0.09
0.03
0.01
0.04
0.01
0.01
0.01
0.08
0.16
0.08
0.02
0.01
0.02
0.01
0.01

0.80
0.37
0.11
0.04
0.06
0.48
0.07
0.02
0.07
0.01
0.04
0.09
0.01
0.18
0.05
0.01
0.07
0.01
0.01
0.02
0.01
0.16
0.30
0.14
0.04
0.02
0.04
0.02
0.03

1.04
0.48
0.14
0.05
0.08
0.64
0.10
0.02
0.09
0.01
0.05
0.12
0.02
0.23
0.07
0.01
0.10
0.02
0.01
0.03
0.01
0.21
0.38
0.18
0.06
0.02
0.05
0.02
0.04

1.63
0.74
0.23
0.08
0.12
1.02
0.15
0.03
0.14
0.02
0.08
0.17
0.03
0.35
0.11
0.01
0.15
0.02
0.01
0.05
0.02
0.32
0.58
0.27
0.09
0.03
0.07
0.03
0.06

0.01
0.01
0.05
0.01
0.01
0.02
0.01
0.01
0.01
0.01
0.02
0.03
0.01

0.01
0.01
0.09
0.02
0.01
0.04
0.01
0.01
0.01
0.01
0.05
0.06
0.02

0.01
0.11
0.03
0.01
0.05
0.01
0.01
0.02
0.01
0.06
0.08
0.03

0.01
0.18
0.04
0.01
0.08
0.01
0.01
0.03
0.01
0.09
0.12
0.04

0.01
0.01

0.01
0.01

0.01
0.01

0.01
0.01
0.01

II
III
IV

NOMINAL
5" (127 mm)
6" (152 mm)
8" (203 mm)
10" (254 mm)

OUTLET PLENUM
ARRANGEMENTS
(TOP VIEW)

SD 8

0.03
0.01

0.08
0.01

0.01
0.01

0.15
0.03
0.01
0.02
0.01

0.02
0.01

0.01
0.03

0.04
0.01
0.06
0.02
0.01
0.02
0.01
0.01

0.03
0.06

0.01
0.01
0.01
0.01

0.05
0.10
0.05
0.01
0.01

0.01
0.01
0.01
0.01

0.01
0.01
0.01
0.01
0.03
0.01
0.01
0.01
0.01
0.01

0.02

OUTL CONVERSION CHART


SYMBOL
I

Airflow (Cfm)
500 600 800

50

900

1100 1200 1400 1600 2000

0.33
0.12
0.17

0.58
0.21
0.29

0.74
0.27
0.37

1.11
0.41
0.54

1.33
0.48
0.64

1.81
0.66
0.86

1.11

1.71

0.05
0.20
0.02
0.11

0.07
0.35
0.04
0.19

0.09
0.44
0.06
0.24

0.65
0.08
0.36

0.76
0.10
0.43

1.03
0.13
0.58

0.76

1.17

0.49
0.15
0.01
0.22
0.04
0.01
0.07
0.02

0.85
0.26
0.01
0.38
0.06
0.02
0.12
0.04

1.06
0.32
0.01
0.48
0.08
0.02
0.15
0.05

0.72
0.12
0.03
0.23
0.07

0.85
0.14
0.04
0.28
0.08

1.16
0.19
0.05
0.38
0.11

0.49
0.14

0.77
0.21

0.83
0.37
0.13
0.04
0.10
0.04

1.43
0.61
0.23
0.07
0.17
0.06

1.78
0.76
0.29
0.08
0.21
0.08

1.08
0.43
0.12
0.31
0.11

1.26
0.52
0.14
0.37
0.13

1.66
0.71
0.18
0.50
0.16

0.64
0.21

0.98
0.30

0.25
0.06
0.01
0.11
0.02
0.01
0.04
0.01
0.13
0.17
0.06

0.43
0.10
0.02
0.18
0.03
0.01
0.06
0.02
0.23
0.30
0.11

0.54
0.13
0.03
0.22
0.03
0.01
0.08
0.02
0.29
0.38
0.14

0.32
0.05
0.01
0.11
0.03
0.43
0.57
0.21

0.38
0.05
0.01
0.13
0.03
0.51
0.68
0.25

0.50
0.07
0.01
0.17
0.05
0.70
0.92
0.35

0.21
0.06

0.32
0.09

1.20
0.45

1.87
0.71

OUTLET AVAILABILITY CHART - SEE OUTL CONVERSION FOR NOMINAL


VALV
4
5
6
8
10
I, II
I, II
I, II
A,B,C
III
III, IV
D,E,F
I, II, III
I, II
I, II
I, II
II, III, IV
OUTL
II, III, IV
I, II, III
I, II
I, II
I, II
H
N/A
I
N/A
N/A
J
N/A

12
IV
III, IV
III, IV
I, II

VAV-PRC008-EN

Single-Duct

Performance
DataAir Pressure
Requirements (SI)

Integral Outlet Plenum Air Pressure Drop Pa (SI)


Inlet
Size

Outlet
Configuration

4,5,6
4,5,6
8,10
10
12
4,5,6
4,5,6
8
10
10
12
4,5,6
4,5,6
8
8
8
10
10
10
12
12
4,5,6
4,5,6,8
8,10
8,10
10
12
12
4,5,6
4
5
6
8
8
8
10
10
10
12
12
10
12
12

A,C

Outlet
Diameter
(mm)
127
152
203
254
254
127
152
203
203
254
254
127
152
127
152
203
152
203
254
203
254
152
127
152
203
254
203
254
127
152
152
152
127
152
203
152
203
254
203
254
127
127
152

AC

D,E
D, E

D, E

D, E
F
F
F

H
J

50

70

95

120

165

190

4
3

17
8

37
18
9

66
32
14
3

102
49
27
5
8
58
10
3
9
3
5
13
3
23
7
3
9
3
3
3
3
21
39
19
5
3
5
3
3

199
93
36
10
15
119
19
5
17
3
10
23
3
44
13
3
18
3
3
6
3
40
74
35
10
4
9
4
7

260
120
56
13
19
158
24
6
22
3
12
29
4
57
17
3
24
4
3
7
3
52
95
45
14
5
11
5
9

405
185
81
21
29
254
37
8
35
4
19
42
6
87
26
3
37
6
3
12
4
81
145
66
22
7
18
7
15

3
3
12
3
3
5
3
3
3
3
6
7
3

3
3
22
6
3
10
3
3
3
3
11
14
5

3
29
7
3
13
3
3
4
3
15
19
7

3
44
11
3
19
3
3
6
3
23
29
11

3
3

3
3

3
3

3
3
3

OUTL CONVERSION CHART


SYMBOL
I
II
III
IV

NOMINAL
5" (127 mm)
6" (152 mm)
8" (203 mm)
10" (254 mm)

OUTLET PLENUM
ARRANGEMENTS
(TOP VIEW)

VAV-PRC008-EN

Airflow (L/s)
235 280 375

25

8
3

20
4

3
3

36
6
3
6
3

6
3

4
7

9
3
15
5
3
6
3
3

8
15

3
3
3
3

14
25
13
3
3

3
3
3
3

3
3
3
3
8
3
3
4
3
3

420

520

565

660

755

940

145
30
42

185
53
73

277
67
91

330
101
134

451
120
159

164
214

277

427

11
49
6
28

19
86
11
48

23
109
14
61

161
20
90

190
24
107

257
33
145

188

292

123
37
3
54
9
3
17
6

211
64
3
95
16
4
30
10

264
81
3
120
20
5
38
12

179
30
8
57
17

213
35
9
69
20

289
48
12
94
27

123
34

193
52

206
92
31
10
25
9

355
153
56
17
43
16

444
189
72
21
53
19

269
108
29
78
27

315
129
34
92
31

414
177
45
124
41

159
51

244
75

62
15
3
27
4
3
9
3
33
42
15

108
26
5
45
6
3
15
4
58
75
28

136
33
6
56
8
3
19
5
73
95
35

81
12
3
27
7
108
142
53

95
14
3
32
9
128
168
63

126
18
3
42
11
173
229
86

53
15

80
22

299
113

467
178

OUTLET AVAILABILITY CHART - SEE OUTL CONVERSION FOR NOMINAL


VALV
4
5
6
8
10
I, II
I, II
I, II
A,B,C
III
III, IV
D,E,F
I, II, III
I, II
I, II
I, II
II, III, IV
OUTL
II, III, IV
I, II, III
I, II
I, II
I, II
H
N/A
I
N/A
N/A
J
N/A

12
IV
III, IV
III, IV
I, II

SD 9

Single-Duct

Performance
DataHot Water
Coil (I-P)

Inlet Size 04, 05, 06 (I-P)


Rows

Water
Pressure
Drop (ft)

Gpm

1-Row
Capacity
MBH

0.5
1.0
1.5
2.0
2.5
2-Row
0.5
Capacity
1.0
MBH
1.5
2.0
2.5
Applicable Range

0.55
1.84
3.74
6.22
9.24
1.14
3.84
7.80
12.95
19.16
Size 04
Size 05
Size 06

45

60

90

100

Airflow (Cfm)
150
200

250

300

400

500

4.16
4.42
4.52
4.57
4.61
5.07
5.25
5.31
5.34
5.36

4.82
5.20
5.34
5.41
5.46
6.36
6.68
6.79
6.84
6.88

5.83
6.41
6.63
6.75
6.82
8.47
9.16
9.40
9.52
9.59

6.10
6.75
7.00
7.13
7.22
9.06
9.89
10.18
10.32
10.41

7.26
8.22
8.60
8.80
8.93
11.41
12.97
13.53
13.83
14.01

8.94
10.47
11.11
11.46
11.68
14.30
17.23
18.39
19.01
19.39

9.62
11.40
12.17
12.59
12.86

18.77
20.21
20.99
21.48

10.73
13.00
14.02
14.60
14.97

21.15
23.10
24.18
24.87

11.60
14.36
15.62
16.34
16.81

22.90
25.30
26.65
27.51

165

200

300

Airflow (Cfm)
400
500
600

700

800

900

8.81
10.04
10.52
10.78
10.95
15.01
16.00
16.36
16.55
16.66
16.76

9.51
10.97
11.56
11.88
12.08
16.97
18.30
18.79
19.05
19.21
19.34

11.15
13.19
14.06
14.54
14.85
21.32
23.68
24.57
25.05
25.35
25.59

12.41
14.99
16.14
16.79
17.20
24.48
27.79
29.09
29.79
30.23
30.60

13.41
16.54
17.95
18.76
19.29
26.88
31.06
32.75
33.67
34.25
34.74

14.24
17.92
19.56
20.53
21.17
28.78
33.75
35.79
36.92
37.63
38.24

14.95
19.13
21.01
22.14
22.88
30.32
36.00
38.37
39.69
40.54
41.25

20.21
22.35
23.61
24.46
31.61
37.92
40.60
42.10
43.06
43.87

21.18
23.58
24.97
25.93
32.70
39.58
42.55
44.21
45.29
46.20

350

450

550

650

Airflow (Cfm)
750
850

1000

1100

1300

1400

15.52
16.89
18.16
18.87
19.31
27.75
30.43
31.41
31.92
32.24

17.18
18.79
20.40
21.30
21.88
31.74
35.52
36.93
37.68
38.15

18.54
20.51
22.37
23.47
24.18
34.93
39.76
41.62
42.61
43.23

19.71
22.01
24.13
25.42
26.26
37.54
43.37
45.66
46.89
47.66

20.72
23.34
25.76
27.22
28.19
39.72
46.48
49.19
50.65
51.57

26.12
29.33
31.18
32.45
43.91
52.71
56.36
58.37
59.64

27.07
30.58
32.62
33.97
45.22
54.74
58.73
60.94
62.35

28.74
32.81
35.23
36.82
47.42
58.23
62.86
65.44
67.10

29.48
33.83
36.42
38.14
48.35
59.74
64.67
67.43
69.20

8.17
9.42
9.93
10.21
10.39
13.07
15.34
16.20
16.66
16.94

Inlet Size 08 (I-P)


Rows

Gpm

Water
Pressure
Drop (ft)

1-Row
Capacity
MBH

0.5
1.0
1.5
2.0
2.5
2.0
4.0
6.0
8.0
10.0
12.5

0.86
2.90
5.96
9.97
14.89
0.35
1.22
2.57
4.38
6.63
10.05

2-Row
Capacity
MBH

Inlet Size 10 (I-P)


Rows

Gpm

Water
Pressure
Drop (ft)

1-Row
Capacity
MBH

0.7
1.0
1.5
2.0
2.5
2.0
4.0
6.0
8.0
10.0

2.07
3.87
7.93
13.20
19.67
0.72
2.62
5.61
9.65
14.71

2-Row
Capacity
MBH

24.54
27.28
28.87
29.98
41.58
49.21
52.30
53.99
55.05

Notes:
1. Fouling Factor = 0.00025
2. Capacity based on 55F entering air temperature and 180F entering water temperature. Refer to correction factors for different
entering conditions on page 42.
3. The following equations may be used in calculating Leaving Air Temperature (LAT) and WaterTemperature Difference (WTD).

LAT = EAT +

SD 10

MBH x 921.7
Cfm

WTD = EWT - LWT =

2 x MBH
Gpm

VAV-PRC008-EN

Single-Duct

Performance
DataHot Water
Coil (I-P)

Inlet Size 12 (I-P)


Rows

Gpm

Water
Pressure
Drop (ft)

1-Row
Capacity
MBH

1.0
2.0
3.0
4.0
5.0
2.0
5.0
8.0
11.0
14.0
17.5

0.68
2.37
4.95
8.38
12.62
0.25
1.38
3.35
6.14
9.72
14.90

2-Row
Capacity
MBH

400

600

800

Airflow (Cfm)
1000
1200
1400

1600

1800

2000

18.07
20.76
21.84
22.42
22.78

35.55
36.91
37.56
37.95
38.24

21.12
24.83
26.41
27.28
27.83

45.61
47.07
49.28
50.00
50.54

23.48
28.16
30.24
31.40
32.14

53.18
56.74
58.51
59.58
60.39

25.37
31.04
33.58
35.02
35.95

59.13
63.72
66.04
67.45
68.53

29.47
37.91
41.74
43.99
45.49

71.36
78.57
82.33
84.66
86.46

30.49
39.74
44.03
46.51
48.21

74.28
82.22
86.40
88.99
91.01

31.39
41.41
46.13
48.88
50.74

76.82
85.44
90.01
92.85
95.06

26.96
33.61
36.55
38.28
39.41

63.96
69.50
72.33
74.06
75.39

28.30
35.88
39.24
41.26
42.57

67.96
74.37
77.69
79.73
81.30

Notes:
1. Fouling Factor = 0.0005 F ft h/Btu.
2. Capacity based on 55F entering air temperature and 180F entering water temperature.

Inlet Size 14 (I-P)


Rows

Gpm

Water
Pressure
Drop (ft)

1-Row
Capacity
MBH

2.0
3.0
4.0
5.0
6.0
7.0
5.0
9.0
13.0
17.0
21.0
22.5

1.23
2.56
4.32
6.50
9.08
12.05
1.09
3.32
6.71
11.24
16.89
19.29

2-Row
Capacity
MBH

700

900

1100

1300

Airflow (Cfm)
1500
1700

2000

2300

2600

3000

31.76
34.35
35.80
36.73
37.38
37.86
55.66
59.72
61.41
62.34
62.94
63.11

35.18
38.43
40.28
41.47
42.31
42.93
63.95
69.65
72.08
73.44
74.31
74.56

38.24
42.00
44.24
45.70
46.73
47.49
70.65
77.96
91.13
82.92
84.06
84.40

40.91
45.19
47.82
49.54
50.76
51.67
76.21
85.04
88.93
91.13
92.56
92.98

43.27
48.14
51.09
53.07
54.48
55.53
80.91
91.16
95.74
98.35
100.05
100.54

48.18
54.53
58.28
60.85
62.74
64.15
90.02
103.42
109.59
113.16
115.49
116.17

50.62
57.80
62.10
64.96
67.12
68.75
94.23
109.29
116.30
120.39
123.08
123.87

52.77
60.73
65.56
68.79
71.15
73.01
97.79
114.33
122.14
126.71
129.73
130.62

55.28
64.21
69.72
73.44
76.13
78.21
101.78
120.09
128.86
134.03
137.45
138.46

45.38
50.86
54.10
56.34
57.94
59.14
84.94
96.51
101.76
104.76
106.72
107.29

Notes:
1. Fouling Factor = 0.0005 F ft h/Btu.
2. Capacity based on 55F entering air temperature and 180F entering water temperature.

Inlet Size 16 (I-P)


Rows

Gpm

Water
Pressure
Drop (ft)

1-Row
Capacity
MBH

2.0
3.0
4.0
5.0
6.0
7.5
5.0
9.0
13.0
17.0
21.0
22.5

1.37
2.84
4.77
7.16
9.98
15.02
1.15
3.50
7.05
11.78
17.67
20.18

2-Row
Capacity
MBH

900

1200

1500

1800

Airflow (Cfm)
2000
2400

2800

3200

3600

4000

38.24
41.85
43.89
45.21
46.14
47.10
68.70
74.51
76.95
78.30
79.16
79.40

43.01
47.41
50.10
51.85
53.08
54.38
79.75
88.21
91.85
93.89
95.20
95.58

46.92
52.24
55.46
57.64
59.19
60.81
88.29
99.24
104.07
106.80
108.56
109.07

50.22
56.54
60.22
62.82
64.67
66.64
95.11
108.35
114.31
117.70
119.91
120.55

52.17
59.12
63.20
66.00
68.06
70.24
98.96
113.62
120.28
124.11
126.60
127.32

58.48
67.76
73.40
77.19
79.91
82.97
110.59
130.12
139.34
144.71
148.26
149.30

60.99
71.32
77.69
82.01
85.13
88.52
114.89
136.45
146.78
152.85
156.86
158.04

63.19
74.49
81.56
86.39
89.90
93.67
118.51
141.90
153.23
159.94
164.39
165.70

65.12
77.34
85.07
90.40
94.29
98.49
121.61
146.64
158.90
166.20
171.06
172.49

55.58
63.73
68.61
71.85
74.28
76.91
105.40
122.64
130.63
135.27
138.31
139.19

Notes:
1. Fouling Factor = 0.0005 F ft h/Btu.
2. Capacity based on 55F entering air temperature and 180F entering water temperature. Refer to correction factors found on page 42
for different entering conditions.
3. The following equations may be used in calculating Leaving AirTemperature (LAT) and WaterTemperature Difference (WTD).

LAT = EAT +

VAV-PRC008-EN

MBH x 921.7
Cfm

WTD = EWT - LWT =

2 x MBH
Gpm

SD 11

Single-Duct

Performance
DataHot Water
Coil (I-P)

Inlet Size 16 x 24 (I-P)


Rows

Gpm

Water
Pressure
Drop (ft)

1-Row
Capacity
MBH

2.0
3.0
4.0
5.0
6.0
7.5
5.0
9.0
13.0
17.0
21.0
22.5

1.51
3.11
5.21
7.81
10.88
16.35
1.26
3.71
7.34
12.13
18.02
20.52

2-Row
Capacity
MBH

1000

1700

2400

3100

Airflow (Cfm)
3800
4500
5200

5900

6600

7300

42.77
47.00
49.47
51.07
52.20
53.37
77.04
83.86
86.70
88.27
89.27
59.56

52.52
58.99
62.79
65.46
67.37
69.38
99.78
113.03
118.88
122.18
124.32
124.93

59.23
68.05
73.31
76.79
79.41
82.26
113.85
132.54
141.13
146.09
149.31
150.25

64.28
75.19
81.88
86.39
89.63
93.19
123.52
146.70
157.68
164.10
168.32
169.56

68.27
81.02
89.04
94.52
98.51
102.80
130.63
157.53
170.59
178.31
183.42
184.92

76.44
93.62
105.05
113.15
119.18
125.79
144.09
179.13
196.97
207.78
215.05
217.20

78.38
96.75
109.14
118.01
124.65
131.98
147.10
184.17
203.26
214.89
222.75
225.07

80.05
99.50
112.79
122.37
129.60
137.62
149.66
188.53
208.74
221.13
229.51
232.00

71.50
85.90
95.14
101.55
106.25
111.34
136.11
166.15
181.01
189.88
195.79
197.53

74.18
90.04
100.43
107.71
113.09
118.95
140.49
173.21
189.66
199.55
206.17
208.13

8000

Notes:
1. Fouling Factor = 0.0005 F ft h/Btu.
2. Capacity based on 55F entering air temperature and 180F entering water temperature. Refer to correction factors found on page 42
for different entering conditions.
3. The following equations may be used in calculating Leaving AirTemperature (LAT) and WaterTemperature Difference (WTD).

LAT = EAT +

MBH x 921.7
Cfm

WTD = EWT - LWT =

2 x MBH
Gpm

Temperature Correction Factors for Water Pressure Drop (ft)


Average WaterTemperature
Correction Factor

200
0.970

190
0.985

180
1.000

170
1.020

160
1.030

150
1.050

140
1.080

130
1.100

120
1.130

110
1.150

70
0.56

80
0.64

100
0.80

125
1.00

140
1.12

150
1.20

160
1.28

Temperature Correction Factors for Coil Capacity (MBH)


Entering Water Minus Entering Air
Correction Factor

40
0.32

50
0.40

60
0.48

180
1.44

200
1.60

Coil OnlyWater Weights


Inlet
Size
04
05
06
08
10
12
14
16
24 x 16
04
05
06
08
10
12
14
16
24 x 16

SD 12

Coil
Type
1-Row
1-Row
1-Row
1-Row
1-Row
1-Row
1-Row
1-Row
1-Row
2-Row
2-Row
2-Row
2-Row
2-Row
2-Row
2-Row
2-Row
2-Row

Internal
Volume
(in.3)
9.37
9.37
9.37
12.78
19.06
30.05
51.21
58.62
66.03
23.68
23.68
23.68
35.47
48.83
67.34
94.27
109.09
123.91

Internal Operating
Volume Weight
(Gal.)
(lbs)
0.041
5.3
0.041
5.3
0.041
5.3
0.055
5.5
0.083
7.7
0.130
10.7
0.222
13.9
0.254
16.2
0.286
20.4
0.102
6.9
0.102
6.9
0.102
6.9
0.154
9.0
0.211
11.7
0.292
15.5
0.408
19.8
0.472
23.3
0.536
29.8

VAV-PRC008-EN

Single-Duct

Performance
DataHot Water
Coil (SI)

Inlet Size 04, 05, 06 (SI)


Rows

L/s

Water
Pressure
Drop (kPa)

1-Row
Capacity
kW

0.03
0.06
0.010
0.13
0.16
0.06
0.13
0.19
0.25
0.32

1.57
5.26
10.72
17.82
26.47
1.85
6.39
13.28
22.39
33.61

2-Row
Capacity
kW

21

28

42

47

1.20
1.27
1.30
1.32
1.32
1.48
1.52
1.53
1.54
1.54

1.38
1.49
1.53
1.55
1.56
1.88
1.94
1.96
1.97
1.98

1.66
1.82
1.88
1.91
1.93
2.54
2.68
2.72
2.75
2.76

1.73
1.91
1.98
2.02
2.04
2.73
2.90
2.95
2.98
3.00

Airflow (L/s)
71
94

118

142

189

236

2.05
2.31
2.42
2.47
2.51
3.53
3.84
3.96
4.01
4.05

2.52
2.93
3.10
3.20
3.26
4.61
5.22
5.45
5.57
5.65

2.70
3.19
3.39
3.51
3.58
4.99
5.73
6.02
6.18
6.28

3.01
3.63
3.91
4.06
4.16
5.58
6.56
6.96
7.18
7.32

3.26
4.01
4.35
4.54
4.67
6.00
7.19
7.69
7.96
8.14

2.30
2.64
2.78
2.86
2.91
4.14
4.60
4.77
4.86
4.92

Notes:
1. Fouling Factor = 0.0005.
2. Capacity based on 12C entering air temperature and 82C entering water temperature.

Inlet Size 08 (SI)


Rows

L/s

Water
Pressure
Drop (kPa)

1-Row
Capacity
kW

0.03
0.06
0.09
0.13
0.16
0.13
0.25
0.38
0.50
0.63
0.79

2.12
7.05
14.35
23.82
35.35
0.98
3.48
7.37
12.56
19.04
28.90

2-Row
Capacity
kW

78

94

142

189

2.47
2.81
2.94
3.01
3.06

4.54
4.65
4.70
4.74
4.77

2.66
3.06
3.22
3.31
3.37

5.18
5.33
5.40
5.45
5.49

3.12
3.68
3.92
4.05
4.13

6.67
6.92
7.06
7.15
7.22

3.47
4.18
4.49
4.67
4.78

7.79
8.16
8.36
8.49
8.60

Airflow (L/s)
236
283
3.75
4.61
4.99
5.22
5.36

8.69
9.16
9.42
9.59
9.73

3.99
4.99
5.44
5.71
5.88

9.42
9.99
10.31
10.51
10.68

330

378

425

4.18
5.33
5.84
6.15
6.35

10.03
10.70
11.07
11.30
11.50

4.35
5.63
6.22
6.56
6.79

10.55
11.30
11.72
11.99
12.22

4.50
5.90
6.56
6.93
7.20

11.01
11.83
12.29
12.59
12.84

Notes:
1. Fouling Factor = 0.0005.
2. Capacity based on 12C entering air temperature and 82C entering water temperature.

Inlet Size 10 (SI)


Rows

L/s

Water
Pressure
Drop (kPa)

1-Row
Capacity
kW

0.04
0.06
0.09
0.13
0.16
0.13
0.25
0.38
0.50
0.63

5.29
9.81
19.90
33.00
48.93
2.07
7.53
16.15
27.83
42.50

2-Row
Capacity
kW

165

212

260

307

Airflow (L/s)
354
401

472

519

613

661

4.36
4.74
5.09
5.28
5.40
7.87
8.64
8.93
9.07
9.17

4.83
5.27
5.71
5.96
6.11
8.98
10.06
10.46
10.68
10.81

5.21
5.75
6.26
6.56
6.75
9.87
11.23
11.76
12.05
12.22

5.54
6.17
6.75
7.10
7.33
10.59
12.23
12.88
13.23
13.45

5.83
6.54
7.21
7.60
7.87
11.20
13.10
13.86
14.27
14.53

6.41
7.33
8.21
8.71
9.06
12.36
14.81
15.83
16.40
16.75

6.61
7.60
8.55
9.11
9.48
12.73
15.37
16.49
17.10
17.50

6.94
8.07
9.18
9.84
10.28
13.34
16.34
17.62
18.34
18.80

7.09
8.28
9.47
10.17
10.64
13.60
16.75
18.12
18.88
19.38

6.08
6.88
7.63
8.07
8.37
11.72
13.85
14.72
15.19
15.49

Notes:
1. Fouling Factor = 0.0005.
2. Capacity based on 12C entering air temperature and 82C entering water temperature. Refer to correction factors for different
entering conditions on page 45.
3. The following equations may be used in calculating Leaving AirTemperature (LAT) and WaterTemperature Difference (WTD).

LAT = EAT +

VAV-PRC008-EN

kW x 0.83
L/s

WTD = EWT - LWT =

kW
(4.19) L/s

SD 13

Single-Duct

Performance
DataHot Water
Coil (SI)

Inlet Size 12 (SI)


Rows

L/s

Water
Pressure
Drop (kPa)

1-Row
Capacity
kW

0.06
0.13
0.19
0.25
0.32
0.13
0.32
0.50
0.69
0.88
1.10

2.04
7.08
14.79
25.04
37.73
0.74
4.12
10.01
18.35
29.06
44.53

2-Row
Capacity
kW

Airflow (L/s)
566
661

189

283

378

472

5.30
6.08
6.40
6.57
6.68

10.42
10.82
11.01
11.12
11.21

6.19
7.28
7.74
8.00
8.16

13.37
14.09
14.44
14.65
14.81

6.88
8.25
8.86
9.20
9.42

15.59
16.63
17.15
17.46
17.70

7.44
9.10
9.84
10.26
10.54

17.33
18.68
19.35
19.77
20.08

7.90
9.85
10.71
11.22
11.55

18.74
20.37
21.20
21.71
22.10

8.29
10.51
11.50
12.09
12.48

19.92
21.80
22.77
23.37
23.83

755

849

944

8.64
11.11
12.23
12.89
13.33

20.91
23.03
24.13
24.81
25.34

8.93
11.65
12.90
13.63
14.13

21.77
24.10
25.32
26.08
26.67

9.20
12.14
13.52
14.33
14.87

22.51
25.04
26.38
27.21
27.86

Notes:
1. Fouling Factor = 0.0005.
2. Capacity based on 12C entering air temperature and 82C entering water temperature.

Inlet Size 14 (SI)


Rows

L/s

Water
Pressure
Drop (kPa)

1-Row
Capacity
kW

0.13
0.19
0.25
0.32
0.38
0.44
0.32
0.57
0.82
1.07
1.32
1.42

3.69
7.67
12.93
19.43
27.13
36.01
3.24
9.93
20.07
33.61
50.49
57.67

2-Row
Capacity
kW

330

425

519

613

Airflow (L/s)
708
802

944

1085

1227

1416

9.31
10.07
10.49
10.76
10.95
11.09
16.31
17.50
18.00
18.27
18.45
18.50

10.31
11.26
11.80
12.15
12.40
12.58
18.74
20.41
21.13
21.52
21.78
21.85

11.21
12.31
12.97
13.39
13.69
13.92
20.71
22.85
23.78
24.30
24.64
24.73

11.99
13.24
14.01
14.52
14.88
15.14
22.34
24.92
26.06
26.71
27.13
27.25

12.68
14.11
14.97
15.55
15.97
16.28
23.71
26.72
28.06
28.82
29.32
29.47

14.12
15.98
17.08
17.83
18.39
18.80
26.38
30.31
32.12
33.16
33.85
34.05

14.84
16.94
18.20
19.04
19.67
20.15
27.62
32.03
34.08
35.28
36.07
36.30

15.47
17.80
19.21
20.16
20.85
21.40
28.66
33.51
35.80
37.14
38.02
38.28

16.20
18.82
20.43
21.52
22.31
22.92
29.83
35.20
37.76
39.28
40.28
40.58

13.30
14.91
15.86
16.51
16.98
17.33
24.89
28.28
29.82
30.70
31.28
31.44

Notes:
1. Fouling Factor = 0.0005.
2. Capacity based on 12C entering air temperature and 82C entering water temperature.

Inlet Size 16 (SI)


Rows

L/s

Water
Pressure
Drop (kPa)

1-Row
Capacity
kW

0.13
0.19
0.25
0.32
0.38
0.47
0.32
0.57
0.82
1.07
1.32
1.42

4.10
8.48
14.26
21.39
29.83
44.89
3.44
10.45
21.07
35.21
52.82
60.31

2-Row
Capacity
kW

425

566

708

849

Airflow (L/s)
944
1133

1321

1510

1699

1888

11.21
12.26
12.86
13.25
13.52
13.80
20.13
21.84
22.55
22.95
23.20
23.27

12.61
13.90
14.68
15.20
15.56
15.94
23.37
25.85
26.92
27.52
27.90
28.01

13.75
15.31
16.25
16.89
17.35
17.82
25.88
29.08
30.50
31.30
31.82
31.97

14.72
16.57
17.65
18.41
18.95
19.53
27.88
31.76
33.50
34.50
35.14
35.33

15.29
17.33
18.52
19.34
19.95
20.59
29.00
33.30
35.25
36.37
37.10
37.31

17.14
19.86
21.51
22.62
23.42
24.32
32.41
38.14
40.84
42.41
43.45
43.75

17.87
20.90
22.77
24.03
24.95
25.94
33.67
39.99
43.02
44.79
45.97
46.32

18.52
21.83
23.90
25.32
26.35
27.45
34.73
41.59
44.91
46.87
48.18
48.56

19.09
22.67
24.93
26.49
27.63
28.87
35.64
42.98
46.57
48.71
50.13
50.55

16.29
18.68
20.11
21.06
21.77
22.54
30.89
35.94
38.28
39.64
40.53
40.79

Notes:
1. Fouling Factor = 0.0005.
2. Capacity based on 12C entering air temperature and 82C entering water temperature. Refer to correction factors for different
entering conditions on page 45.
3. The following equations may be used in calculating Leaving Air Temperature (LAT) and WaterTemperature Difference (WTD).

LAT = EAT +

SD 14

kW x 0.83
L/s

WTD = EWT - LWT =

kW
(4.19) L/s

VAV-PRC008-EN

Single-Duct

Performance
DataHot Water
Coil (SI)

Inlet Size 16x24 (SI)


Rows

L/s

Water
Pressure
Drop (kPa)

1-Row
Capacity
kW

0.13
0.19
0.25
0.32
0.38
0.47
0.32
0.57
0.82
1.07
1.32
1.42

4.50
9.28
15.59
23.35
32.53
48.88
3.75
11.08
21.95
36.25
53.88
61.34

2-Row
Capacity
kW

472

802

1133

1463

Airflow (L/s)
1793
2124
2454

2784

3115

3445

12.54
13.77
14.50
14.97
15.30
15.64
22.58
24.58
25.41
25.87
26.16
26.25

15.39
17.29
18.40
19.19
19.74
20.33
29.24
33.13
34.84
35.81
36.43
36.61

17.36
19.94
21.48
22.50
23.27
24.11
33.37
38.84
41.36
42.81
43.76
44.03

18.84
22.04
24.00
25.32
26.27
27.31
36.20
42.99
46.21
48.09
49.33
49.69

20.01
23.74
26.09
27.70
28.87
30.13
38.28
46.17
49.99
52.26
53.76
54.20

22.40
27.44
30.79
33.16
34.93
36.87
42.23
52.50
57.73
60.89
63.02
63.65

22.97
28.35
31.99
34.58
36.53
38.68
43.11
53.97
59.57
62.98
65.28
65.96

23.46
29.16
33.05
35.86
37.98
40.33
43.86
55.25
61.18
64.81
67.26
67.99

20.95
25.17
27.88
29.76
31.14
32.63
39.89
48.70
53.05
55.65
57.38
57.89

21.74
26.39
29.43
31.57
33.14
34.86
41.17
50.76
55.58
58.48
60.42
61.00

Notes:
1. Fouling Factor = 0.0005.
2. Capacity based on 12C entering air temperature and 82C entering water temperature. Refer to correction factors for different
entering conditions on page 45.
3. The following equations may be used in calculating Leaving Air Temperature (LAT) and WaterTemperature Difference (WTD).

LAT = EAT +

kW x 0.83
L/s

WTD = EWT - LWT =

kW
(4.19) L/s

Temperature Correction Factors for Water Pressure Drop (kPa)


Average Water Temperature
Correction Factor

93
0.970

88
0.985

82
1.000

77
1.020

71
1.030

66
1.050

60
1.080

54
1.100

49
1.130

43
1.150

39
0.56

44
0.64

56
0.80

69
1.00

78
1.12

83
1.20

89
1.29

Temperature Correction Factors for Coil Capacity (kW)


Entering Water Minus Entering Air
Correction Factor

22
0.32

28
0.40

33
0.48

100
1.45

111
1.61

Coil Only Water Weights


Inlet
Size
04
05
06
08
10
12
14
16
24x16
04
05
06
08
10
12
14
16
24x16

VAV-PRC008-EN

Coil
Type
1-Row
1-Row
1-Row
1-Row
1-Row
1-Row
1-Row
1-Row
1-Row
2-Row
2-Row
2-Row
2-Row
2-Row
2-Row
2-Row
2-Row
2-Row

Internal
Volume
(cm3)
153.6
153.6
153.6
209.4
312.4
492.5
839.1
960.6
1082.0
388.0
388.0
388.0
581.3
800.1
1103.0
1545.0
1788.0
2030.0

Internal Operating
Volume Weight
(liters)
(kg)
0.154
2.421
0.154
2.421
0.154
2.421
0.209
2.477
0.312
3.487
0.493
4.853
0.839
6.309
0.961
7.337
1.082
9.273
0.388
3.12
0.388
3.12
0.388
3.12
0.580
4.099
0.799
5.294
1.101
7.026
1.542
8.965
1.784
10.57
2.027
13.53

SD 15

Single-Duct

Performance
Data
Electric Data

VCEF Electric Coil kW Guidelines Minimum to Maximum


Inlet
Size

Stages

120V

Single-Phase Voltage
208V/240V
277V
347V

480V

208V

Three-Phase Voltage
480V
575V
380V/50 Hz

04

1
1.0
1.0
1.0
1.0
1.0
1.0
1.0

1.0
2
1.0
1.0
1.0
1.0

3
1.0
1.0
1.0
1.0

05
1
1.02.5
1.02.5
1.02.5
1.02.5
1.02.5
1.02.5
1.02.5
1.52.5
1.02.5
2
1.02.5
1.02.5
1.02.5
1.02.5
1.52.5
1.02.5

3
1.02.5
1.02.5
1.02.5
1.52.5

06
1
1.04.0
1.04.0
1.04.0
1.04.0
1.04.0
1.04.0
1.04.0
1.54.0
1.04.0
2
1.04.0
1.04.0
1.04.0
1.04.0
1.54.0
1.04.0

3
1.04.0
1.04.0
1.04.0
1.54.0

08
1
1.05.0
1.07.0
1.07.0
1.07.0
1.07.0
1.07.0
1.07.0
1.57.0
1.07.0
2
1.05.0
1.07.0
1.07.0
1.07.0
1.57.0
2.07.0
4.0

3.07.0
3
1.05.0
1.07.0
1.07.0
1.57.0
2.07.0

6.0

4.07.0
10
1
1.05.0
1.09.0
1.011.0
1.011.0
1.011.0
1.011.0
1.011.0
1.511.0
1.011.0
2
1.05.0
1.09.0
1.011.0
1.011.0
1.011.0
1.011.0
3.011.0
9.010.0
2.011.0
3
1.05.0
1.09.0
1.011.0
1.511.0
1.511.0
2.011.0
5.011.0

3.011.0
12
1
1.05.0
1.09.0
1.013.0
1.016.0
1.016.0
1.016.0
1.016.0
1.516.0
1.016.0
2
1.05.0
1.09.0
1.013.0
1.016.0
1.016.0
1.016.0
3.016.0
3.516.0
1.516.0
3
1.05.0
1.09.0
1.013.0
1.516.0
1.516.0
2.016.0
4.015.0
5.516.0
2.516.0
14
1
1.05.0
1.09.0
1.013.0
1.016.0
1.022.0
1.016.0
1.022.0
1.522.0
1.022.0
2
1.05.0
1.09.0
1.013.0
1.016.0
1.022.0
1.016.0
2.022.0
3.022.0
1.522.0
3
1.05.0
1.09.0
1.013.0
1.516.0
1.522.0
2.016.0
3.020.0
4.518.0
2.522.0
16
1
1.05.0
1.09.0
1.013.0
1.016.0
1.022.0
1.016.0
1.030.0
1.530.0
1.030.0
2
1.05.0
1.09.0
1.013.0
1.016.0
1.022.0
1.016.0
2.030.0
2.530.0
1.530.0
3
1.05.0
1.09.0
1.013.0
1.516.0
1.522.0
2.016.0
3.030.0
4.026.0
2.530.0
24 x 16
1
1.05.0
1.09.0
1.013.0
1.016.0
1.022.0
1.016.0
1.038.0
1.546.0
1.030.0
2
1.05.0
1.09.0
1.013.0
1.016.0
1.022.0
1.016.0
2.038.0
2.546.0
1.530.0
3
1.05.0
1.09.0
1.013.0
1.516.0
1.522.0
1.516.0
3.038.0
3.540.0*
2.530.0
* 36.0 not available
Notes:
1. Coils available with 24-volt magnetic or mercury contactors, load carrying P.E switches, and P.E. switch with magnetic or mercury contactors.
2. Available kW increments are by 0.5 kW from 1.0 to 8.0 kW, by 1.0 kW from 9.0 to 18.0 kW, and by 2.0 kW from 18.0 to 46.0 kW.
3. Each stage will be equal in kW output.
4. All heaters contain an auto-thermal cutout and a manual-reset cutout.
5. The current amp draw for the heater elements is calculated by the formula below.
6. The maximum allowable kW is based on the largest kW possible per a voltage and the minimum airflow per an inlet size and kW.
Minimum Circuit Ampacity (MCA) Equation
MCA = heater amps x 1.25
Maximum Overcurrent Protection (MOP) Equation
MOP = heater amps
However since MOP MCA, then choose next fuse greater than MCA.
Units without electric reheat would use smallest fuse sizing.
Standard Fuse Sizes: 15, 20, 25, 30, 35, 40, 45, 50, and 60.
ExampleFor MOP of Single-Duct Unit
A model VCEF, electric reheat unit size 14 has 480/3 phase 15 kW electric reheat with 2 stages.
15 x 1000
= 18.06
15 kW 480/3 heater
480 x 1.73
MCA = 18.06 x 1.25 = 22.58 amps. Since MOP MCA, then MOP = 25.
Useful formulas:
kW =

Cfm x ATD
3145

3amps =

ATD =

SD 16

kW x 1000
Primary Voltage x 3

kW x 3145
Cfm

kW = 1214 x L/s x ATD

kW x 1000
1amps = Primary
Voltage

ATD =

kW
1214 x L/s

VAV-PRC008-EN

Single-Duct

Performance
Data
Electric Data

Minimum
and Maximum Airflow per Inlet Size and kW

I-P
Inlet
Size

Min
kW

Max
Cfm

SI
Min
Cfm

Max
L/s

I-P
L/s

Inlet
Size

kW

14
1.09.0
1.0
130
225
61
106
10.0
1.0
125
350
59
165
11.0
1.5
165
350
78
165
12.0
2.0
185
350
87
165
13.0
2.5
205
350
97
165
14.0
6
1.0
120
500
57
236
15.0
1.5
150
500
71
236
16.0
2.0
180
500
85
236
17.0
2.5
210
500
99
236
18.0
3.0
240
500
113
236
20.0
3.5
270
500
127
236
22.0
4.0
300
500
142
236
16
1.012.0
8
1.03.0
210
900
99
425
13.0
3.5
265
900
125
425
14.0
4.0
315
900
149
425
15.0
4.5
345
900
163
425
16.0
5.0
380
900
179
425
17.0
5.5
420
900
198
425
18.0
6.0
450
900
212
425
20.0
6.5
490
900
231
425
22.0
7.0
525
900
248
425
24.0
10
1.04.5
330
1400
156
660
26.0
5.0
370
1400
175
660
28.0
5.5
410
1400
194
660
30.0
6.0
450
1400
212
660
24 x 16 1.022.0
6.5
495
1400
234
660
24.0
7.0
550
1400
260
660
26.0
7.5
605
1400
286
660
28.0
8.0
660
1400
312
660
30.0
9.0
710
1400
335
660
32.0
10.0
765
1400
361
660
34.0
11.0
820
1400
387
660
36.0
12
1.06.5
470
2000
222
943
38.0
7.0
520
2000
245
943
40.0
7.5
565
2000
267
943
42.0
8.0
615
2000
290
943
44.0
9.0
705
2000
333
943
46.0
10.0
785
2000
371
943
11.0
860
2000
406
943
12.0
940
2000
444
943
13.0
1000
2000
472
943
14.0
1055
2000
498
943
15.0
1115
2000
526
943
16.0
1175
2000
555
943
Note: Minimum and maximum airflow is based on UL listing and certification.
4
5

VAV-PRC008-EN

SI

Min
Cfm

Max
Cfm

Min
L/s

Max
L/s

640
720
800
880
960
1040
1120
1200
1280
1345
1475
1600
840
910
980
1050
1120
1190
1260
1400
1540
1680
1820
1960
2100
1600
1800
2000
2200
2400
2600
2800
3000
3200
3400
3600
3800
4000

3000
3000
3000
3000
3000
3000
3000
3000
3000
3000
3000
3000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000

302
340
378
415
453
491
529
566
604
635
696
755
396
430
463
496
529
562
595
661
727
793
859
925
991
755
850
944
1038
1133
1227
1322
1416
1510
1605
1699
1794
1888

1415
1415
1415
1415
1415
1415
1415
1415
1415
1415
1415
1415
1886
1886
1886
1886
1886
1886
1886
1886
1886
1886
1886
1886
1886
3772
3772
3772
3772
3772
3772
3772
3772
3772
3772
3772
3772
3772

SD 17

Single-Duct

Performance
Data
Acoustics

Discharge Sound Power (dB)


Inlet Fan
Size Cfm
4

10

12

14

16

24
x
16

80
120
150
225
130
200
250
350
200
300
400
500
350
520
700
900
550
820
1100
1400
800
1200
1600
2000
1100
1600
2100
3000
1400
2100
2800
4000
2700
4000
5300
6000
7500
8000

L/s

0.5" Ps
4
5

38
57
71
106
61
94
118
165
94
142
189
236
165
245
330
425
260
387
519
661
378
566
755
944
519
755
991
1416
661
991
1321
1888
1274
1888
2501
2832
3540
3776

57
60
60
65
52
55
57
59
52
56
57
61
54
56
58
61
53
56
60
64
54
56
59
63
54
57
60
66
54
57
61
68
68
70
69
68
67
67

57
60
60
64
52
55
57
59
53
56
56
60
54
56
57
60
52
55
58
61
52
54
57
60
52
55
59
65
52
55
60
67
67
70
70
70
70
70

45
48
48
53
44
47
48
53
45
47
50
54
47
50
53
56
52
54
57
61
52
54
58
61
51
55
59
67
51
55
61
68
61
65
67
68
70
71

44
48
49
54
43
47
49
53
44
48
49
53
45
48
51
56
51
51
54
58
49
50
53
56
46
49
52
57
47
51
54
63
58
62
64
65
67
68

40
43
45
50
41
43
44
48
41
44
44
49
44
45
48
52
45
46
49
53
47
49
52
56
44
46
49
55
46
49
51
57
54
58
61
62
63
64

37
41
42
49
38
40
42
47
38
41
42
47
40
42
44
49
40
42
46
51
41
43
46
51
39
41
44
52
40
43
48
54
50
54
58
60
63
64

58
64
65
70
55
59
62
66
56
59
63
65
57
59
62
65
58
61
65
69
59
62
64
68
60
63
65
71
60
63
66
71
72
74
75
75
76
76

Discharge Sound Power (dB)


1.0" Ps
2.0" Ps
4
5
6
7
2
3
4
5

Ps
3.0"
4
5

61
65
66
71
58
61
63
65
59
61
63
65
61
63
64
65
60
62
65
66
59
62
64
67
60
61
65
70
60
62
65
70
71
75
76
76
76
76

52
54
55
60
51
55
56
58
54
55
57
60
53
56
59
61
57
60
63
64
57
60
62
65
57
60
63
68
58
60
64
70
67
71
75
76
77
78

60
57
58
61
58
58
58
59
58
58
58
60
58
60
61
62
62
62
63
63
63
64
65
65
61
62
62
64
63
64
64
65
68
72
74
75
76
77

56
55
56
59
55
56
57
58
55
56
57
59
60
66
64
65
58
60
60
60
61
62
63
64
59
61
61
61
62
61
63
64
65
68
70
71
73
74

61
65
68
72
59
61
65
70
60
64
68
71
64
66
68
72
66
69
72
74
67
72
73
76
68
70
72
77
69
70
72
77
75
79
81
81
82
82

69
72
72
78
68
69
71
74
70
71
72
74
73
73
74
75
69
72
73
75
69
73
75
75
72
75
73
77
75
75
73
76
77
81
84
85
86
86

66
70
71
72
68
69
71
72
71
71
72
72
70
71
73
73
69
69
72
72
68
71
73
74
71
72
73
75
73
73
73
76
76
80
84
86
90
91

64
63
64
65
63
63
63
64
63
64
63
64
63
65
66
67
66
66
67
67
67
68
69
69
66
67
67
69
67
68
69
70
72
76
78
79
80
81

61
60
61
63
60
61
61
63
60
62
62
63
61
66
69
68
62
63
64
64
64
66
66
67
63
64
64
66
66
66
65
67
69
72
74
75
76
77

51
53
54
59
50
53
55
57
52
53
55
58
51
53
56
59
57
60
61
62
55
57
58
61
54
56
57
61
55
57
58
63
65
68
71
72
73
74

47
49
51
55
48
50
52
53
49
50
51
53
50
52
53
56
53
55
56
57
55
57
57
60
53
54
54
58
55
55
57
61
62
65
67
68
70
71

46
47
49
54
47
49
50
53
47
48
50
53
53
56
57
57
48
52
53
54
52
55
56
59
51
51
52
58
51
52
54
59
58
61
63
65
68
69

60
64
67
73
57
62
65
70
58
63
66
69
61
64
66
70
64
66
70
73
66
68
70
73
65
67
69
76
66
68
69
75
74
78
78
79
80
80

66
69
72
77
64
67
69
72
66
67
69
71
68
71
71
72
66
68
70
72
67
69
71
73
71
70
71
76
71
70
71
75
75
79
82
82
83
83

60
63
64
67
60
63
63
66
63
64
65
68
61
64
66
68
64
65
67
69
65
67
69
70
66
67
69
72
67
68
70
73
73
77
81
83
88
89

60
60
61
64
59
61
60
62
60
61
61
63
58
61
62
64
66
66
68
66
63
63
64
65
62
63
64
66
63
64
65
68
71
75
78
79
81
82

66
68
68
69
66
67
69
69
67
69
68
69
66
66
68
68
71
70
71
70
67
68
69
69
67
67
68
70
69
70
70
72
75
78
81
82
84
85

Notes:
1. All data are measured in accordance with current Industry Standard ARI 880, version 1998.
2. All sound power levels, dB re: 10-12 watts.
3. Where Ps is inlet static pressure minus discharge static pressure.

SD 18

VAV-PRC008-EN

Single-Duct

Performance
Data
Acoustics

Radiated Sound Power (dB)


Inlet
Size Cfm
4

10

12

14

16

24
x
16

80
120
150
225
130
200
250
350
200
300
400
500
350
520
700
900
550
820
1100
1400
800
1200
1600
2000
1100
1600
2100
3000
1400
2100
2800
4000
2700
4000
5300
6000
7500
8000

L/s

0.5" Ps
4
5

38
57
71
106
61
94
118
165
94
142
189
236
165
245
330
425
260
387
519
661
378
566
755
944
519
755
991
1416
661
991
1321
1888
1274
1888
2501
2832
3540
3776

48
47
47
52
47
48
48
51
52
52
55
55
46
49
50
56
48
53
58
62
49
54
60
63
47
52
55
63
50
51
56
61
65
67
67
68
69
69

45
45
45
49
44
45
44
47
46
48
49
49
42
43
46
49
44
47
50
53
46
48
53
58
46
49
52
59
47
49
54
60
63
67
66
66
67
67

40
40
41
44
35
38
40
44
38
41
44
47
38
41
44
50
42
43
46
49
40
43
47
52
36
39
43
51
38
41
45
55
53
57
58
59
61
62

33
33
35
40
29
32
34
38
31
33
36
40
31
35
38
44
32
36
39
42
33
35
38
42
30
32
35
42
32
35
38
45
45
48
49
51
54
55

31
30
30
35
24
25
27
31
25
25
28
32
27
31
34
37
25
28
30
34
27
29
32
37
24
24
27
34
26
28
31
38
38
40
42
44
48
49

23
23
24
30
21
22
23
26
22
22
24
27
22
24
26
29
24
25
27
30
27
27
30
34
23
23
25
31
23
24
27
32
30
32
35
37
42
44

48
49
51
57
48
49
50
55
50
55
56
59
48
51
54
59
52
57
61
66
54
59
63
67
53
56
59
65
54
56
59
63
70
71
74
74
75
75

Radiated Sound Power (dB)


Ps
1.0" Ps
2.0"
4
5
6
7
2
3
4
5

3.0" Ps
4
5

47
48
49
54
45
47
48
51
47
50
53
54
45
48
51
53
49
52
55
58
51
54
58
62
53
54
57
64
54
54
56
63
65
71
75
75
74
74

43
45
46
49
41
43
45
47
43
46
48
51
43
47
50
53
48
49
51
54
46
48
50
54
42
45
48
54
45
47
49
56
60
64
69
69
70
70

43
42
43
45
39
39
40
41
38
38
40
41
41
43
45
46
39
40
42
43
42
43
43
45
40
39
40
41
43
44
44
46
51
54
56
57
58
59

35
36
37
39
33
35
35
37
33
35
35
36
36
38
39
39
32
33
35
37
35
37
39
42
35
35
36
37
38
39
39
41
45
48
50
51
52
52

46
51
51
59
48
50
53
56
51
57
59
63
56
56
60
63
58
62
67
71
59
66
71
75
60
63
65
69
63
64
65
69
72
76
78
79
80
80

52
54
56
61
51
55
56
58
55
57
58
60
58
57
59
61
58
61
63
65
62
64
66
68
64
67
67
69
66
66
65
66
71
77
79
80
81
82

60
60
61
63
58
58
60
60
59
60
60
61
64
63
62
62
59
60
61
63
59
60
61
61
60
60
61
60
61
60
61
62
69
72
76
77
79
80

48
47
48
49
45
45
44
44
44
44
43
44
46
47
48
49
44
44
45
46
47
47
48
50
43
43
44
45
47
48
49
50
54
58
60
61
62
63

42
42
42
44
40
40
40
40
40
39
40
40
42
44
44
44
38
38
39
41
40
42
43
45
38
40
40
41
43
43
44
45
50
52
53
54
55
56

37
38
39
43
35
37
38
41
36
38
40
43
36
39
42
46
40
41
43
46
39
41
42
45
36
38
40
44
40
41
43
47
52
55
57
58
59
59

34
34
35
39
30
32
33
35
31
32
33
36
35
37
38
41
31
33
35
38
34
35
37
40
32
32
33
36
35
36
37
41
45
48
49
50
51
52

25
27
28
33
25
26
27
31
26
27
28
31
27
29
34
35
26
27
29
33
29
30
32
38
27
26
28
34
29
30
32
36
37
41
42
43
45
46

48
50
52
60
48
50
52
59
52
56
59
62
54
55
58
62
55
60
64
69
58
64
68
72
57
60
63
68
60
61
62
67
71
74
76
77
78
79

51
51
53
59
48
52
53
56
51
53
56
59
52
54
57
59
55
58
61
63
58
61
64
68
61
63
64
68
62
61
62
66
69
75
77
78
80
81

53
54
55
57
50
52
53
55
52
53
55
57
53
54
57
57
53
55
57
58
53
55
57
58
52
52
55
57
53
55
56
59
66
69
74
75
78
79

47
46
47
48
45
45
44
47
43
44
46
47
42
45
48
49
47
48
50
51
46
48
49
50
43
44
46
48
47
49
49
51
59
61
64
65
66
67

54
52
53
54
51
51
52
51
50
50
50
52
52
51
52
53
50
52
53
55
51
52
53
54
48
49
50
52
52
53
54
55
62
65
67
68
69
70

Notes:
1. All data are measured in accordance with current Industry Standard ARI 880, version 1998.
2. All sound power levels, dB re: 10-12 watts.
3. Where Ps is inlet static pressure minus discharge static pressure.

VAV-PRC008-EN

SD 19

Single-Duct

Performance
Data
Acoustics

Sound Noise Criteria (NC)


Inlet
0.5"
Size Cfm L/s (127 Pa)

Discharge
Ps)
Inlet Pressure (
1.0"
2.0"
(254 Pa)
(508 Pa)

3.0"
(762 Pa)

0.5"
(127 Pa)

Radiated
Ps)
Inlet Pressure (
1.0"
2.0"
(254 Pa)
(508 Pa)

3.0"
(762 Pa)

80
38
15
20
26
30

16
27
35
120
57
19
25
30
34

19
29
35
150
71
19
26
34
34

20
30
36
225 106
24
32
39
40
17
23
32
38
5 130
61

16
24
29

15
24
33
200
94

20
27
30

16
26
33
250 118
15
22
30
32

19
27
35
350 165
17
25
34
36
17
21
30
35
6 200
94

17
26
31

16
26
34
300 142

20
27
32
15
20
27
35
400 189

22
30
34
17
22
30
35
500 236
19
25
32
36
21
25
32
36
8 350 165

17
27
34

16
27
39
520 245

21
31
34

21
29
38
700 330

22
31
35
17
24
32
37
900 425
17
24
32
36
24
27
32
37
10 550 260

16
24
27
15
22
27
34
820 387

19
26
31
16
23
30
35
1100 519

22
29
32
20
25
32
36
1400 661
17
24
31
35
25
30
34
38
12 800 378

16
25
27

20
27
34
1200 566

19
27
32
16
22
31
35
1600 755

21
30
35
22
27
35
37
2000 944
16
25
32
35
27
32
39
41
14 1100 519

16
30
31

21
31
35
1600 755

17
29
35
16
22
34
38
2100 991
15
22
30
32
20
26
35
38
3000 1416
22
29
36
37
29
35
39
40
16 1400 661

16
30
35

22
32
37
2100 991

19
29
35
16
22
31
37
2800 1321
16
22
30
32
22
25
32
36
4000 1888
25
29
35
36
30
34
37
37
24 2700 1274
25
30
35
37
34
36
41
45
x 4000 1888
29
35
39
41
38
42
47
50
16 5500 2501
29
36
42
45
37
47
50
52
6000 2832
29
36
42
46
37
47
51
54
7500 3540
29
36
44
47
38
46
55
56
8000 3776
29
36
44
47
38
46
56
57
Notes:
1. represents NC levels below NC 15.
2. NC Values are calculated using current Industry Standard ARI 885, 2002 addendum to revision 1998. RadiatedTransfer Function
obtained from Appendix E, Type 2 Mineral Fiber Insulation.
3. Where Ps is inlet static pressure minus discharge static pressure.

ARI 885-98 DISCHARGE TRANSFER FUNCTION ASSUMPTIONS:


Octave Band
2
3
4
5
6
7
Small Box (< 300 cfm)
-24
-28
-39
-53
-59
-40
Medium Box (300-700 cfm)
-27
-29
-40
-51
-53
-39
Large Box (> 700 cfm)
-29
-30
-41
-51
-52
-39
Note: Add to terminal unit sound power to determine discharge sound
pressure in the space.

ARI 885-98 RADIATED TRANSFER FUNCTION ASSUMPTIONS:


Octave Band
2
3
4
5
6
7
Type 1 Glass Fiber
-19
-19
-21
-25
-29
-35
Type 2 Mineral Fiber Insulation -18
-19
-20
-26
-31
-36
Type 3 Solid Gypsum Board
-23
-26
-25
-27
-27
-28
Note: Select the ceiling type which most closely represents the
application. Next, add to terminal unit sound power to determine radiated
sound pressure in the space.

SD 20

VAV-PRC008-EN

Single-Duct

Performance
Data
Acoustics
Discharge Sound Power (dB)
ARI Conditions
Inlet
Size

Cfm

L/s

4
5
6
8
10
12
14
16
24x16

150
250
400
700
1100
1600
2100
2800
5300

71
118
189
330
519
755
991
1321
2501

67
63
65
64
69
68
68
69
77

1.5" Inlet Pressure (381 Pa)


3
4
5
6
70
66
67
68
68
69
68
68
79

60
60
62
62
66
66
66
67
78

58
57
59
59
66
61
61
62
75

55
55
56
58
61
62
59
61
71

7
53
54
55
60
57
60
58
60
68

Radiated Sound Power (dB)


ARI Conditions
Inlet
Size Cfm L/s
4
5
6
8
10
12
14
16
24x16

150
250
400
700
1100
1600
2100
2800
5300

71
118
189
330
519
755
991
1321
2501

2
52
52
58
57
63
66
61
60
75

1.5" Inlet Pressure (381 Pa)


3
4
5
6
52
50
54
54
59
62
61
60
76

50
49
51
53
54
54
51
53
72

43
42
43
45
47
46
43
46
61

39
37
37
42
39
40
37
41
53

7
33
31
32
36
32
36
32
36
46

Notes:
1. All sound data rated in accordance with current Industry Standard
ARI 880, version 1998.
2. All sound power levels, dB re: 10-12 watts.

VAV-PRC008-EN

SD 21

Single-Duct

Dimensional
Data

SINGLE-DUCT COOLING ONLY WITH OPTIONAL OUTLET PLENUM (VCCF)


VALV CFM

L/s

INLET SIZE
(NOMINAL )
C

11.50" (292 mm)

9.50" [241 mm]

11.50" (292 mm)

5.00" (127 mm)

2.75" (70 mm)

8.00" (203 mm)

9.85" (250 mm)

DISCHARGE DIM W/O OUTLET PLENUM

A (h)

WT
LBS
(KGS)

B (w)

11.50" (292 mm)

04

225

106

4" (104 mm)

05

350

165

5" (127 mm)

06

500

236

6" (152 mm)

08

900

425

8" (203 mm)

11.00" (279 mm) 11.50" [292 mm]

12.50" (318 mm)

5.50" (140 mm)

2.25" (57 mm)

10.00" (254 mm)

11.00" (279 mm)

10

1400

661

10" (254 mm)

12.00" (305 mm) 13.50" [343 mm]

15.50" (394 mm)

5.00" (127 mm)

2.75" (70 mm)

12.00" (305 mm)

14.00" (356 mm)

14.00" (356 mm)

30 (14)

12

2000

994

12" (305 mm)

13.00" (330 mm) 15.50" [394 mm]

18.50" (470 mm)

4.50" (114 mm)

3.25" (83 mm)

14.00" (356 mm)

17.00" (432 mm)

14.00" (356 mm)

38 (17)

14

3000 1416

14" (356 mm)

14.00" (356 mm) 19.50" [495 mm]

20.50" (521 mm)

18.00" (457 mm)

19.00" (483 mm)

NA

46 (21)

16

4000 1888

16" (406 mm)

15.00" (381 mm)

24.50" (622 mm)

3.50" (89 mm)

4.25" (108 mm)

23.00" (584 mm)

NA

51 (23)

28.50" (724 mm)

5.55" (141 mm)

2.25" (57 mm)

27.00" (686 mm)

NA

70 (32)

24" x 16"
18.00" (457 mm)
24RT 8000 3776
(610 mm x 406 mm)

21 (9.5)

22 (10)

Z
OUTL CONVERSION CHART

CONTROL BOX
ANALOG OR DDC/UCM
(PNEU. CONTROLS AREA)

SYMBOL
I

SIZE 04 & 05
5.75" (146 mm)

C
AIRFLOW

II
III
IV

FLOW RING
TUBING
AIR
VALVE

4.00"
[102mm]

A,B,C
D,E,F

4
I, II
I, II

5
I, II
I, II

6
I, II
I, II

H
J

I, II
N/A

I, II
N/A

I, II

VALV

OUTL
L

8" (203 mm)


10" (254 mm)

OUTLET AVAILABILITY CHART - SEE OUTL CONVERSION FOR NOMINAL

6.50"
(165 mm)

ACTUATOR

NOMINAL
5" (127 mm)
6" (152 mm)

N/A

8
III
I, II, III
I, II, III
N/A

10

12

III, IV
II, III, IV
II, III, IV
I

IV
III, IV
III, IV
I, II

1.00"
(25.4 mm)

SLIP & DRIVE


CONNECTION
AIRFLOW

DISCHARGE
DIMENSIONS (BxA)

ARRANGEMENT "H"
1.50" (38 mm) FLANGE

TOP VIEW

5.50"
(140 mm)

NOTES:
1. Air inlet centered in unit front panel.
8.25"
(210 mm)

2. Outlet combinations to remote diffusers have


optional integral balancing dampers. (See
specification sheet.)

3. Outlet connections are centered in plenum panel.


4. Plenum not available with size 14 & 16 units.

BACK VIEW

5. Minimum of 1.5 duct diamenters of straight duct


required at inlet for proper flow reading.
6. Allow 12" (305 mm) on control side for servicing.
A

OUTLET PLENUM
ARRANGEMENTS
(TOP VIEW)

SD 22

7. Weights are an estimation and will vary based on


selected options, insulation type, etc.
8. Unit is field convertible from a left-hand connection
(shown) to right-hand by rotating unit.

VAV-PRC008-EN

Single-Duct

Dimensional
Data

SINGLE-DUCT HOT WATER WITH OPTIONAL OUTLET PLENUM (VCWF)


VALV CFM

L/s

INLET SIZE
(NOMINAL )
C

04

225

106

4" (104 mm)

05

350

165

5" (127 mm)

06

500

236

6" (152 mm)

08

900

425

10

1400

661

10" (254mm)

12

2000

994

14
16

DISCHARGE DIM W/O OUTLET PLENUM

A (h)

B (w)

WT
LBS
(KGS)
27 (12)

11.50" (292 mm)

9.50" (241 mm)

11.50" (292 mm)

5.00" (127 mm)

2.75" (70 mm)

8.00" (203 mm)

10.00" (254 mm)

11.00" (279 mm)

11.50" (292 mm) 12.50" (318 mm)

5.50" (140 mm)

2.25" (57 mm)

10.00" (254 mm)

11.00" (279 mm)

12.00" (305 mm)

13.50" (343 mm) 15.50" (394 mm)

5.00" (127 mm)

2.75" (70 mm)

12.00" (305 mm)

14.00" (356 mm)

14.00" (356 mm)

40 (18)

12" (305 mm)

13.00" (330 mm)

15.50" (394 mm) 18.50" (470 mm)

4.50" (114 mm)

3.25" (83 mm)

14.00" (356 mm)

17.00" (432 mm)

14.00" (356 mm)

51 (23)

3000 1416

14" (356 mm)

14.00" (356 mm)

19.50" (495 mm) 20.50" (521 mm)

18.00" (457 mm)

19.00" (483 mm)

NA

62 (28)

4000 1888

16" (406 mm)

15.00" (381 mm)

24.50" (622 mm)

3.50" (89 mm)

4.25" (108 mm)

23.00" (584 mm)

NA

71 (32)

24" x 16"
18.00" (457 mm)
(610 mm x 406 mm)

28.50" (724 mm)

5.55" (141 mm)

2.25" (57 mm)

27.00" (686 mm)

NA

95 (43)

8" (203 mm)

24RT 8000 3776

CONTROL BOX
ANALOG OR DDC/UCM
(PNEU. CONTROLS AREA)
Z

FLOW RING
TUBING

11.50" (292 mm)

30 (14)

OUTL CONVERSION CHART


C

SIZE 04 & 05
5.75" (146 mm)

AIRFLOW

AIR
VALVE

SYMBOL
I
II
III
IV

4.00"
(102 mm)

6.50"
(165 mm)

NOMINAL
5" (127 mm)
6" (152 mm)
8" (203 mm)
10" (254 mm)

OUTLET AVAILABILITY CHART - SEE OUTL CONVERSION FOR NOMINAL


VALV
4
5
6
8
10
I, II
I, II
I, II
III
A,B,C
III, IV
D,E,F
I, II, III
I, II
I, II
I, II
II, III, IV
OUTL
II, III, IV
I, II, III
I, II
I, II
I, II
H
N/A
I
N/A
N/A
J
N/A

ACTUATOR
L

12
IV
III, IV
III, IV
I, II

SLIP & DRIVE


CONNECTION

04, 05, 06 7.70" (196 mm)


all others 7.40" (188 mm)

WATER
COIL

DISCHARGE
DIMENSIONS (BxA)

AIR FLOW
E

ARRANGEMENT "H"
1.50" (38 mm) FLANGE
COIL ACCESS
76 mm x 178 mm
(3.00" x 7.00")

TOP VIEW

5.50"
(140 mm)

NOTES:

1. Air inlet is centered in unit front panel.


2. Outlet combinations to remote diffusers have
optional integral balancing dampers (See
specification sheet.)

8.25
(210 mm)

3. Outlet connections are centerd in plenum panel.


4. Plenum not available with sizes 14 & 16 units.
5. Minimum of 1.5 duct diameters of straight duct
required for proper flow reading.

BACK VIEW

6. Allow 12" (305 mm) on control side for servicing.

OUTLET PLENUM
ARRANGEMENTS
(TOP VIEW)

7. Weights are an estimation and will vary based


on selected options, insulation type, etc.
8. Coil furnished with stub sweat connections.
Handedness of coil connections is determined
by facing air stream.
9. Coils are provided without internal insulation. If
the unit is to be installed in a location with high
humidity, external insulation around the heating
coil should be installed as required.
10. Unit is field convertible from a left-hand connection
(shown) to right-hand by rotating unit.

VAV-PRC008-EN

SD 23

Single-Duct

Dimensional
Data

COIL INFORMATION FOR 1-ROW COIL


CFM

LITERS
per
SECOND

04

225

106

05

350

06

VALV

COIL
CONNECTION
3/

B
21 /

32 "

(17 mm)

7" (178 mm)

/ 32 "

(17 mm)

(10 mm) O.D.

7" (178 mm)

"

(17 mm)

"

(10 mm) O.D.

9" (229 mm)

"

(10 mm) O.D.

11" (279 mm)

"

(22 mm) O.D.

SEE

"

(22 mm) O.D.

(FIG 2)

"

(22 mm) O.D.

"

(22 mm) O.D.

"

(10 mm) O.D.

SEE

7" (178 mm)

165

/8"

(10 mm) O.D.

(FIG 1)

500

236

"

08

900

425

3/

10

1400

661

3/

12

2000

994

7/

14

3000

1416

16

4000

1888

7/

24 x 16

8000

3776

7/

7/

1/

2"

(13 mm)

7/

"

(22 mm)
(64 mm)

7/

"

(11 mm)

"

(53 mm)

(248 mm)

"

(400 mm)

"

15

(400 mm)

"

(38 mm)

" (27 mm)

15 / 4 "

(400 mm)

1 1/ "

(38 mm)

1 1 / " (27 mm)

10"

(254 mm)

10"

(254 mm)

"

10"

(254 mm)

10 "

11"

(279 mm)

12 " (305 mm)


14 " (356 mm)

14"

(356 mm)

17"

(432 mm)

19"

(482 mm)

23"

(584 mm)

27"

(686 mm)

(13 mm)

(22 mm)

8 " (203 mm)


8 " (203 mm)

"

"

18 "
18 " (457 mm)

E
E

CUSTOMER NOTES:
1.

Location of coil connections is determined by facing air stream.


L.H. and R.H. coil connections are available (L.H. shown).
Coils can be field rotated 180 for opposite connections.

2.

Coil furnished with stub sweat connections.

3.

Use port at bottom for inlet and port at top for outlet.

4.

Coil height and width is dependent upon unit height


and width.

5.

Access Panel is standard and found on connection side.

6.

Water coil discharge dimensions located on VCWF


dimension page.

AIR FLOW

AIR FLOW

(FIG 2)
(FIG 1)
9

13

/ 32"

13

1 / 64"
/32"

(29 mm)

(86 mm)

OUTLET

OUTLET

7
AIR FLOW

13

/ 16"
A

(198 mm)

7
AIR FLOW

INLET

13

/ 16"

(198 mm)

INLET
B

8 1/ 4 "
(210 mm)

1 3 /4 "
(44 mm)

8 1/ "
(210 mm)

(FIG 1)
SD 24

2 1/ 4 "
(57 mm)

(FIG 2)
VAV-PRC008-EN

Single-Duct

Dimensional
Data

COIL INFORMATION FOR 2-ROW COIL


VALV

CFM

LITERS
per
SECOND

225

106

(10 mm) O.D.

SEE

(FIG 1)

04

COIL
CONNECTION

A
" (191 mm)

(206 mm)

10"

(254 mm)

10"

(254 mm)

10"

(254 mm)

05

350

165

(10 mm) O.D.

06

500

236

08

900

425

(10 mm) O.D.


(22 mm) O.D.

SEE

" (210 mm)

(257 mm)

11"

(279 mm)

10

1400

661

(22 mm) O.D.

(FIG 2)

(308 mm)

14"

(356 mm)

12

2000

994

(22 mm) O.D.

" (260 mm)


" (311 mm)

(359 mm)

17"

(432 mm)

14

3000

1416

(22 mm) O.D.

(460 mm)

19"

(482 mm)

16

4000

1888

(460 mm)

23"

(584 mm)

24 x 16

8000

3776

"
1 / " (413 mm)
4
16 / 4 " (413 mm)

(460 mm)

27"

(686 mm)

7/

"

(22 mm) O.D.

/8 "

(22 mm) O.D.

"

18 /8

CUSTOMER NOTES:
1.

Location of coil connections is determined by facing air stream.


L.H. and R.H. coil connections are available (L.H. shown).
Coils can be field rotated 180 for opposite connections.

2.

Coil furnished with stub sweat connections.

3.

Use port at bottom for inlet and port at top for outlet.

4.

Coil height and width is dependent upon unit height


and width.

5.

Access Panel is standard and found on connection side.

6.

Water coil discharge dimensions located on VCWF


dimension page.

AIR FLOW

(FIG 2)
(FIG 1)

AIR FLOW

19/664"
3 13 / 32"
(86 mm)

23/

64"

3 13/332"

(9 mm)
7/
16 "
(11 mm)

OUTLET

AIR FLOW

7 13/ 32 "
(198 mm)

11/16"
(27 mm)

OUTLET

A
AIR FLOW

7 133/ 32"
(198 mm)

INLET
23/ "
64
(9 mm)

1"

2 1/2"

(25 mm)
8 1/ 4 "
(210 mm)

3 7/64"
(79 mm)
8 1/ 4 "
(210 mm)

(FIG 1)
VAV-PRC008-EN

(FIG 2)
SD 25

Single-Duct

Dimensional
Data

SINGLE-DUCT ELECTRIC HEAT (VCEF)


INLET SIZE
(NOMINAL )
C

04

225

LITERS
per
SECOND
106

05

350

165

5" (127 mm)

06

500

236

6" (152 mm)

08

900

425

8" (203 mm)

11.50" (292 mm)

17.00" (432 mm)

10.00" (254 mm)

11.00" (279 mm)

67 (30)

10

1400

661

10" (254 mm)

13.50" (343 mm)

20.00" (508 mm)

5.00" (127 mm)

12.00" (305 mm)

14.00" (356 mm)

81 (37)

12

2000

994

12" (305 mm)

15.50" (394 mm)

23.00" (584 mm)

4.50" (114 mm)

14.00" (356 mm)

17.00" (432 mm)

93 (42)

14

3000

1416

14" (356 mm)

19.50" (495 mm)

25.00" (635 mm)

18.00" (457 mm)

19.00" (483 mm)

108 (49)

16

4000

1888

16" (406 mm)

29.00" (737 mm)

3.50" (89 mm)

23.00" (584 mm)

121 (55)

24RT 8000

3776

24" x 16"
(610 mm x 406 mm)

33.00" (838 mm)

5.55" (141 mm)

27.00" (686 mm)

135 (61)

VALV CFM

4" (104 mm)

45.50" (1156 mm)

9.50" (241 mm)

16.00" (406 mm)

5.50" (140 mm)

43.50" (1105 mm)

CONTROL BOX
ELECTRIC OR DDC/UCM
(PNEU. CONTROLS AREA)

DISCHARGE DIMENSIONS
A

WT
LBS/KGS

8.00" (203 mm)

10.00" (254 mm)

63 (29)

ELECTRIC HEATER
CONTROL AREA
C

SIZE 04 & 05
5.75" (146 mm)

AIRFLOW
FLOW RING
TUBING
AIR
VALVE

4.00"
(102 mm)

6.50"
(165 mm")

ACTUATOR

TOP VIEW

AIRFLOW

SLIP & DRIVE


CONNECTION
W
5.50"
(140 mm)

CUSTOMER NOTES:
8.25"
(210 mm)

1. Air inlet is centered in unit front panel.


2. Slip and Drive discharge outlet standard.
3. 1.5 times duct diameter of straight duct at inlet for
proper flow reading.

BACK VIEW

4. For electric heater access, side hinged door must have


minimum distance per NEC or local code.
5. Allow 48" (1219 mm) of straight duct downstream of
unit before first runout & inside of the duct should be
equal discharge size (A & B).
6. Left-hand unit shown. Opposite hand available. (Moves
all components to the other side of the unit.)

SD 26

VAV-PRC008-EN

Single-Duct

Dimensional
Data

SINGLE-DUCT ELECTRIC HEAT (VCEF) RIGHT-HAND


INLET SIZE
(NOMINAL )
C

04

LITERS
per
SECOND
225
106

05

350

165

5" (127 mm)

06

500

236

6" (152 mm)

08

900

425

8" (203 mm)

10

1400

661

10" (254 mm)

12

2000

994

14

3000

16

4000

VALV CFM

24RT 8000

DISCHARGE DIMENSIONS

16.00" (406 mm)

5.50" (140 mm)

WT
LBS/KGS

8.00" (203 mm)

10.00" (254 mm)

63 (29)

45.50" (1156 mm)

9.50" (241 mm)

43.50" (1105 mm)

11.50" (292 mm)

17.00" (432 mm)

10.00" (254 mm)

11.00" (279 mm)

67 (30)

13.50" (343 mm)

20.00" (508 mm)

5.00" (127 mm)

12.00" (305 mm)

14.00" (356 mm)

81 (37)

12" (305 mm)

15.50" (394 mm)

23.00" (584 mm)

4.50" (114 mm)

14.00" (356 mm)

17.00" (432 mm)

93 (42)

1416

14" (356 mm)

19.50" (495 mm)

25.00" (635 mm)

18.00" (457 mm)

19.00" (483 mm)

108 (49)

1888

16" (406 mm)

3776

4" (104 mm)

24" x 16"
(610 mm x 406 mm)

3.50" (89 mm)

23.00" (584 mm)

121 (55)

33.00" (838 mm)

5.55" (141 mm)

27.00" (686 mm)

135 (61)

CONTROL BOX
ELECTRIC OR DDC/UCM
(PNEU. CONTROLS AREA)

C
SIZE 04 & 05
5.75" (146 mm)

29.00" (737 mm)

ELECTRIC HEATER
CONTROL AREA

AIRFLOW
FLOW RING
TUBING
4.00"
(102 mm)

AIR
VALVE

6.50"
(165 mm")

ACTUATOR

TOP VIEW

AIRFLOW
DISCHARGE OUTLET

SLIP & DRIVE


CONNECTION

5.50"
(140 mm)

CUSTOMER NOTES:
1. Air inlet is centered in unit front panel.
2. Slip & Drive discharge outlet standard.
3. 1.5 times duct diameter of straight duct at inlet.

8.25"
(210 mm)

BACK VIEW

VAV-PRC008-EN

4. For electric heater access, side hinged door must have


minimum distance per NEC or local code for proper
flow reading.
5. Allow 48" (1219 mm) of straight duct downstream of
unit before first runout & inside of the duct should be
equal discharge size (A & B)

SD 27

Single-Duct

MODELS VCCF, VCWF


and VCEF
Single-duct terminal units.

exposed edges of insulation (complete


metal encapsulation).

INSULATION

1" (25.4 mm) Double-wall


InsulationThe interior surface of the
unit casing is acoustically and
thermally lined with a 1-inch, 1.0 lb./ft3
(25.4 mm, 16.0 kg/m3) composite
density glass fiber with high-density
facing. The insulation R-value is 3.8. The
insulation is UL listed and meets
NFPA-90A and UL 181 standards. The
insulation is covered by an interior
liner made of 26-gage galvanized steel.
All wire penetrations are covered by
grommets. There are no exposed
edges of insulation (complete metal
encapsulation).

1/2" (12.7 mm) Matte-faced


InsulationThe interior surface of
the unit casing is acoustically and
thermally lined with -inch, 1.5 lb/ft3
(12.7 mm, 24.0 kg/m3) composite
density glass fiber with a high-density
facing. The insulation R-Value is 1.9.The
insulation is UL listed and meets NFPA90A and UL 181 standards. There are
no exposed edges of insulation
(complete metal encapsulation).

3/8" (9.5 mm) Closed-cell


InsulationThe interior surface of the
unit casing is acoustically and
thermally lined with 3/8-inch, 4.4 lb/ft3
(9.5 mm, 70.0 kg/m3) closed-cell
insulation. The insulation is UL listed
and meets NFPA-90A and UL 181
standards.The insulation has an
R-Value of 1.4. There are no exposed
edges of insulation (complete metal
encapsulation).

VCCF Cooling Only


VCWF With Hot Water Coil
VCEF With Electric Coil
CASING
22-gage galvanized steel.
AGENCY LISTING
The unit is UL and Canadian UL Listed
as a room air terminal unit. Control #
9N65.
ARI 880 Certified.

PRIMARY AIR VALVE

1" (25.4 mm) Matte-faced


InsulationThe interior surface of
the unit casing is acoustically and
thermally lined with 1-inch, 1.0 lb/ft3
(25.4 mm, 16.0 kg/m3) composite
density glass fiber with a high-density
facing. The insulation R-Value is 3.85.
The insulation is UL listed and meets
NFPA-90A and UL 181 standards.There
are no exposed edges of insulation
(complete metal encapsulation).
1/2" (12.7 mm) Foil-faced
InsulationThe interior surface of
the unit casing is acoustically and
thermally lined with -inch, 1.5 lb/ft3
(12.7 mm, 24.0 kg/m3) density glass
fiber with foil facing. The insulation
R-Value is 2.1.The insulation is UL
listed and meets NFPA-90A and UL 181
standards as well as bacteriological
standard ASTM C 665. There are no
exposed edges of insulation (complete
metal encapsulation).
1" (25.4 mm) Foil-faced
InsulationThe interior surface of the
unit casing is acoustically and
thermally lined with 1-inch, 1.5 lb/ft3
(25.4 mm, 24.0 kg/m3) density glass
fiber with foil facing. The insulation
R-Value is 4.1.The insulation is UL
listed and meets NFPA-90A and UL 181
standards as well as bacteriological
standard ASTM C 665. There are no
SD 28

Air Valve RoundThe primary air


inlet connection is an 18-gage
galvanized steel cylinder sized to fit
standard round duct. A multiple-point,
averaging flow sensing ring is
provided with balancing taps for
measuring +/-5% of unit cataloged
airflow. An airflow-versus-pressure
differential calibration chart is provided.
The damper blade is constructed of a
closed-cell foam seal that is
mechanically locked between two
22-gage galvanized steel disks. The
damper blade assembly is connected
to a cast zinc shaft supported by selflubricating bearings.The shaft is cast
with a damper position indicator.The
valve assembly includes a mechanical
stop to prevent over-stroking. At 4.0 in.
wg, air valve leakage does not exceed
1% of cataloged airflow.
Air Valve Rectangular Inlet collar is
constructed of 22-gage galvanized steel
sized to fit standard rectangular duct.
An integral multiple-point, averaging
flow-sensing ring provides primary
airflow measurement within +/-5% of
unit cataloged airflow. Damper is
22-gage galvanized steel. The damper
blade assembly is connected to a cast
zinc shaft supported by self-lubricating
bearings.The shaft is cast with a
damper position indicator.The valve
assembly includes a mechanical stop

Mechanical
Specifications
to prevent over-stroking. At 3.0 in. wg
air valve leakage does not exceed
6% of maximum airflow.
Air Valve Combinations Available:
Air Valve Size Maximum Cataloged Airflow
in. (mm)
cfm (L/s)
04 (102)
05 (127)
06 (152)
08 (203)
10 (254)
12 (305)
14 (356)
16 (406)
24 RT24x16 (610x406)

225 (106)
350 (165)
500 (236)
900 (425)
1400 (660)
2000 (943)
3000 (1415)
4000 (1886)
8000 (3773)

OUTLET CONNECTION

Slip & Drive ConnectionTerminal


units come standard with slip & drive
connection.
Outlet Plenum A sheet metal,
insulated box with circular opening(s)
is attached to the discharge of the
main unit at the factory. The circular
opening(s) are centered on the unit
plenum to accept round ductwork
connections.
Outlet Plenum with Balancing
DampersA sheet metal, insulated
box with circular opening(s) is factoryconnected to the main unit. The
circular opening(s) with balancing
damper(s) are centered on the unit
plenum to accept round ductwork
connections.
HOT WATER COILS

1-Row Hot Water CoilsThe 1-row


hot water reheat coil is factory-installed
on the discharge outlet.The coil has
144 aluminum-plated fins per foot. Full
fin collars provided for accurate fin
spacing and maximum fin-tube
contact. The 3/8" (9.5 mm) OD
seamless copper tubes are
mechanically expanded into the fin
collars. Coils are proof tested at
450 psig (3102 kPa) and leak tested at
300 psig (2068 kPa) air pressure under
water. Coil connections are left-hand.
Right-hand connections are optional.
2-Row Hot Water CoilsThe 2-row
hot water reheat coil is factory-installed
on the discharge outlet.The coil has
144 aluminum-plated fins per foot. Full
fin collars provided for accurate fin
spacing and maximum fin-tube
contact.The 3/8" (9.5 mm) OD seamless
copper tubes are mechanically
expanded into the fin collars. Coils are
proof tested at 450 psig (3102 kPa) and
leak tested at 300 psig (2068 kPa) air
pressure under water. Coils are
assembled with headers that provide
VAV-PRC008-EN

Single-Duct

7/8" (22.2 mm) OD braze connections.


Right-hand connections are optional.
ELECTRIC HEAT COIL
The electric heater is a factory-provided
and -installed, UL recognized
resistance open-type heater with
airflow switch. It also contains a disctype automatic pilot duty thermal
primary cutout, and manual reset load
carrying thermal secondary device.
Heater element material is nickelchromium. The heater terminal box is
provided with 7/8" (22 mm) knockouts
for customer power supply. Terminal
connections are plated steel with
ceramic insulators. Heater control
access is on the left-hand side.
ELECTRIC HEAT OPTIONS

Electric Heat Transformer An


optional transformer is an integral
component of the heater control panel
(dependent on unit load requirements)
to provide 24 VAC for controls.There is
19 VA available for controls.
Magnetic ContactorAn optional
electric heater 24-volt contactor for use
with direct digital control (DDC) or
analog electronic controls.
Mercury Contactor An optional
electric heater 24-volt contactor for use
with direct digital control (DDC) or
analog electronic controls.
P.E. Switch with Magnetic
ContactorThis optional switch and
magnetic contactor is for use with
pneumatic controls.
P.E. Switch with Mercury
Contactor This optional switch and
mercury contactor is for use with
pneumatic controls.
Airflow Switch An air pressure
device designed to disable the heater
when the system fan is off.This is
standard on single-duct units.
Line Fuse An optional safety fuse
located in the line of power of the
electric heater to prevent power surge
damage to the electric heater.
Disconnect Switch A optional
factory-provided door interlocking
disconnect switch on the heater control
panel disengages primary voltage to
the terminal.
UNIT CONTROLS SEQUENCE OF
OPERATION
The unit controller continuously
monitors the zone temperature against
its setpoint and varies the primary
airflow as required to meet zone
setpoints. Airflow is limited by
VAV-PRC008-EN

minimum and maximum position


setpoints. Upon a further call for heat
after the air valve is at minimum, any
hot water or electric heat associated
with the unit is enabled.
DIRECT DIGITAL CONTROLS
DDC ActuatorTrane 3-wire,
24-VAC, floating-point control actuator
with linkage release button.Torque is
35 in-lb minimum and is non-spring
return with a 90-second drive time.
Travel is terminated by end stops at
fully-opened and -closed positions. An
integral magnetic clutch eliminates
motor stall.
Direct Digital ControllerThe
microprocessor based terminal unit
controller provides accurate, pressureindependent control through the use
of a proportional integral control
algorithm and direct digital control
technology.The controller, named the
Unit Control Module (UCM), monitors
zone temperature setpoints, zone
temperature and its rate of change,
and valve airflow using a differential
pressure signal from the pressure
transducer. Additionally, the controller
can monitor either supply duct air
temperature or CO2 concentration via
appropriate sensors.The controller is
provided in an enclosure with 7/8"
(22 mm) knockouts for remote control
wiring. A Trane DDC zone sensor
is required.
DDC Zone SensorThe UCM
controller senses zone temperature
through a sensing element located in
the zone sensor. In addition to the
sensing element, zone sensor options
may include an externally-adjustable
setpoint, communications jack for use
with a portable edit device, and an
override button to change the
individual controller from unoccupied
to occupied mode. The override button
has a cancel feature that will return the
system to unoccupied. Wired zone
sensors utilize a thermistor to vary the
voltage output in response to changes
in the zone temperature. Wiring to the
UCM controller must be 18- to 22-awg.
twisted pair wiring.The setpoint
adjustment range is 5088F (1031C).
Depending upon the features available
in the model of sensor selected, the
zone sensor may require from a 2-wire
to a 5-wire connection. Wireless zone
sensors report the same zone
information as wired zone sensors, but
do so using radio transmitter
technology. Therefore with wireless,

Mechanical
Specifications
wiring from the zone sensor to the UCM
is unnecessary.
Digital Display Zone Sensor with
Liquid Crystal Display (LCD)
The digital display zone sensor contains
a sensing element, which sends a signal
to the UCM. A Liquid Crystal Display
(LCD) displays setpoint or space
temperature. Sensor buttons allow the
user to adjust setpoints, and allow space
temperature readings to be turned on or
off.The digital display zone sensor also
includes a communication jack for use
with a portable edit device, and an
override button to change the UCM from
unoccupied to occupied.The override
button has a cancel feature, which
returns the system to unoccupied mode.
System CommunicationsThe
Controller is designed to send and
receive data from a Tracer Summit
or otherTrane controllers. Current unit
status conditions and setpoints may be
monitored and/or edited via this data
communication feature.The network
type is a twisted wire pair shielded
serial communication.
ANALOG ELECTRONIC CONTROLS
Analog ActuatorATrane 3- wire,
24-VAC, floating-point control actuator
with linkage release button.Torque is
35 in-lb minimum and is non-spring
return with a 90-second drive time.
Travel is terminated by end stops at
fully-opened and -closed positions. An
integral magnetic clutch eliminates
motor stall.
Analog Electronic ControllerThe
controller consists of a circuit board that
offers basic VAV unit operation and
additional override functions and
operates using 24 VAC power.The
controller uses a capacitive type
pressure transducer to maintain
consistent air delivery regardless of
system pressure changes.The enclosure
has 7/8" (22 mm) knockouts for remote
control wiring. ATrane electronic zone
sensor is required.
Analog Electronic Thermostat This
single-temperature, wall-mounted
electronic device utilizes a thermistor to
vary the voltage output in response to
changes in the zone temperature.
Connections to the VAV unit circuit
board are made using standard threeconductor thermostat wire.The setpoint
adjustment range is 6385F (1729C).
The sensor is available in two models.
One model has a concealed, internallyadjustable setpoint. The other model
has an externally-adjustable setpoint.
SD 29

Single-Duct

PNEUMATIC CONTROLS

HOT WATER VALVES

Normally Open Actuator


Pneumatic 3 to 8 psig (20 to 55 kPa)
spring-range pneumatic actuator.

Two-Position Valve The valve is a


field-adaptable, 2-way or 3-way
configuration and ships with a cap to
be field-installed when configured as a
2-way valve. All connections are
National Pipe Thread (NPT). The valve
body is forged brass with a stainless
steel stem and spring. Upon demand,
the motor strokes the valve. When the
actuator drive stops, a spring returns
the valve to its fail-safe position.

Normally-Closed Actuator
Pneumatic 8 to 13 psig (55 to 90 kPa)
spring-range pneumatic actuator.
3011 Pneumatic Volume Regulator
(PVR)The regulator is a thermostat
reset velocity controller, which
provides consistent air delivery within
5% of cataloged flow down to 18% or
less of unit cataloged cfm, independent
of changes in system static pressure.
Factory-calibrated, field-adjustable
setpoints for minimum and maximum
flows. Average total unit bleed rate,
excluding thermostat, is 28.8 scim at
20 psig (7.87 ml/min at 138 kPa) supply.
CONTROL OPTIONS

Transformer (VCCF, VCWF)The


50-VA transformer is factory-installed
in an enclosure with 7/8" (22 mm)
knockouts to provide 24 VAC for
controls.
Disconnect Switch (VCCF, VCWF)
A toggle disconnect disengages
primary power to the terminal.
Fuse (VCCF, VCWF)Optional fuse is
factory-installed in the primary voltage
hot leg.

Flow Capacity 1.17 Cv


Overall Diameter " NPT
Close-off Pressure 30 psi (207 kPa)
Flow Capacity 3.0 Cv
Overall Diameter 3/4" NPT
Close-off Pressure 14.5 psi (100 kPa)
Flow Capacity 6.4 Cv
Overall Diameter 1" NPT
Close-off Pressure 9 psi (62 kPa)
Maximum Operating Fluid
Temperature 203F (95C)
Maximum system pressure 300 psi
(2067 kPa)
Maximum static pressure 300 psi
(2067 kPa)
Electrical Rating 7 VA at 24 VAC,
6.5 Watts, 50/60 Hz
8 feet (2.44 m) of plenum rated wire
lead is provided with each valve.

Mechanical
Specifications
Proportional Water ValveThe
valve is a field-adaptable, 2-way or
3-way configuration and ships with a
cap over the bottom port.This
configures the valve for 2-way
operation. For 3-way operation,
remove the cap. The valve is designed
with an equal percentage plug. The
intended fluid is water or water and
glycol (50% maximum glycol). The
actuator is a synchronous motor drive.
The valve is driven to a predetermined
position by the UCM controller using a
proportional plus integral control
algorithm. If power is removed, the
valve stays in its last position.The
actuator is rated for plenum
applications under UL 94-5V and UL
873 standards.
Pressure andTemperature Ratings
The valve is designed and tested in full
compliance with ANSI B16.15 Class
250 pressure/temperature ratings,
ANSI B16.104 Class IV control shutoff
leakage, and ISA S75.11 flow
characteristic standards.
Flow Capacity 3.80 Cv , 6.60 Cv,
0.70 Cv, 2.2 Cv
Overall Diameter " NPT, " NPT
(7.30 Cv)
Maximum Allowable Pressure 300
psi (2068 kPa)
Maximum Operating Fluid
Temperature 200F (93C)
Maximum Close-off Pressure 55 psi
(379 kPa)
Electrical Rating 6VA at 24 VAC.
10 feet (3.05 m) of plenum rated
22-gage wire for connection.
Terminations are #6 stabs.

SD 30

VAV-PRC008-EN