The RS-485 standard was developed jointly by the Electronic Industries Association (eia) and the Telecommunications Industry Association (tia) a four-wire connection must be used (plus the power supply leads) for RS-422 / rs-485 four-wire use two twisted pairs of 24AWG wires. The second pair is for Tx+and Txand the third pair is for Rx+and Rx-.
The RS-485 standard was developed jointly by the Electronic Industries Association (eia) and the Telecommunications Industry Association (tia) a four-wire connection must be used (plus the power supply leads) for RS-422 / rs-485 four-wire use two twisted pairs of 24AWG wires. The second pair is for Tx+and Txand the third pair is for Rx+and Rx-.
The RS-485 standard was developed jointly by the Electronic Industries Association (eia) and the Telecommunications Industry Association (tia) a four-wire connection must be used (plus the power supply leads) for RS-422 / rs-485 four-wire use two twisted pairs of 24AWG wires. The second pair is for Tx+and Txand the third pair is for Rx+and Rx-.
4242 Reynolds Drive For the Surface Mount Version Hilliard, Ohio 43026 of the Digital Load Monitor Phone: 614-777-1005 E-mail sales@ohiosemi.com Connecting Multiple Digital Load Monitors to an RS-485 or RS-422 System This paper applies to the surface mount version of the Digital Load Monitors, which have a barrier strip with 6 terminals to attach the communications cable. The connection positions are: +5 volts DC this is for the OSI IFC-4498A RS-422 to RS-432 converter only. Common this is for the OSI IFC-4498A RS-422 to RS-432 converter only. Tx+ Transmit + TX- Transmit - Rx+ Receive + Rx- Receive - If you are using the IFC-4498A RS-422 to RS-232 converter to connect to a COM port on your computer, the leads are labeled +5V, Com, Tx+, Tx-, Rx+, and Rx-. Connect these leads to the matching terminals on the Digital Load Monitor (DLM) closest to your computer. The terminals labeled +5V and Comare used to supply the converter with the required operating voltage. The 5V and Comshould be connected only on the DLM that is connected to the IFC-4498A. All other DLM meters should have these terminals open (no connection). When using the IFC-4498A, a four-wire connection must be used (plus the power supply leads). Note: The RS-485 standard was developed jointly by the Electronic Industries Association (EIA) and the Telecommunications Industry Association (TIA). The EIA once labeled all of its standards with the prefix "RS" (Recommended Standard). Many of us still use this designation but the TIA and EIA have officially replaced the "RS" with "EIA/TIA" to help identify the origin of the standard. Recommendations: For RS-422 / RS-485 four-wire use two twisted pairs of 24AWG wires. One pair is for Tx+and Tx- and the second pair is for Rx+and Rx-. For RS-485 two-wire applications use one twisted pair of 24AWG wire. Essential for minimizing reflections in two-wire systems are termination resistors. These should be 120-ohm resistors at both ends. Many RS-485 ports already include the host end resistor. Check the instructions for the port. Maximumloads (DLMs) on a 4-wire systemis 10. Maximumloads (DLMs) on a 2-wire systemis 32. Each Digital Load Monitor on a two or four wire systemmust have a separate 4-digit address. The user may assign the address using the software supplied with these meters. Ohio Semitronics, Inc. Page 2 of 3 Communication Connections 4242 Reynolds Drive For the Surface Mount Version Hilliard, Ohio 43026 of the Digital Load Monitor Phone: 614-777-1005 E-mail sales@ohiosemi.com +5V COM Tx+ Tx- Rx+ Rx- +5V COM Tx+ Tx- Rx+ Rx- +5V COM Tx+ Tx- Rx+ Rx- Tx+ Tx- Rx+ Rx- DLM Surface Mount Versi on DLM Surface Mount Versi on DLM Surface Mount Versi on Host RS-422 or RS-485 To additional Digital Load Moni tors or other RS-422 Devi ces if there are any. +5V COM Tx+ Tx- Rx+ Rx- +5V COM Tx+ Tx- Rx+ Rx- +5V COM Tx+ Tx- Rx+ Rx- DLM Surface Mount Versi on DLM Surface Mount Versi on DLM Surface Mount Versi on To additional Digital Load Moni tors or other RS-485 Devi ces if there are any. Connect i ng mul t i pl e sur f ace mount Di gi t al Load Moni t or s t o a host wi t h an RS- 422 or RS- 485 i nput . 4 Wi r e Connect i on Connect i ng mul t i pl e sur f ace mount Di gi t al Load Moni t ors t o a host wi t h an RS-485 i nput . 2 Wi r e Connect i on Tx+ Tx- Rx+ Rx- Host RS-485 120-ohm resi stor on the l ast DLM. Ohio Semitronics, Inc. Page 3 of 3 Communication Connections 4242 Reynolds Drive For the Surface Mount Version Hilliard, Ohio 43026 of the Digital Load Monitor Phone: 614-777-1005 E-mail sales@ohiosemi.com IFC-4498A RS-422 to RS-232 Converter. +5V COM Tx+ Tx- Rx + Rx- +5V COM Tx+ Tx- Rx + Rx- +5V COM Tx+ Tx- Rx + Rx- DLM Surface Mount Version DLM Surface Mount Version DLM Surface Mount Version To addi t i onal Di gi t al Load Moni t or s or ot her RS- 422 Devi ces i f t here are any. Connect i ng mul t i pl e sur f ace mount Di gi t al Load Moni t ors t o a host wi t h usi ng t he OSI I FC-4498A RS- 422 t o RS- 232 conver t er . Cabl e t o t he COM Por t on a per sonal comput er . +5V COM Tx+ Tx- Rx+ Rx- If you have any questions regarding the connections or use of the Ohio Semitronics, Inc. Digital Load Monitors (DLM), please contact us at Ohio Semitronics, Inc. There is a manual available that describes using these meters and that describes the communications protocol. If you require one of these manuals, please call or e-mail us. August 3, 2001