You are on page 1of 76

M0098A0F.

doc



Users Manual

for

MORx00BP

in the F-Cabinet




Users Manual for MORx00BP

Page 2 M0098A0F.doc

































Copyright 2007 Andrew Wireless Systems GmbH

All rights reserved.
All information contained in this manual has been revised thoroughly. Yet Andrew
Wireless Systems accepts no liability for any omissions or faults.
Andrew Wireless Systems reserves the right to change all hard- and software
characteristics without notice.
Names of products mentioned herein are used for identification purposes only and
may be trademarks and / or registered trademarks of their respective companies.
No parts of this publication may be reproduced, stored in a retrieval system,
transmitted in any form or by any means, electronical, mechanical photocopying,
recording or otherwise, without prior written permission of the publisher.

Andrew Wireless Systems GmbH, 30-October-2007



Page 3

TABLE OF CONTENTS
1. GENERAL 7
1.1. USED ABBREVIATIONS 7
1.2. HEALTH AND SAFETY WARNINGS 8
1.3. ABOUT ANDREW WIRELESS SYSTEMS 9
1.4. INTERNATIONAL CONTACT ADDRESSES 10
2. INTRODUCTION 11
2.1. PURPOSE 11
2.2. THE MORx00BP 11
3. FUNCTIONAL DESCRIPTION 13
3.1. GENERAL 13
3.2. FACTORY SETTINGS 13
3.3. COMPONENTS OF THE MORX00BP 14
3.3.1. Duplexer 14
3.3.2. Connecting Board 15
3.3.3. FSK-Modulator 15
3.3.4. Transceiver 16
3.3.5. UL / DL Amplifier 17
3.3.6. Feed-Forward Amplifiers 17
3.3.7. Feed-Forward Amplifier Kit 19
3.3.8. Control Module 20
3.3.9. Power Supply 21
3.3.10. Motherboard 22
3.4. OPTIONAL EQUIPMENT 23
3.4.1. External Alarms 23
3.4.2. VSWR (Voltage Standing Wave Ratio) 24
4. INSTALLATION 25
4.1. MECHANICAL INSTALLATION 25
4.1.1. General 25
4.1.2. Wall-Mounting Procedure 26
4.1.3. Pole-Mounting Procedure 27
4.2. ELECTRICAL INSTALLATION 28
4.2.1. General 28
4.2.2. Grounding 29
4.2.3. Power Connection 29
4.2.4. Connection of the Antenna Cables 30
4.2.5. Optical Fibre-Cable Connection 30
5. COMMISSIONING 33
5.1. GENERAL 33
5.2. BOOT PROCESS 34
5.3. SOFTWARE ATTENUATION SETTINGS 35
5.4. SETTINGS VIA SOFTWARE 35
5.4.1. Local Login 35
5.4.2. Remote Login 37
5.5. MANUAL ATTENUATION SETTINGS 38
5.6. LEVELLING INSTRUCTIONS 38

Users Manual for MORx00BP

Page 4 M0098A0F.doc

6. ALARMS 39
6.1. BITE AND ALARMS 39
6.2. HANDLING OF ALARMS 39
6.3. SUMMARY ALARM RELAY 39
6.4. STATUS REPORT 40
7. TROUBLESHOOTING 41
8. MAINTENANCE 43
8.1. GENERAL 43
8.2. REPLACEMENT OF COMPONENTS 43
8.2.1. Duplexer 44
8.2.2. Transceiver 45
8.2.2.1. Standard Transceiver 45
8.2.2.2. DFB Transceiver 46
8.2.3. FSK-Modulator 47
8.2.4. UL/DL Amplifiers 48
8.2.4.1. Mounted under the Transceiver 48
8.2.4.2. Mounted beside the Transceiver 48
8.2.4.3. Fastened with a Mounting Plate 49
8.2.5. Feed-Forward Amplifiers 49
8.2.6. Feed-Forward Amplifier Kit 51
8.2.7. RTC Battery 54
8.2.8. Control Module 55
8.2.9. Power Supply 56
8.2.10. Fuses 57
8.2.10.1. Fine-Wire Fuse 57
8.2.10.2. Blade-Type Electric Fuse Link 57
8.2.11. Connecting Board 58
8.2.12. VSWR Module 59
8.2.13. Mains Cable 60
9. APPENDIX 61
9.1. ILLUSTRATIONS 61
9.1.1. Installation Drawings 61
9.1.2. Repeater Layout 62
9.2. SPECIFICATIONS 66
9.2.1. Electrical Specifications 66
9.2.2. Optical Specifications 67
9.2.3. Mechanical Specifications 68
9.3. SPARE PARTS 68
9.3.1. Repeater Type Specific Spare Parts for MORx00BP 68
9.3.1.1. Spare Parts List of MOR300BP 68
9.3.1.2. Spare Parts List of MOR400BP 69
9.3.2. Common Spare Parts for all MORx00BP 71
9.4. ADDITIONAL INFORMATION ON CONTROL MODULE SM2009 72
9.5. DIP-SWITCH SETTINGS 73
10. INDEX 75
11. LIST OF CHANGES 76



Page 5

FIGURES AND TABLES

figure 3-1 Configuration of a MORx00BP ................................................................. 13
figure 3-2 Duplexer................................................................................................... 14
figure 3-3 Connecting board..................................................................................... 15
figure 3-4 FSK-Modulator ......................................................................................... 15
figure 3-5 Transceiver, MFY2314............................................................................. 16
figure 3-6 Transceiver, MFY1340HDI ....................................................................... 16
figure 3-7 UL / DL amplifier....................................................................................... 17
figure 3-8 Feed-forward amplifier, former version..................................................... 17
figure 3-9 Feed-forward amplifier, new version......................................................... 18
figure 3-10 Feed-forward amplifier kit....................................................................... 19
figure 3-11 Step-up DC/DC converter....................................................................... 19
figure 3-12 Control module....................................................................................... 20
figure 3-13 AC power supply, exemplary.................................................................. 21
figure 3-14 DC power supply, exemplary.................................................................. 21
figure 3-15 Motherboard........................................................................................... 22
figure 3-16 Location of external alarm clamps.......................................................... 23
figure 3-17 VSWR module, location in the D- and F-cabinet.................................... 24
figure 4-1 Installation drawings of a repeater............................................................ 26
figure 4-2 Pole-mounting kits.................................................................................... 27
figure 4-3 Grounding bolt.......................................................................................... 29
figure 4-4 Front view of antenna connection and optical fibre connection................ 31
figure 5-1 Control module position of LEDs........................................................... 34
figure 5-2 Manual attenuation setting via amplifier ................................................... 38
figure 6-1 Relay contacts, alarm condition................................................................ 39
figure 8-1 Duplexer, position of screws..................................................................... 44
figure 8-2 Transceiver, position of screws ................................................................ 45
figure 8-3 DFB transceiver, position of screws ......................................................... 46
figure 8-4 Transceiver assembly............................................................................... 47
figure 8-5 FSK-modulator, position of screws........................................................... 47
figure 8-6 Feed-forward amplifier, former version, uninstalled, position of screws ... 49
figure 8-7 Feed-forward amplifier, former version, installed, position of screws ....... 50
figure 8-8 Feed-forward amplifier kit, position of screws........................................... 51
figure 8-9 I2C board.................................................................................................. 51
figure 8-10 Feed-forward amplifier mounting plate, position of screws..................... 52
figure 8-11 Feed-forward amplifier, new version, position of screws ........................ 52
figure 8-12 DC/DC converter, position of screws...................................................... 53
figure 8-13 Feed-forward amplifier with VSWR module, new version, position of
screws.................................................................................................... 53
figure 8-14 Position of RTC battery.......................................................................... 54
figure 8-15 Power supply fuses, exemplary.............................................................. 57
figure 8-16 Connections of connecting board........................................................... 58
figure 9-1 F-cabinet for MORx00BP ......................................................................... 61
figure 9-2 Layout of repeater lid, former version, exemplary..................................... 62
figure 9-3 Layout of repeater lid, new version, exemplary........................................ 63
figure 9-4 Layout of heat sink, former version, exemplary........................................ 64
figure 9-5 Layout of heat sink, new version, exemplary............................................ 65


Users Manual for MORx00BP

Page 6 M0098A0F.doc

table 1-1 List of international contact addresses....................................................... 10
table 5-1 LED indication during boot process........................................................... 34
table 6-1 Relay contacts, pin assignment................................................................. 39
table 8-1 Specified torques....................................................................................... 44

1 General

Page 7

1. GENERAL
1.1. USED ABBREVIATIONS

ALC Automatic Level Control
AMPS American Mobile Phone System or Advanced Mobile Phone System
APAC Automatic Power Adjustment Circuit
BCCH Broadcast Control Channel
BITE Built-In Test Equipment
BTS Base Transceiver Station
CDMA Code Division Multiple Access
CEPT Confrnce Europenne des Postes et Tlcommunications
CF Center Frequency
CFO Center Frequency Offset
DL Downlink
EDGE Enhanced Data Rates for GSM Evolution
ESD Electrostatic Discharge
ETACS Enhanced TACS
ETS European Telecommunication Standard
ETSI European Telecommunication Standards Institute
FSK Frequency Shift Keying
GSM Global System for Mobile Communication
I
2
C-Bus Inter Integrated Circuit Bus (Philips)
ID No Identification Number
IF Intermediate Frequency
LMT Local Maintenance Terminal
MS Mobile Station
OMC Operation and Maintenance Center
PCMCIA Personal Computer Modem Communication International Association
PCS Personal Communication System
PSTN Public Switched Telephone Network
Rev Revision
RF Radio Frequency
RLP Radio Link Protocol
RSSI Receive Signal Strength Indication
RTC Real-Time Clock
RX Receiver
SCL Serial Clock
SDA Serial Data
TACS Total Access Communication System
TCH Traffic Channel
TDMA Time Division Multiple Access
TX Transmitter
UE User Equipment
UL Uplink
UMTS Universal Mobile Telecommunication System
UPS Uninterruptible Power Supply
VSWR Voltage Standing Wave Ratio


Users Manual for MORx00BP

Page 8 M0098A0F.doc

1.2. HEALTH AND SAFETY WARNINGS

1. Only suitably qualified people are allowed to work on this unit and only after
becoming familiar with all safety notices, installation, operation and maintenance
procedures contained in this manual.

2. Read and obey all the warning labels attached to the unit. Make sure that the
warning labels are kept in a legible condition and replace any missing or
damaged labels.

3. Obey all general and regional installation and safety regulations relating to work
on high voltage installations, as well as regulations covering correct use of tools
and personal protective equipment.

4. Keep operating instructions within easy reach and make them available to all
users.

5. It is the responsibility of the network provider to implement prevention measures
to avoid health hazards which may be associated to radiation from the antenna(s)
connected to the unit.

6. The antennas of the repeater (integrated and / or external) have to be installed in
a way that the regional and national RF exposure compliance requirements are
met.

7. Make sure access is restricted to qualified personnel.

8. Only licence holders for the respective frequency range are allowed to operate
this unit.

9. Use this equipment only for the purpose specified by the manufacturer. Do not
carry out any modifications or fit any spare parts which are not sold or
recommended by the manufacturer. This could cause fires, electric shock or other
injuries.

10. Due to power dissipation, the repeater may reach a very high temperature. Do not
operate this equipment on or close to flammable materials.

11. Before opening the unit, disconnect mains.

12. ESD precautions must be observed! Before commencing maintenance work, use
the available grounding system to connect ESD protection measures.

13. This unit complies with European standard EN60950.

14. Make sure the repeater settings are according to the intended use (see also
product information of the manufacturer) and regulatory requirements are met.

15. Although the repeater is internally protected against overvoltage, it is strongly
recommended to earth the antenna cables close to the antenna connectors of the
repeater for protection against atmospheric discharge.
1 General

Page 9

1.3. ABOUT ANDREW WIRELESS SYSTEMS

Andrew Wireless Systems is a leading manufacturer of coverage equipment for
mobile radio networks, specializing in low cost, high performance, RF and optical
repeaters. Our optical distributed networks and RF repeater systems provide
coverage for every application: outdoor use, indoor installations, tunnels, subways
and many more.

Andrew Wireless Systems has engineering and manufacturing facilities in Germany,
Italy and the USA. In addition, it maintains field engineering offices throughout the
world.

Andrew Wireless Systems GmbH operates a quality management system which
complies with the requirements of ISO 9001. All equipment is manufactured using
highly reliable material. In order to ensure constant first-rate quality of the products,
comprehensive quality monitoring is conducted at all fabrication stages. Finished
products leave the factory only after a thorough final acceptance test, accompanied
by a test certificate guaranteeing optimal operation.

The declaration of conformity for the product is available upon request from the local
offices or from Andrew Wireless Systems directly.

Any intervention must be carried out by authorized persons only.

For technical assistance, contact the local office or Andrew Wireless Systems directly
at one of the following addresses:


Andrew Wireless Systems GmbH
Industriering 10
86675 Buchdorf
Germany
Phone: +49 9099 69-0
Fax: +49 9099 69-930
E-mail: WIsupport.germany@andrew.com


for The Americas:

Wireless Innovations Group
Andrew Corporation
Phone: +1 888 297 6433
E-mail: WIsupport.us@andrew.com


When set-up is performed according to this manual, the system will operate without
complications for a significant length of time.

Users Manual for MORx00BP

Page 10 M0098A0F.doc

1.4. INTERNATIONAL CONTACT ADDRESSES

Australia Austria Brazil
6 Stuart Street
Padstow NSW 2211
Australia
Weglgasse 10
Wien-Schwechat 2320
Austria
Av Com Camilo J ulio 1256
Predio B
Zonal Industrial CP 597
Sorocaba SP 18086-000
Brazil
Phone +61 2 9774-4200 Phone +43 1706 3999-10 Phone +55 15 2102-4000
Fax +61 2 9774-4500 Fax +43 1706 3999-9 Fax +55 15 2102-4001
E-mail E-mail E-mail
WIsupport.australia@andrew.com WIsupport.austria@andrew.com WIsupport.brazil@andrew.com
Canada China Czech Republic
606 Beech St W
Whitby ON L1N 5S2
Canada
RM 915 Chevalier
Commercial Centre
8 Wang Hoi Rd
Kowloon Bay SAR
Hong Kong
U Moru 888
Pardubice
53006
Czech Republic
Phone +1 905 668-3348 Phone +852 3106 6100 Phone +420 46 63012-80
Fax +1 905 668-8590 Fax +852 2751 7800 Fax +420 46 63012-98
E-mail E-mail E-mail
WIsupport.canada@andrew.com WIsupport.china@andrew.com WIsupport.czechrep@andrew.com
France Italy Switzerland
28 Rue Fresnel
Z.A Pariwest
BP 182
Coignires cedex 78313
France
Via de Crescenzi 40
Faenza 48018
Italy
Tiergartenweg 1
4710 Balsthal CH-4710
Switzerland
Phone +33 1 300-54550 Phone +39 0546 697111 Phone +41 62 386-1260
Fax +33 1 346-11374 Fax +39 0546 682768 Fax +41 62 386-1261
E-mail E-mail E-mail
WIsupport.france@andrew.com WIsupport.italy@andrew.com WIsupport.switzerland@andrew.com
UK U.S.A.
Ilex Bldg Mulberry Business
Park
Fishponds Rd
Wokingham Berkshire
England RG41 2Gy
620 North Greenfield
Parkway
Garner, NC 27529
United States

Phone +44 118 936-6700 Phone +1 919 329-8700
Fax +44 118 936-6773 Fax +1 919 329-8950
E-mail E-mail
WIsupport.uk@andrew.com WIsupport.us@andrew.com
table 1-1 List of international contact addresses
2 Introduction

Page 11

2. INTRODUCTION
2.1. PURPOSE
Cellular telephone systems transmit signals in two directions between a base
transceiver station (BTS) and mobile stations (MS) within the signal coverage area.

If weak signal transmissions occur within the coverage area because of indoor
applications, topological conditions or distance from the transmitter, a repeater
system is used to extend transmission range.

In the downlink (DL) path, the repeater system picks up the signal from a donor
antenna of an existing cell, processes and retransmits it into the desired dark spot. In
the uplink (UL) direction, the repeater system receives a signal from mobile stations
present in its coverage area and forwards them to the corresponding BTS.

2.2. THE MORx00BP

The repeater MORx00BP is a wide-band optical repeater which bi-directionally
amplifies signals between a base transceiver station and mobile stations in the
corresponding network using optical fibres for inter-connection to a master unit. It can
provide high amplification, thus enabling radio coverage in tunnels, canyons and
regions where satisfactory quality of communication is disabled.

The modular design of the MORx00BP repeater provides unparalleled flexibility in
addressing present and future system needs. Every repeater is custom configured.


Users Manual for MORx00BP

Page 12 M0098A0F.doc

For your notes:


3 Functional Description

Page 13

3. FUNCTIONAL DESCRIPTION
3.1. GENERAL

The following figure shows the configuration of an optical remote unit MORx00BP.


figure 3-1 Configuration of a MORx00BP

The repeater MORx00BP comprises two amplifier chains. The signals to and from
the mobiles are combined and forwarded to an antenna by a frequency separation
unit denominated as duplexer. The optical signals to and from the master unit are
converted by the optical transceiver.

In the downlink direction, the optical signals from the master unit are converted into
RF-signals by the transceiver. The RF-signals are amplified in the DL by a feed-
forward amplifier. Finally, the signals are fed to the antenna via the duplexer.

In the uplink direction, the signals from the mobiles are separated by the duplexer
and forwarded to a pre-amplifier and afterwards to the UL amplifier. By the
transceiver, the signals are converted into optical signals and finally are transmitted
to the master unit.

3.2. FACTORY SETTINGS

The motherboard is coded. Generally, the setting is factory set. It is defined and must
be kept in case of an upgrade of the repeater or a replacement of parts. The defined
motherboard setting is 0.


Users Manual for MORx00BP

Page 14 M0098A0F.doc

3.3. COMPONENTS OF THE MORX00BP

The actual configuration of the repeater can be seen at the configuration list, which is
part of the delivery.

3.3.1. Duplexer

The task of the duplexer is to isolate uplink from downlink, i.e. to separate the
transmitting path from the receiving path. The pass bandwidth of the duplexer is the
entire width of the UL and DL band of the corresponding network.


figure 3-2 Duplexer

With the built-in RF probe at the duplexer, test signals can be applied or detected.
The probe is provided with 30 dB for measurements. This facilitates measurements
under all operational conditions while an antenna or a dummy load may be
connected.

30 dB
coupler
Pre-
amplifier
3 Functional Description

Page 15

3.3.2. Connecting Board

The connecting board is
mounted on top of the FSK-
modulator and serves as an
interface for the mains cable,
for external alarms, and for
summary alarms.

In repeaters providing the
VSWR option the voltage for
the VSWR module is fed via
the connecting board.





figure 3-3 Connecting board
3.3.3. FSK-Modulator

To enable remote control between master unit and remote unit, the FSK-modulator is
implemented as serial interface. Control signals from the remote unit are modulated
to a 10.7 MHz carrier. The signals are then fed to the optical transceiver to be
transmitted to the master unit via optical fibre and vice versa. The FSK-modulator is
mounted on top of the transceiver.


figure 3-4 FSK-Modulator
Interface to
control unit
DC
connection
Transceiver
connections

Users Manual for MORx00BP

Page 16 M0098A0F.doc

3.3.4. Transceiver

The transceiver is the interface between the optical and the electrical distribution unit
and converts optical signals into electrical signals and vice versa.


figure 3-5 Transceiver, MFY2314

A transceiver with a temperature-stabilised DFB laser is available. If the remote units
are connected to the master unit in a backbone system, where the transmitter signals
are coupled and transmitted via a single fibre, this transceiver type is required to
prevent signal interference and, therefore, is necessary to ensure system operation.


figure 3-6 Transceiver, MFY1340HDI

3 Functional Description

Page 17

3.3.5. UL / DL Amplifier

In the UL path, the
UL amplifier
provides the
necessary gain to
adjust the signals
to the level
required at the
optical transceiver
input.

The DL amplifier
drives the feed-
forward amplifier
with the
corresponding
input power.



figure 3-7 UL / DL amplifier

3.3.6. Feed-Forward Amplifiers

The feed-forward amplifier is the final stage which enables high output power as well
as a high intermodulation distance in the DL path.

Two types of feed-forward amplifiers are used for the 300 and 400BP series since
the old type (figure 3-8 Feed-forward amplifier, former version) is successively being
replaced by a new version, (figure 3-9 Feed-forward amplifier, new version). The
actual amplifier type of each individual repeater can be seen in the configuration list.


figure 3-8 Feed-forward amplifier, former version

Users Manual for MORx00BP

Page 18 M0098A0F.doc



figure 3-9 Feed-forward amplifier, new version

3 Functional Description

Page 19

3.3.7. Feed-Forward Amplifier Kit


figure 3-10 Feed-forward amplifier kit

The feed-forward amplifier kit is
the new method of construction of
the MOR300 and 400BP series in
the F-cabinet, consisting of feed-
forward amplifier and mounting
plate, step-up DC/DC converter
and mounting plate and various
types of screws. For the exact
designation of the screws please
refer to chapter 8.2.5 Feed-
Forward Amplifiers.


figure 3-11 Step-up DC/DC converter

As the PSU provides repeaters of
the 300 and 400BP series with just
12 V but the feed-forward amplifier
has to be provided with 28 V, a
step-up DC/DC converter is used.
It serves to convert 12 V into 28 V.

Mounting
plate
DC-DC converter
Feed-
forward
amplifier

Users Manual for MORx00BP

Page 20 M0098A0F.doc

3.3.8. Control Module

The control module is a DOS compatible micro computer. Data exchange between
operator and repeater can be done via the control module.


figure 3-12 Control module

The repeater can be controlled remotely via a master unit or locally via a VT100
terminal or a PC emulating the VT100 terminal.

The data transfer between the control module and the motherboard is made via the
I
2
C-Bus system.

The I
2
C-Bus concept was developed by Philips for the serial connection of integrated
circuits within one device. Two wires, serial data (SDA) and serial clock (SCL), carry
information between the devices connected to the bus. Each device is distinguished
between by a unique address and can operate either as transmitter or receiver.

All MORx00BP configuration parameters are non-volatile stored in an EEPROM on
the control module if a power supply failure occurs.


3 Functional Description

Page 21

3.3.9. Power Supply

The power supply transforms the input power from mains into a defined DC voltage
by which all active components of the repeater are supplied. An external switch,
mounted on the power supply, is provided to disconnect the repeater from mains
during maintenance work to ensure that all circuits are voltage-free.

The power supply is factory-set and must not be changed. The power supply can be
fuse-protected.


figure 3-13 AC power supply, exemplary

Optionally, the repeater can be equipped with a DC power supply.


figure 3-14 DC power supply, exemplary

Mains
switch
Mains
switch

Users Manual for MORx00BP

Page 22 M0098A0F.doc

3.3.10. Motherboard

The purpose of the motherboard is to support all necessary DC voltages and
connections. All signals will be acknowledged by the motherboard logic. The
motherboard is located underneath the amplifiers in the bottom of the repeater.


figure 3-15 Motherboard


3 Functional Description

Page 23

3.4. OPTIONAL EQUIPMENT

The actual repeater configuration can be seen at the configuration list, which is part
of the delivery.

3.4.1. External Alarms

With the external alarms option, it is possible to monitor the status of connected
devices via the repeater software, e.g. a UPS. The DIP-switches of the external-
alarms switch on the control module have to be set to position ON Ext. Alarm 1-4.
The DIP-switch settings are factory-set and should not be changed. For details, see
chapter 9.5 DIP-Switch Settings.

The connecting clamps are located on the connecting board mounted on the
duplexer (BTS side).













figure 3-16 Location of external alarm clamps

All external alarms are normally high (5 Vdc) without connection. Via the software
command SET LOGIC, the external alarms can be set to high active (H) or low active
(L). Depending on the settings, the external alarms show the status failure or OK
on the display. The configuration for open collector applications is 5 Vdc / 0.5 mA.

When only two external alarms are required, ensure that the other two external
alarms are set to low active, otherwise the status will always show an alarm.
Note: The name for each external alarm and the name for the alarm
message can be defined by the customer with the corresponding
software command (see software manual).
Note: A special software blocking must be removed to use the external
alarm option. This can only be carried out by authorized persons
from the manufacturer.


Users Manual for MORx00BP

Page 24 M0098A0F.doc

3.4.2. VSWR (Voltage Standing Wave Ratio)

The VSWR option enables the provider to query the status of the antenna system
(antenna and cable). The VSWR module measures the voltage standing wave ratio
of the DL output antenna port. If a cable is defect or the antenna is covered with ice,
the VSWR will get worse.

If the VSWR falls below approximately 13 dB, an alarm will be released. The alarm
can be forwarded to the OMC where the faults and irregularities can be
acknowledged and eliminated promptly. The VSWR module cannot be installed on
site.



figure 3-17 VSWR module, location in the D- and F-cabinet

VSWR module
4 Installation

Page 25

4. INSTALLATION
4.1. MECHANICAL INSTALLATION
4.1.1. General

Read the health and safety warnings in chapter
1.2 Health and Safety Warnings.

1. Do not install the unit in a way or at a
place where the specifications outlined
in the Environmental and Safety
Specifications leaflet of the
manufacturer are not met.

2. It is recommended only to use the
mounting hardware delivered by the
manufacturer. If different mounting
hardware is used, the specifications for
stationary use of the repeater must not
be exceeded.

Note: Exceeding the specified load limits
may cause the loss of warranty.

3. The unit is considerably heavy. Make sure that a
suitable mounting surface is used. Ensure there is
adequate manpower to handle the weight of the system.

4. Due to power dissipation, the repeater may reach a very high temperature.
Ensure sufficient airflow for ventilation. It is necessary to mount the
repeater vertically to a wall or a mast without additional enclosure and a
clearance of one metre to the sides, above and below. Between the housing
and the wall, a minimum distance of 20 mm must be kept.

5. When connecting and mounting the cables( RF, optical, mains, ...) ensure
no water can penetrate into the unit through these cables.

If any different or additional mounting material is used, ensure that the mounting
remains as safe as the mounting designed by the manufacturer. Ensure that the
static and dynamic strengths are adequate for the environmental conditions of the
site. The mounting itself must not vibrate, swing or move in any way that might cause
damage to the repeater.


Users Manual for MORx00BP

Page 26 M0098A0F.doc

4.1.2. Wall-Mounting Procedure

Check the suitability of the wall-
mounting kit and the wall.
Dismount the mounting brackets which
are screwed to the housing with four
socket-head-cap screws M8x16 and
two tire bolts.
Use the wall-mounting template to
mark the position of the drilling holes. Drill
four holes and screw the mounting brackets to
the wall.
Attach the upper two socket-head-cap screws M8x16 to the repeater housing.
Hang the repeater into the mounting brackets.
Fasten the lower two socket-head-cap screws M8x16 and the two tire bolts.
Ensure that there is free access to the electrical connections as well as to the
individual units inside the cabinet while the door of the repeater is open (clearance
distance of 1 m is recommended). The approved bending radius of the connected
cables must not be exceeded.

figure 4-1 Installation drawings of a repeater

4 Installation

Page 27

4.1.3. Pole-Mounting Procedure

Standard mounting hardware cannot be used to mount the repeater to a pole, a mast
or other similar structures. Additional hardware must be used for this type of
installation. Such a pole-mounting kit could include two threaded rods M8, two
U-beams and mounting material like bolts and nuts.


Dismount the mounting
brackets which are screwed
to the housing with four
socket-head-cap screws
M8x16 and two tire bolts
(see 4.1.2 Wall-Mounting
Procedure).
Fasten the mounting kits
and the mounting brackets
to the pole or mast.
Attach the upper two socket-
head-cap screws M8x16 to
the repeater housing.
Hang the repeater into the
mounting brackets.
Fasten the lower two socket-
head-cap screws M8x16 and
the two tire bolts.



figure 4-2 Pole-mounting kits

Make sure that there is free access to the electrical connections and to the individual
units inside the cabinet while the door of the repeater is open (clearance distance of
1 m is recommended). The allowed bending radius of the connected cables must not
be exceeded.

Note: Two pole-mounting kits are required to mount the repeater to a pole
or a mast.

Users Manual for MORx00BP

Page 28 M0098A0F.doc

4.2. ELECTRICAL INSTALLATION
4.2.1. General

Read the health and safety warnings in chapter1.2 Health and Safety Warnings.
1. This unit contains dangerous voltages. Loss of life, severe personal injury
or property damage can be the result if the instructions contained in this
manual are not followed.
2. It is compulsory to ground the unit before connecting power supply. A
grounding bolt is provided on the cabinet to connect the ground-bonding
cable.
3. Although the repeater is internally protected against overvoltage, it is
strongly recommended to earth the antenna cables close to the antenna
connectors of the repeater for protection against atmospheric discharge. In
areas with strong lightning it is strongly recommended to insert additional
lightning protection.
4. Hard-wired installation of mains supply for the repeater requires an easily
accessible disconnect device in the mains circuit.
5. Make sure that an appropriate circuit breaker and an overcurrent limiting
device are connected between mains and repeater.
6. A connection of mains supply to a power socket requires the power socket
to be nearby the repeater.
7. The repeater might be supplied from IT mains. (The maximum nominal line
to line voltage must not exceed 400 VAC).
8. Incorrectly wired connections can destroy electrical and electronic
components.
9. To avoid corrosion at the connectors caused by electrochemical processes,
the material of the cable connectors must not cause a higher potential
difference than 0.6 V (see electrochemical contact series).
10. It is sufficient to tighten the 7/16 or N-antenna connector hand-screwed. Any
use of a tool (e.g. pair of pliers) might cause damage to the connector and
thus lead to malfunctioning of the repeater.
11. For unstabilized electric networks which frequently generate spikes, it is
advised to use a voltage limiting device.
12. The unit complies with the surge requirement according to EN 61000-4-5
(fine protection); however, it is recommended to install an additional
medium (via local supply connection) and/or coarse protection (external
surge protection) depending on the individual application in order to avoid
damage caused by overcurrent.
13. Observe the labels on the front panels before connecting any cables.
4 Installation

Page 29

4.2.2. Grounding

Grounding must be carried out. An earth-bonding cable must be connected to the
grounding bolt provided at the outside of the cabinet on the left-hand side. Do not use
the grounding screw for connecting external devices. The complete grounding kit is
part of the delivery schedule.


figure 4-3 Grounding bolt
4.2.3. Power Connection

Before connecting electrical power to the repeater, it must be grounded. The repeater
is equipped with a firmly connected mains cable which is fed into the housing through
a watertight cable gland. Due to safety reasons, the power supply lead must be
protected by fuses. Inside the repeater, the mains cable is connected to a screw
terminal on the connecting board. In case the length of the power cable should not be
sufficient, it can be replaced by a longer cable.


Users Manual for MORx00BP

Page 30 M0098A0F.doc

4.2.4. Connection of the Antenna Cables

The repeater has a female antenna connector 7/16 (N as an option) located on the
lower side of the cabinet. For mounting the cable connectors, it is recommended to
refer to the corresponding documentation of the connector manufacturer. The
bending radius of the antenna cables must remain within the given specifications.


For the selection of cable and antenna it should be considered that, on the one hand,
a cable with higher loss is less expensive but, on the other hand, it impairs
performance.

It is sufficient to tighten the 7/16 (or N) connectors hand-tight. The use of
a tool (like pliers) may cause damage to the connector and therefore,
lead to a malfunctioning of the repeater.

4.2.5. Optical Fibre-Cable Connection

Optical signals are transmitted by use of a pair of optical fibres for each remote unit.
Note: Care should be taken when connecting and disconnecting fibre-
optic cables. Scratches and dust significantly affect system
performance and may permanently damage the connector. Always
use protective caps on fibre-optic connectors not in use.
In general, optical fibres do not need special protective measures. However,
protection against environmental influences e.g. rodents and humidity must be
considered.

The optical fibre is a single mode fibre. Type is E9/125 with the following minimum
requirements.

Attenuation <0.3 dB / km @ 1300 nm
Dispersion <3.5 ps / nm km @ 1300 nm

The specified bending radius of the optical fibres must not be exceeded. The pigtails
for the connection between master unit and remote unit must have a sufficient length.
A protection for the feeding into units must be given. The system attenuation of the
optical fibres, including the connectors, must not exceed 10 dB. Less than 5 dB is
desired.

System attenuation and attenuation of optical components must be determined. This
can be achieved by measuring attenuation and reflection with an appropriate
measuring instrument. For pigtails, a total value of <0.4 dB (measured to a reference
plug) can be assumed due to the dead zone of the reflectometer. These
measurements must be made with a sufficient length of optical fibre, at the input and
output of the device which has to be measured.
4 Installation

Page 31


Fibre cable connectors have to be of the same type (DIN/APC, FC/APC, SC/APC or
E2000APC) as the connectors used for the unit. The fibre-optic cables are connected
to the optical transceiver.

Note: Angled connectors are not compatible with straight optical
connectors; non-compatibility of connectors will result in
permanent damage to both connectors.

Before connecting the fibre cables, follow the procedure below to ensure optimized
performance. It is important that these procedures are carried out with care:

Remove the fibre-optic protective caps.

Do not bend the fibre-optic cable in a tight radius (<4 cm) as this may cause
cable damage and interrupt transmission.

Using high-grade alcohol and lint-free cotton cleaning swabs, clean the end of
the fibre-optic cable that will be inserted into the optical connectors on the
donor interface box.

Blow out the laser receptacle with clean and dry compressed air to remove
any particulate matter.

Connect the fibre-optic cables by inserting the cable end into the laser
receptacle and aligning the key (on the cable end) with the keyed slot.

Do not use any index matching gels or fluids of any kind in these connectors.
Gels are intended for laboratory use and attract dirt in the field.

G0860Z2

figure 4-4 Front view of antenna connection and optical fibre connection

Users Manual for MORx00BP

Page 32 M0098A0F.doc

For your notes:

5 Commissioning

Page 33

5. COMMISSIONING
5.1. GENERAL

Read the health and safety warnings in chapter 1.2 Health and Safety Warnings as
well as the description carefully to avoid mistakes and proceed step by step as
described.

Do not operate the repeater without termination of the antenna connections.
The termination can be achieved by connecting the antennas, a dummy load
or the 50-Ohm-terminated connection of a measuring instrument.

To ensure safety, the electrical and subsequent installations, commissioning
and maintenance activities that require the unit to be under power while open,
must only be carried out by suitably qualified personnel.

When opening the repeater, do not damage the seals on the devices inside
the repeater. Warranty void if the seals are broken.

Note: Each connected extension unit must be switched on before the
main unit! Otherwise the extension unit(s) will not be recognized by
the control module of the main unit, which scans the system during
the boot process.


Users Manual for MORx00BP

Page 34 M0098A0F.doc

5.2. BOOT PROCESS

As soon as the repeater is switched on, the control module of the repeater starts the
boot process; LE3 displays Power on. The initialization of the hardware is part of
the boot process. The whole process may take up to several minutes.

After booting the system, LE1 turns red for a few moments, then flashes green. LE2
also flashes red and then green. This is just an optical functionality test of the two-
coloured LEDs.


figure 5-1 Control module position of LEDs

Internal
LED LE1
Internal
LED LE2
Internal
LED LE3
Cause
green
Power on
Software booting

Flashes red
for a short
time

Flashes red
for a short
time
green LED test
green green green
Software boot
successful

table 5-1 LED indication during boot process
LE3
LE2
LE1
5 Commissioning

Page 35

5.3. SOFTWARE ATTENUATION SETTINGS

In order to enable the provider to set the gain via software, the UL and the DL
amplifiers have to be addressed. The UL amplifier has to be set with rotary switch [2]
to position 0. The rotary switch [2] of the DL amplifier is set to position 1. For the
position of the rotary switches refer to chapter 5.5 Manual Attenuation Settings.
These settings are factory-set and must not be changed.

5.4. SETTINGS VIA SOFTWARE

After the boot process, the software login is possible. All parameters of the software
can be changed by the provider to optimize the repeater according to the network
system. There are two possibilities how to login to the software:

locally, via a VT100 terminal or a PC with VT100 terminal emulation
remotely, via a master unit

5.4.1. Local Login

The login via a VT100 terminal or a PC with VT100 emulation can only be performed
at the repeater. Open the repeater carefully and connect the terminal or PC to the
RS232 interface on the control module by means of a standard RS232 null modem
cable.

Check the communication mode at the terminal. If necessary, set the following
parameters:

Bit rate / bit per second: 9600 baud Number of data bit: 8 bit
Parity bit: No parity Stopbit: 1 stopbit

Note: The input is case sensitive, no blanks allowed. The connection will
be torn down after three wrong inputs.

There are two possibilities to login to the repeater software:

Repeater off: The repeater is switched off, the RS232 interface cable is already
connected and the DIP-switch 2 of the mode-switch (1) is set to
position OFF.

Users Manual for MORx00BP

Page 36 M0098A0F.doc


After switching on the repeater, the boot procedure starts. Subsequently, the display
of the terminal shows the following report.

-----------------------------------------------------------------------------------------------------------------
AT

ANDREW REPEATER MORXXX SM2009 - SW: SLV 1XXX
VX. XX

ENTER <. > <CR> TO LOGI N
-----------------------------------------------------------------------------------------------------------------

Please type
<.> (fullstop) and confirm with <CR> (carriage return)

to get to the login orders.
Note: The following step can only be carried out by qualified personnel in
consideration of the health and safety warnings. Pay attention not
to touch devices while the repeater is operating.
Repeater On: The repeater is operating.

After connecting the RS232 interface cable and changing the DIP-switch 2 of mode-
switch (1) to OFF, the display will not show a report.

Please type
<.> (fullstop) and confirm with <CR> (carriage return)

to get to the login orders.
Note: Sometimes it is necessary to type the <.> (fullstop) command two or
three times to get access to the repeater software.

After successful login, the USERID is required.

-----------------------------------------------------------------------------------------------------------------
ENTER USER I D:
-----------------------------------------------------------------------------------------------------------------

Please enter
<UserID1>* and confirm with <CR> (carriage return).

* UserID1 is factory-set and can be changed by the software.

Note case sensitivity and blanks!
5 Commissioning

Page 37


Now, the correct password is asked. The following order will be displayed on the
terminal:

-----------------------------------------------------------------------------------------------------------------
ENTER PASSWORD:
-----------------------------------------------------------------------------------------------------------------

Please enter
<P-word1>** and confirm with <CR> (carriage return).

** P-word1 is factory-set and can be changed by the software.

Note case sensitivity and blanks!

If the software login procedure was successful, the input request shown below
displays on the terminal:

-----------------------------------------------------------------------------------------------------------------
ANDREW >
-----------------------------------------------------------------------------------------------------------------

All parameters of the repeater can now be changed to optimize the repeater to the
network system.

5.4.2. Remote Login

A login e.g. via a master unit and the OMC enables the operator to set parameters
and to query the status of each repeater. The access commands to the repeater
software are the same as described in chapter 5.4.1 Local Login. If the OMC is used
for the remote login, the input <.> (fullstop) and <CR> (carriage return) is skipped
and UserID and Password are requested right away.

For further details on software login and software commands, please refer to the
software manual.


Users Manual for MORx00BP

Page 38 M0098A0F.doc

5.5. MANUAL ATTENUATION SETTINGS

If necessary, it is also possible to optimize the gain manually by means of rotary
switches on the UL and DL amplifiers. With the rotary switch [1], the attenuation can
be set in steps of 2 dB up to the specified maximum value. The rotary switch [2] of
the UL and DL amplifier must be set to the according position shown in the following
table to enable the manual settings.

Address UL Amplifier Address DL Amplifier
Attenuation setting Attenuation setting
by SW manually by SW manually
UL_1 0 8 DL_1 1 9
UL_2 2 A DL_2 3 B
UL_3 4 C DL_3 5 D
UL_4 6 E DL_4 7 F


figure 5-2 Manual attenuation setting via amplifier

To change back to software mode, rotary switch [2] has to be reset to its original
software setting position (see table above).

5.6. LEVELLING INSTRUCTIONS

For a detailed description for levelling an optical system, please see separate
levelling documentation, which is part of the delivery of the remote unit.

[1] Rotary switch to
set the attenuation
[2] Rotary switch to
change between manual
mode and software mode
6 Alarms

Page 39

Pin 3 Pin 1 Pin 2
6. ALARMS
6.1. BITE AND ALARMS

The Built-In Test concept comprises the monitoring of the power supplies, the
motherboard and the remote control interface. Furthermore, the temperature of the
repeater is monitored.

All alarms occurred can be checked via the software by typing the STATUS HIST
command. The provider is then able to acknowledge the alarm manually by the
software command ALARMACKN, e.g. ALC active, RSSI, door open or stability
control. If all alarms have been acknowledged, the summary error LEDs are set back
to green indication.

6.2. HANDLING OF ALARMS

As soon as the software acknowledges a valid alarm, a message is transmitted to the
operator. In remote mode, the alarm can be acknowledged by simply ringing back
and typing ALARMACKN.

If the reason for the alarm has been cleared or if the alarm should continue, a new
alarm message will not be repeated. If there was an interruption of at least one
second after acknowledgement, a new alarm message will be generated.

6.3. SUMMARY ALARM RELAY

The summary alarm relay is a potential-free relay. It is raised when one or more of
the alarms is / are raised and is only re-set when all alarms are cleared. It can be
used to monitor alarms with an external alarm indicator. Devices connected to this
relay must not exceed a maximum switching power of 12 Vdc, 0.125 A. For the
location of the connecting clamps of the summary alarm relay please refer to chapter
3.3.2 Connecting Board.




Pin Description
1 Open in alarm condition
2 Common
3 Closed in alarm condition






figure 6-1 Relay contacts, alarm condition table 6-1 Relay contacts, pin assignment


Users Manual for MORx00BP

Page 40 M0098A0F.doc

6.4. STATUS REPORT

Two instructions enable the operator to get the information of the system status.
Typing GET, commands will be responded by a listing of all settings of the repeater.
STATUS will be responded by a listing of all individual status information which can
be monitored only, but not influenced by SET commands.

The complete listing of the syntax with the processor of the control module including
the instructions and the messages as well as all available alarms from the system is
available as a separate software manual.

7 Troubleshooting

Page 41

7. TROUBLESHOOTING

In the event of a malfunction, it is always recommendable to check the status of the
antenna systems as well as the continuity of the entire cabling including connectors.

For troubleshooting, always check the status of the system via the software
commands STATUS and GET.

Failure Cause Repair
No mains power Check mains power.
Power supply fuse defect Replace power supply fuse.
Mains fuse at mains
power terminal defect
Replace mains fuse of terminal.
Power supply defect
Check input and output voltages of
power supplies.
Replace power supply.
Remote unit
does not work;
no function
Faulty mains power cable Replace cable.
Power supply defect
Check input and output voltages of
all power supplies.
Replace power supply.
IC-Bus cable defect or
loosened
Fasten cable.
If the cable is defect, contact
customer service.
IC-Bus failure
Control module defect Replace control module.
Input power too low Check output power of BTS.
Wrong ALC setting
Adjust ALC as given on the yellow
label of the module.
Feed-forward amplifier
defect
Measure output power of feed-
forward amplifier and replace it if
necessary.
Low output
power
Cable defect
Measure cables and replace
defect cable.
ALC
Too high input power, check and
regulate input power.
Module/feed-forward
amplifier defect
Replace module/feed-forward
amplifier.
Remote unit
oscillates
Current failure appears
Measure and check the power
supply voltage 8 V/12 V.

Users Manual for MORx00BP

Page 42 M0098A0F.doc


Failure Cause Repair
8 V failure
Measure voltage on power
supplies, 8 V necessary for
modules.
Current failure
12 V failure
Measure voltage on power
supplies, 12 V necessary for
modules as well as feed-forward
amplifier.
Loosened IC-Bus cable
on duplexer
Check IC-Bus cable on duplexer.
Cable bridge failure
Disconnect cable bridge and
check connectors, make sure that
no pins are bent, then reinstall
cable bridge carefully.
No access or
recognition of
module
Incorrect boot process Boot remote unit again.
Remote unit
cannot be
recognized by
the OMC
Modem in master unit
defect
Check initstring.
Check OMC settings.
Measure power supply of
modem.
Check SIM-card.
Replace modem.
Check control module.
Optical attenuation >10 dB
Measure optical attenuation
(must be less than 10 dB).
Check cable connectors and
clean them if necessary.
Check splice losses.
Remote units
cannot be
recognized by
the master unit
FSK-Modulator defect
Measure 10.7 MHz signal.
Replace FSK-Modulator.
Check transmitter and receiver *.
Optical transmission error
Check optical losses.
Check receiver and transmitter *.
RX/TX failure
Wrong coding of control
module
Check coding of control module.
*Transmitter and receiver must be replaced by qualified personnel only.
8 Maintenance

Page 43

8. MAINTENANCE
8.1. GENERAL

Read the health and safety warnings in chapter 1.2 Health and Safety Warnings.
Note: The repeater does not require preventative maintenance measures.
It is only recommended to replace the RTC battery after three years of usage as a
preventive measure. The nominal lifetime of this battery is five years under normal
environmental conditions.
Note: The RTC battery must be removed for long term storage.
In the event of malfunction, it is advantageous to check the status of the antenna
systems as well as the continuity of the entire cabling including connectors before
replacing any components.
8.2. REPLACEMENT OF COMPONENTS

Read the health and safety warnings in chapter 1.2 Health and Safety Warnings.

Maintenance on the repeater shall be performed by replacing components only.
Soldering on printed circuit boards must be avoided. In order to maintain warranty,
take care not to damage unintentionally the seals on the components. To open the
housing, the upper screws have to be removed first and then the lower screws.
Proceed in reverse order to close the housing.

Consequently, the spare parts list only contains units which can be replaced without
tuning or complex soldering work. Those units are all parts from the manufacturer as
well as internal and external cables.
Note: Defect parts should only be replaced by original parts from the
supplier. All interventions inside the housing are at ones own risk.
Note: During maintenance ensure that the repeater has been
disconnected from mains.
Open the lock at the left-hand side of the repeater. Use a torx key and unscrew the
four torx screws.
Note: Before disconnecting any cables, label any unlabeled cables to
ensure correct reconnection, and check the switch positions of the
removed part to set the switches of the new part accordingly.
Note: Depending on the repeater configuration some components are
equipped with a 50-Ohm termination resistor. In such a case, use
the termination resistor of the removed part to terminate the
respective connector of the replacement part.

Users Manual for MORx00BP

Page 44 M0098A0F.doc

For most maintenance procedures appropriate tools are required to ensure correct
handling. All these tools can be ordered from the supplier. For screwing procedures
observe that all screws have a right-hand thread, i.e. for fastening the screws turn the
tool clockwise and for unscrewing them turn it anti-clockwise.

For SMA connectors, a specified torque of 100 Ncm has to be observed. Therefore,
use an appropriate tool. Also, specified torques have to be observed for screws,
depending on the screw type and thread.

The table below shows a survey of the various screws with their respective torques.
In order not to exceed these torques, use appropriate tools for screwing procedures.

Screw Type
Tallow-drop Socket-head-cap Countersunk-head
Thread size Specified torque (in Ncm)
M 2.0 40 not in use 40
M 2.5 82 not in use 82
M 3.0 145 100 145
M 4.0 330 330 330
M 5.0 650 not in use 650
table 8-1 Specified torques
Note: After the replacement of a component, check whether the system
has to be levelled anew.
8.2.1. Duplexer


figure 8-1 Duplexer, position of screws
NOTE: Each duplexer is equipped with an amplifier at its backside. Do not
separate the two parts. The new duplexer will be supplied with a
pre-mounted amplifier.
Screws
M3x10
Screws
M3x10
8 Maintenance

Page 45

If the duplexer is equipped with a VSWR module for the VSWR option, at first
remove this module. To do so, refer to chapter 8.2.12 VSWR Module.
To remove the duplexer, first disconnect all cables and SMA connectors from the
duplexer (and amplifier).
Unscrew the four countersunk-head screws M3x10 by which the duplexer is
fastened to the connector panel of the repeater.
Take the duplexer out completely, making sure that the black seal between the
duplexer and the connector panel of the cabinet is also removed.
A new seal is supplied with the new duplexer, therefore, we recommend to throw
the old seal away immediately in order to avoid confusion.
IMPORTANT: Before starting to mount the new duplexer make sure to have put
the new seal the one that was delivered with the new duplexer correctly on
the surface of the duplexer that is fitted on the connector panel of the cabinet. The
left and right edge of the seal must be level with the left and right edge of the
surface. The position of the seal is not correct if a part of it stands out at the
bottom.
Fasten the duplexer with the four countersunk-head screws M3x10 to the
connector panel of the repeater and re-connect the SMA connectors.
Install the VSWR module according to chapter 8.2.12 VSWR Module if this
module was mounted on the duplexer.
Re-connect all cables and SMA connectors to the duplexer (and amplifier).
8.2.2. Transceiver
8.2.2.1. Standard Transceiver

Before starting to remove the
transceiver, the FSK-modulator has to
be removed. To do so, refer to chapter
8.2.3 FSK-Modulator.
Disconnect the fibre-optic cables and
put the protective caps onto their tips.
Disconnect all SMA connectors
making sure to remember their
respective positions and unscrew the
four countersunk-head screws M3x12.
figure 8-2 Transceiver, position of screws
Screws
M3x12
Screws
M3x12

Users Manual for MORx00BP

Page 46 M0098A0F.doc


Take the transceiver out, making sure that the black seal between the transceiver
and the connector panel of the cabinet is also removed.
A new seal is supplied with the new transceiver, therefore, we recommend to
throw the old seal away immediately in order to avoid confusion.
IMPORTANT: Before starting to mount the new transceiver make sure to have put
the new seal that was delivered with the new transceiver correctly on the surface
of the transceiver that is fitted on the connector panel of the cabinet. The position of
the seal is not correct if a part of it stands out at one side, top or bottom.
Fasten the new transceiver with the four countersunk-head screws M3x12 to the
connector panel of the repeater and carefully re-connect the SMA connectors.
To mount the FSK-modulator, refer to chapter 8.2.3 FSK-Modulator and re-
connect the fibre-optic cables.

8.2.2.2. DFB Transceiver

Before starting to remove the transceiver, the FSK-modulator has to be removed.
To do so, refer to chapter 8.2.3 FSK-Modulator.

Disconnect the fibre-optic cables and put the protective caps onto their tips.





Disconnect all SMA connectors
making sure to remember their
respective positions and unscrew
the four socket-head-cap screws
M3x18.

Take both parts of the transceiver
out and remove the two seals
from the transceiver parts.


figure 8-3 DFB transceiver, position of
screws

Push the four socket-head-cap screws M3x18 through the corresponding holes of
the outside part of the transceiver, put on seal A over the screw threads and push
the screws through the respective holes in the cabinet.
Screws M3x18
(two lower screws
hidden)
Fibre-optic cables
8 Maintenance

Page 47



figure 8-4 Transceiver assembly

From inside the cabinet put seal B over the screw threads and position the inside
part of the transceiver.

Fasten both parts to the connector panel of the repeater by tightening the four
socket-head-cap screws M3x18.

Re-connect the SMA connectors and refer to chapter 8.2.3 FSK-Modulator to
mount the FSK-modulator, then, re-connect the fibre-optic cables.

8.2.3. FSK-Modulator

If the repeater is equipped with a connecting board, refer to chapter 8.2.11
Connecting Board in order to remove the connecting board, first.
To remove the FSK-modulator
disconnect all cables.

Unscrew the two tallow-drop screws
M2.5x12.

When taking out the FSK-modulator
the black plug and socket connection
with the transceiver is disconnected.

To mount the new FSK-modulator,
carefully, fit the black connector into
its socket on the transceiver.
figure 8-5 FSK-modulator, position of
screws
Four screws
M3x18
Seal A
Seal B
Connector
panel of
cabinet
Outer side Inner side

Users Manual for MORx00BP

Page 48 M0098A0F.doc


Fasten the new FSK-modulator with the two tallow-drop screws M2.5x12 and re-
connect all cables.

For mounting the connecting board if present refer to chapter 8.2.11
Connecting Board.

8.2.4. UL/DL Amplifiers

Depending on the location of the amplifier to be removed, proceed as follows:
8.2.4.1. Mounted under the Transceiver

Before removing the amplifier, the optical system has to be removed first. To do
so, refer to chapter 8.2.2 Transceiver.

To remove the amplifier, disconnect all SMA connectors as well as the two I
2
C
bus connectors. Make sure to remember their respective positions.

Unscrew the two countersunk-head screws M3x14 and take the amplifier out.

Fasten the new amplifier with the two countersunk-head screws and carefully re-
connect the two I
2
C-Bus and the SMA connectors.

To mount the optical system refer to chapter 8.2.2 Transceiver.

8.2.4.2. Mounted beside the Transceiver

To remove the amplifier, disconnect the SMA connection with the transceiver.

Before the amplifier can be removed, the optical system has to be taken out first.
To do so, refer to chapter 8.2.2 Transceiver. This is necessary to get access to
the screw by which the amplifier is fastened.

Unscrew the countersunk-head screw M3x12 and take the amplifier out.

Fasten the new amplifier with the countersunk-head screws M3x12.

To mount the optical system, refer to chapter 8.2.2 Transceiver and re-connect
the SMA connector with the transceiver.

8 Maintenance

Page 49

8.2.4.3. Fastened with a Mounting Plate

There are two types of mounting plates, a smaller one designed for one and the other
for two amplifiers.

To remove the amplifier, the mounting plate has to be taken out first, together with
the amplifier(s).

To do so, disconnect all SMA connectors of the amplifier(s) as well as the flat-line
cable(s) leading to the motherboard. Make sure to remember their respective
positions.

Unscrew the tallow-drop screws M3x8. There are two of them for the smaller plate
and five for the bigger one.

Take the plate out, turn it upside down, and unscrew the four countersunk-head
screws M2.5x5 at its bottom, by which the amplifier is screwed to the plate.

Remove the amplifier and fasten the new amplifier with the four countersunk-head
screws M2.5x5 to the mounting plate.

Screw the mounting plate to the cabinet with the two, respectively five tallow-drop
screws M3x8, and re-connect all SMA connectors of the amplifier(s) as well as
the flat-line cable(s) leading to the motherboard.

8.2.5. Feed-Forward Amplifiers


figure 8-6 Feed-forward amplifier, former version, uninstalled, position of screws
M3x10
socket-
head-cap
screws
M3x25
socket-head-cap
screws

Users Manual for MORx00BP

Page 50 M0098A0F.doc



1.) Remove the VSWR module by
unscrewing the two M3x6
tallow-drop screws and lay the
VSWR module aside.
2.) Remove the old feed-forward
amplifier to be replaced which is
mounted directly to the cabinet.
Unscrew the five M3x25 socket-
head-cap screws (circle-marked
in figure 3-1) and the two M3x10
socket-head-cap screws (circle-
marked in figure 3-1) and
unplug the DC connector and
the two SMA-connectors.
3.) Bring the DC cable into its
position.
figure 8-7 Feed-forward amplifier, former
version, installed, position of screws


4.) In order to take out the DC-cable out of the pre-milled cable channel, unscrew
the five M3.0x6 tallow-drop screws which are screwed to the mounting plate
on the right of the feed-forward amplifier and lay the mounting plate aside.
5.) Remove the touch-guard plate.
6.) Take out the DC-cable of the pre-milled channel.
7.) Before the cable can be placed in an upper position, the SMA-connector
located at the duplexer has to be removed.
8.) Insert the touch-guard material.
9.) Fasten the mounting plate to the right with five M3x6 tallow-drop screws.
10.) Put heat-conductive paste at the bottom of the new amplifier.
11.) Fasten it with the five socket-head-cap screws M3x25 as well as the two
socket-head-cap screws M3x10.
12.) Re-connect the SMA-connector to the duplexer.
Feed-forward
amplifier
M3x25
socket-head-cap
screws
VSWR
module
DC cable
M3x10
socket-head-cap
screws
M3x6
tallow-drop
screws
8 Maintenance

Page 51

8.2.6. Feed-Forward Amplifier Kit

The feed-forward amplifier kit is the new method of construction of MOR300BP and
MOR400BP in the F-cabinet with the consisting of feed-forward amplifier and
mounting plate, step-up DC/DC converter and mounting plate and various types of
screws. For their exact description, see following figures:


figure 8-8 Feed-forward amplifier kit, position of screws

figure 8-9 I2C board

Note: Before replacing the
new version of the
final amplifier with the
24 VDC and 48 VDC
power supplies being
installed in the
MOR300BP or
MOR400BP repeater,
at first remove the I
2
C
board if installed.

Mounting plate
DC cable from Sub D
15 connector to
DC/DC-converter
DC-DC converter
with mounting plate
Knurled nuts
Fin. Ampl.
(MOR300)
DC-cable
from DC/DC-converter to
feed-forward amplifier
M2.5x5
tallow-drop screws
Spacing bolts
M3.0x8
countersunk-
head-screws

Users Manual for MORx00BP

Page 52 M0098A0F.doc



figure 8-10 Feed-forward amplifier mounting plate, position of
screws

1.) Before the
amplifier
can be
installed
in the
repeater,
the
spacing
bolts have
to be fixed
onto the
feed-
forward
amplifier
mounting
plate.


figure 8-11 Feed-forward amplifier,
new version, position of screws

2.) Fasten the new feed-forward amplifier with
the five captive socket-head-cap screws,
which are part of the feed-forward
amplifier.
3.) As the HF input/output has remained
unchanged the SMA connectors can be
connected as usual.
4.) Connect the DC-cable and fix it with cable
fasteners.
Socket-head-cap
screws
M3x8 spacing bolts
M3x15 spacing bolts
Tallow-drop screws
M3.0x8 countersunk-
head screws
8 Maintenance

Page 53



figure 8-12 DC/DC converter, position
of screws

5.) Fasten the DC/DC-converter with four
M2.5x5 tallow-drop screws onto the
mounting plate.
6.) Fasten the DC/DC converter and
mounting plate with two knurled nuts
onto the inside wall on the left in the lid.

figure 8-13 Feed-forward amplifier
with VSWR module, new version,
position of screws

7.) Fasten the VSWR module to the two
spacer blocks.
Knurled nuts
M2.5x5
tallow-drop
screws
VSWR
module

Users Manual for MORx00BP

Page 54 M0098A0F.doc

8.2.7. RTC Battery

The RTC battery of the control module has to be replaced in case of memory loss or
as a preventive measure after approximately three years of usage. The RTC battery
is mounted in the lid of the repeater on the control module.
NOTE: Before replacing the battery, do not forget to disconnect the
repeater from mains.
The type of battery is CR 2450N Lithium 3 V / 500 mAh, manufactured by RENATA.
Note: Observe the rules for changing Lithium batteries. Wrong connection
or treatment may result in bursting of the battery and dissemination
of hazardous substances.
Note: Do not try to charge this battery.
Place a small screwdriver in the gap between the battery and the battery socket,
push the battery carefully forward until it is pressed out of the socket, and take it
out.


figure 8-14 Position of RTC battery

To mount the new battery, carefully, push it into the socket via the opening,
straight along the groove at the outer rim of the battery and the inner rim of the
socket with the narrower part of the battery on the upside.
Note: After replacement of the RTC battery, date and time are set to basic
settings.
RTC battery
Gap for
screwdriver
8 Maintenance

Page 55

8.2.8. Control Module

The control module is a printed circuit board situated in the lid of the repeater.

To remove the control module, disconnect the green plug and socket connection
coming from the power supply as well as the grey flat-line cable leading to the
motherboard.

Disconnect the remaining cable connection by using the pressing mechanism of
its black connector.

Separate the module from the grey mains cable by cutting the two plastic-cable
clamps.

Unscrew the four knurled nuts M2.5x20 by which the module is fastened to the
cabinet of the repeater. Take good care not to damage the board with the tool
during screwing since that may destroy vital data carriers.

Take the module out carefully again taking care not to damage the board.

To mount the new module, fasten it with the four knurled nuts M2.5x20 to the
cabinet of the repeater. When tightening the nuts, take special care not to
damage the board with the tool.

Fasten the grey mains cable using two plastic-cable clamps of appropriate size,
and connect the cable connection with the black connector by pressing it into its
black socket on the module.

Connect the green plug and socket connection coming from the power supply as
well as the grey flat-line cable leading to the motherboard.



Users Manual for MORx00BP

Page 56 M0098A0F.doc

8.2.9. Power Supply

To remove the power supply, at first switch off the black external switch (see
chapter 3.3.9 Power Supply) to position 0.

Unscrew the two nuts by which the power supply is fastened to the cabinet of the
repeater. In order not to exceed the specified torque of 1100 Ncm use an
appropriate tool.

Use both hands to remove the power supply. To do so, put your thumbs on the
casing and grip the power supply with your fingers. Slowly, pull it up with your
fingers and take it out carefully. Avoid contact with the heat-conducting paste at
the connecting surface of cabinet and power supply.

Before bringing the new power supply in position, apply heat-conducting paste to
its connecting surface with the cabinet.

Fasten the power supply with the two nuts. In order not to exceed the specified
torque of 1100 Ncm use an appropriate tool.

Connect the two green plug and socket connections and switch on the black main
switch (position 1).

8 Maintenance

Page 57

8.2.10. Fuses

The power supply is protected with one or two primary fuses, their type depending on
the power supply unit.
NOTE: Use only fuses of the same type and the same rating as
replacement, i.e. before throwing away a blown fuse check its type
and rating.
8.2.10.1. Fine-Wire Fuse

figure 8-15 Power supply fuses, exemplary

To remove such a fuse, use a screwdriver to open the bayonet-cap finish of the
fuse holder by turning it left, take out the fuse holder, and remove the fuse. Do not
forget to check its type and rating.

To mount the new fuse put it into the fuse holder and push it back in, turning the
bayonet-cap finish right with the screwdriver until the fuse holder is locked into
place.

8.2.10.2. Blade-Type Electric Fuse Link

This fuse type can be removed by pulling it out of its socket. Do not forget to
check its type and rating.

To mount the new fuse insert it carefully back into its socket.

Fine-wire
fuses
Blade-type
electric fuse link

Users Manual for MORx00BP

Page 58 M0098A0F.doc

8.2.11. Connecting Board
Note: For removing the connecting board it is necessary to disconnect
the mains cable. Therefore, make absolutely sure that mains is
disconnected so that no voltage is fed at the mains cable.
To remove the connecting board carefully take off the grey cover.

Then, it is necessary to disconnect the mains cable. This is fastened by a six-pole
insulating screw joint. Unscrew the three screws holding the cable side that is
leading to the repeater and pull the three cable wires out.

Disconnect the grey flat-line cable leading to the motherboard and unscrew the
three tallow-drop screws M3x10. Take them out completely.

1
Screw joint for
clamping mains
cable
2 Door contact
3
Connection for flat-
line cable to
motherboard
4
VSWR module *
connection
5
External alarms
interface
6
Summary alarms
and PSTN modem
interfaces
figure 8-16 Connections of connecting board
* Only connected if the option is installed.

Take out the connecting board, and to mount the new connecting board, carefully
fit the black connector into its socket on the FSK-modulator.

Fasten the connecting board with the three tallow-drop screws M3x10 and re-
connect the grey flat-line cable leading to the motherboard.

Carefully, push the three wires of the mains cable back into their respective
positions and tighten the corresponding screws.

Put on the grey cover by fitting the pins into the respective holes.

3
2 1
4
5
6
8 Maintenance

Page 59

8.2.12. VSWR Module

The VSWR module is clamped into a mounting plate that is screwed on top of the
final or feed-forward amplifier.
Note: To remove the mounting plate, always take out the VSWR module,
first.
To remove the VSWR module, disconnect the two semi-rigid cables leading to the
bottom of the duplexer from the module. Make sure to remember the position of
their corresponding connectors at the bottom of the module.

Disconnect the black cable leading to the mainboard from the module. Make sure
to remember the position of its corresponding connector at the bottom of the
module and take the module out of the mounting plate.

If, the main purpose is to exchange the component on which the module is placed,
the mounting plate has to be removed, as well. Depending on the location of the
VSWR module, continue as follows:

On the former version of the feed-forward amplifier:

The plate is held by two of the six socket-head-cap screws M3x25 of the feed-
forward-amplifier.

Loosen the two socket-head-cap screws M3x25 of the feed-forward-amplifier
holding the mounting plate. To pull out the mounting plate, these screws just have
to be loosened, not unscrewed.

To mount the plate again, place it under the two socket-head-cap screws M3x25
of the amplifier by which it was held and tighten them, thus, clamping the
mounting plate to the module.

To install the VSWR module, connect the black cable from the mainboard at the
bottom of the VSWR module.

Connect the two semi-rigid cables from the bottom of the duplexer at the bottom
of the module and clamp the module into the mounting plate.

On the new version of the feed-forward amplifier:

For replacing the VSWR module, please refer to chapter 8.2.6 Feed-Forward
Amplifier Kit.


Users Manual for MORx00BP

Page 60 M0098A0F.doc

8.2.13. Mains Cable

The repeater is delivered with a firmly connected mains cable. In case the length of
the delivered mains cable should not be sufficient or in case of a defect, the mains
cable can be replaced.
Note: Disconnect repeater from mains first.

To remove the mains cable, at first open the grey cover of the connecting board.

Use a small screwdriver to loosen the three screws of the grounding terminal and
fuse terminals, where the three wires of the mains cable are clamped. Make sure
to remember their respective positions for mounting the new cable.

Pull the three cable wires out of the terminals and remove the insulating tubing
from the cable.

Open the nut of the cable gland with a spanner, size 20 mm.

Pull the cable out of the housing and remove the nut and joint rubber both parts
forming the cable gland from the cable.

For the installation of a new mains cable strip its isolation to the required length.

First, slide the nut and then the joint rubber of the cable gland over the new mains
cable. The joint rubber must be level with the end of the isolation.

Insert the new mains cable through the opening in the housing until the joint
rubber is stuck in the opening.

Close the cable gland by tightening its nut with a spanner, size 20 mm and slide
the insulating tubing over the three cable wires inside the housing.

Insert the three cable wires into their respective grounding and fuse terminals and
tighten the corresponding screws to clamp the wires.

Close the cover of the connecting board.
9 Appendix

Page 61

9. APPENDIX
9.1. ILLUSTRATIONS
9.1.1. Installation Drawings


figure 9-1 F-cabinet for MORx00BP


Users Manual for MORx00BP

Page 62 M0098A0F.doc

9.1.2. Repeater Layout


figure 9-2 Layout of repeater lid, former version, exemplary
9 Appendix

Page 63



figure 9-3 Layout of repeater lid, new version, exemplary

Users Manual for MORx00BP

Page 64 M0098A0F.doc



figure 9-4 Layout of heat sink, former version, exemplary
9 Appendix

Page 65



figure 9-5 Layout of heat sink, new version, exemplary


Users Manual for MORx00BP

Page 66 M0098A0F.doc

9.2. SPECIFICATIONS
9.2.1. Electrical Specifications
Note: For detailed information, refer to the Environmental and Safety
Specifications leaflet of the supplier, related to ETS 300 019
(European Telecommunication Standard).
Repeater type MOR300BP *
GSM UL: 890 - 915 MHz; DL: 935 - 960 MHz
EGSM UL: 880 - 915 MHz; DL: 925 - 960 MHz Frequency range
GSM-Rail UL: 876 - 880 MHz; DL: 921 - 925 MHz
Gain UL / DL 50 dB min.
Gain setting range 30 dB in steps of 2 dB
Gain variation
- over normal operating temp.
- over extreme operating temp.

1.5 dB
2.0 dB
Tolerance of gain over full bandwidth 2.0 dB
Delay (excluding fiber optics) 1 sec max.
Group delay <100 nsec in each 200 kHz segment
P
out
max. DL
(@ 600 kHz channel spacing)
2 x 27 dBm
DL output ICP3 58 dBm
UL output noise power @ max. gain,
200kHz
-115 dBm typ. with corresponding master
unit set to unity gain
UL noise figure @ max. gain
@ 40 dB gain
6 dB
12 dB
DL output noise @ 0 dB optical loss
-40 dBm / 200 kHz @ 40 dB gain
-30 dBm / 200 kHz @ 50 dB gain
UL input ICP3 @ max. gain
@ 40 dB gain
-20 dBm
-10 dBm
ALC overload reaction time 3 msec
Return loss
- over frequency and normal temp.
- over frequency and extreme temp.

15 dB
12 dB
Power supply
230 Vac / 50 Hz
Option: 110 Vac / 50 Hz,
+24 Vdc or -48 Vdc
Power consumption 90 W
Alarm monitoring Current monitor, temperature
Operating temp., normal temp. range
Operating temp., extreme temp. range
+5C ... +40C
-33C ... +50C
* Unless otherwise noted all specifications are given @ maximum gain.
All data is subject to change without notice.
9 Appendix

Page 67


Repeater type MOR400BP*
Frequency range 55 MHz in GSM1800 band
Gain UL / DL 50 dB min.
Gain setting range 20 dB in steps of 2 dB
Gain variation
- over normal operating temperature
- over extreme operating temp.

1.5 dB
2.0 dB
Tolerance of gain over full bandwidth 2.0 dB
Delay (excluding fiber optics) 1 sec max.
Delay ripple <100 nsec in each 200 kHz segment
P
out
max. DL
@ 600 kHz channel spacing
2 x 27 dBm
DL output ICP3 57 dBm
UL output noise power @ max. gain,
200kHz
-115 dBm typ. with corresponding master
unit set to unity gain
UL noise figure @ max. gain
@ 40 dB gain
6 dB
12 dB
DL output noise @ 0 dB optical loss
-40 dBm / 200 kHz @ 40 dB gain
-30 dBm / 200 kHz @ 50 dB gain
UL input ICP3 @ max. gain
@ 40 dB gain
-20 dBm
-15 dBm
ALC overload reaction time 3 msec
Return loss
- over frequency and normal temp.
- over frequency and extreme temp.

15 dB
12 dB
Power supply
Options:
230 Vac / 50 Hz
110 Vac / 50 Hz,
+24 Vdc or -48 Vdc
Power consumption 90 W
Alarm monitoring Current monitor, temperature
Operating temp., normal temp. range
Operating temp., extreme temp. range
+5C ... +40C
-33C ... +50C
* Unless otherwise noted all specifications are given @ maximum gain.
All data is subject to change without notice.

9.2.2. Optical Specifications

Max. allowed optical loss master / remote 10 dB *
Required optical return loss 45 dB
* Optical loss up to 12 dB with slightly degraded performance.
All data is subject to change without notice.


Users Manual for MORx00BP

Page 68 M0098A0F.doc

9.2.3. Mechanical Specifications

The MORx00BP is available in the standard F-Cabinet:
Height x Width x Depth* 445 x 255 x 167 mm
Weight approx. 14 kg
* without connectors and mounting brackets
All data is subject to change without notice.

9.3. SPARE PARTS

The following lists contain all parts available for the MORx00BP. The repeater
configuration can also be seen at the configuration list, which is part of the delivery.
9.3.1. Repeater Type Specific Spare Parts for MORx00BP
9.3.1.1. Spare Parts List of MOR300BP

Designation ID No
MOR300BP (F) 7154874
Ampl. 10 dBm 921-960 3.5 dB 7151713
Ampl. 19 dBm 876-915 30.5 dB 7155683
DC-DC Converter IN 10-14 V OUT 24-34 V 60 W 7164502
Dpx UL-active 876-880 921-925 * 7143131
1)

Dpx UL-active 880-915 925-960 7150310
2)

Dpx UL-active 890-915 935-960 7150302
Fin. Ampl. 921-960 50 dB (new version) 7164414
Fin. Ampl. 921-960 50 dB (old version) 7149014
SW manual for universal SLV 1400 7159453
SW SLV1400 7158836
Transceiver MFY1340 DIN 7152313
Transceiver MFY1340 E2000 7152500
Transceiver MFY1340 FC 7152499
Transceiver MFY1340 SC 7152498
Transceiver MFY2314 DIN 7154880
Transceiver MFY2314 E2000 7154883
Transceiver MFY2314 FC 7154881
Transceiver MFY2314 SC 7154882
VSWR Kit GSM +EGSM +GSMR 7143437
* ID No 7154874 is available for GSM and optionally for GSM-R or EGSM:
1)
available for GSM-R, only
2)
available for EGSM, only
The manufacturer reserves the right to replace the spare parts listed above by
equivalent substitutes!
9 Appendix

Page 69


MOR300BP MU (F) 7154787
Ampl. 10 dBm 921-960 3.5 dB 7151713
Ampl. 19 dBm 876-915 30.5 dB 7155683
Coupler IC-Bus 7157422
Crossband coupler 1710-1785 1920-1980 7157233
Crossband coupler 1805-1880 2110-2170 7157234
DC-DC Converter IN 10-14 V OUT 24-34 V 60 W 7164502
Crossband coupler 20-1000 1450-2200 7155042
Dpx UL-active 880-915 925-960 7150310
Dpx UL-active 890-915 935-960 7150302
Fin. Ampl. 921-960 50 dB (new version) 7164414
Fin. Ampl. 921-960 50 dB (old version) 7149014
SW manual for universal SLV 1400 7159453
SW SLV1400 7158836
Transceiver MFZ900/1800 DIN 7153284
Transceiver MFZ900/1800 E2000 7153695
Transceiver MFZ900/1800 FC 7153698
Transceiver MFZ900/1800 SC 7153696
VSWR Kit GSM +EGSM +GSMR 7143437
The manufacturer reserves the right to replace the spare parts listed above by
equivalent substitutes!

9.3.1.2. Spare Parts List of MOR400BP

Designation ID No
MOR400BP (F) 7155425
Ampl. 1710-1785 36 dB 7153049
Ampl. 1805-1880 5.5 dB 7153727
Amp. Kit DL 7500546
Connecting Board 7147115
Control Unit SM2009 7143051
DC-DC Converter IN 10-14V OUT 24-34 V 60 W 7164502
Dpx UL-active 1710-1765 1805-1860 7157423
Dpx UL-active 1730-1785 1825-1880 7159565
Fin. Ampl. 1805-1880 50 dB (former version) 7152251
Fin. Ampl. 12 W 1805-1880 50 dB (new version) 7164413
FSK-Modem 57.6 kbit 10.7 MHz 12 V 7153490
Manual SW SLV1200V1.xx f. ID No: 7148546 7148799
SW manual for universal SLV 1400 7159453
SW SLV1400 7158836

Users Manual for MORx00BP

Page 70 M0098A0F.doc


Transceiver MFY1318 DIN 7143093
Transceiver MFY1318 E2000 7153895
Transceiver MFY1318 FC 7146678
Transceiver MFY1318 SC 7146615
Transceiver MFY1348 DIN 7152311
Transceiver MFY1348 E2000 7152497
Transceiver MFY1348 FC 7152496
Transceiver MFY1348 SC 7152495
VSWR Kit DCS 7143436
The manufacturer reserves the right to replace the spare parts listed above by
equivalent substitutes!

MOR400BP MU (F) 7157776
Ampl. 1710-1785 36 dB 7153049
Ampl. 1805-1880 5.5 dB 7153727
Config. SLV1400 V1.1.2 7160008
Coupler IC-Bus 7157422
Crossband coupler 1710-1785 1920-1980 7157233
Crossband coupler 1805-1880 2110-2170 7157234
DC-DC Converter IN 10-14V OUT 24-34 V 60 W 7164502
Dpx UL-active 1710-1765 1805-1860 7157423
Dpx UL-active 1730-1785 1825-1880 7159565
Fin. Ampl. 1805-1880 50 dB (former version) 7152251
Fin. Ampl. 12 W 1805-1880 50 dB (new version) 7164413
SW manual for universal SLV 1400 7159453
SW SLV1400 7158836
Transceiver MFY1318 DIN 7143093
Transceiver MFY1318 E2000 7153895
Transceiver MFY1318 FC 7146678
Transceiver MFY1318 SC 7146615
Transceiver MFY1348 DIN 7152311
Transceiver MFY1348 E2000 7152497
Transceiver MFY1348 FC 7152496
Transceiver MFY1348 SC 7152495
VSWR Kit DCS 7143436
The manufacturer reserves the right to replace the spare parts listed above by
equivalent substitutes!
9 Appendix

Page 71


MOR400BP EU (F) 7154786
Ampl. 1710-1785 36 dB 7153049
Ampl. 1805-1880 5.5 dB 7153727
Coupler IC-Bus 7157422
Crossband coupler 1710-1785 1920-1980 7157233
Crossband coupler 1805-1880 2110-2170 7157234
DC-DC Converter IN 10-14V OUT 24-34 V 60 W 7164502
Dpx UL-active 1710-1765 1805-1860 7157423
Dpx UL-active 1730-1785 1825-1880 7159565
Fin. Ampl. 1805-1880 50 dB (former version) 7152251
Fin. Ampl. 12W 1805-1880 50 dB (new version) 7164413
SW manual for universal SLV 1400 7159453
SW SLV1400 7158836
VSWR Kit DCS 7143436
The manufacturer reserves the right to replace the spare parts listed above by
equivalent substitutes!

9.3.2. Common Spare Parts for all MORx00BP
Designation ID No
Additional information for all MORs 7154765
Connecting Board 7147115
Control Unit SM2009 7143051
FSK-Modem 57.6 kbit 10.7 MHz 12 V 7153490
Manual SW SLV1200V1.xx for ID No:7148546 7148799
Pole Mounting Kit for D-/F-cabinet 7158617
Power Supply Unit AC IN 115 V 7155721
Power Supply Unit AC IN 230 V 7144306
Power Supply Unit DC IN 24 V 7160393
Power Supply Unit DC IN 48 V 7160392
SW Option External Alarms 7145067
SW SLV1200 for wide band 7148546
User's Manual for MORx00BP in F-Cab. 7155512
Wall-mounting Kit for F-cabinet 7150519
The manufacturer reserves the right to replace the spare parts listed above by
equivalent substitutes!


Users Manual for MORx00BP

Page 72 M0098A0F.doc

9.4. ADDITIONAL INFORMATION ON CONTROL MODULE SM2009












































(1) External alarms or PSTN modem selection by DIP-switches
(2) MR or MOR (master unit) repeater selection DIP-switches
(3) Fixed location for labels (control module ID No, revision stage, repeater software, serial number)
BBU-switch
No BBU: Pos. 1
BBU: Pos. 2
RS 232
(1) PSTN /
Ext. alarms
RTC
battery
PCMCIA slot
L3
L1 & L2
Mode
switch
(3) Software
information
Solder
bridge (Rev.
09 & 10)
1
2
(2) MR/MOR
DIP-switch
9 Appendix

Page 73

9.5. DIP-SWITCH SETTINGS

















Factory set
ON
OFF(default
values)
4 DO NOT USE! auto
3 n.c. n.c.
2 remote mode local mode
1 manual auto
ON OFF
4 Ext. Alarm 1 PSTN (a)
3 Ext. Alarm 2 PSTN (b)
2 Ext. Alarm 3 PSTN (c)
1 Ext. Alarm 4 PSTN (d)

Repeater in D-, F-cab
and master units
Repeater in G-cab
ON OFF ON OFF
8 MOR MR MR & MOR
7 MOR MR MR & MOR
6 MOR MR MR & MOR
5 MOR MR MR & MOR
4 MR MOR MR & MOR
3 MR MOR MR & MOR
2 MR MOR MR & MOR
1 MR MOR MR & MOR

Users Manual for MORx00BP

Page 74 M0098A0F.doc

For your notes:

10 Index

Page 75

10. INDEX
A
Abbreviations 7
About Andrew Wireless Systems 9
Address of Andrew Wireless Systems GmbH 9
Alarms
Bite and Alarms 39
Handling of Alarms 39
Status Report 40
Summary Alarm Relay 39
Amplifier
UL / DL 17
Attenuation
Manual Setting 38
Software Setting 35
B
Boot Process 34
C
Commissioning 33
Connecting Board 15
Connections
Antenna 30
Optical Fibres 30
Power 29
Contact Addresses 10
Control Module 20
D
DC/DC Converter 19
DL Amplifier 17
Duplexer 14
E
External Alarms 23
F
Factory Settings 13
Feed-Forward Amplifier Kit 19
Feed-Forward Amplifiers 17
FSK-Modulator 15
G
Grounding 29
H
Health and Safety Warnings 8
I
Installation
Electrical 28
Mechanical 25
Installation Drawing 61
L
Layout
Heat Sink (Former Version) 64, 65
Repeater Lid (Former Version) 62
Repeater Lid (New Version) 63
Local Login 35
M
Maintenance 43
Measuring Aids 14
Motherboard 22
Mounting
Pole 27
Wall 26
Mounting Brackets 26
O
Optional Equipment 23
P
Power Supply 21
R
Remote Login 37
Repeater Design 13
Replacement of
Amplifier (UL/DL) 48
Components 43
Connecting Board 58
Control Module 55
Duplexer 44
Feed-Forward Amplifier, Former Version 49
FSK-modulator 47
Fuses 57
General 43
Mains Cable 60
Power Supply 56
RTC Battery 54
Transceiver (DFB) 46
Transceiver (Standard) 45
VSWR Module 59
S
Settings via Software 35
SM2009
Additional Information 72
DIP Switch Settings 73
Spare Parts 68
Specifications
Electrical (MOR300BP) 66
Electrical (MOR400BP) 67
Mechanical 68
Optical 67
Step-Up DC/DC Converter 19
T
Transceiver 16
Troubleshooting 41
U
UL Amplifier 17
V
VSWR 24


Users Manual for MORx00BP

Page 76 M0098A0F.doc

11. LIST OF CHANGES

Version Changes Release Date
M0098A0E 06-October-2005
M0098A0F - Mikom GmbH changed its names into
Andrew Wireless System GmbH
- Chapter 5.4 changed
30-October-2007

You might also like