You are on page 1of 2

ABB Switzerland Ltd 1KHL015788-EN

Archive No.: Rev. Date:


Instruction for Changing the Input Voltage of B5LC
- A 2005-09-30
Responsible Department: Prepared: Approved: Distribution: Lang.: Page:
PSND 1998-01-23 sig. R. Pauli 1998-01-29 sig. T. Ruckli - EN 1/2
Valid for: Derived from: Replaces: Classification-No.: File:
- - - - 1KHL015788ae Input Voltage
Change B5LC.doc

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to
Power Line Carrier Equipment: Series ETL500/ETL600
Instruction for Changing the Input Voltage of B5LC

Contents

1 Purpose of document...................................................................................... 1
2 Safety instructions .......................................................................................... 1
3 Changing from 230 VAC to 115 VAC............................................................. 2
4 Changing from 115 VAC to 230 VAC............................................................. 2

1 Purpose of document
This document describes how to change the input voltage of the AC power supply type B5LC from
230 VAC to 115 VAC or vice versa.
2 Safety instructions

third parties without express authority is strictly forbidden. ABB Switzerland Ltd


DANGER
Hazardous voltage and hazardous energy level.
Beware of electric shock.
Unplug the cables to the module from the mains before opening.


Caution
Follow the instruction below carefully and do not modify anything.


Caution
Wrong programming can damage the module and the equipment.
Check if programmed input voltage of the module is equal to the mains
voltage.
Verify the programming information on the right side of the module.


Caution
Operate the module only in the condition specified by the manufacturer.


Revision: Language: Page:
A EN 2/2
1KHL015788-EN

3 Changing from 230 VAC to 115 VAC

1) Unplug the module from the equipment
2) Unscrew the four bolts on top to remove the cover
3) Remove the wire bridge X14-X15 for 230 VAC
4) Remove the two fuses F1 and F3
5) Insert two wire bridges X13-X14 and X15-X16 for 115 VAC
6) Insert two new fuses F1 and F3: 4 A slow-blow (ABB part no. XN 400018P0022)
7) Close the module by adding the cover and fixing it with the four bolts
8) Mark the 115 VAC box on the right side of the module with a pen

4 Changing from 115 VAC to 230 VAC

1) Unplug the module from the equipment
2) Unscrew the four bolts on top to remove the cover
3) Remove the wire bridges X13-X14 and X15-X16 for 115 VAC
4) Remove the two fuses F1 and F3
5) Insert the wire bridge X14-X15 for 230 VAC
6) Insert two new fuses F1 and F3: 2 A slow-blow (ABB part no. XN 400018P0019)
7) Close the module by adding the cover and fixing it with the four bolts
8) Mark the 230 VAC box on the right side of the module with a pen